Air Cooled Screw Water Chillers

ASY Series
ASY050B thru ASY500B
50 TR thru 487 TR
176 kW thru 1715 kW

R-134a
Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.

The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:


1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,
retrofit & operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations
from the corporate headquarters in Dammam, Saudi Arabia.

Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions


Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facility
in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZACs products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Condition-
ers manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the
Concealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin
Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.
INDEX

Contents Page

Model decoding ........................................................................................................................................ 2

Unit features, standard specifications & options .................................................................................... 3-7

Physical data ....................................................................................................................................... 8-10

Selection procedure .......................................................................................................................... 11-12

Performance data .............................................................................................................................. 13-18

Electrical data .................................................................................................................................... 19-21

Water side pressure drop ....................................................................................................................... 22

Recommended installation for sensor & water flow switch ..................................................................... 23

Unit dimensions ................................................................................................................................ 24-29

Typical schematic wiring diagram ...................................................................................................... 30-31

Microprocessor controller ....................................................................................................................... 32

Troubleshooting guide ....................................................................................................................... 33-34

Application guidelines ........................................................................................................................ 35-44

Rigging instructions ................................................................................................................................ 45

Installation clearance .............................................................................................................................. 46

Mounting location ................................................................................................................................... 47

Load distribution ................................................................................................................................ 48-49

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
MODEL DECODING
1, 2 & 3 4, 5 & 6 7 8 9 10 11 12 13 & 14
BASIC UNIT SIZE REFRIGER- ELECTRICAL CONDENSER COIL CIRCUIT BREAKER COOLER HGBP OPTIONS
(SERIES) ANT SUPPLY OPTIONS OPTIONS OPTIONS &
( V-Ph-Hz ) ACCESSORIES

ASY 050 B : R-134a H : 208/230-3-60 A : ALUMINUM FIN A : STANDARD A : STANDARD WITH A : STANDARD UNIT SEE NOTE # 2
060 VICTAULIC CONN. WITHOUT HGBP BELOW
AIR COOLED
070 M: 380-3-60 B : PRE-COATED B : COMPRESSOR CIRCUIT
SCREW WATER
080 (4 WIRE) ALUMINUM FIN BREAKER B : FLANGE CONN. B : HGBP (OPTIONAL)
CHILLERS
090 (OPTIONAL)
100 C : COPPER FIN
F : 460-3-60
120 C : ASME STAMPED
D : ALUMINUM FIN
130 WITH VICTAULIC
WITH ResisTec
140 COATING CONN. (OPTIONAL)
150
160 E : COPPER FIN
170 WITH ResisTec D : ASME STAMPED
180 COATING WITH FLANGE
190 CONN.(OPTIONAL)
(SEE NOTE # 1
200
BELOW)
215
230
240
250
270
295
310

2
330
350
375
400
420
450
475
500

NOTES:
1. FOR OTHER COATING, SPECIFY YOUR REQUIREMENTS IN WRITING.
2. COMPUTER SELECTED DIGITS (FROM 'AA' TO 'ZZ') DESCRIBING OTHER OPTIONS & ACCESSORIES OR COMBINATIONS THEREOF, SUCH AS: - CONDENSER COIL GUARD
- COOLER GUARD
- UNIT DISCONNECT SWITCH
- COMPRESSOR ENCLOSURE
- WATER FLOW SWITCH
- SPRING ISOLATOR
- MULTI-ResisTec PIPING
- MULTI-ResisTec SHEET METAL etc...
FEATURES
These ASY air cooled screw water chillers offer the ultimate combination of energy saving design, superior engineering
features and flexibility of application as required by todays market.

* These chillers incorporate the newest advanced microprocessor controller. This controller monitors analog and digital
inputs to achieve precise control & protective functions of the air cooled water chiller units. This microprocessor
controller is complete with all the hardware and software necessary to control the chiller unit and ensures its effi-
ciency and reliability.

* Designed to conform to ARI standard 550/590 water chilling packages using the vapor compression cycle.

Designed to conform to ANSI/ASHRAE 15-1994 Safety code for Mechanical Refrigeration.


*
Compact unit design and excellent serviceability.
*
All packaged chillers incorporate compact water coolers with enhanced inner grooved copper tubes bundled into a
*
"U" shape and expanded into a steel tubular sheets which offer efficient water flow as well as heat transfer design
resulting in optimal unit performance.

High Energy Efficiency Ratio (EER) semi-hermetic compact twin screw compressors are provided in these units.
*
* Single point power connection to minimize job site installation cost and time.

* Completely wired control panel with the advanced microprocessor controller provides all the necessary operating and
safety controls.

Compressors are with part winding start.


*
* Low noise condenser fans, direct drive at 1000 RPM with rolled form venturi design to eliminate short circuiting of
airflow.

All fans are die cast aluminum propeller type with aerodynamic design, top discharge, provided with protective
*
grille mounted on top panel within the unit casing.

All condenser fan motors are totally enclosed air over type (TEAO) with class ''F'' winding insulation and ball bearings.
*
Inherent thermal protection of the automatic reset type and specially designed for outdoor application is included.

STANDARD SPECIFICATIONS
CAPACITY CONTROL
These chillers are equipped with stepless capacity control system as standard for very accurate response to load
requirements and best part load efficiency. Each compressor is equipped with a slider controller that enables to modulate
capacity between 25% to 100%, thus giving a broad range to control total chiller capacity between 10% to 100% on an
average. This system has the following advantages:

1. Infinite capacity modulation that allows the compressor capacity to exactly match the cooling load.

2. Reduce compressor cycling which leads to better operational reliability.

3. Reduce operating cost.

4. For units with Hot gas bypass (optional): The unit modulates to approximately 50% of its compressor lowest unloaded
capacity.

3
SEMI-HERMETIC COMPACT TWIN SCREW COMPRESSORS
All compressors are compact semi-hermetic twin screw of the high capacity and efficiency due to their perfect profile
form ratio 5:6. They are simple and of robust construction with slider control valve for capacity unloading, suction/
discharge shut-off valves, check valve in discharge gas outlet, oil sight glass, oil fill/drain service valve, directly flanged-
on three stage oil separator with long-life fine filter 10 microns mesh size, robust axial bearings in tandem configuration,
suction gas filter, internal pressure relief valve and manual lock-out electronic protection system for thermal motor
winding temperature, phase reversal, discharge gas temperature protection controls.

CONDENSER COILS
W-configuration condenser coils are corrugated fin and tube type, constructed of seamless 3/8" dia. & 0.011" (0.27 mm)
thick copper tubes, mechanically bonded to aluminum fins for maximum heat transfer efficiency.

As a standard on aluminum fins, ZAC provides Coil ResisTec Coating, which is a single component of aluminum
impregnated coating applied on the fins of heat exchanging coils. The product has been designed for Middle East climate
conditions. A high chemical, abrasion and UV resistance has been proven in both laboratories and on field environment.
The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance or rejuvenation
purposes.

The fins have full self spacing collars which completely cover each tube. The staggered tube design improves the
thermal efficiency. End plates support sheets are 14 gauge galvanized steel, formed to provide structural strength.
Each coil is pressure tested in the factory at not less than 450 psi air pressure.

COMPACT DESIGN SHELL AND TUBE WATER COOLERS


The DX shell & tube cooler with removable U shaped bundled tubes are made of internally grooved copper tubes
expanded into a heavy steel tubular sheets.

The chiller cooler & baffles are constructed of steel and brass respectively. The coolers are insulated with heavy closed
cellular foam insulation (3/4" thick). All chiller barrels are fitted with vent, drain connection and victaulic water pipe
connection as standard.
SHELL & TUBE WATER SIDE REFRIGERANT SIDE
HEAT
EXCHANGER DESIGN PRESSURE, TEST PRESSURE, DESIGN PRESSURE, TEST PRESSURE,
(COOLER) (BAR/PSIG) (BAR/PSIG) (BAR/PSIG) (BAR/PSIG)
STD 16/235 22.8/335 29/426 41.5/610

ASME (option) 10/147 11.3/165 15.5/228 23.3/342

CABINET
All units are of heavy gauge (G-90) galvanized steel. Steel sheet panels are zinc coated and galvanized by hot dip
process of lock-forming quality conforming to ASTM A 653 commercial weight G-90 followed by air dry paint or backed on
electrostatic polyester dry powder coat.

CONTROL PANEL
The control panel design is equivalent to NEMA 4 (IP55) with hinged door for easy access ensuring dust and weather-
proof construction. Internal power and control wiring is neatly routed, adequately anchored and all wires are identified
with cable markers as per NEC standards applicable to HVAC industry.

The electrical controls used in the control panel are UL approved which are reliable in operation at high ambient condi-
tions for a long period.

CONDENSER FANS
Condenser fans, the impeller and motors are so constructed to form an integral unit. All fan motors shall be three phase
with class ''F'' winding insulation and ball bearings for high ambient application. These fan motors are of totally enclosed
air over type (TEAO) with inherent thermal protection of automatic reset type.

4
MICROPROCESSOR CONTROLLER
The microprocessor controller works on the state of art microprocessor technology. This controller monitors analog and
digital inputs to achieve precise control & safety functions of the unit.
The Software works on the Proportional Integral Derivative (PID) algorithm for precise control logic.
The simple to use push button keyboard allows accessing to the operating conditions, control set points & alarm history
that are clearly displayed on a multi-line back illuminated LCD panel.
An easy to install serial port/modem option allows remote monitoring of the operating parameters. With corresponding
windows software, the system allows data to be viewed in tabular or graphic format as well as interact with system set up.
This chiller controller is compatible with the Building Management System (BMS) BACNET/MODBUS protocols through
corresponding optional gateway interfaces.
It is also compatible with GSM protocol through GSM optional gateway that sends up to 3 mobile phone SMS messages
whenever alarm take place, indicating the type of alarm, the corresponding compressor, the related chiller and which
location.
The microprocessor consists of the following hardware:
1. User Interface Board: Provided with simple to use push button keyboard and menu driven software to access operat-
ing conditions, control set points & alarm history that are clearly displayed on the LCD panel.
2. Main Board: This controls up to two (2) compressor system.
3. Auxiliary Boards: Required for controlling an additional two (2) or more compressors.
4. Remote Monitoring System [Optional]: The micro controller is complete with all hardware and software necessary to
remotely monitor and control the chiller unit.
DISPLAY INFORMATION:
In the normal operating mode the 20 x 4 characters LCD panel display the system status, the temperature of the water
inlet & outlet, the set point, run time of the compressor & the alarm history.
Easily accessible measurements for each circuit include the following:

Suction and discharge temperatures

Suction and discharge pressures

Water inlet/outlet temperatures

Compressor status

Fan status

Liquid line solenoid status

Unit/Compressor run time


The control temperature is continuously displayed on the 3 Digit 7 segments LED Display. The 3 LED lights indicate the
Power ON, Menu adjustment and Fault.
SYSTEM PROTECTION:
The following system protection is provided to ensure system reliability:

compressor winding overheating

Low suction pressure

High discharge pressure

Freeze protection

Low oil level (optional)

Sensor error

Time delay Anti recycle time for compressor

Serial communication error

5
STANDARD CONTROL & SAFETY DEVICES
MICROPROCESSOR CONTROLLER: This controller monitors analog and digital inputs to achieve precise control &
safety functions of the unit.

COMPRESSOR IN-BUILT PROTECTION DEVICE: Protects the compressor by monitoring:

A) Motor winding temperature in case of overload.

B) Discharge gas temperature in case of overheating.

C) Phase reversal for direction of rotation.

STARTERS: The starter is operated by the control circuit and provides power to the compressor motors. These devices
are rated to handle safely both RLA and LRA of motors.

CRANKCASE HEATERS: Each compressor has immersion type crankcase heater. The compressor crankcase heater
is always on when the compressors are de-energized. This protects the system against refrigerant migration, oil dilution
and potential compressor failure.

HIGH PRESSURE SWITCH: This switch provides an additional safety protection in the case of excessive discharge
pressure.

UNDER & OVER VOLTAGE AND PHASE PROTECTION: Protects against low & high incoming voltage as well as
single phasing, phase reversal and phase imbalance by de-energizing the control circuit. It is an automatic reset device,
but it can be set up for manual reset.

COMPRESSOR CIRCUIT BREAKERS: Protects against compressor branch circuit fault. When tripped (manually or
automatically), the breaker opens the power supply to the compressor and control circuit through auxiliary contacts.

STANDARD ACCESSORIES
UNIT ON-OFF SWITCH: ON-OFF switch is provided for manually switching the unit control circuit.

INDICATOR LIGHTS: LED lights indicates power ON to the units, MENU adjustment and FAULT indications due to trip
on safety devices.

ELECTRONIC EXPANSION VALVE: Electronic expansion valve is used to regulate the refrigerant flow to the water
cooler and maintain a constant superheat and load optimization.

FILTER DRIER (REPLACEABLE CORE TYPE): Refrigerant circuits are kept free of harmful moisture, sludge, acids
and oil contaminating particles by the filter drier.

SIGHT GLASS: A moisture indicating sight glass is installed in the liquid line. An easy-to-read color indicator shows
moisture contents and provides a mean for checking the system refrigerant charge.

LIQUID LINE SOLENOID VALVE: Closes when the compressor is off to prevent any liquid refrigerant from accumulating
in the water cooler during the off cycle.

CONTROL CIRCUIT TRANSFORMER: On 460V-3Ph-60Hz power supply factory mounted and wired control circuit
transformer is furnished eliminating the need for running a separate 220 volt control circuit power supply.

6
OPTIONS
(All options are at extra cost. Please check with your nearest dealer/sales office)
HOT GAS BYPASS SYSTEM: Hot gas bypass is provided on the lead circuit to permit operation of the system down to 50%
of its unloaded capacity. Under low ambient condition, it controls temperature by eliminating the need to cycle the compressor
on and off, ensuring narrow temperature swing and lengthen the life span of the compressor.
WATER FLOW SWITCH: Paddle type field adjustable flow switch for water cooler circuits. Interlock into unit safety
circuits so that the unit will remain off until water flow is determined.
UNIT MOUNT SPRING ISOLATORS: This housed spring assemblies have a neoprene friction pad on the bottom to
prevent vibration transmission.
LIQUID COOLERS: ASME code stamped liquid cooler.
PRESSURE GAUGES: Suction & discharge pressures gauges.
NON-FUSED MAIN DISCONNECT SWITCHES: De-energize power supply during servicing/repair works as well as with
door interlock.
CONDENSER COIL GUARD: Protects the condenser coils from physical damage.
COMPRESSOR/COOLER GUARD: Protects the compressor from vandalism.
COMPRESSOR ENCLOSURE BOX: Reduces compressor operating noise and keeps the compressor clean.
FLANGED COOLER CONNECTION: Easy on-site piping connections.
COOLER HEATER WRAPPED: Prevents freezing up of water on low ambient temperature.
COPPER FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments.
ResisTec COATED COPPER FINS/TUBES CONDENSER COILS: For seashore or acid corrosive environments.
BMS: BACNET, MODBUS, GSM and stand alone remote display panel.
POWER LINE ANALYZER: Performs motor current limitation. Protects against high motor current & over/under voltage.
MULTI ResisTec: A two component coating system that withstands the extreme climate conditions. The coating can be
applied to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre-
treatment and layer build up. Please check ResisTec product information sheets, the heat exchangers can not be coated
using this type. The coating can be applied at the Zamil Air Conditioners factory as well as in the field for maintenance or
rejuvenation purposes.
HAND HELD CONTROLLER: Enables the chiller technician to monitor and serve the chiller by plugging this portable
wired controller into the chiller controller. With built-in magnets, it provides convenient access for chiller status diagnoses
and trouble shooting.

HAND HELD CONTROLLER

7
PHYSICAL DATA
UNIT SIZE ASY050B ASY060B ASY070B ASY080B ASY090B ASY100B ASY120B ASY130B ASY140B ASY150B

COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 800-683-13 800-683-16 800-683-19 800-683-22 800-683-13 (2) 800-683-13 (2) 800-683-16 (2) 800-683-19 (2) 800-683-19 (2) 800-683-19 (2)

380V-3Ph-60Hz 800-683-14 800-683-17 800-683-20 800-683-23 800-683-14 (2) 800-683-14 (2) 800-683-17 (2) 800-683-20 (2) 800-683-20 (2) 800-683-20 (2)

460V-3Ph-60Hz 800-683-15 800-683-18 800-683-21 800-683-24 800-683-15 (2) 800-683-15 (2) 800-683-18 (2) 800-683-21 (2) 800-683-21 (2) 800-683-21 (2)

NUMBER OF COMPRESSORS 1 1 1 1 2 2 2 2 2 2

OIL CHARGE PER COMPRESSOR, Liters 15 22 22 22 15 15 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 50 100 - 25

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 200 300 300 300 400 400 600 600 600 600

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
CONDENSER Tube Dia.- Rows - Fins per inch 3/8214 3/8314 3/8414 3/8414 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314
COIL
Total face area, Sq. ft. 87.5 87.5 87.5 87.5 100.1 100.1 140 140 140 175

AIRFLOW, CFM 45264 43920 47644 47644 63798 63798 93256 87032 87032 116570

NUMBER OF FAN/FAN DIA.,mm 4/762 4/762 4/800 4/800 6/800 6/800 8/800 8/800 8/800 10/800

FAN MOTOR RPM @ 230/380/460-3-60 1100/1100/1100 1100/1100/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100

COOLER
COOLER PART NUMBER 800-732-01 800-732-05 800-732-05 800-732-05 800-732-13 800-732-13 800-732-21 800-732-25 800-732-33 800-732-41

SHELL DIAMETER, mm 219.1 273 273 273 323.8 323.8 323.8 323.8 323.8 406.4

TOTAL LENGTH, mm 2316 2168 2168 2168 2498 2498 2698 2698 2698 2741

WATER HOLDING VOLUME, Liters 49.3 58 58 58 142 142 129.5 113.5 113.5 161.7

WATER IN/OUT PIPE DIA.mm 75 100 100 100 125 125 125 125 125 150

ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. 800-516-90 (2) N.A. N.A. 800-516-90 (2) 800-516-90 (2)

EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. T.E.V. N.A. N.A. T.E.V. T.E.V.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 1 1 1 1 2 2 2 2 2 2

REFRIGERANT CHARGE PER COMP., kg 33 39 45 50 33 33 39 45 47 48

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 72.2/68.7/63.4 72.6/69.1/63.8 75.4/71.9/66.6 75.6/72.1/66.8 74.4/71/65.7 74.5/71/65.7 75.3/71.8/66.5 78.4/74.9/69.6 78.4/74.9/69.6 78.7/75.2/69.9

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 1895/1944 2443/2501 2563/2621 2580/2638 3256/3398 3267/3398 4358/4488 4541/4655 4568/4682 5049/5211

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 2019/2068 2635/2693 2843/2901 2858/2916 3575/3717 3589/3731 4667/4797 4988/5102 5014/5128 5435/5597
NOTES: 1. All compressors with slider control valve unloading.
2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.

