MV/LV prefabricated substation

Biosco H Mo 1000
Half-buried type, up to 24kV-1000kVA,
4 MV functions
Purpose
Biosco H Mo 1000 is a MV/LV prefabricated substation dedicated to
underground networks.
Rated power up to 630/1000kVA.

Standards
Designed in accordance with IEC 62271-202.
Manufactured in accordance with ISO 9001 and ISO 14001.

RT
U

Enclosure
Pu
@ Enclosure made of reinforced concrete, bli
including the underground tub (foundation) c lig
with pre-broken holes for cables entry hti
@ Back half part of the roof removable by
ng
lifting for transformer replacement
@ Lateral access to the transformer through
a hatch
@ Front face including a removable metallic
footpath (safe operating area and easy Equipment
access for cable connection) @ MV switchboard: RM6 Ring Main Unit 3 or 4 functions (depending
@ Protection degree: on LV switchboard size)
_ IP 25 D (against ingress of foreign objects @ MV interconnection with 50mm2 aluminium cables
and liquids) @ Transformer: oil type, 630/1000kVA (depending on dimensions)
_ IK 10 (mechanical resistance to impacts) @ LV interconnection with copper bars or 240mm2 aluminium cables
@ Enhanced protection against step-up @ LV switchboard: 6 to 10 outgoings with fuses or circuit breakers
voltage by the installation of an (according to MV switchboard number of functions)
equipotential loop @ Earthing circuit, internal lighting
@ Oil retention tank @ Optional equipment:
@ Ground surface: 5,6m2 _ Remote Terminal Unit: Easergy T200
@ Approximate weight with equipment: 8t _ Fault Passage Indicator: Easergy Flair
@ Height above ground level: 1,68m _ LV capacitors embedded in the LV switchboard
@ Finish: choice of colours, optional cladding _ Public lighting feeder, LV metering
Biosco H Mo 1000
Dimensions
Front face Left side view

Layout
Legend
1 MV switchboard: RM6 3 or 4 functions
2 MV/LV transformer
3 LV switchboard
4 Easergy Remote Terminal Unit or Fault Passage
Indicator
5 Lower ventilation louvre

ART. 836955 2008 Schneider Electric - All rights reserved.

Schneider Electric Industries S.A.S. As standards, specifications and designs change from time to time, please ask
Head Office for confirmation of the information given in this publication.
35 rue Joseph Monier
CS 30323 This document has been printed
92506 Rueil-Malmaison on ecological paper
Tel: +33 (0)1 41 29 85 00
www.schneider-electric.com Publishing: Schneider Electric Industries SAS
Design: Link to Business
Printing: Imprimerie du Pont de Claix/JPF - Made in France
DESWED108037EN 11-2008
MV/LV prefabricated substation

Biosco N In 1000
Non walk-in type, up to 24kV-1000kVA,
3 to 4 MV functions
Purpose
Biosco N In 1000 is a MV/LV prefabricated substation dedicated
to underground networks.
Rated power up to 1000kVA.

Standards
Designed in accordance with IEC 62271-202
Manufactured in accordance with ISO 9001 and ISO 14001.

RT
U

Enclosure
@ Compartmented substation operated from
outside
@ 2.5mm thick galvanised steel enclosure
mounted on a 4mm thick hot-dip
galvanised steel base
@ Access to the MV and LV compartments Equipment
by two double doors @ MV switchboard: RM6 or Ringmaster up to 4 functions
@ Access to the transformer compartment (up to 13.8kV with Ringmaster)
by removable panels or doors @ MV interconnection with 50mm2 aluminium cables
@ Protection degree: @ Transformer: oil type up to 1000kVA (according to dimensions)
_ IP 54 (MV and LV compartments) @ LV switchboard: TIPI, TUR or Opus with 4 to 8 outgoings with
_ IP 23D (transformer compartment) fuses or circuit breakers
_ IK 10 (mechanical resistance to impacts) @ Earthing circuit, internal lighting
@ Dielectric retention tank @ Optional equipment:
@ Ground surface: 6.6m2 _ Automatic Power Factor Correction (APFC) compartment
@ Approximate weight with equipment: 3 to 6t _ Remote Terminal Unit: Easergy T200
@ Height above ground level: 2.4m _ Fault Passage Indicator: Easergy Flair
@ Internal arc withstand : IAC AB - 20kA 1s _ Public lighting feeder, LV metering
Biosco N In 1000
Dimensions
Front face Left side view

Layout

Legend
1 MV switchboard: RM6 or Ringmaster up to 4 units
2 MV/LV transformer up to 1000 kVA (according to
dimensions)
3 LV switchboard
4 Option APFC (capacitors)

ART. 836955 2008 Schneider Electric - All rights reserved.

