Вы находитесь на странице: 1из 7

Calculation - Area of

Compartment Width Depth


Number Zone for the Fire Riser (mm) (mm)
Compartment (m2)

Fresh Air 1 4000 2400


Exhaust Air 2 4000 2400
Fresh Air 3 2400 2400
1 2000
Exhaust Air 4 3200 3000
Fresh Air 5 2400 2400
Exhaust Air 6 3200 3000
Exhaust Air 7 2400 2400
Fresh Air 8 2400 2400
2 2000
Fresh Air 9 2400 2400
Exhaust Air 10 4000 2400
Exhaust Air 11 4000 2400
Fresh Air 12 3000 2400
Fresh Air 13 2400 3000
3 2100
Exhaust Air 14 4000 2400
Fresh Air 15 5750 1550
Exhaust Air 16 10400 1600
Exhaust Air 17 4000 24000
Fresh Air 18 2400 2400
Fresh Air 4 1750 19 3300 1500
Exhaust Air 20 3900 1500
Exhaust Air 21 3900 1500
Air Flow Rate - Number Number Total Air Flow Rate Air Velocity Percentage of Free
Normal Mode / - Normal Mode Through Louver Area for Louver ( /
of Fan of Floors
Fan (cfm) (cfm) (fpm) 100)

17,500 3 2 105,000 800 0.4


12,500 4 3 150,000 800 0.4
17,500 2 2 70,000 800 0.4
12,500 4 3 150,000 800 0.4
17,500 2 2 70,000 800 0.4
12,500 4 3 150,000 800 0.4
12,500 2 3 75,000 800 0.4
17,500 1 2 35,000 800 0.4
17,500 2 2 70,000 800 0.4
12,500 4 3 150,000 800 0.4
13,000 4 3 156,000 800 0.4
18,000 2 3 108,000 800 0.4
18,000 2 3 108,000 800 0.4
13,000 4 3 156,000 800 0.4
18,000 2 3 108,000 800 0.4
13,000 6 3 234,000 800 0.4
11,000 4 3 132,000 800 0.4
15,000 2 2 60,000 800 0.4
15,000 2 2 60,000 800 0.4
11,000 2 3 66,000 800 0.4
11,000 2 3 66,000 800 0.4
Area of Louver Width of louver Height of Louver
Required (m2) Required (mm) Required (mm)

30.5 2300 13.3


43.6 3900 11.2
20.3 2300 8.8
43.6 3100 14.1
20.3 2300 8.8
43.6 3100 14.1
21.8 2300 9.5
10.2 2300 4.4
20.3 2300 8.8
43.6 3900 11.2
45.3 3900 11.6
31.4 2900 10.8
31.4 2300 13.6
45.3 3900 11.6
31.4 5650 5.6
68.0 10300 6.6
38.3 3900 9.8
17.4 2300 7.6
17.4 3200 5.4
19.2 3800 5.0
19.2 3800 5.0
Calculation - Area of Air Flow Rate - Total Air Flow Rate Air Velocity Percentage of Free
Compartment Width Depth Number Number Area of Louver Width of louver Height of Louver
Number Zone for the Fire Riser (mm) (mm) Normal Mode / of Fan of Floors - Normal Mode Through Louver Area for Louver ( / Required (m2) Required (m) Required (m)
Compartment (m2) Fan (cfm) (cfm) (fpm) 100)

Exhaust Air 1 2400 2400 12,500 4 3 150,000 500 0.4 69.7


Fresh Air 2 2400 2400 17,500 4 2 140,000 500 0.4 65.1
Exhaust Air 1 2000 3 2400 2400 12,500 4 3 150,000 500 0.4 69.7
Fresh Air 4 2400 2400 17,500 3 2 105,000 500 0.4 48.8
Exhaust Air 5 2400 2400 12,500 4 3 150,000 500 0.4 69.7
Exhaust Air 6 2400 2400 16,000 2 3 96,000 800 0.4 27.9
Fresh Air 7 2400 2400 22,500 1 2 45,000 800 0.4 13.1
2 2600
Fresh Air 8 2400 2400 22,500 2 2 90,000 800 0.4 26.1
Exhaust Air 9 4000 2400 16,000 4 3 192,000 800 0.4 55.8
Exhaust Air 10 4000 2400 16,000 2 3 96,000 800 0.4 27.9
Fresh Air 11 4150 2400 15,500 3 3 139,500 500 0.4 64.8
2600
Fresh Air 12 2400 3000 22,500 1 3 67,500 800 0.4 19.6
Exhaust Air 3 13 4000 2400 10,850 2 3 65,100 500 0.4 30.3
Fresh Air 14 5750 1550 18,000 2 3 108,000 800 0.4 31.4
Exhaust Air 2100 15 10400 1600 13,000 2 3 78,000 800 0.4 22.7
Exhaust Air 16 10400 1600 13,000 4 3 156,000 800 0.4 45.3
Exhaust Air 17 4000 24000 11,000 4 3 132,000 800 0.4 38.3
Fresh Air 18 2400 2400 15,000 4 2 120,000 800 0.4 34.9
4 1750
Exhaust Air 19 3900 1500 11,000 2 3 66,000 800 0.4 19.2
Exhaust Air 20 3900 1500 11,000 2 3 66,000 800 0.4 19.2
Compartment Calculation - Area of Width Depth Air Flow Rate - Number Number Total Air Flow Rate Air Velocity Percentage of Free Area of Louver Width of louver Height of Louver
Number
Zone for the Fire Riser (mm) (mm)
Normal Mode /
of Fan of Floors
- Normal Mode Through Louver Area for Louver ( /
Required (m2) Required (m) Required (m)
Compartment (m2) Fan (cfm) (cfm) (fpm) 100)