8
PHYSICAL DATA
UNIT SIZE ASY160B ASY170B ASY180B ASY190B ASY200B ASY215B ASY230B ASY240B ASY250B ASY270B

COMPRESSOR
800-683-22 (2)
PART NUMBER 208/230V-3Ph-60Hz 800-683-22 (2) 800-683-22 (2) 800-683-16 (3) 800-683-16 (3) 800-683-16 (3) 800-683-19 (1) 800-683-22 (3) 800-683-22 (3) 800-683-16 (4) 800-683-19 (4)
800-683-23 (2)
380V-3Ph-60Hz 800-683-23 (2) 800-683-23 (2) 800-683-17 (3) 800-683-17 (3) 800-683-17 (3) 800-683-20 (1) 800-683-23 (3) 800-683-23 (3) 800-683-17 (4) 800-683-20 (4)

800-683-24 (2)
460V-3Ph-60Hz 800-683-24 (2) 800-683-24 (2) 800-683-18 (3) 800-683-18 (3) 800-683-18 (3) 800-683-21 (1) 800-683-24 (3) 800-683-24 (3) 800-683-18 (4) 800-683-21 (4)

NUMBER OF COMPRESSORS 2 2 3 3 3 3 3 3 4 4

OIL CHARGE PER COMPRESSOR, Liters 22 22 22 22 22 22 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 25 100 - 16 100 - 12

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 600 600 900 900 900 900 900 900 1200 1200

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
3/8414 3/8414
CONDENSER Tube Dia.- Rows - Fins per inch 3/8314 3/8414 3/8314 3/8314 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314
COIL
Total face area, Sq. ft. 175 175 210 210 210 240 240 240 304 304

AIRFLOW, CFM 116570 108790 139884 133524 130548 140892 138276 138276 192048 192048

NUMBER OF FAN/FAN DIA.,mm 10/800 10/800 12/800 12/800 12/800 12/800 12/800 12/800 16/800 16/800

FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100

COOLER
COOLER PART NUMBER 800-732-41 800-732-41 800-732-11 800-732-11 800-732-11 800-732-12 800-732-45 800-732-45 800-732-25 (2) 800-732-41(2)

SHELL DIAMETER, mm 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 323.8 406.4

TOTAL LENGTH, mm 2741 2741 2717 2717 2717 3217 3717 3717 2698 2741

WATER HOLDING VOLUME, Liters 161.7 161.7 184.4 184.4 184.4 222.2 256 256 227 323.4

WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 150 125 150

ECONOMIZER
PART NUMBER N.A. 800-516-90 (2) N.A. 800-516-90 (2) 800-516-90 (3) N.A. 800-516-90 800-516-90 (3) N.A. N.A.

EXPANSION DEVICE N.A. T.E.V. N.A. T.E.V. T.E.V. N.A. T.E.V. T.E.V. N.A. N.A.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 2 2 3 3 3 3 3 3 4 4

REFRIGERANT CHARGE PER COMP., kg 50 54 39 42/39 42 50/45 54/50 54 39 45

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 78.9/75.4/70.1 78.9/75.4/70.1 77.1/73.6/68.3 77.1/73.6/68.3 77.1/73.6/68.3 80.3/76.8/71.5 80.4/76.9/71.6 80.4/76.9/71.6 81.4/77.9/72.6 81.4/77.9/72.6

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 5054/5216 5200/5362 6653/6838 6773/6958 6833/7018 7034/7256 7202/7458 7233/7489 8892/9120 9308/9632

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 5438/5600 5759/5921 7113/7298 7373/7558 7503/7688 7720/7942 7968/8224 7998/8254 9561/9789 9976/10300
NOTES: 1. All compressors with slider control valve unloading.
2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.

9
PHYSICAL DATA
UNIT SIZE ASY295B ASY310B ASY330B ASY350B ASY375B ASY400B ASY420B ASY450B ASY475B ASY500B

COMPRESSOR
800-683-22 (2) 800-683-16 (4) 800-683-22 (3) 800-683-22 (4)
PART NUMBER 208/230V-3Ph-60Hz 800-683-19 (2) 800-683-22 (4) 800-683-13 (2) 800-683-16 (6) 800-683-19 (6) 800-683-19 (6) 800-683-19 (3) 800-683-19 (2) 800-683-22 (6) 800-683-22 (6)
800-683-23 (2) 800-683-17 (4) 800-683-23 (3) 800-683-23 (4)
380V-3Ph-60Hz 800-683-20 (2) 800-683-23 (4) 800-683-14 (2) 800-683-17 (6) 800-683-20 (6) 800-683-20 (6) 800-683-20 (3) 800-683-20 (2) 800-683-23 (6) 800-683-23 (6)
800-683-24 (2) 800-683-18 (4) 800-683-24 (3) 800-683-24 (4)
460V-3Ph-60Hz 800-683-21 (2) 800-683-24 (4) 800-683-15 (2) 800-683-18 (6) 800-683-21 (6) 800-683-21 (6) 800-683-21 (3) 800-683-21 (2) 800-683-24 (6) 800-683-24 (6)

NUMBER OF COMPRESSORS 4 4 6 6 6 6 6 6 6 6

OIL CHARGE PER COMPRESSOR, Liters 22 22 22/15 22 22 22 22 22 22 22

CAPACITY CONTROL (STEPLESS) % 100 - 12 100 - 8

MOTOR OVERLOAD PROTECTION (INTERNAL) ELECTRONIC

OIL LUBRICATION INJECTION

TOTAL CRANKCASE HEATER WATTS 1200 1200 1600 1800 1800 1800 1800 1800 1800 1800

REFRIGERANT R-134a

EXPANSION DEVICE ELECTRONIC EXPANSION VALVE

CONTROL VOLTAGE 220V-1Ph-60Hz

AIRCOOLED CONDENSER
3/8414 3/8414
CONDENSER Tube Dia.- Rows - Fins per inch 3/8414 3/8414 3/8314 3/8414 3/8414 3/8314 3/8314 3/8414 3/8414 3/8414
COIL
Total face area, Sq. ft. 304 304 430.7 430.7 430.7 521.3 521.3 521.3 521.3 521.3

AIRFLOW, CFM 180560 180560 224046 220770 220770 281490 275110 269038 269038 269038

NUMBER OF FAN/FAN DIA.,mm 16/800 16/800 18/800 18/800 18/800 22/800 22/800 22/800 22/800 22/800

FAN MOTOR RPM @ 230/380/460-3-60 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100 1080/1080/1100

COOLER
COOLER PART NUMBER 800-732-41 (2) 800-732-41 (2) 800-732-73 (2) 800-732-54 (2) 800-732-11 (2) 800-732-11 (2) 800-732-11 (2) 800-732-65 (2) 800-732-65 (2) 800-732-65 (2)

SHELL DIAMETER, mm 406.4 406.4 406.4 406.4 406.4 406.4 406.4 457.2 457.2 457.2

TOTAL LENGTH, mm 2741 2741 2717 2717 2717 2717 2717 2762 2762 2762

WATER HOLDING VOLUME, Liters 323.4 323.4 323.4 323.4 368.8 368.8 368.8 504 504 504

WATER IN/OUT PIPE DIA.mm 150 150 150 150 150 150 150 200 200 200

ECONOMIZER
PART NUMBER N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. 800-516-90 (3) 800-516-90 (6)

EXPANSION DEVICE N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. T.E.V. T.E.V.

GENERAL
NUMBER OF REFRIGERANT CIRCUITS 4 4 6 6 6 6 6 6 6 6

REFRIGERANT CHARGE PER COMP., kg 50/45 50 39/33 39 45 47 50/45 50/45 54/50 54

SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) 81.5/78/72.7 81.6/78.1/72.8 79.4/75.8/70.6 79.4/75.9/70.6 82.9/79.3/74.1 83.1/79.5/74.3 83.2/79.7/74.4 83.2/79.7/74.4 83.3/79.8/74.5 83.3/79.8/74.5

SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg 9542/9866 9575/9899 11909/12233 12770/13094 13026/13396 13260/13630 13467/13837 14057/14561 14134/14638 14183/14687

SHIPPING /OPERATING WEIGHTS (Copper coils), kg 10512/10836 10545/10869 13122/13446 14142/14466 14401/14771 14408/14778 14873/15243 15716/16220 15793/16297 15842/16346

NOTES: 1. All compressors with slider control valve unloading.


2. All compressors operate at 3500 RPM @ 60Hz.
3. Cooler vent and drain size are 1/2" MPT.
4. All coolers are single face refrigerant connection.
5. Sound pressure level : 2dBA.

10
SELECTION PROCEDURE (English units)
DESIGN REQUIREMENTS
The following design requirements must be known to select a package chiller. ELEVATION ABOVE CAPACITY
CORRECTION
1. Required cooling capacity in tons SEA LEVEL (FT.) FACTOR
2. Leaving chilled water temperature in 0F (LCWT) 0 1.00
2000 0.99
3. Chilled water flow rate in GPM 4000 0.98
0 _
4. Chilled water cooling range in F (water in temp. water out temp.) 6000 0.97
5. Design ambient temperature 8000 0.96
10000 0.95
6. Minimum ambient temperature
TABLE - 1
7. Altitude
8. Electrical power supply EVAPORATOR FOULING CAPACITY POWER ARI
CORRECTION INPUT STANDARDS
FACTOR (HR-FT2-0F/BTU) FACTOR FACTOR
SAMPLE SELECTION 0.00010 1.000 1.000
Select an Air Cooled Packaged chiller for the following conditions: 0.00025 0.992 0.997
0.00050 0.978 0.990 ARI-550/590
Required system capacity is 115 tons at 540F entering chilled water 0.965
0.00075 0.984
and 440F leaving water. Design ambient temperature is 950F. 0.00100 0.951 0.978
Altitude is 2000 feet above sea level. TABLE - 2
Water cooler fouling factor is 0.00010. Power supply: 380V-3Ph-60Hz.
STEP-1: UNIT SELECTION
Entering the capacity performance data at given LCWT and ambient temperature.
+0.6
ASY120B chiller unit at sea level will produce 116.5 tons and 129.3 kW compressor

CORRECTION FACTOR (0F)


power input at 440F leaving chilled water temperature with 100F water temperature +0.4
difference and 950F ambient temperature.
+0.2

For the conditions required, the unit actual cooling capacity when corrected for
0
altitude (0.99) and fouling factor (1.0).
Capacity = 116.5x0.99x1.0 = 115.3 Tons, which then exceeds the requirements. -0.2

So the selection is correct.


-0.4
5 10 15 20
STEP-2: CHILLED WATER FLOW (GPM): CHILLED WATER TEMPERATURE RISE (0F)

Required capacity (Tons) x 24 115 x 24 TABLE - 3


Water GPM = = = 276 GPM
Cooling Range, T 100F

Referring to pressure drop chart (page # 23), pressure drop at 276 GPM = 17 ft. of water for selected model.
NOTE: The total flow rate should be divided by 2 for models ASY250B - ASY500B to find out the total pressure drop.
STEP-3: ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuit
ampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.

STEP-4: CHILLED WATER PUMP SELECTION


For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop
calculated in step 2.

STEP-5: LCWT CORRECTION


Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water tempera-
ture range is above 100F and subtract correction from design leaving chilled water temperature (LCWT) when water
temperature range is below 100F.
EXAMPLE:
If LCWT rise is 12.50F, enter correction curve at 12.50F and read the correction factor of 0.2. The corrected LCWT is
44+0.2 = 44.20F.
NOTE: 1.When the chilled water temperature rise is less than 50F, the high water flow rate will result to excessive
pressure drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.
2.Please refer to water pressure drop curves.

11
SELECTION PROCEDURE (Metric units)
DESIGN REQUIREMENTS
The following design requirements must be known to select a proper package chiller. ELEVATION ABOVE CAPACITY
CORRECTION
1. Required cooling capacity in kilowatt (kW) SEA LEVEL (Meter) FACTOR
2. Leaving chilled water temperature in 0C (LCWT) 0 1.00
600 0.99
3. Chilled water flow rate in LPS
1200 0.98
0 _
4. Chilled water cooling range in C (water in temp. water out temp.) 1800 0.97
5. Design ambient temperature 2400 0.96
3000 0.95
6. Minimum ambient temperature
7. Altitude TABLE - 1
8. Electrical power supply EVAPORATOR FOULING CAPACITY POWER ARI
CORRECTION INPUT STANDARDS
FACTOR (M2-0C/W) FACTOR FACTOR
SAMPLE SELECTION 0.000018 1.000 1.000
Select an Air Cooled Packaged chiller for the following conditions: 0.000044 0.992 0.997
0.000088 0.978 0.990 ARI-550/590
Required system capacity is 390 kW at 120C entering chilled water 0.000132 0.965 0.984
and 60C leaving water. Design ambient temperature is 350C. 0.000176 0.951 0.978
Altitude is 600 meter above sea level. TABLE - 2
Water cooler fouling factor is 0.000018. Power supply: 380V-3Ph-60Hz.
STEP-1: UNIT SELECTION
Entering the capacity performance data at given LCWT and ambient temperature. +0.33
ASY120B chiller unit at sea level will produce 407.9 kW and 129.1 kW compressor

CORRECTION FACTOR (0C)


power input at 60C leaving chilled water temperature with 60C water temperature +0.22

difference and 350C ambient temperature.


+0.11

For the conditions required, the unit actual cooling capacity when corrected for 0
altitude (0.99) and fouling factor (1.0).
Capacity = 407.9x0.99X1.0 = 403.8 kW, which then exceeds the requirements. -0.11

So the selection is correct.


-0.22
4 5 6 7 8 9 10
STEP-2: CHILLED WATER FLOW (LPS): CHILLED WATER TEMPERATURE RISE (0C)

Required capacity (kW) x 0.239 390 x 0.239 TABLE - 3


Water LPS = = = 15.5 LPS
Cooling Range, T 60 C
Referring to pressure drop chart (page # 23), pressure drop at 15.5 LPS = 40.3 kPa for selected model.
NOTE: The total flow rate should be divided by 2 for models ASY250B - ASY500B to find out the total pressure drop.

STEP-3: ELECTRICAL
Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ASY120B is to be sized for a minimum circuit
ampacity (MCA) of 311 Amps and maximum over current protection (MOCP) of 437 Amps.

STEP-4: CHILLED WATER PUMP SELECTION


For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop
calculated in step 2.
STEP-5: LCWT CORRECTION
Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water tempera-
ture range is above 60C and subtract correction from design leaving chilled water temperature (LCWT) when water
temperature range is below 60C.
EXAMPLE:
If LCWT rise is 7.40C, enter correction curve at 7.40C and read the correction factor of 0.11. The corrected LCWT is
60C+0.11 = 6.110C.

NOTE: 1.When the chilled water temperature rise is less than 30C, the high water flow rate will result to excessive
pressure drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing.
2.Please refer to water pressure drop curves.

12
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP.
WATER CAP.
COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 44.4 50.7 9.7 106.5 41.6 56.5 8.2 99.9 38.7 63.3 6.9 92.9 35.6 71.1 5.7 85.4 34.0 75.3 5.1 81.5
ASY 060B 53.1 61.3 9.7 127.4 49.8 68.9 8.1 119.5 46.3 77.9 6.7 111.1 42.6 88.1 5.5 102.2 40.7 93.7 5.0 97.6
ASY 070B 59.3 67.9 9.4 142.4 55.6 75.4 8.0 133.5 51.6 84.0 6.8 123.9 47.4 93.6 5.6 113.7 45.1 98.8 5.1 108.3
ASY 080B 65.9 83.4 8.7 158.1 62.0 93.2 7.4 148.8 58.0 104.0 6.2 139.3 53.8 115.9 5.2 129.2 51.6 122.3 4.8 123.9
ASY 090B 90.0 102.0 9.5 216.1 84.2 113.6 8.1 202.1 78.1 127.1 6.8 187.4 71.6 142.5 5.6 171.9 68.2 150.9 5.0 163.8
ASY 100B 94.8 112.5 9.2 227.5 90.2 128.3 7.7 216.4 85.1 146.8 6.5 204.2 79.5 168.1 5.3 190.8 76.5 179.8 4.8 183.6
ASY 120B 111.9 127.2 9.4 268.5 104.5 142.7 7.9 250.8 96.8 160.7 6.6 232.2 88.6 181.0 5.4 212.7 84.4 192.1 4.9 202.7
ASY 130B 124.5 144.0 9.4 298.7 116.0 159.5 8.0 278.3 107.0 177.0 6.7 256.7 97.4 196.3 5.5 233.7 92.3 206.7 5.0 221.6
ASY 140B 133.9 170.0 8.7 321.3 126.8 195.5 7.2 304.3 118.8 224.9 5.9 285.0 109.6 258.3 4.8 263.1 104.6 276.3 4.3 251.1
ASY 150B 142.3 166.6 9.2 341.4 134.8 191.2 7.7 323.5 126.2 219.6 6.3 303.0 116.6 251.8 5.2 279.8 111.3 269.2 4.6 267.2
ASY 160B 148.6 176.1 9.1 356.6 139.1 196.2 7.8 333.9 129.2 218.3 6.5 310.1 118.8 242.4 5.5 285.0 113.4 255.2 5.0 272.0
ASY 170B 159.9 186.3 9.3 383.7 152.7 212.6 7.9 366.5 144.8 242.0 6.7 347.5 136.1 274.6 5.6 326.7 131.5 292.1 5.1 315.5
ASY 180B 165.0 189.6 9.3 396.0 154.4 213.0 7.9 370.5 143.1 240.0 6.5 343.5 131.4 270.8 5.4 315.3 125.3 287.5 4.8 300.7
ASY 190B 176.8 205.8 9.3 424.3 167.9 235.9 7.8 403.0 158.4 271.3 6.5 380.2 148.3 312.3 5.3 356.0 143.1 334.8 4.8 343.4
ASY 200B 182.6 214.2 9.2 438.2 174.6 247.9 7.7 419.1 166.0 287.9 6.4 398.5 156.8 334.3 5.3 376.4 152.0 360.0 4.8 364.8
40 0F ASY 215B 205.3 247.4 9.1 492.6 192.2 275.5 7.7 461.2 178.4 306.5 6.5 428.1 163.7 340.5 5.4 393.0 156.1 358.6 4.9 374.7
ASY 230B 217.8 271.0 8.9 522.8 205.6 304.7 7.5 493.5 192.6 341.8 6.3 462.3 178.8 382.6 5.3 429.0 171.5 404.4 4.8 411.5
ASY 240B 226.6 291.5 8.7 543.7 216.3 332.6 7.3 519.1 205.0 378.4 6.1 491.9 192.5 429.1 5.1 462.0 185.8 456.4 4.7 445.9
ASY 250B 235.6 254.7 9.9 565.5 219.8 284.9 8.4 527.4 203.2 319.9 7.0 487.7 186.0 359.7 5.7 446.4 177.1 381.4 5.2 425.1
ASY 270B 257.1 299.7 9.3 617.0 238.6 331.2 7.9 572.7 219.0 366.4 6.6 525.7 198.3 405.0 5.5 476.0 187.5 425.6 4.9 450.1
ASY 295B 279.2 322.5 9.5 670.1 260.5 358.1 8.0 625.3 240.8 397.5 6.8 578.0 220.0 440.8 5.6 528.1 209.2 463.8 5.1 502.1
ASY 310B 294.7 357.5 9.1 707.2 275.7 398.1 7.7 661.6 255.7 442.7 6.5 613.7 234.8 491.3 5.4 563.5 223.9 517.1 4.9 537.4
ASY 330B 314.4 351.7 9.8 754.6 294.0 393.6 8.2 705.6 272.5 442.3 6.9 653.9 249.9 497.9 5.6 599.7 238.2 528.2 5.1 571.6
ASY 350B 331.2 377.2 9.7 794.9 309.5 423.4 8.1 742.8 286.6 477.0 6.7 687.9 262.7 537.9 5.5 630.4 250.2 571.1 5.0 600.6
ASY 375B 359.9 442.2 9.1 863.7 334.7 490.1 7.7 803.2 307.8 543.7 6.4 738.7 279.3 602.8 5.3 670.2 264.3 634.4 4.7 634.4
ASY 400B 363.8 432.6 9.2 873.0 339.3 479.9 7.8 814.4 313.3 533.0 6.5 751.9 285.5 591.8 5.4 685.3 271.0 623.2 4.9 650.3
ASY 420B 388.5 473.6 9.0 932.3 363.9 527.4 7.7 873.5 337.9 587.1 6.4 811.0 310.3 652.9 5.4 744.6 295.8 688.0 4.9 709.9
ASY 450B 430.0 495.5 9.6 1032.0 401.8 551.0 8.1 964.3 372.1 612.2 6.8 893.1 340.9 679.3 5.7 818.0 324.6 715.0 5.1 779.0
ASY 475B 458.3 558.4 9.2 1100.0 432.8 629.3 7.7 1038.7 405.5 707.8 6.5 973.2 376.2 794.0 5.4 903.0 360.8 840.1 4.9 866.0
ASY 500B 471.9 589.3 9.0 1132.6 449.5 671.8 7.6 1078.8 424.8 763.8 6.3 1019.6 397.7 865.4 5.3 954.5 383.1 919.8 4.8 919.5
ASY 050B 47.3 52.1 10.0 113.6 44.3 58.0 8.5 106.4 41.2 64.7 7.2 98.8 37.8 72.3 5.9 90.8 36.1 76.5 5.4 86.6