Schneider Electric Industries S.A.S. As standards, specifications and designs change from time to time, please ask
Head Office for confirmation of the information given in this publication.
35 rue Joseph Monier
CS 30323 This document has been printed
92506 Rueil-Malmaison on ecological paper
Tel: +33 (0)1 41 29 85 00
www.schneider-electric.com Publishing: Schneider Electric Industries SAS
Design: Link to Business
Printing: Imprimerie du Pont de Claix/JPF - Made in France
DESWED108037EN 11-2008
MV/LV prefabricated substation

Biosco N Ir 1000
Non walk-in type, up to 24kV-1000kVA
or 36kV-630kVA, 3 to 4 MV functions
Purpose
Biosco N Ir 1000 is a MV/LV prefabricated substation dedicated to
underground networks.
Rated power up to 630/1000kVA.

Standards
Designed in accordance with IEC 62271-202.
Manufactured in accordance with ISO 9001 and ISO 14001.

RT
U

Enclosure
@ Compartmented substation operated from
outside
@ 2.5mm thick galvanised steel enclosure
mounted on a 4mm thick hot-dip
galvanised steel base
@ Access to the MV and LV compartments
by two double doors
@ Access to the transformer compartment Equipment
by removable panels or doors @ MV switchboard: RM6, SM6 or CAS-36 up to 4 functions
@ Protection degree: @ MV interconnection with 50mm2 aluminium cables
_ IP 54 (MV and LV compartments) @ Transformer: oil type up to 630/1000kVA (according to dimensions)
_ IP 23D (transformer compartment) @ LV switchboard: TIPI, TUR or Opus with 4 to 8 outgoings with fuses
_ IK 10 (mechanical resistance to impacts) or circuit breakers
@ Dielectric retention tank @ Earthing circuit, internal lighting
@ Ground surface: 7.6m2 @ Optional equipment:
@ Approximate weight with equipment: 3.5 to 7t _ Remote Terminal Unit: Easergy T200
@ Height above ground level: 2.8m _ Fault Passage Indicator: Easergy Flair
@ Internal arc withstand: IAC AB - 20kA 1s _ Public lighting feeder, LV metering
Biosco N Ir 1000
Dimensions
Front face Left side view

Layout

Legend
1 MV switchboard: SM6 or RM6 or CAS 36
up to 4 functions
2 MV/LV transformer up to 1000kVA (according to
dimensions)
3 LV switchboard
4 Easergy Remote Terminal Unit or Fault Passage
Indicator

ART. 836955 2008 Schneider Electric - All rights reserved.

Schneider Electric Industries S.A.S. As standards, specifications and designs change from time to time, please ask
Head Office for confirmation of the information given in this publication.
35 rue Joseph Monier
CS 30323 This document has been printed
92506 Rueil-Malmaison on ecological paper
Tel: +33 (0)1 41 29 85 00
www.schneider-electric.com Publishing: Schneider Electric Industries SAS
Design: Link to Business
Printing: Imprimerie du Pont de Claix/JPF - Made in France
DESWED108037EN 11-2008
MV/LV prefabricated substation

Biosco W AI 1000
Walk-in type, up to 24kV1000kVA
or 36kV630kVA, 3 to 4 MV functions
Purpose
Biosco W AI 1000 is a MV/LV prefabricated substation dedicated to
underground networks.
Rated power up to 630/1000kVA.

Standards
Designed in accordance with IEC 62271-202
Manufactured in accordance with ISO 9001 and ISO 14001.

