S. SHEE
N T FRAZIMEX RESPONSE IMPaC COMMENTS FRAZIMEX RESPONSE
COMMENTS
O NUM
. BER
1- Kindly write 1. Implemented 1. Implemented
flow rate instead
of design flow 2. Auto blow down 2. Not implemented 2. Implemented
rate in data valve already
panels. provided upstream of
2- Kindly provide the preheater. High
auto blow down pressure can NEVER
receiver.
Regeneration
cycle will be done
with dry gas and 5. Vendor to advise
regenerated gas 6. Please can you
will be wet gas provide the reasons
and it cannot be for the requesting
routed to NRV before the
instrument gas instrument gas
receiver and receiver.
therefore 7. It is a statutory
regenerated gas requirement for a
should be vessel operating at
recycled. Please more than 3bar. For
provide the inventory evacuation
process in case of emergency.
description of
dryer package.
Also provide the
flow rate for
regeneration cycle
in data panel of
dryers.
5- Column for Cycle
time with VTS
should be
provided in data
panel of
instrument gas
dryers.
6- NRV should be
provided before
instrument gas
receiver.
7- Review the
requirement of
auto-blow down
valve (10-BDV-
902) at instrument
gas receiver.