13
ASY 060B 57.0 62.9 10.2 136.8 53.4 70.6 8.5 128.2 49.6 79.5 7.1 119.1 45.7 89.6 5.8 109.7 43.7 95.1 5.3 104.8
ASY 070B 63.9 69.8 9.9 153.5 59.9 77.4 8.5 143.7 55.6 86.0 7.1 133.4 50.9 95.5 5.9 122.3 48.5 100.7 5.4 116.4
ASY 080B 71.0 85.5 9.1 170.4 66.9 95.5 7.8 160.5 62.5 106.6 6.6 150.0 57.9 118.7 5.5 138.9 55.4 125.1 5.0 133.1
ASY 090B 92.4 103.2 9.7 221.9 86.5 114.8 8.2 207.7 80.3 128.3 6.9 192.7 73.7 143.7 5.7 176.8 70.2 152.0 5.2 168.6
ASY 100B 97.1 113.6 9.3 233.0 92.4 129.4 7.9 221.7 87.2 147.9 6.6 209.3 81.5 169.2 5.4 195.5 78.4 180.8 4.9 188.2
ASY 120B 114.4 128.4 9.6 274.6 107.0 143.9 8.1 256.8 99.2 161.9 6.7 238.0 91.0 182.3 5.5 218.4 86.8 193.3 5.0 208.3
ASY 130B 127.2 145.2 9.5 305.2 118.6 160.9 8.1 284.7 109.5 178.5 6.8 262.9 99.8 197.9 5.6 239.6 94.8 208.2 5.1 227.5
ASY 140B 136.5 171.3 8.8 327.5 129.3 197.0 7.3 310.4 121.2 226.5 6.0 290.8 111.9 260.0 4.9 268.5 106.8 278.1 4.4 256.3
ASY 150B 145.8 168.1 9.3 349.9 138.2 192.9 7.8 331.6 129.4 221.4 6.5 310.6 119.5 253.7 5.3 286.9 114.1 271.1 4.7 273.9
ASY 160B 152.5 177.8 9.3 366.0 142.9 198.1 7.9 342.9 132.7 220.4 6.7 318.6 122.1 244.7 5.6 293.0 116.6 257.7 5.1 279.8
ASY 170B 163.7 187.6 9.5 392.9 156.4 214.1 8.1 375.4 148.3 243.8 6.8 356.0 139.4 276.6 5.7 334.6 134.6 294.3 5.2 323.1
ASY 180B 171.4 192.5 9.6 411.5 160.4 215.9 8.1 385.1 148.9 242.9 6.7 357.4 136.8 273.6 5.5 328.3 130.6 290.2 5.0 313.4
ASY 190B 183.5 208.5 9.5 440.3 174.3 238.8 8.0 418.4 164.6 274.4 6.6 395.0 154.3 315.5 5.5 370.2 148.9 338.1 5.0 357.3
ASY 200B 189.3 216.9 9.5 454.4 181.2 250.8 7.9 434.8 172.4 291.1 6.6 413.7 163.0 337.7 5.4 391.2 158.1 363.5 4.9 379.4
42 0F ASY 215B 210.3 249.7 9.3 504.7 197.0 278.0 7.9 472.9 183.0 309.3 6.6 439.2 168.2 343.5 5.5 403.6 160.4 361.8 5.0 385.0
ASY 230B 222.9 273.3 9.0 535.0 210.5 307.2 7.7 505.3 197.3 344.7 6.4 473.6 183.2 385.8 5.4 439.7 175.8 407.9 4.9 421.8
ASY 240B 231.5 293.6 8.8 555.6 221.0 335.0 7.4 530.5 209.5 381.3 6.2 502.8 196.8 432.4 5.2 472.2 189.9 459.9 4.7 455.7
ASY 250B 242.2 257.5 10.1 581.3 226.1 287.9 8.5 542.6 209.3 323.0 7.1 502.3 191.9 362.7 5.9 460.5 182.9 384.3 5.3 439.0
ASY 270B 264.0 303.2 9.5 633.7 245.3 335.0 8.1 588.7 225.4 370.3 6.8 540.9 204.3 409.0 5.6 490.4 193.4 429.6 5.0 464.0
ASY 295B 286.7 325.8 9.7 688.0 267.7 361.7 8.2 642.4 247.6 401.5 6.9 594.3 226.5 445.0 5.7 543.5 215.4 468.1 5.2 517.1
ASY 310B 302.3 361.1 9.3 725.6 283.0 402.1 7.9 679.2 262.7 447.1 6.6 630.5 241.3 496.2 5.5 579.2 230.2 522.3 5.0 552.6
ASY 330B 322.8 355.3 9.9 774.8 302.1 397.4 8.4 725.0 280.3 446.3 7.0 672.7 257.4 501.8 5.8 617.7 245.6 532.0 5.2 589.4
ASY 350B 340.0 381.0 9.8 816.1 318.0 427.4 8.3 763.2 294.9 481.0 6.9 707.7 270.6 541.9 5.6 649.5 258.1 575.1 5.1 619.5
ASY 375B 369.1 447.0 9.2 885.8 343.5 495.2 7.8 824.4 316.3 549.1 6.5 759.1 287.4 608.3 5.4 689.7 272.2 639.9 4.8 653.3
ASY 400B 378.1 439.5 9.4 907.4 352.8 487.1 8.0 846.8 325.9 540.4 6.7 782.1 297.2 599.2 5.6 713.2 282.1 630.6 5.0 677.1
ASY 420B 403.9 480.6 9.3 969.3 378.4 534.9 7.9 908.2 351.4 595.1 6.6 843.4 322.7 661.2 5.5 774.5 307.7 696.5 5.0 738.5
ASY 450B 439.1 499.4 9.7 1053.8 410.5 555.3 8.3 985.3 380.5 617.0 6.9 913.2 348.8 684.5 5.8 837.2 332.3 720.4 5.2 797.6
ASY 475B 467.3 562.4 9.3 1121.6 441.5 633.8 7.8 1059.6 413.8 712.9 6.6 993.1 384.0 799.7 5.5 921.7 368.3 846.1 5.0 884.0
ASY 500B 480.7 593.1 9.1 1153.7 458.0 676.2 7.7 1099.2 432.9 768.8 6.4 1038.9 405.2 871.1 5.3 972.5 390.3 925.9 4.8 936.8

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 49.7 53.3 10.3 119.3 46.5 59.1 8.8 111.5 43.1 65.7 7.4 103.3 39.5 73.3 6.1 94.7 37.6 77.3 5.5 90.3
ASY 060B 60.4 64.4 10.5 145.0 56.5 72.0 8.9 135.6 52.4 80.8 7.4 125.8 48.2 90.8 6.1 115.6 46.0 96.3 5.5 110.4
ASY 070B 68.2 71.5 10.3 163.6 63.7 79.1 8.8 152.9 59.0 87.7 7.4 141.5 53.9 97.1 6.2 129.4 51.3 102.2 5.6 123.1
ASY 080B 76.0 87.6 9.6 182.3 71.4 97.7 8.1 171.3 66.5 108.9 6.9 159.6 61.4 121.0 5.7 147.4 58.7 127.5 5.2 141.0
ASY 090B 94.7 104.3 9.8 227.2 88.8 116.0 8.4 213.0 82.5 129.5 7.0 198.0 75.8 144.9 5.8 182.0 72.4 153.2 5.3 173.7
ASY 100B 99.2 114.5 9.4 238.0 94.4 130.4 8.0 226.7 89.2 149.0 6.7 214.1 83.4 170.3 5.5 200.2 80.3 181.9 5.0 192.8
ASY 120B 116.5 129.3 9.7 279.5 109.2 145.0 8.2 262.0 101.5 163.1 6.8 243.6 93.5 183.6 5.6 224.3 89.3 194.7 5.1 214.4
ASY 130B 128.9 146.1 9.6 309.4 120.6 161.9 8.2 289.4 111.7 179.7 6.9 268.1 102.2 199.3 5.7 245.3 97.2 209.8 5.2 233.3
ASY 140B 137.9 172.0 8.8 331.0 130.9 197.9 7.4 314.2 122.9 227.7 6.1 295.0 113.7 261.3 4.9 272.9 108.7 279.6 4.4 260.8
ASY 150B 149.2 169.6 9.5 358.1 141.5 194.6 8.0 339.6 132.7 223.3 6.6 318.5 122.7 255.7 5.4 294.4 117.2 273.2 4.8 281.2
ASY 160B 156.1 179.4 9.4 374.7 146.5 200.0 8.0 351.6 136.3 222.5 6.8 327.2 125.6 247.2 5.7 301.5 120.0 260.3 5.2 288.1
ASY 170B 167.1 188.8 9.6 401.1 159.8 215.5 8.2 383.5 151.7 245.4 6.9 364.1 142.7 278.6 5.8 342.4 137.8 296.4 5.2 330.8
ASY 180B 177.7 195.3 9.8 426.6 166.4 218.8 8.3 399.5 154.6 245.9 6.9 371.1 142.3 276.5 5.7 341.5 135.9 293.1 5.2 326.2
ASY 190B 189.9 211.1 9.7 455.8 180.5 241.7 8.2 433.3 170.6 277.5 6.8 409.5 160.1 318.7 5.6 384.3 154.6 341.3 5.1 371.1
ASY 200B 195.8 219.4 9.7 470.0 187.5 253.7 8.1 450.0 178.6 294.2 6.8 428.6 169.1 341.1 5.6 405.7 164.1 367.0 5.1 393.8
44 0F ASY 215B 214.2 251.5 9.4 514.0 201.1 280.1 8.0 482.6 187.2 311.8 6.7 449.3 172.5 346.5 5.6 413.9 164.7 365.0 5.1 395.4
ASY 230B 226.5 274.9 9.1 543.7 214.3 309.2 7.7 514.4 201.3 347.1 6.5 483.0 187.2 388.8 5.5 449.3 179.8 411.1 5.0 431.5
ASY 240B 234.8 295.1 8.9 563.5 224.5 336.8 7.5 538.8 213.0 383.5 6.3 511.3 200.3 435.2 5.2 480.8 193.4 463.0 4.8 464.2
ASY 250B 249.2 260.5 10.3 598.2 233.0 291.2 8.7 559.3 216.2 326.4 7.3 518.9 198.7 366.2 6.0 476.9 189.7 387.9 5.4 455.4
ASY 270B 271.1 306.8 9.6 650.7 252.3 338.9 8.2 605.6 232.4 374.6 6.9 557.7 211.2 413.6 5.7 506.8 200.1 434.3 5.2 480.2
ASY 295B 293.9 329.1 9.8 705.4 274.9 365.4 8.3 659.7 254.8 405.6 7.0 611.5 233.5 449.5 5.8 560.4 222.4 473.0 5.3 533.7
ASY 310B 309.5 364.4 9.4 742.9 290.2 406.0 8.0 696.5 269.8 451.6 6.7 647.5 248.3 501.3 5.6 595.9 237.1 527.8 5.1 569.0
ASY 330B 330.4 358.7 10.1 792.9 309.7 401.1 8.5 743.2 287.9 450.2 7.1 691.1 265.1 505.8 5.9 636.3 253.3 536.0 5.3 608.0
ASY 350B 347.6 384.3 10.0 834.2 325.7 431.1 8.4 781.6 302.7 485.0 7.0 726.4 278.6 546.1 5.8 668.7 266.2 579.2 5.2 638.9
ASY 375B 376.4 450.8 9.3 903.4 351.0 499.6 7.9 842.5 324.0 553.9 6.6 777.6 295.2 613.7 5.5 708.4 280.0 645.5 4.9 672.1
ASY 400B 391.8 446.1 9.6 940.3 365.9 494.1 8.2 878.1 338.2 547.6 6.9 811.8 308.8 606.6 5.7 741.1 293.3 638.0 5.2 704.0
ASY 420B 418.4 487.4 9.5 1004.2 392.3 542.1 8.1 941.4 364.5 602.8 6.8 874.8 335.0 669.4 5.7 803.9 319.5 704.9 5.1 766.8
ASY 450B 446.3 502.6 9.8 1071.2 418.3 559.1 8.4 1003.9 388.6 621.6 7.0 932.7 357.3 690.0 5.9 857.4 340.9 726.4 5.3 818.2
ASY 475B 473.8 565.2 9.4 1137.1 448.4 637.3 7.9 1076.1 421.0 717.3 6.7 1010.5 391.5 805.1 5.5 939.6 375.9 852.1 5.0 902.1
ASY 500B 486.7 595.7 9.2 1168.1 464.3 679.5 7.7 1114.4 439.5 772.9 6.5 1054.8 412.0 876.2 5.4 988.8 397.1 931.6 4.9 953.1
ASY 050B 51.3 54.1 10.5 123.0 47.8 59.8 8.9 114.8 44.3 66.4 7.5 106.3 40.5 73.8 6.2 97.3 38.6 77.9 5.6 92.7

14
ASY 060B 62.7 65.3 10.8 150.5 58.6 73.0 9.1 140.5 54.3 81.8 7.6 130.2 49.8 91.7 6.2 119.6 47.5 97.1 5.6 114.1
ASY 070B 71.0 72.6 10.6 170.4 66.3 80.3 9.1 159.1 61.3 88.8 7.6 147.0 55.9 98.2 6.3 134.3 53.2 103.3 5.8 127.6
ASY 080B 79.4 89.0 9.9 190.5 74.4 99.2 8.4 178.6 69.2 110.4 7.0 166.2 63.8 122.6 5.9 153.1 60.9 129.1 5.3 146.2
ASY 090B 97.5 105.7 10.0 233.9 91.6 117.5 8.5 219.7 85.3 131.1 7.2 204.7 78.6 146.4 6.0 188.7 75.1 154.7 5.4 180.3
ASY 100B 101.3 115.6 9.6 243.2 97.0 131.7 8.1 232.8 91.7 150.4 6.8 220.2 85.9 171.6 5.6 206.2 82.8 183.2 5.1 198.7
ASY 120B 119.2 130.5 9.8 286.1 112.2 146.5 8.3 269.2 104.8 164.8 7.0 251.5 97.1 185.5 5.8 232.9 93.0 196.7 5.3 223.3
ASY 130B 131.2 147.1 9.7 314.9 123.2 163.3 8.3 295.8 114.7 181.4 7.0 275.3 105.5 201.4 5.8 253.3 100.7 212.0 5.3 241.7
ASY 140B 139.6 172.8 8.9 335.1 132.9 199.0 7.4 319.0 125.2 229.2 6.1 300.5 116.3 263.2 5.0 279.0 111.3 281.7 4.5 267.2
ASY 150B 153.5 171.5 9.7 368.5 145.8 196.7 8.1 349.9 136.9 225.7 6.7 328.6 126.8 258.3 5.5 304.3 121.2 275.9 4.9 291.0
ASY 160B 160.7 181.5 9.6 385.6 151.1 202.3 8.2 362.6 140.9 225.3 6.9 338.3 130.2 250.4 5.8 312.5 124.6 263.7 5.3 299.0
ASY 170B 171.4 190.3 9.8 411.3 164.1 217.3 8.3 393.8 155.9 247.5 7.0 374.2 146.9 281.0 5.9 352.5 141.9 299.1 5.4 340.7
ASY 180B 184.0 198.2 10.0 441.6 172.5 221.8 8.5 413.9 160.4 249.0 7.1 385.0 147.9 279.6 5.9 354.9 141.4 296.1 5.3 339.4
ASY 190B 196.3 213.8 10.0 471.0 186.7 244.6 8.4 448.2 176.6 280.6 7.0 423.9 166.0 321.9 5.8 398.3 160.4 344.6 5.2 385.0
ASY 200B 202.2 222.0 9.9 485.3 193.8 256.6 8.3 465.0 184.7 297.4 6.9 443.3 175.1 344.5 5.7 420.2 170.0 370.5 5.2 408.0
46 0F ASY 215B 219.0 253.7 9.5 525.5 206.2 282.8 8.1 494.9 192.6 315.0 6.8 462.4 178.1 350.4 5.7 427.5 170.5 369.2 5.2 409.2
ASY 230B 230.9 276.9 9.2 554.2 219.0 311.6 7.9 525.6 206.2 350.1 6.6 494.9 192.4 392.5 5.6 461.7 185.0 415.2 5.1 444.1
ASY 240B 238.7 296.8 9.0 573.0 228.7 339.0 7.6 548.9 217.5 386.3 6.4 521.9 204.9 438.7 5.3 491.7 198.0 466.8 4.9 475.2
ASY 250B 258.4 264.5 10.5 620.2 242.2 295.6 8.9 581.2 225.3 331.1 7.5 540.7 207.8 371.1 6.2 498.7 198.8 392.7 5.6 477.0
ASY 270B 280.3 311.4 9.8 672.6 261.5 344.1 8.4 627.6 241.5 380.2 7.1 579.6 220.2 419.6 5.9 528.5 209.1 440.5 5.3 501.7
ASY 295B 303.1 333.3 10.0 727.5 284.2 370.2 8.5 682.0 264.1 411.0 7.2 633.8 242.7 455.5 6.0 582.5 231.5 479.3 5.5 555.7
ASY 310B 318.6 368.7 9.6 764.7 299.3 411.0 8.1 718.4 279.0 457.3 6.9 669.5 257.4 508.0 5.7 617.6 246.1 535.0 5.2 590.5
ASY 330B 339.7 362.8 10.3 815.3 319.2 405.7 8.7 766.2 297.7 455.2 7.3 714.5 275.1 511.0 6.1 660.2 263.4 541.2 5.5 632.1
ASY 350B 356.9 388.4 10.1 856.4 335.2 435.7 8.6 804.6 312.6 490.0 7.2 750.1 288.8 551.4 5.9 693.2 276.6 584.8 5.4 663.7
ASY 375B 385.2 455.4 9.4 924.5 360.3 504.9 8.0 864.7 333.6 560.0 6.7 800.7 305.1 620.5 5.6 732.2 290.1 652.7 5.1 696.1
ASY 400B 405.3 452.7 9.8 972.7 378.9 501.1 8.4 909.3 350.6 555.0 7.1 841.5 320.5 614.1 5.9 769.3 304.7 645.5 5.3 731.3
ASY 420B 432.6 493.9 9.7 1038.2 405.9 549.3 8.2 974.1 377.5 610.5 6.9 905.9 347.2 677.6 5.8 833.4 331.4 713.4 5.3 795.3
ASY 450B 456.6 507.1 10.0 1095.8 429.6 564.8 8.5 1031.0 400.8 628.5 7.2 962.0 370.2 698.3 6.0 888.5 354.1 735.6 5.5 849.9
ASY 475B 482.6 569.1 9.5 1158.4 458.2 642.4 8.0 1099.6 431.6 723.7 6.8 1035.8 402.7 813.2 5.7 966.6 387.4 861.1 5.1 929.7
ASY 500B 494.7 599.2 9.3 1187.4 473.1 684.0 7.8 1135.5 449.0 778.7 6.6 1077.6 422.0 883.6 5.5 1012.8 407.3 939.9 5.0 977.6

