HILTI HIT RE 500 ADHESIVE ANCHORING SYSTEM 5, respectively. Anchors are permitted for live, dead, wind,
and earthquake loads. Where adjustments to the allowable
HILTI, INC. loads are permitted or required in accordance with Section
5400 SOUTH 122ND EAST AVENUE 1612.3 of the UBC and Section 1605.3 of the IBC, those
TULSA, OKLAHOMA 74146 adjustments shall be as follows:
1. For allowable short-term tension loads resulting from
1.0 SUBJECT wind and seismic forces, the concrete/bond and steel
Hilti HIT RE 500 Adhesive Anchoring System. values may be taken as 1.33 times the values given in
Tables 4 and 5.
2.0 DESCRIPTION
2. For allowable short-term shear loads resulting from wind
2.1 General:
and seismic forces, the concrete/bond values may be
The Hilti HIT RE 500 Adhesive Anchoring System is taken as 1.33 times the values given in Tables 4 and 5.
intended for installation of post-installed threaded rods and
3. For allowable short-term shear loads resulting from wind
deformed reinforcing bars in minimum 2,000 psi (13.7 MPa)
and seismic forces based on steel strength, the steel
normal-weight concrete. The Hilti HIT RE 500 Adhesive
shear values must be calculated as follows:
Anchoring System is permitted to resist dead, live, seismic
and wind loads. The anchor system is an alternative to a. For Standard HAS rods (ASTM A 36 rods), the
cast-in-place anchors described in Section 1923.1 of the allowable shear load based on steel strength may be
1997 Uniform Building Code (UBC), and Section 1912 of taken as 1.33 times the A 36 value for static loads
the 2000 International Building Code (IBC). given in Table 4.
2.2 Materials: b. For HAS Super rods (ASTM A 193 B7 rods), the
allowable shear load based on steel strength may be
2.2.1 Hilti HIT RE 500 High Strength Epoxy Adhesive: taken as 0.94 times the A 193 B7 value for static loads
The Hilti HIT RE 500 adhesive is a two-component given in Table 4.
injectable epoxy adhesive with the components contained
in a dual-chambered cartridge. Available cartridge sizes c. For stainless rods (ASTM F 593 CW rods), the
include 11.1 ounces (330 ml) and 37 ounces (1100 ml). allowable shear load based on steel strength may be
The two components combine when dispensed through a taken as 1.14 times the AISI 304/316 SS value for
static mixing nozzle attached to the cartridge at a 3:1 ratio static loads given in Table 4.
of resin to hardener. The static mixing nozzle is supplied by d. For reinforcing bar (Grade 60), the allowable shear
Hilti. Each cartridge is stamped with an adhesive expiration load based on steel strength may be taken as 1.33
date. The Hilti HIT RE 500 epoxy adhesive has a times the value for static loads given in Table 5.
recommended maximum shelf life of nine months when The allowable tension and shear values in Tables 4 and
stored in the manufacturers unopened container at 5 must be adjusted in accordance with Figure 1 for in-
temperatures between 23F (-5C) and 77F (25C). service base-material temperatures in excess of 120F
2.2.2 Threaded Steel Rods: Threaded steel rods consist (49C). Allowable loads for anchors subjected to combined
of all-thread rods in diameters shown in Table 1. The rods, shear and tension forces are determined as follows:
with nut and washer, are available in three steel (Ps / Pt )5/3 + (Vs / Vt )5/3 1
specifications as shown in Table 2. The Standard HAS Rod
where:
and the HAS Super Rod are furnished with a 5 m zinc
electroplate coating in accordance with ASTM B 633 SC 1. Ps = Applied service tension load.
2.2.3 Reinforcing Bars: Deformed reinforcing bars Pt = Allowable service tension load.
range in size from No. 3 to No. 11, as shown in Table 3, and Vs = Applied service shear load.
are manufactured from steel conforming with ASTM A 615, Vt = Allowable service shear load.
A 616, A 617 or A 706 (Grade 60, minimum).
For anchors installed at edge distances less than ccr, or
2.2.4 Normal-weight Concrete: Concrete must be spacing less than scr, or both, the concrete/bond values
normal-weight stone aggregate concrete having a minimum given in Tables 4 and 5 must be reduced in accordance with
28-day compressive strength of 2,000 psi (13.78 MPa) at the reduction factors given in Table 6. The reduced
the time of anchor installation. concrete/bond-strength anchor values must be compared
2.3 Design: with the corresponding allowable steel strength, and the
Allowable tension and shear loads for threaded rod and lesser value must be used to establish allowable anchor
rebar in normal-weight concrete are given in Tables 4 and capacity.
are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as
an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICBO Evaluation Service, Inc., express or implied,
as to any finding or other matter in this report, or as to any product covered by the report.