RT
U

P
ub
lic
Enclosure lig
ht
@ Enclosure made of reinforced concrete, in
including the underground tub (foundation) g
with pre-broken holes for cables entry
@ Underground tub may be delivered
separately in case of uneasy access Equipment
@ Protection degrees: @ MV switchboard: RM6 or SM6 or CAS-36 up to 4 functions
_ IP 25 D (against ingress of foreign objects @ MV interconnection with 50mm2 aluminium cables
and liquids) @ Transformer: oil type up to 630/1000kVA (according to dimensions)
_ IK 10 (mechanical resistance to impacts) @ LV interconnection with 240mm2 aluminium cables
@ Enhanced protection against step-up @ LV switchboard: TUR, TIPI or OPUS 6 to 8 outgoings
voltage by the installation of an with fuses or circuit breakers
equipotential loop @ Earthing circuit, internal lighting
@ Oil retention tank @ Optional equipment:
@ Ground surface: 9.6m2 _ Remote Terminal Unit: Easergy T200
@ Approximate weight with equipment: 17t _ Fault Passage Indicator: Easergy Flair
@ Height above ground level: 2,62m _ Public lighting cabinet
@ Finish: choice of colours, optional cladding _ LV metering
Biosco W AI 1000
Dimensions
Front face Left side view

ART. 836955 2008 Schneider Electric - All rights reserved.


Layout
Legend
1 MV switchboard: SM6 or RM6 or CAS 36
up to 4 functions
2 MV/LV transformer up to 630/1000 kVA
(according to dimensions)
3 LV switchboard: TIPI or TUR, 4 or 8 outgoings
with fuses
4 Easergy Remote Terminal Unit or Fault Passage
Indicator

Schneider Electric Industries S.A.S. As standards, specifications and designs change from time to time, please ask
Head Office for confirmation of the information given in this publication.
35 rue Joseph Monier
CS 30323 This document has been printed
92506 Rueil-Malmaison on ecological paper
Tel: +33 (0)1 41 29 85 00
www.schneider-electric.com Publishing: Schneider Electric Industries SAS
Design: Link to Business
Printing: Imprimerie du Pont de Claix/JPF - Made in France
DESWED108037EN 11-2008
MV/LV prefabricated substation

Biosco W Ta 2000
Twin walk-in type, up to 24kV2X1000kVA,
2 X 4 MV functions
Purpose
Biosco W Ta 2000 is a range of MV/LV prefabricated substation
dedicated to underground networks.
Rated power up to 2 x 630/1000 kVA.

Standards
Designed in accordance with IEC 62271-202
Manufactured in accordance with ISO 9001 and ISO 14001.

RT
U

RT
U
TU
8 t R or
o 1 TIP
2o Io
utg r O
oin PU
gs S
Enclosure
@ Enclosures made of reinforced concrete, TU
including the underground tub (foundation) 8 t R or
o 1 TIP
with pre-broken holes for cables entry 2o Io
utg r O
@ Underground tub is usually delivered oin PU
gs S
separately
@ The two modules are designed to be
transported separately and assembled Equipment
on site @ MV switchboard: RM6 or SM6 up to 4 functions
@ Protection degrees: @ MV interconnection with 50mm2 aluminium cables
_ IP 25 D (against ingress of foreign objects @ Transformer: oil type up to 630/1000kVA (according to dimensions)
and liquids) @ LV interconnection with 240mm2 aluminium cables
_ IK 10 (mechanical resistance to impacts) @ LV switchboard: TUR, TIPI or OPUS 6 to 8 outgoings with fuses
@ Oil retention tank or circuit breakers
@ Ground surface of one module: 11 to @ Earthing circuit, internal lighting
14.3m2 @ Optional equipment:
@ Approximate weight with equipment _ Remote Terminal Unit: Easergy T200
of one module: 17t _ Fault Passage Indicator: Easergy Flair
@ Height above ground level: 2,68m _ Public lighting box
@ Finish: choice of colours, optional cladding _ LV metering
Biosco W Ta 2000
Dimensions
Front face Left side view

Layout

Legend
1 MV switchboard: RM6
(or SM6) 4 functions
2 MV/LV transformer
up to 1000 kVA
(according to
dimensions)
3 LV switchboard: TUR
or TIPI or OPUS 6 to
12 outgoings
with fuses
4 LV transfer switch

ART. 836955 2008 Schneider Electric - All rights reserved.


(manual or automatic)

Schneider Electric Industries S.A.S. As standards, specifications and designs change from time to time, please ask
Head Office for confirmation of the information given in this publication.
35 rue Joseph Monier
CS 30323 This document has been printed
92506 Rueil-Malmaison on ecological paper
Tel: +33 (0)1 41 29 85 00
www.schneider-electric.com Publishing: Schneider Electric Industries SAS
Design: Link to Business
Printing: Imprimerie du Pont de Claix/JPF - Made in France
DESWED108037EN 11-2008