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio
PERFORMANCE DATA (English units)
LEAVING 950F AMBIENT TEMPERATURE 1050F AMBIENT TEMPERATURE 1150F AMBIENT TEMPERATURE 1250F AMBIENT TEMPERATURE 1300F AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
EER EER FLOW EER EER EER
(LCWT) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM) (Tons) kW (GPM)
ASY 050B 52.6 54.7 10.7 126.2 49.1 60.5 9.1 117.7 45.4 67.0 7.6 108.9 41.5 74.4 6.3 99.7 39.5 78.4 5.7 94.9
ASY 060B 64.5 66.1 11.0 154.7 60.2 73.8 9.2 144.4 55.8 82.6 7.7 133.9 51.2 92.4 6.3 122.9 48.9 97.8 5.7 117.3
ASY 070B 73.1 73.5 10.8 175.6 68.3 81.2 9.2 163.8 63.1 89.7 7.8 151.4 57.6 99.1 6.5 138.2 54.7 104.1 5.9 131.3
ASY 080B 81.8 90.1 10.0 196.3 76.7 100.3 8.5 184.0 71.3 111.6 7.2 171.1 65.6 123.8 6.0 157.5 62.7 130.4 5.5 150.4
ASY 090B 101.1 107.5 10.2 242.6 95.1 119.4 8.7 228.3 88.8 133.0 7.4 213.1 82.0 148.3 6.2 196.8 78.5 156.5 5.6 188.3
ASY 100B 105.1 117.3 9.8 252.3 100.3 133.4 8.3 240.8 95.0 152.1 7.0 228.0 89.0 173.3 5.8 213.7 85.8 184.9 5.2 206.0
ASY 120B 123.6 132.5 10.0 296.7 116.8 148.8 8.5 280.3 109.6 167.4 7.2 263.0 102.0 188.3 6.0 244.8 98.1 199.6 5.5 235.4
ASY 130B 135.3 149.0 9.9 324.7 127.6 165.6 8.5 306.3 119.3 184.0 7.2 286.4 110.4 204.4 6.0 264.9 105.7 215.2 5.5 253.6
ASY 140B 143.2 174.6 9.1 343.7 136.7 201.2 7.6 328.1 129.1 231.8 6.3 309.8 120.3 266.2 5.1 288.7 115.4 284.8 4.6 276.9
ASY 150B 159.1 173.8 9.9 381.7 151.2 199.4 8.3 362.9 142.2 228.6 6.9 341.2 131.8 261.4 5.6 316.4 126.2 279.1 5.1 302.9
ASY 160B 166.6 184.1 9.8 399.9 157.0 205.3 8.4 376.7 146.7 228.7 7.1 352.1 135.8 254.2 6.0 325.9 130.1 267.9 5.4 312.2
ASY 170B 177.1 192.3 10.1 424.9 169.7 219.6 8.5 407.3 161.4 250.2 7.2 387.4 152.2 284.1 6.0 365.2 147.1 302.4 5.5 353.1
ASY 180B 190.2 201.0 10.2 456.5 178.5 224.9 8.6 428.3 166.2 252.1 7.3 399.0 153.5 282.8 6.0 368.4 146.9 299.3 5.5 352.6
ASY 190B 202.5 216.4 10.2 486.0 192.8 247.5 8.6 462.8 182.6 283.7 7.1 438.3 171.8 325.2 5.9 412.3 166.1 347.9 5.4 398.7
ASY 200B 208.4 224.5 10.1 500.3 199.9 259.4 8.5 479.8 190.8 300.5 7.1 457.8 181.0 347.9 5.9 434.3 175.8 374.0 5.3 421.9
48 0F ASY 215B 226.2 257.1 9.7 542.9 213.6 286.7 8.3 512.6 200.1 319.5 7.0 480.2 185.6 355.5 5.9 445.4 177.9 374.7 5.4 427.1
ASY 230B 237.9 280.0 9.4 570.9 226.1 315.3 8.0 542.6 213.3 354.4 6.8 512.0 199.5 397.6 5.7 478.8 192.1 420.8 5.2 461.1
ASY 240B 245.3 299.7 9.1 588.7 235.3 342.5 7.7 564.7 224.1 390.4 6.5 537.7 211.4 443.5 5.4 507.3 204.4 472.1 5.0 490.7
ASY 250B 269.6 269.5 10.8 647.1 253.2 301.0 9.2 607.7 236.2 336.8 7.7 566.8 218.4 376.9 6.4 524.0 209.2 398.6 5.9 502.0
ASY 270B 291.7 317.3 10.1 700.0 272.7 350.5 8.6 654.5 252.5 387.0 7.3 606.0 230.9 426.8 6.1 554.1 219.5 447.9 5.5 526.9
ASY 295B 314.9 338.7 10.2 755.7 295.8 376.2 8.7 709.9 275.5 417.6 7.4 661.1 253.8 462.8 6.2 609.1 242.4 486.8 5.6 581.8
ASY 310B 330.4 374.4 9.8 793.0 311.0 417.3 8.3 746.3 290.3 464.5 7.0 696.8 268.4 516.1 5.9 644.1 256.8 543.6 5.4 616.4
ASY 330B 352.2 368.4 10.5 845.2 331.6 411.8 8.9 795.9 310.0 461.6 7.5 744.1 287.3 517.5 6.2 689.6 275.6 547.8 5.7 661.3
ASY 350B 369.5 394.1 10.4 886.8 347.9 441.9 8.8 834.9 325.2 496.6 7.4 780.5 301.5 558.3 6.1 723.6 289.2 591.8 5.5 694.2
ASY 375B 397.7 462.0 9.6 954.6 372.9 512.3 8.2 895.0 346.3 568.1 6.9 831.0 317.6 629.2 5.7 762.4 302.5 661.7 5.2 726.1
ASY 400B 418.5 459.1 10.0 1004.4 391.6 508.0 8.5 939.9 362.9 562.2 7.2 871.1 332.3 621.6 6.0 797.5 316.2 653.2 5.5 758.8
ASY 420B 446.4 500.3 9.9 1071.3 419.2 556.3 8.4 1006.0 390.3 618.1 7.1 936.6 359.4 685.8 5.9 862.6 343.2 721.8 5.4 823.8
ASY 450B 473.8 514.7 10.2 1137.0 447.4 573.7 8.7 1073.9 419.3 639.0 7.4 1006.3 389.1 710.6 6.2 933.8 373.2 748.8 5.7 895.6
ASY 475B 498.5 576.2 9.7 1196.3 474.6 650.8 8.2 1139.0 448.5 733.9 6.9 1076.3 419.9 825.4 5.8 1007.8 404.6 874.5 5.3 971.0
ASY 500B 509.7 605.7 9.4 1223.3 488.5 691.9 8.0 1172.5 464.7 788.3 6.7 1115.3 437.9 895.2 5.6 1050.8 423.2 952.6 5.1 1015.6
ASY 050B 54.3 55.6 10.9 130.4 50.7 61.4 9.3 121.8 47.0 67.9 7.8 112.8 43.1 75.2 6.5 103.3 41.0 79.1 5.9 98.4

15
ASY 060B 66.6 67.1 11.2 159.7 62.2 74.8 9.4 149.3 57.7 83.6 7.9 138.6 53.1 93.5 6.5 127.5 50.7 98.8 5.9 121.7
ASY 070B 75.4 74.4 11.0 181.0 70.5 82.2 9.4 169.1 65.2 90.8 8.0 156.5 59.6 100.2 6.6 143.1 56.7 105.3 6.0 136.1
ASY 080B 84.2 91.1 10.2 202.0 79.0 101.4 8.7 189.5 73.5 112.8 7.3 176.4 67.7 125.2 6.1 162.5 64.7 131.8 5.6 155.3
ASY 090B 104.7 109.4 10.4 251.4 98.5 121.2 8.9 236.4 91.9 134.8 7.5 220.6 84.9 149.8 6.3 203.7 81.2 157.9 5.8 194.9
ASY 100B 108.6 119.0 10.0 260.7 103.6 135.1 8.5 248.7 98.0 153.7 7.1 235.3 91.8 174.8 5.9 220.4 88.5 186.3 5.4 212.4
ASY 120B 128.4 134.7 10.3 308.1 121.1 151.0 8.7 290.7 113.6 169.6 7.4 272.6 105.6 190.4 6.2 253.5 101.5 201.7 5.6 243.6
ASY 130B 140.8 151.6 10.1 337.9 132.7 168.2 8.7 318.4 123.9 186.7 7.4 297.5 114.5 206.9 6.2 274.8 109.5 217.7 5.6 262.9
ASY 140B 148.8 177.4 9.3 357.2 141.8 204.2 7.8 340.4 133.7 234.8 6.4 320.9 124.4 269.2 5.2 298.5 119.2 287.7 4.7 286.1
ASY 150B 164.2 176.0 10.1 394.1 156.0 201.7 8.5 374.4 146.6 231.0 7.0 351.8 135.9 263.9 5.8 326.1 130.1 281.6 5.2 312.1
ASY 160B 172.4 186.7 10.1 413.8 162.4 208.1 8.6 389.7 151.7 231.7 7.3 364.0 140.3 257.4 6.1 336.7 134.3 271.1 5.6 322.4
ASY 170B 182.9 194.4 10.3 439.0 175.2 221.9 8.7 420.5 166.6 252.7 7.4 399.8 156.9 286.8 6.2 376.5 151.6 305.2 5.6 363.9
ASY 180B 196.1 203.8 10.4 470.7 184.2 227.8 8.8 442.1 171.8 255.2 7.4 412.4 158.9 285.9 6.2 381.3 152.2 302.4 5.6 365.2
ASY 190B 208.4 219.0 10.3 500.2 198.6 250.3 8.7 476.7 188.3 286.7 7.3 451.9 177.3 328.3 6.1 425.5 171.5 351.0 5.5 411.6
ASY 200B 214.4 226.9 10.3 514.4 205.7 262.1 8.7 493.7 196.5 303.5 7.2 471.5 186.5 351.0 6.0 447.7 181.3 377.2 5.4 435.1
50 0F ASY 215B 234.7 261.0 9.9 563.3 221.5 290.9 8.5 531.6 207.3 323.8 7.2 497.6 192.2 360.0 6.0 461.2 184.1 379.2 5.5 442.0
ASY 230B 246.8 284.0 9.7 592.3 234.4 319.6 8.2 562.5 221.0 359.1 6.9 530.3 206.4 402.6 5.8 495.3 198.6 425.9 5.3 476.7
ASY 240B 254.2 303.6 9.3 610.1 243.6 346.8 7.9 584.7 231.7 395.1 6.7 556.1 218.3 448.6 5.6 523.8 210.9 477.4 5.1 506.2
ASY 250B 278.6 273.6 11.0 668.7 261.7 305.2 9.4 628.1 244.1 341.0 7.9 585.8 225.6 381.1 6.6 541.5 216.1 402.7 6.0 518.6
ASY 270B 301.5 322.3 10.3 723.6 281.9 355.6 8.8 676.5 260.9 392.2 7.4 626.2 238.5 432.0 6.2 572.5 226.8 453.1 5.6 544.3
ASY 295B 325.7 343.7 10.4 781.7 305.9 381.4 8.9 734.1 284.8 423.0 7.5 683.5 262.3 468.3 6.3 629.5 250.5 492.5 5.7 601.1
ASY 310B 341.8 379.9 10.0 820.3 321.5 423.1 8.5 771.7 300.1 470.7 7.2 720.1 277.2 522.6 6.0 665.2 265.2 550.2 5.5 636.4
ASY 330B 365.0 374.3 10.7 875.9 343.6 417.8 9.1 824.7 321.2 467.4 7.7 771.0 297.7 523.2 6.4 714.5 285.5 553.2 5.8 685.1
ASY 350B 383.2 400.3 10.6 919.6 360.7 448.2 9.0 865.7 337.2 503.0 7.5 809.4 312.7 564.6 6.3 750.4 300.0 597.9 5.7 719.9
ASY 375B 412.6 469.8 9.8 990.1 386.7 520.4 8.4 928.1 359.0 576.3 7.1 861.6 329.3 637.3 5.9 790.3 313.6 669.7 5.3 752.6
ASY 400B 431.0 465.2 10.2 1034.3 403.8 514.6 8.7 969.1 374.7 569.2 7.4 899.2 343.5 628.9 6.1 824.5 327.2 660.6 5.6 785.2
ASY 420B 459.2 506.4 10.1 1102.2 431.7 562.9 8.6 1036.1 402.4 625.3 7.2 965.7 371.0 693.6 6.1 890.5 354.5 729.9 5.5 850.9
ASY 450B 491.6 522.6 10.5 1179.8 463.8 581.9 8.9 1113.2 434.2 647.5 7.6 1042.1 402.4 719.2 6.3 965.8 385.7 757.4 5.8 925.6
ASY 475B 517.0 584.4 9.9 1240.7 491.7 659.7 8.4 1180.0 464.0 743.2 7.1 1113.6 433.8 835.3 5.9 1041.1 417.6 884.5 5.4 1002.3
ASY 500B 528.2 613.8 9.7 1267.6 505.7 700.7 8.2 1213.6 480.3 797.8 6.9 1152.7 451.8 905.3 5.7 1084.3 436.3 962.9 5.2 1047.1

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
GPM - Gallons Per Minute 2. Performance data are based on 100F water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator. 6. EER for entire unit. Refer to electrical data for fan kW.
EER - Energy Efficiency Ratio
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 154.2 50.4 2.81 6.1 145.5 55.6 2.42 5.8 134.4 62.9 2.00 5.4 122.6 71.3 1.62 4.9 116.4 75.9 1.45 4.6
ASY 060B 184.8 61.1 2.82 7.4 174.3 67.9 2.41 6.9 161.0 77.4 1.97 6.4 146.8 88.5 1.58 5.9 139.4 94.5 1.41 5.6
ASY 070B 206.9 67.7 2.75 8.2 195.1 74.4 2.38 7.8 179.9 83.5 1.97 7.2 163.5 93.9 1.61 6.5 154.9 99.5 1.45 6.2
ASY 080B 231.0 82.4 2.6 9.2 218.0 92.0 2.19 8.7 202.4 103.5 1.82 8.1 186.5 116.3 1.51 7.4 178.0 123.1 1.36 7.1
ASY 090B 313.9 101.7 2.78 12.5 295.7 112.0 2.40 11.8 272.6 126.4 1.98 10.9 248.1 143.1 1.61 9.9 235.3 152.3 1.44 9.4
ASY 100B 330.8 112.2 2.68 13.2 316.3 126.2 2.30 12.6 297.3 146.0 1.89 11.9 276.1 169.1 1.53 11.0 264.7 181.9 1.37 10.6
ASY 120B 390.4 126.9 2.75 15.6 367.2 140.7 2.36 14.6 338.1 159.9 1.93 13.5 307.3 182.0 1.56 12.3 291.4 194.1 1.39 11.6
ASY 130B 434.2 143.5 2.74 17.3 407.7 157.4 2.36 16.3 373.8 176.2 1.95 14.9 337.5 197.1 1.59 13.5 318.5 208.3 1.42 12.7
ASY 140B 467.3 169.5 2.53 18.6 445.3 192.2 2.15 17.8 415.3 223.7 1.74 16.6 380.9 259.8 1.38 15.2 361.8 279.5 1.23 14.4
ASY 150B 496.4 166.1 2.68 19.8 473.0 188.0 2.28 18.9 441.1 218.4 1.86 17.6 404.7 253.2 1.49 16.1 384.6 272.2 1.32 15.3
ASY 160B 518.3 175.6 2.66 20.7 488.6 193.6 2.30 19.5 451.2 217.2 1.91 18.0 411.8 243.2 1.57 16.4 391.3 257.1 1.42 15.6
ASY 170B 558.0 185.9 2.72 22.2 535.6 209.4 2.35 21.4 506.0 240.9 1.95 20.2 473.2 276.0 1.60 18.9 455.5 295.0 1.45 18.2
ASY 180B 574.8 189.0 2.71 22.9 541.4 209.8 2.33 21.6 499.2 238.7 1.91 19.9 454.6 272.0 1.54 18.1 431.4 290.3 1.38 17.2
ASY 190B 616.3 205.1 2.70 24.6 588.3 231.9 2.31 23.5 552.6 269.9 1.89 22.0 514.3 314.2 1.53 20.5 494.0 338.7 1.37 19.7
ASY 200B 636.6 213.6 2.69 25.4 611.6 243.6 2.30 24.4 579.2 286.3 1.87 23.1 544.2 336.5 1.51 21.7 525.8 364.5 1.36 21.0
4 0C ASY 215B 716.3 246.7 2.66 28.6 675.0 271.8 2.29 26.9 623.2 305.0 1.90 24.9 568.0 341.7 1.56 22.6 539.0 361.4 1.40 21.5
ASY 230B 760.4 270.3 2.59 30.3 722.1 300.4 2.23 28.8 673.3 340.2 1.85 26.8 620.8 384.2 1.53 24.8 593.2 407.8 1.38 23.7
ASY 240B 791.1 290.8 2.52 31.5 759.0 327.5 2.17 30.3 716.5 376.5 1.79 28.6 669.5 431.3 1.47 26.7 644.0 460.9 1.33 25.7
ASY 250B 821.4 253.8 2.89 32.8 771.6 280.8 2.48 30.8 709.2 318.3 2.03 28.3 644.1 361.4 1.64 25.7 610.5 385.0 1.47 24.3
ASY 270B 896.5 298.6 2.72 35.7 838.5 326.8 2.35 33.4 764.8 364.5 1.94 30.5 686.5 406.2 1.57 27.4 645.5 428.6 1.41 25.7
ASY 295B 973.8 321.4 2.77 38.8 915.1 353.3 2.39 36.5 840.9 395.5 1.97 33.5 762.4 442.2 1.61 30.4 721.4 467.2 1.45 28.8
ASY 310B 1027.8 356.4 2.66 41.0 968.2 392.7 2.29 38.6 893.1 440.5 1.90 35.6 814.0 492.9 1.56 32.5 772.9 520.9 1.40 30.8
ASY 330B 1096.5 350.5 2.85 43.7 1032.3 387.9 2.45 41.2 951.2 440.1 2.01 37.9 865.7 500.3 1.62 34.5 821.2 533.4 1.45 32.7
ASY 350B 1155.1 376.1 2.82 46.1 1086.9 417.2 2.41 43.3 1000.7 474.6 1.97 39.9 909.8 540.6 1.58 36.3 862.7 576.8 1.41 34.4
ASY 375B 1255.4 440.7 2.64 50.1 1176.2 483.5 2.27 46.9 1075.1 540.9 1.87 42.9 967.1 604.8 1.51 38.6 910.3 639.2 1.35 36.3
ASY 400B 1267.6 431.1 2.68 50.5 1191.0 473.2 2.31 47.5 1093.0 530.1 1.91 43.6 987.9 593.7 1.55 39.4 932.6 627.9 1.39 37.2
ASY 420B 1353.9 472.0 2.63 54.0 1277.0 520.0 2.27 50.9 1179.0 584.0 1.88 47.0 1074.5 655.0 1.54 42.8 1019.6 693.1 1.39 40.7
ASY 450B 1500.6 494.0 2.80 59.8 1412.2 543.7 2.41 56.3 1300.6 609.3 2.00 51.9 1182.6 681.8 1.63 47.2 1121.1 720.6 1.47 44.7
ASY 475B 1599.8 557.0 2.67 63.8 1520.0 620.3 2.30 60.6 1417.6 704.4 1.90 56.5 1307.3 797.5 1.56 52.1 1248.9 847.5 1.40 49.8
ASY 500B 1647.7 587.9 2.62 65.7 1577.7 661.6 2.24 62.9 1485.4 760.1 1.85 59.2 1383.2 869.8 1.52 55.2 1328.0 928.9 1.37 53.0
ASY 050B 162.3 51.5 2.90 6.5 153.1 56.7 2.50 6.1 141.5 64.0 2.07 5.6 129.2 72.3 1.68 5.2 122.8 76.9 1.51 4.9