4.10 Since an ICBO ES acceptance criteria for Installation of the Hilti HIT RE 500 Adhesive
evaluating the performance of adhesive anchors Anchor System in base materials having interior
in cracked concrete is unavailable at this time, temperatures outside this range is beyond the
the use of anchors is limited to installation in scope of this report. The temperature of the Hilti
uncracked concrete. Cracking occurs when ft > HIT RE 500 Adhesive must be between 40F
fr due to service loads or deformations. (5C) and 105F (40C) at the time of installation.
4.11 Use of the Hilti HIT RE 500 Adhesive Anchor 4.14 When anchors are located where the interior
System in conjunction with carbon steel base-material temperature may exceed 120F
threaded rods shall be limited to interior (49C), allowable tension and shear loads in this
exposure. Installations exposed to severe, report must be adjusted for in-service
moderate or negligible exterior weathering temperatures in accordance with Figure 1. The
conditions, as defined in Figure 21-1-1 of UBC use of the Hilti HIT RE 500 Adhesive Anchor
Standard 21-1 or Figure 1 of ASTM C 62, are System in base materials having interior
permitted where stainless steel anchors are temperatures exceeding 212F (100C) is beyond
used. the scope of this report.
4.12 During anchor installation, the hole and 4.15 The Hilti HIT RE 500 Adhesive Anchor System is
surrounding location are permitted to be dry, manufactured by Hilti GmbH at their facilities in
damp or wet (including standing water). Kaufering, Germany, with quality control
inspections by Underwriters Laboratories Inc.
4.13 The Hilti HIT RE 500 Adhesive Anchor System
(AA-668).
may be installed in base materials having
interior temperatures between 23F (-5C) and This report is subject to re-examination in one year.
110F (43C) at the time of installation.
Page 4 of 7 ER-6010
Anom = Nominal area of threaded rod (in.2) 0.1104 0.1963 0.3068 0.4418 0.6013 0.7854 1.2272
7 9 3 7
BD = Nominal bit diameter (inches) /16 /16 /4 /8 1 11/8 13/8
Standard embedment depth (inches) 33/8 41/2 55/8 63/4 77/8 9 111/4
d = Nominal bar diameter (inches) 0.375 0.500 0.625 0.750 0.875 1.000 1.125 1.250 1.375
1 5 3 7 1 3 1
BD = Nominal bit diameter (inches) /2 /8 /4 /8 1 1 /8 1 /8 1 /2 13/4
Embedment depth (inches) 33/8 41/2 55/8 63/4 77/8 9 101/8 111/4 123/8
For SI: 1 inch = 25.4 mm.
TABLE 4ALLOWABLE TENSION AND SHEAR VALUES IN NORMAL-WEIGHT
CONCRETE FOR THREADED RODS INSTALLED WITH HILTI HIT RE 500 ADHESIVE (pounds)1,2,3,4,5
DIAMETER MENT
(inches) DEPTH Based on Bond or Based on Steel Strength Based on Bond or Based on Steel Strength
(inches) Concrete Concrete
9 15,985 18,205
No. 8 18,960 12,985 12,085
12 17,400 18,235
SPACING FACTORS FOR EDGE DISTANCE FACTORS FOR EDGE DISTANCE FACTORS FOR TENSION
TENSION AND SHEAR LOADS SHEAR LOADS LOADS
Scr Smin fA ccr cmin fRV ccr cmin fRN
1.5 hef 0.5 hef 0.70 1.5 hef 0.5 hef 0.30 toward edge 1.5 hef 0.5 hef 0.70
0.60 not toward edge
Linear interpolation may be used for spacings between scr and smin and edge distances between ccr and cmin, as well as intermediate
embedment depths.
1
For an anchor affected by multiple anchor spacings and/or edge distances, the allowable adjusted load is the product of the following factors:
HIT RE 500
IN-SERVICE TEMPERATURE
100% @ 120 F
100% @ 23 F
100% @ 70 F
120
100
% of Load @ 70oF
80
86% @ 23 F
38% @ 212
60
40
Install at 70 F
20 Install at 23 F
0
0 50 100 150 200 250
Base Material Temperature, oF
For SI: tC = (tF - 32) 1.8.
FIGURE 1INFLUENCE OF TEMPERATURE ON ALLOWABLE TENSION AND SHEAR LOADS FOR HILTI HIT RE 500 ADHESIVE