Paraiso - Tabasco
TG-2 UNIT
All the above specifications are intended as applicable in their latest revision
2. INSTALLATION DATA
The plant is in an marine environment, with humid tropical climate (subject to tropical
rains) and with the following main characteristics:
temperature range min/max.... 10 / 42 C
Design temperature ............... 35 C
relative humidity...................... 90 %
altitude .................................... = 20 m a.s.l.
Seismic design ....................... UBC Zone 1
Wind speed............................. 38 m/s
Area classification................... Safe
The Panel will be installed inside an air-conditioned technical room. In normal
operation the HVAC system will maintain the following condition:
- Air temperature..................... 25 C 2%
- Relative humidity .................. 50% (min) 100% (max)
In case of HVAC failure the Panel may be subjected to outdoor conditions for a short
period, in such case they shall be able to operate without alteration of its
performance.
After the order NP will give to supplier basic information relevant to control logics in order
to allow the 1st issue of schematic diagrams. Is Manufacturer responsibility to ask missing
information/documentation that will impact on the drawing/manufacturing schedule. NP
will never accept any delay on Drawings or Manufacturing if not officially advised in
proper way and timing.
5.2.2. PT's
N 2 PTs with 1 secondary (on Line side)
VTGMP/AVR - Core for Measures / Synchronising & Protection :
Ratio ................ 14400 / 120 V
For CTs and PTs configuration refer to NP General Single line diagram
SOK7350070.
NOTE 1
the generator protection relays G60 will be provided by GE-NP. The manufacturer will
only install the G60 relays and make all connections (terminals etc) for the proper
functioning of equipment.
Ref. to Tech.
Exception to NP NP Comment NP
Spec./Document/ NP Accept/Reject
Techn. Requirement Supplier's Alternative Proposal (3) to Qualification Remarks
International Code Qualification (5)
(2) (4) (6)
and Paragraph (1)
ITK para 2.1 Mechanical parts: Doors shall be provided with facilities to lock the
door in open position.
ITK para 2.3.3 (or 3.8) Multipoint Signalling Panel: Signalling Points shall be
LED type (not lamp).