16
ASY 060B 194.7 62.2 2.92 7.8 183.8 69.1 2.50 7.3 170.0 78.6 2.05 6.8 155.4 89.6 1.65 6.2 147.8 95.6 1.48 5.9
ASY 070B 218.1 69.0 2.85 8.7 205.8 75.8 2.47 8.2 190.0 85.0 2.05 7.6 173.0 95.3 1.68 6.9 164.1 100.9 1.51 6.5
ASY 080B 242.3 84.6 2.63 9.7 229.8 93.6 2.27 9.2 213.5 105.3 1.89 8.5 196.7 118.3 1.56 7.8 187.8 125.3 1.41 7.5
ASY 090B 322.9 102.9 2.82 12.9 304.2 113.2 2.44 12.1 280.5 127.7 2.02 11.2 255.4 144.3 1.64 10.2 242.2 153.4 1.47 9.7
ASY 100B 339.5 113.4 2.72 13.5 324.7 127.4 2.34 12.9 305.0 147.2 1.92 12.2 283.2 170.2 1.56 11.3 271.5 182.9 1.40 10.8
ASY 120B 400.9 128.2 2.80 16.0 377.2 142.0 2.40 15.0 347.3 161.2 1.97 13.8 316.0 183.2 1.59 12.6 299.8 195.3 1.42 12.0
ASY 130B 446.1 145.1 2.78 17.8 418.9 159.1 2.40 16.7 384.1 177.8 1.99 15.3 347.0 198.7 1.62 13.8 327.5 210.0 1.45 13.1
ASY 140B 479.3 171.2 2.57 19.1 456.6 194.1 2.18 18.2 425.6 225.7 1.77 17.0 389.9 261.8 1.41 15.5 370.2 281.5 1.25 14.8
ASY 150B 509.4 167.7 2.73 20.3 485.4 189.8 2.32 19.4 452.4 220.3 1.89 18.0 414.8 255.1 1.51 16.5 394.1 274.1 1.34 15.7
ASY 160B 532.8 177.4 2.71 21.2 502.3 195.5 2.34 20.0 463.9 219.3 1.95 18.5 423.4 245.5 1.60 16.9 402.3 259.5 1.44 16.0
ASY 170B 572.6 187.3 2.78 22.8 549.5 211.0 2.39 21.9 519.0 242.7 1.98 20.7 485.1 278.1 1.63 19.3 466.8 297.3 1.48 18.6
ASY 180B 595.8 191.6 2.78 23.8 561.2 212.5 2.39 22.4 517.7 241.4 1.96 20.6 471.9 274.5 1.59 18.8 448.2 292.7 1.42 17.9
ASY 190B 638.1 207.7 2.77 25.4 609.3 234.6 2.37 24.3 572.5 272.7 1.94 22.8 533.4 317.1 1.57 21.3 512.9 341.7 1.41 20.5
ASY 200B 658.7 216.1 2.76 26.3 633.0 246.3 2.35 25.2 599.9 289.2 1.92 23.9 564.2 339.6 1.56 22.5 545.4 367.7 1.40 21.7
5 0C ASY 215B 736.8 249.4 2.71 29.4 694.6 274.6 2.34 27.7 641.1 308.0 1.94 25.6 584.3 344.9 1.59 23.3 554.5 364.7 1.43 22.1
ASY 230B 781.7 273.0 2.64 31.2 742.3 303.3 2.28 29.6 691.9 343.4 1.89 27.6 637.8 387.8 1.55 25.4 609.2 411.6 1.40 24.3
ASY 240B 812.2 293.4 2.57 32.4 779.0 330.4 2.21 31.1 735.1 379.9 1.83 29.3 686.3 435.1 1.50 27.4 659.8 464.9 1.35 26.3
ASY 250B 844.4 256.6 2.94 33.7 793.4 283.7 2.53 31.6 729.7 321.2 2.08 29.1 663.3 364.1 1.68 26.4 629.2 387.6 1.50 25.1
ASY 270B 921.3 302.2 2.77 36.7 861.9 330.5 2.39 34.4 786.5 368.2 1.97 31.4 706.4 410.0 1.60 28.2 664.5 432.4 1.44 26.5
ASY 295B 1001.0 324.9 2.82 39.9 940.8 357.0 2.43 37.5 864.7 399.4 2.01 34.5 784.2 446.3 1.65 31.3 742.2 471.4 1.48 29.6
ASY 310B 1056.3 360.2 2.70 42.1 995.1 396.8 2.33 39.7 917.9 444.9 1.93 36.6 836.7 497.7 1.58 33.4 794.3 525.9 1.43 31.7
ASY 330B 1128.5 354.5 2.90 45.0 1062.6 392.0 2.49 42.4 979.6 444.2 2.05 39.1 892.2 504.2 1.66 35.6 846.9 537.1 1.48 33.8
ASY 350B 1189.1 380.2 2.87 47.4 1119.2 421.5 2.46 44.6 1031.0 478.9 2.01 41.1 938.4 544.7 1.62 37.4 890.4 580.7 1.45 35.5
ASY 375B 1292.0 446.1 2.69 51.5 1210.8 489.1 2.31 48.3 1107.2 546.7 1.91 44.1 996.5 610.6 1.55 39.7 938.4 644.8 1.38 37.4
ASY 400B 1314.5 437.5 2.74 52.4 1235.2 479.9 2.37 49.3 1133.7 536.9 1.96 45.2 1025.1 600.4 1.60 40.9 967.9 634.5 1.43 38.6
ASY 420B 1404.6 478.6 2.70 56.0 1324.7 527.0 2.33 52.8 1223.0 591.4 1.93 48.8 1114.5 662.7 1.58 44.4 1057.5 701.0 1.42 42.2
ASY 450B 1538.2 498.7 2.85 61.3 1447.5 548.6 2.45 57.7 1333.0 614.5 2.03 53.2 1211.9 687.3 1.66 48.3 1148.8 726.2 1.50 45.8
ASY 475B 1638.6 561.8 2.71 65.3 1556.5 625.6 2.33 62.1 1451.0 710.2 1.93 57.9 1337.3 803.8 1.58 53.3 1277.1 854.1 1.43 50.9
ASY 500B 1685.7 592.6 2.66 67.2 1614.2 666.8 2.28 64.4 1518.8 766.0 1.88 60.6 1413.0 876.3 1.54 56.3 1355.9 935.8 1.39 54.1

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
COP - Coefficient of Performance
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 171.1 52.8 2.99 6.8 161.3 58.0 2.59 6.4 148.8 65.2 2.14 5.9 135.6 73.3 1.74 5.4 128.7 77.8 1.57 5.1
ASY 060B 207.1 63.7 3.04 8.3 195.2 70.6 2.60 7.8 180.3 80.1 2.14 7.2 164.7 90.9 1.73 6.6 156.6 96.9 1.55 6.2
ASY 070B 233.1 70.7 2.98 9.3 219.6 77.5 2.58 8.8 202.4 86.7 2.15 8.1 184.0 97.0 1.76 7.3 174.3 102.6 1.58 6.9
ASY 080B 259.3 86.7 2.75 10.3 245.5 95.7 2.38 9.8 228.0 107.6 1.98 9.1 209.4 120.8 1.63 8.3 199.6 127.8 1.47 8.0
ASY 090B 330.1 103.9 2.86 13.2 311.2 114.3 2.48 12.4 287.3 128.7 2.05 11.5 261.8 145.3 1.67 10.4 248.6 154.4 1.50 9.9
ASY 100B 346.2 114.2 2.76 13.8 331.2 128.4 2.37 13.2 311.3 148.2 1.95 12.4 289.2 171.2 1.58 11.5 277.3 183.8 1.42 11.1
ASY 120B 407.9 129.1 2.83 16.3 384.3 143.0 2.43 15.3 354.5 162.3 2.00 14.1 323.4 184.3 1.62 12.9 307.3 196.4 1.45 12.3
ASY 130B 453.1 146.0 2.81 18.1 426.0 160.1 2.43 17.0 391.4 179.0 2.02 15.6 354.4 200.0 1.65 14.1 334.9 211.3 1.48 13.4
ASY 140B 485.6 172.1 2.59 19.4 463.0 195.1 2.20 18.5 431.9 226.9 1.78 17.2 396.1 263.1 1.42 15.8 376.4 282.9 1.26 15.0
ASY 150B 520.1 169.0 2.77 20.7 495.7 191.2 2.36 19.8 462.3 221.9 1.92 18.4 424.1 256.8 1.54 16.9 403.0 275.8 1.37 16.1
ASY 160B 544.4 178.8 2.75 21.7 513.6 197.1 2.38 20.5 474.8 221.2 1.98 18.9 433.9 247.6 1.63 17.3 412.5 261.8 1.47 16.4
ASY 170B 583.8 188.5 2.81 23.3 560.5 212.2 2.42 22.4 529.6 244.2 2.01 21.1 495.1 279.9 1.66 19.7 476.5 299.1 1.50 19.0
ASY 180B 616.0 194.1 2.84 24.6 580.4 215.1 2.44 23.1 535.6 244.0 2.01 21.4 489.1 277.1 1.63 19.5 464.9 295.2 1.46 18.5
ASY 190B 658.8 210.1 2.83 26.3 629.3 237.2 2.42 25.1 591.8 275.4 1.98 23.6 551.9 319.9 1.61 22.0 531.1 344.6 1.45 21.2
ASY 200B 679.6 218.4 2.82 27.1 653.4 248.9 2.41 26.1 619.7 292.1 1.97 24.7 583.5 342.7 1.60 23.3 564.4 370.9 1.43 22.5
6 0C ASY 215B 750.5 251.2 2.74 29.9 708.3 276.6 2.37 28.2 654.7 310.4 1.97 26.1 597.7 347.6 1.61 23.8 567.7 367.5 1.45 22.6
ASY 230B 795.1 274.7 2.67 31.7 755.7 305.2 2.30 30.1 705.1 345.7 1.91 28.1 650.7 390.5 1.57 25.9 621.9 414.5 1.42 24.8
ASY 240B 825.0 295.0 2.60 32.9 791.7 332.2 2.23 31.6 747.6 382.1 1.85 29.8 698.3 437.7 1.52 27.8 671.5 467.8 1.37 26.8
ASY 250B 865.3 259.2 2.99 34.5 813.8 286.4 2.57 32.5 749.6 324.0 2.12 29.9 682.8 367.0 1.72 27.2 648.4 390.5 1.54 25.9
ASY 270B 942.9 305.3 2.81 37.6 883.0 333.8 2.42 35.2 807.0 371.8 2.01 32.2 726.1 413.7 1.63 29.0 683.7 436.2 1.47 27.3
ASY 295B 1023.6 327.8 2.86 40.8 963.0 360.1 2.47 38.4 886.2 402.9 2.05 35.3 804.8 450.1 1.67 32.1 762.3 475.4 1.51 30.4
ASY 310B 1079.2 363.2 2.74 43.0 1017.5 400.2 2.36 40.6 939.6 448.8 1.96 37.5 857.4 502.1 1.61 34.2 814.5 530.6 1.45 32.5
ASY 330B 1153.0 357.6 2.94 46.0 1086.8 395.2 2.53 43.3 1003.4 447.6 2.08 40.0 915.7 507.6 1.69 36.5 870.2 540.4 1.51 34.7
ASY 350B 1214.4 383.4 2.91 48.4 1144.1 424.9 2.49 45.6 1055.7 482.4 2.04 42.1 963.0 548.2 1.65 38.4 915.0 584.3 1.48 36.5
ASY 375B 1317.5 449.9 2.72 52.5 1236.1 493.2 2.34 49.3 1132.1 551.2 1.93 45.1 1021.0 615.4 1.57 40.7 962.5 649.7 1.41 38.4
ASY 400B 1358.9 443.6 2.80 54.2 1277.4 486.3 2.42 50.9 1173.2 543.5 2.00 46.8 1061.7 607.1 1.64 42.3 1003.0 641.1 1.47 40.0
ASY 420B 1452.0 484.8 2.76 57.9 1369.8 533.6 2.38 54.6 1265.1 598.5 1.98 50.4 1153.4 670.2 1.62 46.0 1094.7 708.6 1.46 43.7
ASY 450B 1563.0 501.8 2.88 62.3 1472.5 552.1 2.48 58.7 1358.0 618.6 2.06 54.2 1236.7 691.9 1.69 49.3 1173.3 731.2 1.52 46.8
ASY 475B 1662.2 564.8 2.74 66.3 1580.2 629.0 2.36 63.0 1474.5 714.2 1.95 58.8 1360.4 808.6 1.60 54.2 1299.8 859.3 1.44 51.8
ASY 500B 1708.9 595.4 2.68 68.1 1636.7 670.1 2.30 65.3 1541.1 769.9 1.90 61.5 1434.6 881.0 1.55 57.2 1377.0 940.9 1.40 54.9
ASY 050B 177.4 53.7 3.05 7.1 166.9 58.8 2.64 6.7 153.7 65.9 2.19 6.1 139.8 74.0 1.78 5.6 132.6 78.4 1.60 5.3

17
ASY 060B 216.3 64.8 3.12 8.6 203.6 71.7 2.68 8.1 187.7 81.1 2.20 7.5 171.2 91.9 1.78 6.8 162.7 97.8 1.59 6.5
ASY 070B 244.6 72.0 3.07 9.8 230.1 78.9 2.66 9.2 211.6 88.0 2.21 8.4 191.9 98.3 1.81 7.7 181.6 103.8 1.63 7.2
ASY 080B 273.0 88.3 2.85 10.9 258.0 97.4 2.46 10.3 239.0 109.4 2.04 9.5 218.8 122.6 1.68 8.7 208.3 129.7 1.52 8.3
ASY 090B 337.8 105.0 2.90 13.5 318.9 115.5 2.51 12.7 294.9 130.0 2.09 11.8 269.4 146.5 1.71 10.7 256.1 155.5 1.53 10.2
ASY 100B 353.3 115.2 2.79 14.1 338.3 129.4 2.40 13.5 318.3 149.3 1.98 12.7 296.0 172.2 1.61 11.8 284.0 184.9 1.45 11.3
ASY 120B 415.2 130.0 2.86 16.6 392.1 144.1 2.46 15.6 363.0 163.6 2.03 14.5 332.5 185.7 1.65 13.3 316.7 197.9 1.49 12.6
ASY 130B 459.3 146.8 2.83 18.3 433.0 161.1 2.46 17.3 399.3 180.3 2.04 15.9 363.0 201.5 1.67 14.5 343.9 213.0 1.51 13.7
ASY 140B 490.5 172.8 2.61 19.6 468.5 196.0 2.22 18.7 438.0 228.1 1.80 17.5 402.8 264.6 1.44 16.1 383.2 284.4 1.28 15.3
ASY 150B 531.9 170.5 2.81 21.2 507.5 192.9 2.40 20.2 473.8 223.7 1.95 18.9 435.1 258.8 1.57 17.4 413.8 277.9 1.39 16.5
ASY 160B 557.0 180.4 2.79 22.2 526.3 198.9 2.41 21.0 487.4 223.3 2.01 19.4 446.3 250.1 1.66 17.8 424.7 264.5 1.50 16.9
ASY 170B 595.6 189.6 2.85 23.7 572.3 213.6 2.46 22.8 541.3 245.8 2.04 21.6 506.5 281.8 1.68 20.2 487.6 301.3 1.52 19.4
ASY 180B 636.0 196.7 2.90 25.4 599.7 217.8 2.49 23.9 554.2 246.8 2.06 22.1 506.6 279.8 1.67 20.2 482.1 297.9 1.50 19.2
ASY 190B 679.2 212.5 2.89 27.1 649.2 239.8 2.47 25.9 611.0 278.2 2.03 24.4 570.5 322.9 1.65 22.8 549.4 347.5 1.48 21.9
ASY 200B 700.2 220.7 2.87 27.9 673.5 251.4 2.46 26.9 639.4 294.9 2.01 25.5 602.7 345.8 1.63 24.0 583.3 374.1 1.47 23.3
7 0C ASY 215B 763.9 252.9 2.77 30.5 722.4 278.7 2.40 28.8 669.5 312.9 1.99 26.7 613.0 350.6 1.64 24.4 583.2 370.8 1.48 23.3
ASY 230B 807.5 276.3 2.70 32.2 768.7 307.1 2.33 30.7 718.8 348.1 1.94 28.7 664.9 393.4 1.60 26.5 636.2 417.8 1.44 25.4
ASY 240B 836.2 296.4 2.62 33.3 803.5 334.0 2.25 32.0 759.8 384.3 1.87 30.3 710.8 440.5 1.53 28.3 684.0 470.9 1.39 27.3
ASY 250B 890.1 262.2 3.04 35.5 838.4 289.7 2.62 33.4 774.1 327.5 2.16 30.9 707.1 370.6 1.76 28.2 672.6 394.1 1.58 26.8
ASY 270B 967.7 308.9 2.85 38.6 907.9 337.8 2.47 36.2 831.6 376.1 2.05 33.2 750.3 418.4 1.67 29.9 707.6 440.9 1.50 28.2
ASY 295B 1048.8 331.1 2.90 41.8 988.3 363.8 2.51 39.4 911.4 407.1 2.08 36.3 829.6 454.8 1.71 33.1 786.8 480.3 1.54 31.4
ASY 310B 1104.3 366.6 2.78 44.0 1042.6 404.0 2.40 41.6 964.6 453.2 1.99 38.5 881.9 507.3 1.64 35.2 838.6 536.2 1.48 33.4
ASY 330B 1179.0 360.9 2.98 47.0 1113.1 398.8 2.57 44.4 1030.2 451.5 2.12 41.1 942.8 511.6 1.73 37.6 897.5 544.5 1.55 35.8
ASY 350B 1240.3 386.6 2.95 49.5 1170.6 428.4 2.53 46.7 1082.9 486.3 2.08 43.2 990.9 552.4 1.69 39.5 943.4 588.5 1.51 37.6
ASY 375B 1342.4 453.6 2.75 53.5 1261.8 497.5 2.37 50.3 1158.8 556.0 1.96 46.2 1048.2 620.7 1.60 41.8 990.0 655.3 1.44 39.5
ASY 400B 1402.4 449.5 2.85 55.9 1319.1 492.6 2.47 52.6 1212.7 550.1 2.05 48.4 1098.7 613.8 1.68 43.8 1038.6 647.9 1.51 41.4
ASY 420B 1498.0 490.9 2.81 59.7 1413.9 540.1 2.43 56.4 1306.7 605.4 2.02 52.1 1192.3 677.6 1.66 47.5 1132.1 716.3 1.49 45.1
ASY 450B 1589.5 505.1 2.91 63.4 1500.8 556.0 2.51 59.8 1388.2 623.4 2.09 55.4 1268.4 697.8 1.72 50.6 1205.6 737.6 1.55 48.1
ASY 475B 1685.5 567.7 2.77 67.2 1605.1 632.6 2.38 64.0 1501.2 718.8 1.97 59.9 1388.3 814.4 1.62 55.4 1328.1 865.8 1.46 53.0
ASY 500B 1730.3 598.1 2.70 69.0 1659.5 673.3 2.32 66.2 1565.2 774.1 1.92 62.4 1459.7 886.4 1.57 58.2 1402.3 946.9 1.42 55.9