Exhaust Air 1 2400 2400 12,365 5 2 123,650 500 0.4 57.5


Fresh Air 2 2400 2400 17,310 4 2 138,480 500 0.4 64.3
Exhaust Air 3 2400 2400 12,365 5 2 123,650 500 0.4 57.5
1 2000
Fresh Air 4 2400 2400 17,310 3 2 103,860 500 0.4 48.3
Exhaust Air 5 2400 2400 12,365 4 2 98,920 500 0.4 46.0
Exhaust Air 6 2400 2400 12,365 2 3 74,190 500 0.4 34.5
Exhaust Air 7 2400 2400 16,070 2 3 96,420 500 0.4 44.8
Fresh Air 8 2400 2400 22,550 1 2 45,100 500 0.4 21.0
2 2600
Fresh Air 9 2400 2400 22,550 2 2 90,200 500 0.4 41.9
Exhaust Air 10 2600 2400 16,070 4 3 192,840 500 0.4 89.6
Exhaust Air 11 2400 2400 12,365 2 3 74,190 500 0.4 34.5
Fresh Air 12 2400 2400 20,772 3 3 186,948 500 0.4 86.9
Exhaust Air 13 2400 2400 12,365 2 3 74,190 500 0.4 34.5
Exhaust Air 3 2000 14 2400 2400 12,365 2 3 74,190 500 0.4 34.5
Fresh Air 15 2000 1550 20,772 2 3 124,632 500 0.4 57.9
Exhaust Air 16 2100 1500 12,365 2 3 74,190 500 0.4 34.5
Exhaust Air 17 2400 2400 12,365 4 3 148,380 500 0.4 68.9
Exhaust Air 18 2400 2400 10,820 4 3 129,840 500 0.4 60.3
Fresh Air 19 2400 2400 15,150 4 2 121,200 500 0.4 56.3
4 1750
Exhaust Air 20 1600 1500 10,820 2 3 64,920 500 0.4 30.2
Exhaust Air 21 1600 1500 10,820 2 3 64,920 500 0.4 30.2
Compartment Calculation - Area of Width Depth Air Flow Rate - Air Flow Rate -
Normal Mode / Fan (in.wg
Static Pressure Fan Dimension
Number
Zone for the Fire Riser (mm) (mm)
Normal Mode /
/ Pa)
Fan
W x D x H (mm)
Compartment (m2) Fan (cfm) Fan (cmh)

KRUGER
Exhaust Air 1, 3, 5 & 6 2400 2400 12,365 21,008 3.0 / 750 SYSTEMAIR
ROSENBERG
1 2000
KRUGER
Fresh Air 2&4 2400 2400 17,310 29,410 3.0 / 750 SYSTEMAIR
ROSENBERG
KRUGER
Exhaust Air 7 & 10 2400 2400 16,070 27,303 3.0 / 750 SYSTEMAIR
ROSENBERG
2 2600
KRUGER
Fresh Air 8&9 2400 2400 22,550 38,313 3.0 / 750 SYSTEMAIR
ROSENBERG
KRUGER
Exhaust Air 11, 13, 14, 16 & 17 2400 2400 12,365 21,008 3.0 / 750 SYSTEMAIR
ROSENBERG
3 2000
KRUGER
Fresh Air 12 & 15 2400 2400 20,772 35,292 3.0 / 750 SYSTEMAIR
ROSENBERG
KRUGER
Exhaust Air 18, 20 & 21 2400 2400 10,820 18,383 3.0 / 750 SYSTEMAIR
ROSENBERG
4 1750
KRUGER
Fresh Air 19 2400 2400 15,150 25,740 3.0 / 750 SYSTEMAIR
ROSENBERG
Smoke Spilled Compartment Air Flow Rate - Air Flow Rate - Fan Static Pressure Fan Model Fan Dimension
System Number Normal Mode / Normal Mode / (in.wg / Pa) (Centrifugal Fan-Backward Curved Wheel) W x D x H (mm)
Fan (CFM) Fan (CMH)

Exhaust Air 12,400 21,100 3.0 / 750


1
Fresh Air 17,400 29,500 3.0 / 750
Exhaust Air 16,100 27,400 3.0 / 750
2
Fresh Air 22,600 38,400 3.0 / 750
Exhaust Air 12,400 21,100 3.0 / 750
3
Fresh Air 20,800 35,300 3.0 / 750
Exhaust Air 10,900 18,400 3.0 / 750
4
Fresh Air 15,200 25,800 3.0 / 750