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
COP - Coefficient of Performance
PERFORMANCE DATA (Metric units)
LEAVING 350C AMBIENT TEMPERATURE 400C AMBIENT TEMPERATURE 460C AMBIENT TEMPERATURE 520C AMBIENT TEMPERATURE 550C AMBIENT TEMPERATURE
CHILLED UNIT WATER WATER WATER WATER WATER
WATER TEMP. SIZE CAP. COMP. FLOW CAP. COMP. CAP. COMP. FLOW CAP. COMP. FLOW CAP. COMP. FLOW
COP COP FLOW COP COP COP
(LCWT) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS) (kW) kW (LPS)
ASY 050B 181.8 54.3 3.10 7.3 171.0 59.4 2.68 6.8 157.3 66.5 2.22 6.3 142.9 74.5 1.81 5.7 135.4 78.8 1.63 5.4
ASY 060B 222.8 65.6 3.18 8.9 209.5 72.5 2.73 8.4 193.0 81.9 2.24 7.7 175.9 92.6 1.81 7.0 167.1 98.4 1.62 6.7
ASY 070B 252.7 73.0 3.14 10.1 237.5 79.8 2.72 9.5 218.2 89.0 2.26 8.7 197.5 99.1 1.85 7.9 186.8 104.6 1.67 7.4
ASY 080B 282.6 89.5 2.91 11.3 266.7 98.6 2.51 10.6 246.7 110.6 2.09 9.8 225.5 123.9 1.72 9.0 214.5 130.9 1.55 8.6
ASY 090B 347.6 106.4 2.95 13.9 328.7 117.0 2.56 13.1 304.7 131.5 2.13 12.1 279.1 148.0 1.75 11.1 265.6 157.0 1.58 10.6
ASY 100B 362.4 116.4 2.84 14.5 347.3 130.7 2.45 13.8 327.2 150.6 2.02 13.0 304.7 173.6 1.65 12.2 292.5 186.2 1.48 11.7
ASY 120B 425.8 131.4 2.90 17.0 403.5 145.7 2.51 16.1 375.4 165.4 2.08 15.0 345.8 187.8 1.70 13.8 330.4 200.0 1.54 13.2
ASY 130B 468.4 148.1 2.87 18.7 443.1 162.6 2.49 17.7 410.7 182.1 2.08 16.4 375.6 203.8 1.72 15.0 357.0 215.4 1.55 14.2
ASY 140B 497.8 173.8 2.63 19.8 476.5 197.3 2.24 19.0 447.0 229.8 1.82 17.8 412.7 266.7 1.46 16.5 393.4 286.7 1.30 15.7
ASY 150B 547.2 172.4 2.86 21.8 522.6 195.0 2.44 20.8 488.6 226.1 1.99 19.5 449.5 261.4 1.60 17.9 427.9 280.6 1.43 17.1
ASY 160B 573.1 182.5 2.84 22.9 542.5 201.3 2.46 21.6 503.6 226.0 2.06 20.1 462.2 253.3 1.70 18.4 440.5 267.9 1.54 17.6
ASY 170B 610.7 191.1 2.91 24.4 587.5 215.3 2.51 23.4 556.2 247.9 2.08 22.2 521.2 284.3 1.72 20.8 502.0 304.0 1.55 20.0
ASY 180B 656.0 199.3 2.95 26.2 619.0 220.5 2.54 24.7 572.8 249.6 2.10 22.8 524.5 282.7 1.72 20.9 499.5 300.7 1.54 19.9
ASY 190B 699.5 214.9 2.94 27.9 669.0 242.5 2.52 26.7 630.3 281.1 2.07 25.1 589.2 325.8 1.69 23.5 567.7 350.5 1.52 22.6
ASY 200B 720.6 223.1 2.93 28.7 693.6 254.0 2.51 27.7 659.0 297.8 2.06 26.3 621.7 348.9 1.67 24.8 602.2 377.3 1.50 24.0
8 0C ASY 215B 781.8 255.3 2.81 31.2 741.2 281.5 2.44 29.6 689.2 316.2 2.03 27.5 633.4 354.6 1.68 25.3 603.9 375.2 1.52 24.1
ASY 230B 824.0 278.4 2.74 32.9 786.1 309.7 2.36 31.3 737.1 351.2 1.97 29.4 683.7 397.3 1.63 27.3 655.2 422.2 1.47 26.1
ASY 240B 851.4 298.3 2.65 33.9 819.3 336.3 2.28 32.7 776.2 387.2 1.89 31.0 727.5 444.1 1.56 29.0 700.7 474.9 1.41 27.9
ASY 250B 922.0 266.2 3.11 36.8 870.2 294.0 2.68 34.7 805.6 332.1 2.22 32.1 738.3 375.4 1.82 29.4 703.5 399.0 1.64 28.1
ASY 270B 999.8 313.5 2.91 39.9 939.9 342.9 2.52 37.5 863.4 381.7 2.10 34.4 781.5 424.4 1.72 31.2 738.4 447.1 1.55 29.4
ASY 295B 1081.3 335.3 2.96 43.1 1020.8 368.5 2.56 40.7 943.8 412.4 2.13 37.6 861.6 460.8 1.75 34.4 818.3 486.6 1.58 32.6
ASY 310B 1136.4 370.9 2.83 45.3 1074.8 408.9 2.45 42.9 996.6 458.9 2.04 39.7 913.3 514.0 1.68 36.4 869.6 543.4 1.52 34.7
ASY 330B 1212.3 365.1 3.04 48.3 1146.9 403.5 2.62 45.7 1064.5 456.5 2.17 42.4 977.6 516.8 1.77 39.0 932.5 549.7 1.60 37.2
ASY 350B 1273.5 390.8 3.00 50.8 1204.5 433.1 2.58 48.0 1117.7 491.4 2.13 44.6 1026.7 557.8 1.73 40.9 979.5 594.1 1.56 39.1
ASY 375B 1374.3 458.4 2.79 54.8 1294.8 502.9 2.41 51.6 1192.8 562.1 2.00 47.6 1083.1 627.6 1.64 43.2 1025.0 662.6 1.47 40.9
ASY 400B 1445.4 455.5 2.91 57.6 1360.7 498.9 2.52 54.3 1252.4 556.8 2.09 49.9 1136.2 620.7 1.71 45.3 1074.9 654.8 1.54 42.9
ASY 420B 1543.2 496.9 2.86 61.5 1457.5 546.5 2.48 58.1 1348.2 612.4 2.06 53.8 1231.4 685.1 1.69 49.1 1169.9 724.0 1.53 46.7
ASY 450B 1629.7 510.2 2.95 65.0 1543.9 562.1 2.56 61.6 1434.4 630.8 2.13 57.2 1317.0 706.8 1.76 52.5 1255.1 747.5 1.59 50.0
ASY 475B 1721.0 572.2 2.80 68.6 1643.2 638.1 2.42 65.5 1541.9 725.8 2.01 61.5 1431.0 823.2 1.65 57.1 1371.6 875.6 1.49 54.7
ASY 500B 1763.0 602.1 2.74 70.3 1694.4 678.3 2.35 67.6 1602.2 780.5 1.95 63.9 1498.2 894.6 1.60 59.7 1441.3 956.1 1.44 57.5
ASY 050B 191.7 55.7 3.19 7.6 180.4 60.9 2.76 7.2 166.1 67.9 2.30 6.6 151.0 75.7 1.88 6.0 143.2 80.0 1.70 5.7

18
ASY 060B 235.1 67.2 3.28 9.4 221.3 74.1 2.82 8.8 204.3 83.5 2.32 8.1 186.5 94.2 1.89 7.4 177.4 100.1 1.70 7.1
ASY 070B 266.6 74.6 3.24 10.6 250.9 81.5 2.81 10.0 230.8 90.8 2.35 9.2 209.5 101.0 1.93 8.4 198.2 106.5 1.74 7.9
ASY 080B 297.6 91.3 3.01 11.9 281.1 100.6 2.60 11.2 260.1 112.8 2.16 10.4 238.0 126.2 1.78 9.5 226.4 133.4 1.61 9.0
ASY 090B 371.0 109.8 3.06 14.8 351.2 120.4 2.67 14.0 325.9 134.8 2.23 13.0 298.8 151.1 1.84 11.9 284.7 159.9 1.66 11.4
ASY 100B 384.7 119.3 2.94 15.3 368.8 133.7 2.54 14.7 347.4 153.7 2.10 13.9 323.5 176.5 1.72 12.9 310.5 188.9 1.55 12.4
ASY 120B 455.9 135.4 3.03 18.2 432.8 149.9 2.62 17.3 403.7 169.8 2.18 16.1 373.1 192.3 1.80 14.9 357.1 204.5 1.63 14.2
ASY 130B 500.4 152.3 2.99 20.0 474.4 167.2 2.60 18.9 440.7 187.0 2.18 17.6 404.4 208.9 1.80 16.1 385.1 220.6 1.63 15.4
ASY 140B 528.8 178.2 2.73 21.1 506.5 202.2 2.33 20.2 475.3 235.0 1.90 19.0 439.1 272.1 1.53 17.5 418.8 292.2 1.36 16.7
ASY 150B 581.4 176.5 2.97 23.2 555.3 199.5 2.54 22.1 519.3 230.9 2.08 20.7 478.2 266.4 1.68 19.1 455.7 285.7 1.50 18.2
ASY 160B 611.0 187.4 2.96 24.4 578.8 206.5 2.57 23.1 537.9 231.8 2.14 21.4 493.9 259.6 1.77 19.7 471.1 274.5 1.60 18.8
ASY 170B 648.2 194.9 3.03 25.8 623.6 219.5 2.61 24.9 590.4 252.6 2.17 23.5 553.1 289.6 1.79 22.1 532.7 309.6 1.62 21.2
ASY 180B 694.7 204.5 3.06 27.7 656.7 226.0 2.64 26.2 609.3 255.3 2.19 24.3 559.5 288.5 1.80 22.3 533.7 306.4 1.62 21.3
ASY 190B 738.5 219.7 3.05 29.4 707.2 247.7 2.61 28.2 667.5 286.7 2.16 26.6 625.2 331.7 1.76 24.9 602.9 356.4 1.59 24.0
ASY 200B 759.5 227.6 3.03 30.3 732.0 259.1 2.60 29.2 696.5 303.3 2.14 27.8 658.2 354.9 1.74 26.2 637.9 383.4 1.57 25.4
10 0C ASY 215B 833.6 262.1 2.93 33.2 791.2 288.9 2.54 31.5 736.8 324.3 2.12 29.4 678.2 363.4 1.76 27.0 647.1 384.3 1.59 25.8
ASY 230B 876.6 285.1 2.85 35.0 836.8 317.1 2.46 33.4 785.2 359.5 2.05 31.3 728.8 406.6 1.70 29.1 698.6 431.9 1.54 27.9
ASY 240B 902.7 304.7 2.76 36.0 868.8 343.4 2.37 34.6 823.0 395.4 1.97 32.8 770.9 453.4 1.62 30.7 744.8 482.4 1.5 29.5
ASY 250B 986.2 274.5 3.23 39.3 932.2 302.7 2.80 37.2 864.7 341.1 2.33 34.5 793.9 384.4 1.91 31.7 757.0 407.8 1.73 30.2
ASY 270B 1067.5 323.4 3.02 42.6 1004.9 353.3 2.62 40.1 924.7 392.5 2.19 36.9 838.7 435.5 1.80 33.4 793.5 458.3 1.62 31.6
ASY 295B 1153.8 344.9 3.07 46.0 1090.5 378.6 2.67 43.5 1009.7 423.3 2.23 40.3 923.1 472.3 1.84 36.8 877.5 498.5 1.66 35.0
ASY 310B 1211.0 381.1 2.94 48.3 1146.3 419.9 2.55 45.7 1063.9 471.0 2.12 42.4 975.9 527.2 1.75 38.9 929.5 557.2 1.58 37.1
ASY 330B 1294.1 375.7 3.16 51.6 1225.8 414.5 2.73 48.9 1139.9 467.7 2.27 45.5 1049.3 527.9 1.87 41.8 1002.1 560.6 1.68 40.0
ASY 350B 1359.1 401.8 3.12 54.2 1287.2 444.7 2.69 51.3 1197.2 503.4 2.23 47.7 1102.7 569.9 1.83 44.0 1053.6 606.1 1.65 42.0
ASY 375B 1463.9 471.9 2.89 58.4 1381.3 517.1 2.51 55.1 1275.0 577.1 2.09 50.8 1160.4 643.0 1.71 46.3 1099.7 678.1 1.54 43.9
ASY 400B 1527.7 466.9 3.00 60.9 1440.7 511.1 2.61 57.5 1329.4 569.7 2.17 53.0 1209.6 634.2 1.79 48.2 1146.3 668.6 1.61 45.7
ASY 420B 1628.5 508.2 2.96 64.9 1540.5 558.9 2.56 61.4 1428.0 625.9 2.14 56.9 1307.3 699.7 1.76 52.1 1243.6 739.1 1.59 49.6
ASY 450B 1744.9 524.7 3.08 69.6 1656.0 577.9 2.67 66.0 1542.2 648.3 2.23 61.5 1419.5 725.9 1.85 56.6 1354.5 767.4 1.67 54.0
ASY 475B 1834.9 586.7 2.92 73.2 1753.8 654.1 2.52 69.9 1647.6 743.9 2.10 65.7 1530.8 843.6 1.73 61.0 1468.1 897.2 1.56 58.5
ASY 500B 1874.3 616.0 2.85 74.7 1802.3 693.9 2.45 71.9 1704.9 798.2 2.03 68.0 1594.6 914.6 1.67 63.6 1539.5 972.8 1.5 61.0

LEGEND: NOTES:
kW - Compressor power input 1. Packaged chillers are rated with ARI standard 550/590-98. 4. Direct interpolation is permissible. Do not extrapolate.
LPS - Liters Per Second 2. Performance data are based on 60C water range in evaporator. 5. kW power input is for compressor only.
3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 6. COP for entire unit. Refer to electrical data for fan kW.
COP - Coefficient of Performance
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASE HEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
208/230-3-60 187 253 227 393 1 165.6 885 3 265 1 0 0 0 0 0 0 4 5.05 4.40 20.2 2 230 200 0.87 PW
ASY 050B 380-3-60 342 418 137 237 1 100.2 534 3 160 1 0 0 0 0 0 0 4 2.93 4.40 11.7 2 230 200 0.87 PW
460-3-60 414 506 115 197 1 82.8 423 3 132 1 0 0 0 0 0 0 4 2.78 4.40 11.1 2 230 200 0.87 PW
208/230-3-60 187 253 280 488 1 208.0 1040 3 333 1 0 0 0 0 0 0 4 5.05 4.40 20.2 2 230 300 1.30 PW
ASY 060B 380-3-60 342 418 169 295 1 125.9 631 3 201 1 0 0 0 0 0 0 4 2.93 4.40 11.7 2 230 300 1.30 PW
460-3-60 414 506 141 245 1 104.0 520 3 166 1 0 0 0 0 0 0 4 2.78 4.40 11.1 2 230 300 1.30 PW
208/230-3-60 187 253 323 562 1 239.0 1224 3 382 1 0 0 0 0 0 0 4 6.10 6.00 24.4 2 230 300 1.30 PW
ASY 070B 380-3-60 342 418 195 340 1 144.9 742 3 232 1 0 0 0 0 0 0 4 3.52 6.00 14.1 2 230 300 1.30 PW
460-3-60 414 506 164 283 1 119.7 612 3 192 1 0 0 0 0 0 0 4 3.50 7.60 14.0 2 230 300 1.30 PW
208/230-3-60 187 253 371 648 1 277.0 1330 3 443 1 0 0 0 0 0 0 4 6.10 6.00 24.4 2 230 300 1.30 PW
ASY 080B 380-3-60 342 418 224 391 1 167.6 807 3 268 1 0 0 0 0 0 0 4 3.52 6.00 14.1 2 230 300 1.30 PW
460-3-60 414 506 187 326 1 138.5 665 3 222 1 0 0 0 0 0 0 4 3.50 7.60 14.0 2 230 300 1.30 PW
208/230-3-60 187 253 409 575 2 165.6 885 3 265 2 0 0 0 0 0 0 6 6.10 9.00 36.6 3 230 400 1.74 PW
ASY 090B 380-3-60 342 418 247 347 2 100.2 534 3 160 2 0 0 0 0 0 0 6 3.52 9.00 21.1 3 230 400 1.74 PW
460-3-60 414 506 207 290 2 82.8 423 3 132 2 0 0 0 0 0 0 6 3.50 11.40 21.0 3 230 400 1.74 PW
208/230-3-60 187 253 434 611 2 176.7 885 3 283 2 0 0 0 0 0 0 6 6.10 9.00 36.6 3 230 400 1.74 PW
ASY 100B 380-3-60 342 418 262 369 2 107.0 534 3 171 2 0 0 0 0 0 0 6 3.52 9.00 21.1 3 230 400 1.74 PW
460-3-60 414 506 220 308 2 88.4 423 3 141 2 0 0 0 0 0 0 6 3.50 11.40 21.0 3 230 400 1.74 PW
208/230-3-60 187 253 517 725 2 208.0 1040 3 333 2 0 0 0 0 0 0 8 6.10 12.00 48.8 4 230 600 2.61 PW

19
ASY 120B 380-3-60 342 418 311 437 2 125.9 631 3 201 2 0 0 0 0 0 0 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 262 366 2 104.0 520 3 166 2 0 0 0 0 0 0 8 3.50 15.20 28.0 4 230 600 2.61 PW
208/230-3-60 187 253 587 826 2 239.0 1224 3 382 2 0 0 0 0 0 0 8 6.10 12.00 48.8 4 230 600 2.61 PW
ASY 130B 380-3-60 342 418 354 499 2 144.9 742 3 232 2 0 0 0 0 0 0 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 297 417 2 119.7 612 3 192 2 0 0 0 0 0 0 8 3.50 15.20 28.0 4 230 600 2.61 PW
208/230-3-60 187 253 643 907 2 264.0 1224 3 422 2 0 0 0 0 0 0 8 6.10 12.00 48.8 4 230 600 2.61 PW
ASY 140B 380-3-60 342 418 387 547 2 159.5 742 3 255 2 0 0 0 0 0 0 8 3.52 12.00 28.2 4 230 600 2.61 PW
460-3-60 414 506 325 456 2 131.8 612 3 211 2 0 0 0 0 0 0 8 3.50 15.20 28.0 4 230 600 2.61 PW
208/230-3-60 187 253 655 919 2 264.0 1224 3 422 2 0 0 0 0 0 0 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 150B 380-3-60 342 418 394 554 2 159.5 742 3 255 2 0 0 0 0 0 0 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 332 463 2 131.8 612 3 211 2 0 0 0 0 0 0 10 3.50 19.00 35.0 5 230 600 2.61 PW
208/230-3-60 187 253 684 961 2 277.0 1330 3 443 2 0 0 0 0 0 0 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 160B 380-3-60 342 418 412 580 2 167.6 807 3 268 2 0 0 0 0 0 0 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 347 485 2 138.5 665 3 222 2 0 0 0 0 0 0 10 3.50 19.00 35.0 5 230 600 2.61 PW
LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect unit
MOCP - Maximum Over Current Protection performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept
CB - Circuit Breaker two or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5. Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
kW - Kilo Watt 8. Neutral line required on 380V-3Ph-60Hz power supply only.
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA values are based on nominal conditions.
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASE HEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
208/230-3-60 187 253 725 1020 2 295.0 1330 3 472 2 0 0 0 0 0 0 10 6.10 15.00 61.0 5 230 600 2.61 PW
ASY 170B 380-3-60 342 418 438 616 2 178.8 807 3 286 2 0 0 0 0 0 0 10 3.52 15.00 35.2 5 230 600 2.61 PW
460-3-60 414 506 367 515 2 147.7 665 3 236 2 0 0 0 0 0 0 10 3.50 19.00 35.0 5 230 600 2.61 PW
208/230-3-60 187 253 749 957 3 208.0 1040 3 333 3 0 0 0 0 0 0 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 180B 380-3-60 342 418 451 577 3 125.9 631 3 201 3 0 0 0 0 0 0 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 380 484 3 104.0 520 3 166 3 0 0 0 0 0 0 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 810 1045 2 235.0 1040 3 376 2 1 208 1040 3 333 1 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 190B 380-3-60 342 418 488 630 2 142.1 631 3 227 2 1 125.9 631 3 201 1 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 410 528 2 117.4 520 3 188 2 1 104 520 3 166 1 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 837 1072 3 235.0 1040 3 376 3 0 0 0 0 0 0 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 200B 380-3-60 342 418 504 646 3 142.1 631 3 227 3 0 0 0 0 0 0 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 424 541 3 117.4 520 3 188 3 0 0 0 0 0 0 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 935 1212 2 277.0 1330 3 443 2 1 239.0 1224 3 382 1 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 215B 380-3-60 342 418 564 732 2 167.6 807 3 268 2 1 144.9 742 3 232 1 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 473 612 2 138.5 665 3 222 2 1 119.7 612 3 192 1 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 996 1291 1 295.0 1330 3 472 1 2 277.0 1330 3 443 2 12 6.10 18.00 73.2 6 230 900 3.91 PW
ASY 230B 380-3-60 342 418 601 780 1 178.8 807 3 286 1 2 167.6 807 3 268 2 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 504 651 1 147.7 665 3 236 1 2 138.5 665 3 222 2 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 1032 1327 3 295.0 1330 3 472 3 0 0 0 0 0 0 12 6.10 18.00 73.2 6 230 900 3.91 PW

20
ASY 240B 380-3-60 342 418 623 802 3 178.8 807 3 286 3 0 0 0 0 0 0 12 3.52 18.00 42.2 6 230 900 3.91 PW
460-3-60 414 506 522 670 3 147.7 665 3 236 3 0 0 0 0 0 0 12 3.50 22.80 42.0 6 230 900 3.91 PW
208/230-3-60 187 253 982 1190 4 208.0 1040 3 333 4 0 0 0 0 0 0 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 250B 380-3-60 342 418 591 717 4 125.9 631 3 201 4 0 0 0 0 0 0 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 498 602 4 104.0 520 3 166 4 0 0 0 0 0 0 16 3.50 30.40 56.0 8 230 1200 5.22 PW
208/230-3-60 187 253 1113 1352 4 239.0 1224 3 382 4 0 0 0 0 0 0 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 270B 380-3-60 342 418 672 817 4 144.9 742 3 232 4 0 0 0 0 0 0 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 565 684 4 119.7 612 3 192 4 0 0 0 0 0 0 16 3.50 30.40 56.0 8 230 1200 5.22 PW
208/230-3-60 187 253 1199 1476 2 277.0 1330 3 443 2 2 239 1224 3 382 2 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 295B 380-3-60 342 418 723 891 2 167.6 807 3 268 2 2 144.9 742 3 232 2 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 607 746 2 138.5 665 3 222 2 2 119.7 612 3 192 2 16 3.50 30.40 56.0 8 230 1200 5.22 PW
208/230-3-60 187 253 1275 1552 4 277.0 1330 3 443 4 0 0 0 0 0 0 16 6.10 24.00 97.6 8 230 1200 5.22 PW
ASY 310B 380-3-60 342 418 769 936 4 167.6 807 3 268 4 0 0 0 0 0 0 16 3.52 24.00 56.3 8 230 1200 5.22 PW
460-3-60 414 506 645 783 4 138.5 665 3 222 4 0 0 0 0 0 0 16 3.50 30.40 56.0 8 230 1200 5.22 PW
LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect unit
MOCP - Maximum Over Current Protection performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept
CB - Circuit Breaker two or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5. Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
kW - Kilo Watt 8. Neutral line required on 380V-3Ph-60Hz power supply only.
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA values are based on nominal conditions.
ELECTRICAL DATA
SUPPLY VOLTAGE COMPRESSOR TYPE-1 COMPRESSOR TYPE-2 CONDENSER FAN MOTORS CRANKCASE HEATER COMP.
UNIT WIND-
SIZE Nominal RLA LRA CB CB RLA LRA CB CB FLA Total CB Total Total ING
Min. Max. MCA MOCP Qty. Qty. Qty. FCA Volts
(V-Ph-Hz) (each) (each) Poles MTA Qty. (each) (each) Poles MTA Qty. (each) kW (Qty.) Watts Amps
208/230-3-60 187 253 1325 1533 4 208.0 1040 3 333 4 2 165.6 885 3 265 2 18 6.10 27.00 109.8 9 230 1600 6.96 PW
ASY 330B 380-3-60 342 418 799 925 4 125.9 631 3 201 4 2 100.2 534 3 160 2 18 3.52 27.00 63.4 9 230 1600 6.96 PW
460-3-60 414 506 671 775 4 104.0 520 3 166 4 2 82.8 423 3 132 2 18 3.50 34.20 63.0 9 230 1600 6.96 PW
208/230-3-60 187 253 1410 1618 6 208.0 1040 3 333 6 0 0 0 0 0 0 18 6.10 27.00 109.8 9 230 1800 7.83 PW
ASY 350B 380-3-60 342 418 850 976 6 125.9 631 3 201 6 0 0 0 0 0 0 18 3.52 27.00 63.4 9 230 1800 7.83 PW
460-3-60 414 506 713 817 6 104.0 520 3 166 6 0 0 0 0 0 0 18 3.50 34.20 63.0 9 230 1800 7.83 PW
208/230-3-60 187 253 1604 1843 6 239.0 1224 3 382 6 0 0 0 0 0 0 18 6.10 27.00 109.8 9 230 1800 7.83 PW
ASY375B 380-3-60 342 418 969 1114 6 144.9 742 3 232 6 0 0 0 0 0 0 18 3.52 27.00 63.4 9 230 1800 7.83 PW
460-3-60 414 506 811 931 6 119.7 612 3 192 6 0 0 0 0 0 0 18 3.50 34.20 63.0 9 230 1800 7.83 PW
208/230-3-60 187 253 1628 1867 6 239.0 1224 3 382 6 0 0 0 0 0 0 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 400B 380-3-60 342 418 983 1128 6 144.9 742 3 232 6 0 0 0 0 0 0 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 825 945 6 119.7 612 3 192 6 0 0 0 0 0 0 22 3.50 41.80 77.0 11 230 1800 7.83 PW
208/230-3-60 187 253 1751 2028 3 277.0 1330 3 443 3 3 239 1224 3 382 3 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 420B 380-3-60 342 418 1057 1224 3 167.6 807 3 268 3 3 144.9 742 3 232 3 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 886 1025 3 138.5 665 3 222 3 3 119.7 612 3 192 3 22 3.50 41.80 77.0 11 230 1800 7.83 PW
208/230-3-60 187 253 1789 2066 4 277.0 1330 3 443 4 2 239.0 1,224 3 382 2 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 450B 380-3-60 342 418 1080 1247 4 167.6 807 3 268 4 2 144.9 742 3 232 2 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 905 1044 4 138.5 665 3 222 4 2 119.7 612 3 192 2 22 3.50 41.80 77.0 11 230 1800 7.83 PW
208/230-3-60 187 253 1924 2219 3 295.0 1330 3 472 3 3 277 1330 3 443 3 22 6.10 33.00 134.2 11 230 1800 7.83 PW

21
ASY 475B 380-3-60 342 418 1161 1340 3 178.8 807 3 286 3 3 167.6 807 3 268 3 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 973 1120 3 147.7 665 3 236 3 3 138.5 665 3 222 3 22 3.50 41.80 77.0 11 230 1800 7.83 PW
208/230-3-60 187 253 1978 2273 6 295.0 1330 3 472 6 0 0 0 0 0 0 22 6.10 33.00 134.2 11 230 1800 7.83 PW
ASY 500B 380-3-60 342 418 1195 1374 6 178.8 807 3 286 6 0 0 0 0 0 0 22 3.52 33.00 77.4 11 230 1800 7.83 PW
460-3-60 414 506 1000 1148 6 147.7 665 3 236 6 0 0 0 0 0 0 22 3.50 41.80 77.0 11 230 1800 7.83 PW

LEGEND: NOTES:
MCA - Minimum Circuit Ampacity per NEC 430-24 1. Customer to specify the exact nominal power supply available at site so that electrical components are selected accurately, failing to do so will affect unit
MOCP - Maximum Over Current Protection performance & terms of warranty.
RLA - Rated Load Amps 2. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker.
LRA - Locked Rotor Amps 3. The maximum incoming wire size is 500 MCM. On units having MCA greater than 500 MCM wire, the factory supplied power terminal block will accept
CB - Circuit Breaker two or more parallel field wires per pole phase.
MTA - Must Trip Amps 4. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection.
FLA - Full Load Amps 5. Under compressor type 1 are the big compressors or compressor with economizer, and type 2 are the small compressors or compressor without Economizer.
FCA - Fan Circuit Amps 6. All field wiring must be in accordance with NEC and local standards.
PW - Part Winding Start Compressor 7. Minimum and maximum unit supply voltages are shown in the tabulated data above.
kW - Kilo Watt 8. Neutral line required on 380V-3Ph-60Hz power supply only.
9. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
10. RLA values are based on nominal conditions.
WATER SIDE PRESSURE DROP
200

1 2 3 4 5 6 7
60 70 80 90 100

8
50
40
30
PRESSURE DROP (FT. OF WATER)
20
8 9 10
7
6
5
4
3
2
1

10 20 30 40 50 60 70 80 90 100 200 300 400 500 600 700 800 900 1000 1200 1500
FLOW RATE - GPM

MODEL No. CURVE No. Minimum GPM Maximum GPM MODEL No. CURVE No. Minimum GPM Maximum GPM
ASY050B 1 82 138 ASY215B 7 375 593
ASY060B 2 98 170 ASY230B 7 412 620
ASY070B 2 108 192 ASY240B 7 447 633
ASY080B 2 124 214 ASY250B 4 425 708
ASY090B 3 164 265 ASY270B 6 450 768
ASY100B 3 184 271 ASY295B 6 502 826
ASY120B 3 203 325 ASY310B 6 537 866
ASY130B 4 222 356 ASY330B 6 572 925
ASY140B 5 251 372 ASY350B 6 601 971
ASY150B 6 267 411 ASY375B 7 634 1048
ASY160B 6 272 437 ASY400B 7 650 1095
ASY170B 6 315 455 ASY420B 7 710 1164
ASY180B 7 301 498 ASY450B 8 779 1242
ASY190B 7 343 522 ASY475B 8 866 1297
ASY200B 7 365 534 ASY500B 8 920 1315
CONVERSION FACTOR: GPM = 0.063 Liters per second.
Feet of water = 2.989 Kilo Pascal (kpa).
NOTE: 1. If an application requires certain water flow rate outside these limits, please check with your nearest dealer/sales office.
2. If the chiller has 2 evaporators, then the total water flow must be divided by 2 while applying the above curves (applicable for models
ASY250B - ASY500B.

22
RECOMMENDED INSTALLATION
LEAVING/RETURN WATER TEMPERATURE SENSOR & WATER FLOW SWITCH
NOTE: 1. For chiller with 2 coolers, leaving water temperature sensor and return water temperature sensor should be installed in the water piping
main header of every chiller.
2. Water flow switch should be installed vertically on the horizontal pipe line closed to the leaving water port of every cooler.

LEAVING RETURN
WATER WATER

CHILLER # 1

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]

FS
RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]

CHILLER # 2

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]


FS

RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LWT
LEAVING WATER SENSOR
(FIELD INSTALLATION]

CHILLER # n

CONTROL PANEL

IN COOLER 1 OUT IN COOLER 2 OUT

FLS1 FLS2
FS

(FIELD INSTALLATION] (FIELD INSTALLATION]


FS

RWT
RETURN WATER SENSOR
(FIELD INSTALLATION]

LEGEND : LWT
BULB WELL FOR THE LWT/RWT (ZAC NOT SUPPLIED) LEAVING WATER SENSOR
(FIELD INSTALLATION]
LWT LEAVING WATER SENSOR (ZAC SUPPLIED - LOOSE PART)
NOTE :
RWT RETURN WATER SENSOR (ZAC SUPPLIED - LOOSE PART)
1. CHECK WITH THE ENGINEERING DEPARTMENT FOR THE FULL DETAILS
> or < WATER DIRECTION AND ACCURATE DRAWING.
FS WATER FLOW SWITCH / FLS# (ZAC SUPPLIED AS OPTIONAL)
2.HARDWIRE FROM FLOW SWITCH AND LWT/RWT SHOULD BE ROUTED
HARD WIRE TO THE UNIT CONTROLLER (ZAC NOT SUPPLIED)
INDIVIDUALLY AND DIRECT TO THE UNIT CONTROLLER.REFER TO THE
WATER PIPE LINE (CONTRACTOR SCOPE) ACTUAL UNIT WIRING DIAGRAM FOR DETAILS.

23
DIMENSIONS
ASY050B

ASY060B, ASY070B & ASY080B


DIMENSIONS
MODEL A

ASY060B 100

ASY070B - ASY080B 275

NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.

24
DIMENSIONS
ASY090B & ASY100B

ASY120B, ASY130B & ASY140B

NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.

25
DIMENSIONS
ASY150B, ASY160B & ASY170B

ASY180B, ASY190B, ASY200B, ASY215B, ASY230B & ASY240B


DIMENSIONS
MODEL A B C

ASY180B - ASY200B 2075 2200 1650

ASY215B 2185 2700 1115

ASY230B - ASY240B 2185 3200 800

NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.

26
DIMENSIONS
ASY250B, ASY270B, ASY295B & ASY310B
DIMENSIONS
MODEL A B C

ASY250B 422 1890 2250

ASY270B - ASY310B 483 1940 2200

27
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.
DIMENSIONS
ASY330B, ASY350B & ASY375B

28
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.
DIMENSIONS
ASY400B, ASY420B, ASY450B, ASY475B & ASY500B
DIMENSIONS
MODEL A B C

ASY400B - ASY420B 2200 3420 483

ASY450B - ASY500B 2130 3474 510

29
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.
TYPICAL SCHEMATIC WIRING DIAGRAM
(PART WINDING START)
HVTB
L1
REFER TO UNIT
L2
NAMEPLATE FOR
POWER SUPPLY L3

ETB/LUG CB17 CB18 CB19 CB20


CB1 CB3 CB2 CB4
L1A L1I L1J L1K L1L

L1B
L2C
L3C

L2D
L3D
L2A
L3A

L2B
L3B
L1C

L1D
NTB L2I L2J L2K L2L
CC1 CC3 CC2 CC4
N (SEE NOTE -7) L3I L3J L3K L3L

FMC1 FMC2 FMC3 FMC4 FMC5 FMC6 FMC7 FMC8


OLR1 OLR3 OLR2 OLR4
T2C
T3C

T2D
T3D
T1C

T1D
T1A
T2A
T3A

T1B
T2B
T3B

35G
36G
37G

35F
36F
37F
35C
36C
37C

35D
36D
37D

35H
36H
37H
35A
36A
37A

35E
36E
37E

35B
36B
37B
COMP COMP FM FM FM FM FM FM FM FM
1 2 3 7 1 5 4 8 2 6
TO HVTB TO NTB
L1 N

1B F1 5A CONTROL VOLTAGE 2
ATB 230V-1PH ATB
CCA1-1 3A
1HTR COMP1 OILHTR
SEE ALSO UNLOADER
CCA2-1 TIMER DETAILS
3B
2HTR COMP2 OILHTR

T1 T2 COMP1 SSPS
SSPS1
T1 T2
SSPS2 COMP2 SSPS

S1( CONTROL POWER)


SERIAL CABLE
UVR
1A 1 230VAC
(SEE UVM CONNECTION) TRANS TO ATB
230VAC
4 24VAC 5 MB 1 2
SSPS1
8A
A1/D1(SSPS-1)
CBA1-1 CBA3-1 TRANS2
22A 23A
A2/D2(CB-1) EEVB
JP2A 6 7
A3/D3(OL-1)
HPS1 OLR1-1 OLR3-1 12/24VAC OB1 EEVB JUMPER & DIP SWITCH
10A 11A 9A +
X1 RED
A4/D4(HPS-1)
EEV X9 A1 X1 GRN TD1 CLOSED
A5/D5(FCB-1) - 2A - -
X1 WHT EEV
SSPS2 AO1 5A V1 + 1 TU1 CLOSED
8B +
A6/D6(SSPS-2) + B1 X1 BLK
CBA2-1 CBA4-1 DIP S1 -
TL1 OPEN
22B 23B
A7/D7(CB-2) 4
JP3A JU1 OPEN
A8/D8(OL-2) 3 EEV CARD
OLR2-1 OLR4-1 2 1 2 3 4
HPS2 10B 11B 9B 1 S1
A9/D9(HPS-2) X2 RED
+ 24V ON OFF ON OFF
- 2B - A2 X2 GRN
(DIP)
A10/D10(FCB-2)
FLS 10 CWP* 11 A02 5B V2 - 12V OFF ON OFF OFF
X2 WHT EEV
A11/D11(FLW) + + + 2
B2 X2 BLK
1 2G PE - **SEE ALSO DISCHARGE TEMPERATURE
A12/D12 (EXT. ENABLE)
CONNECTION
1 2H PE
A13/D13 (EMERGENCY)

AC/DC(DIGITAL COM)
1C R1(DIG OUT) 1O 12A CC1
COMP1 CONTACTOR
LLS1
R2(DIG OUT) LIQUID LINE SOLENOID1
2C 2O

R3(DIG OUT) UL2-1


3C 3O 14A POWER DECREASE CP1
R4(DIG OUT) 12B CC2
4C 4O COMP2 CONTACTOR
R5(DIG OUT) LLS2
5C 5O LIQUID LINE SOLENOID2
R6(DIG OUT) UL2-2
6C 6O 14B POWER DECREASE CP2
R7(DIG OUT)
7C 7O HOT GAS BYPASS SOLENOID
7A 8C R8(DIG OUT) 8NO
6A ALARM - NO CONTACT
8NC
16 ALARM - NC CONTACT
R9(DIG OUT) TK3
C 9O 18A 112 FMC1
TK7 CTR-FAN 3
116 FMC2
R10(DIG OUT) TK1 CTR-FAN 7
10O 19A 110 FMC3
TK5 CTR-FAN 1
114 FMC4
R11(DIG OUT) CTR-FAN 5
11O

R12(DIG OUT) SL.I1


12O 20A
LIQUID INJECTION 1
R13(DIG OUT) TK4
C 13O 18B 113 FMC5 CTR-FAN 4
TK8
117 FMC6 CTR-FAN 8
R14(DIG OUT) 14O TK2
19B 111 FMC7 CTR-FAN 2
REMOTE MONITORING TK6
115 FMC8
R15(DIG OUT)
CTR-FAN 6
INTERFACE 15O
(SEE OPTION BOX) R16(DIG OUT) SL.I2
16O 20B
COM2 LIQUID INJECTION 2
R17(DIG OUT) UL4-1
17C 17O 15A
POWER INCREASE CP1
18C
R18(DIG OUT)
18O 15B UL4-2
POWER INCREASE CP2

22A 28A
- - SPT1 - COMP1
T1S ST1 O1 SUCTION PRESSURE
23A 29A
SUCTION TEMP SENSOR COMP1 (A1-ST1) (A5-SP1) + + TRANSDUCER

SH SH

24A (A2-TOUT) 30A


- - DPT1 - COMP1
T2S TOUT D1 DISCHARGE PRESSURE
25A 31A
TOUT/LWT TEMP. SENSOR (A6-DP1) + + TRANSDUCER

22B -
O1
T3S 23B
ST2
(A7-OP1) +
(A3-ST2)
SUCTION TEMP SENSOR COMP2
SH
SH
28B
26A - - SPT2 - COMP2
S2 SUCTION PRESSURE
T4S TIN (A8-SP2) +
29B + TRANSDUCER
27A (A4-TIN)
TIN/RWT TEMP. SENSOR JU1 JU2
TU1
TD1
30B
JUMPER & DIP SWITCH TL1 D2 - - DPT2 - COMP2
SELECTION ON MAIN BOARD
DISCHARGE PRESSURE
S1 (A9-DP2)+ 31B + TRANSDUCER
JU1 CLOSED USER INTERFACE BOARD
ON DIP
JU2 CLOSED On/Off * SH
TU1 CLOSED
TD1 CLOSED 1 2 3 4
TOUT=10C TIN=15C
SET MENU * O2 -
TL1 OPEN COOLING 75% X53
S1 1 2 3 4 ESC
SERIAL CABLE (A10-OP2) +
* X52
(DIP) GND
ON OFF OFF OFF

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

30
TYPICAL SCHEMATIC WIRING DIAGRAM
(PART WINDING START)
COMP LAYOUT LEGEND
CBA THERMAL MAGNETIC CIRCUIT BREAKER AUXILIARY
COMP1 COMP2
COMP COMPRESSOR
CONTROL PANEL
CC COMPRESSOR CONTACTOR
CCA COMPRESSOR CONTACTOR AUXILIARY
CWP CHILLED WATER PUMP
ETB EARTH TERMINAL BLOCK
FAN LAYOUT
COMP FAN 1 FLS FLOW SWITCH
FM FAN MOTOR
FMC FAN MOTOR CONTACTOR
CONTROL PANEL FAN1 FAN3 FAN5 FAN7
F FUSE
HPS HIGH PRESSURE SWITCH
HGBS HOT GAS BYPASS SOLENOID
FAN2 FAN4 FAN6 FAN8
HVTB HIGH VOLTAGE TERMINAL BLOCK
COMP FAN 2
JP JUMPER
LPS LOW PRESSURE SWITCH
MB MASTER BOARD
NTB NEUTRAL TERMINAL BLOCK
OLR OVER LOAD RELAY
PT PRESSURE TRANSDUCER
UNLOADER TIMER DETAILS P POTENTIAL BAND
LPS CONNECTION (OPTIONAL)
TIMER 11 SLE ECONOMIZER SOLENOID
CB1A-1 CB3A-1 D2(MB) CCAT11-1 AR11
LPS1 22A
63A 4AA SB SLAVE BOARD
1 23A 3A 2
AR11-1 UL3-1
3AA S1 CONTROL SWITCH
UL3-1
CB2A-1 CB4A-1 D7(MB) SSPS SOLID STATE PROTECTION SYSTEM
LPS2 22B TIMER 21
63B CCAT21-1
1 23B AR21 TK FAN THERMAL CONTACT
4BB
3B TMCB THERMAL MAGNETIC CIRCUIT BREAKER
AR21-1 UL3-2
3BB TRANS TRANSFORMER
UL3-2
REMOTE MONITORING CONNECTION (OPTIONAL)
TDS TIME DELAY SWITCH
GND TS TEMPERATURE SENSOR
- ABOVE CONNECTION IS ONLY FOR ZAC P/N 80062300 ONLY.
+ SET POINT = 180 SEC UL UNLOADER
IS485 TO MAIN 256 UVM UNDER VOLTAGE MONITOR
BOARD (COM2) 1 2 4 8 16 32 64 128 512
TO UVR UNDER VOLTAGE RELAY
ON
GATEWAY
TERMINAL BLOCK
ECONOMIZER CONNECTION (OPTIONAL)
- - - - - FIELD SUPPLY
COMPRESSOR CONTACTOR CONNECTION FOR PART WIND START LEGEND ON MAIN BOARD
ECO1
13A CC1 CC2
TO MB (20) 2 ECONOMIZER 1 2 2
D1 DIGITAL INPUT 1
12A 12B

13B ECO2 CC1A-2 CC3 CC2A-2 CC4


C/1C COMMON
TO MB (50) 2 ECONOMIZER 2 1 61A 2 1 61B 2 1O DIGITAL OUT 1
EQUALIZER CONNECTION (OPTIONAL) DC DIGITAL COMMON
FOR PART WIND START TIME DELAY SWITCH (TDS) OPTION
3A SL.E1 CC1A-2 TDS1-1SEC CC3
T1 THERMISTOR 1
TO CCA1-1 2 EQUALIZER 1
1 61A 62A
2 SH SHIELD
3B SL.E2
TO CCA2-1 2 EQUALIZER 2 CC2A-2 TDS2-1SEC CC4 X52/X53 SERIAL COMMUNICATION PORT
61B 62B
1 2
PE POTENTIAL EARTH
JU/TU/TD/TL BOARD JUMPERS
UNIT EXTERNAL ENABLE/DISABLE OPTION UVM CONNECTION JUMPER SETUP ON
MAIN BOARD
VFC FROM CUSTOMER PANEL L1
ATB ATB TL2 OPEN
1
VFC 2G
L2
L3
NOTES
NOTE: TD2 CLOSED
TERMINAL A,B,& C 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
UVR
TU2 CLOSED
UNIT EMERGENCY OPTION ON UVM TO BE UVM ALL FIELD WIRING TO COMPLY WITH LOCAL CODES.
PHASE MATCHED WITH JU11 1-2 CLOSED
UNIT CONTROLS. 1A 1 2. FUSES TO DUAL ELEMENT TYPE.
ATB VFC FROM CUSTOMER PANEL ATB
JU13 1-2 CLOSED
1 VFC 2H
GROUND FAULT PROTECTION OPTION.(GFP) 3. USE COPPER CONDUCTORS ONLY.
JU15 1-2 CLOSED
4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
COMP JU5 1-2 CLOSED TO BE PROVIDED BY END USER WITH RATING AS
HOT GAS BYPASS OPTION
MB 2 1 JU6 1-2 CLOSED RECOMMENDED BY MANUFACTURER.
70A/B
1 7C R7 7O
HGBS 2 71A/B JU7 1-2 CLOSED
5. POWER MUST BE SUPPLIED TO CRANKCASE
15
HEATER FOR MINIMUM OF 12 HOURS PRIOR TO
TI T2 A1 A2
JU8 1-2 CLOSED SYSTEM START UP.
Current Transformer EARTH FAULT RELAY
wire number, 70A/71A for 32 31 34
JU9 1-2 CLOSED IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
IF THE HGBS IS ENABLE COOLER HEATER TAPE IS NOT POSSIBLE Comp 1 and 70B/71B for
Comp 2. HEATER MUST BE ON FOR 12 HOURS BEFORE
COOLER HEATER TAPE OPTION JU4 1-2 CLOSED OPERATING THE SYSTEM.
MB 32 31 A3/D3 (MB)
1 65A JU3 1-2 CLOSED FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
1 7C R7 HEATER 2 Comp 1 REMOVE JP2A
7O 15 EFR1 JU19 1-2 CLOSED RESULT IN COMPRESSOR DAMAGE.
32 31 A8/D8 (MB)
JU12 1-2 CLOSED 6. MARK IN THE BOX FOUND AT THE UPPER RIGHT OF
1 65A
IF THE COLLER HEATER TAPE IS ENABLE HGBS IS NOT POSSIBLE
Comp 2 REMOVE JP3A THE RESPECTIVE OPTIONAL ITEM, IF THE OPTIONAL
EFR2 JU10 1-2 CLOSED ITEM IS INCLUDED IN THE UNIT.
** DISCHARGE TEMPERATURE SENSOR CONNECTION
7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz
C1 D1 POWER SUPPLY ONLY.
X7 DT1
T1
USE FOR OB1 EEVB ONLY

C2 D2
X8 DT2
T2
EEVB

31
MICROPROCESSOR CONTROLLER
Sequence of operation
The following describes the sequence of operation for a two screw compressor chiller unit.
Operation is similar for a one or four compressor unit.
For initial start-up, the following conditions must be met:
All power supplied to the unit shall be energized for 12 hours.
Control power switch on for at least 5 minutes.
All safety conditions satisfied.
Press ESC on the microcomputer keypad.
Chilled water pump running and chilled water flow switch contact closed.
Customer interlock contact closed, if any.

STAGE - ON SEQUENCE
Staging ON & OFF sequence, shall be accomplished by the Leaving water temperature control selection.

Stage #1:
If the Leaving Water Temperature is greater than the Stage 1- ON water temperature set point value, the Compressor #1
liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or unloaded
capacity. The compressor capacity is varied to achieve the full/part load capacity as per the load demand.

As discharge pressure of Compressor #1 rises, the corresponding fans are energize accordingly to the fan stage-ON set
point. If the discharge pressure falls below the fan stage-OFF set point value, the corresponding fans will turn off.

Stage #2:
If the Leaving Water Temperature is greater than the Stage 2- ON water temperature set point value, the Compressor #2
liquid line solenoid & slider control valves shall be switched ON. Now the compressor is in the minimum or unloaded
capacity. The compressor capacity is varied to achieve the full/part load capacity as per the load demand.

As discharge pressure of Compressor #2 rises, the corresponding fans are energize accordingly to the fan stage-ON set
point. If the discharge pressure falls below the fan stage-OFF set point value, the corresponding fans will turn off.

STAGE - OFF SEQUENCE


During the staging OFF, the first-in last-out sequence is adopted, if equalization of compressor timing is not selected.
Else the more used is switched off.

As the applied load decreases and when the leaving water temperature falls below the stage 2 -OFF water temperature
set point value, stage 2 is turned off.

If the leaving water temperature falls below the stage 1-OFF water temperature set point value, the stage 1 is turned off.

32
TROUBLESHOOTING GUIDE
1) No LED display lit or erratic display behavior
a) Check serial cable integrity.
b) Check serial cable connections on both the User Interface Board and the Main Board.
c) Check correct and tight insertion of jumpers JU1 and JU2 on the Main Board.
d) Check correct and tight insertion of jumpers TU1 and TD1 on the User Interface Board and on the last board of the
network.

2) Controller does not respond to keypad


a) Check serial cable integrity.
b) Check serial cable connections on both the User Interface Board and the Main Board.
c) Check correct and tight insertion of jumpers TU1 and TD1 on the User Interface Board, main and/or auxiliary
board.
d) Check dip switches and integrity on the User Interface Board.

3) Several analog values reading incorrectly


a) Check correct and tight connection of the probes to the board.
b) Check the probe cable: test for short-circuit.
c) The pressure transducer probe is a 4-20mA transmitter check the polarity of the connection on the Board.
d) Check if the power supply voltage is into the specified limits: 24Vac +/- 10%.
e) The temperature probe is a PTC sensor disconnect it from the board and measure its resistance that is 1000 ohm
at 250C or 1200 ohm at 500C.

4) Digital input reading incorrectly


a) Check if the auxiliary 220 Vac voltage is present in the electrical box.
b) Check if the AC input on the Board is correctly connected to one of the 220 Vac terminals in the electrical box.
c) Check if A1/A14 inputs are correctly connected with respect to the cabling diagram of the electrical box.

5) No LCD display lit or erratic display behavior


a) Check serial cable integrity.
b) Check serial cable connections on both the User Interface Board and the Main Board.
c) Check correct and tight insertion of jumpers JU1 and JU2 on the Main Board.
d) Check correct and tight insertion of jumpers TU1 and TD1 on the User Interface Board, main and/or auxiliary
board.
e) Adjust display intensity by rotating trimmer RV1 counter-clockwise (from the back side of the board).

6) No LED H1 blinking light on NG3 Board


a) Check power supply cable an connection.
b) Check if the power supply voltage is into the specified limits: 24Vac +/- 10%.
c) Check for fuse F1, replace with 1AT/250V if blown.

7) No display of leds on User Interface Board


a) Check serial cable integrity.
b) Check serial cable connections on both the User Interface Board and the Main Board.
c) Check correct and tight insertion of jumpers JU1 and JU2 on the Main Board.
d) Check correct and tight insertion of jumpers TU1 and TD1 on the User Interface Board, main and/or auxiliary
board.

33
8) Auxilliary board not responding to commands
a) Check if LED H1 on Auxilliary board is blinking , if not go to point (6).
b) Check serial cable integrity.
c) Check serial cable connections on both the Main and the Auxilliary boards.
d) Check that jumpers JU1 and JU2 on the Auxilliary boards are not installed.
e) Check correct and tight insertion of jumpers TU1 and TD1 on the User Interface Board, main and/or auxiliary
board.

9) Analog Outputs not responding


a) Check Analog Output cables integrity (for short-circuit).
b) Check Analog Output cabling and connections.
c) Check if the power supply voltage is into the specified limits: 24VAC +/- 10%.
d) Check the fuse F1, replace with 1AT/250V if blown.

10) Digital Outputs not responding


a) Check Digital Output cables integrity (no short-circuit, no open-circuit).
b) Check digits Output cabling and connections.
c) Check if the power supply voltage is into the specified limits: 24VAC +/- 10%.
d) Check the fuse F1, replace with 1AT/250V if blown.

11) Serial Communication with Remote Monitoring Control not Functioning


a) Check the serial cable connected on plug-in board IS-485 mounted on the Main Board.
b) Check if the plug-in board is correctly mounted on the Main Board.
c) Check if jumpers X5 and X6 on the plug-in board IS-485 are correctly installed.
d) Check if jumpers X17 and X18 on the GATEWAY board are correctly installed.

34
APPLICATION GUIDELINES
INTRODUCTION
These guidelines should be considered when designing systems and their installation utilizing Zamil ASY series liquid
chillers. Stable operation, performance and reliability of units is often dependent upon proper compliance with these
recommendations. When any application varies from these guidelines, it should be referred with Zamil Air Conditioners
for specific recommendations.

UNIT SELECTION/SIZING
Unit selection procedure and capacities are provided in this catalog for proper selection. The Zamil electronic selection
program may also be utilized for this purpose.
Over sizing chillers beyond a maximum limit of 5 10 % in order to assure adequate capacity or considering future
expansions is not recommended. Over sizing adversely affects the operating efficiency due to erratic system operation
and excessive compressor cycling which also results in reduced compressor life. It should be noted that, units operate
more efficiently when fully loaded rather than larger equipment operating at partial capacities. In addition, an oversized
unit is usually more costly to purchase, install and operate.
When over sizing is desired due to anticipation of future plant expansion, consider using multiple units. For example,
install a single chiller for the present load requirement and install a second chiller for the foreseen additional load demand
due to expansion. Further, it is also recommended that installing two chillers instead of a single chiller be considered in
applications where partial load operation at low capacities is necessary.
Operation of two chillers at higher loading is preferred to operating a single chiller at or near its minimum possible capacity.

FOULING FACTOR AND WATER REQUIREMENT


The tabulated performance data provided in this catalog are based on a fouling factor of 0.00010 hr-ft2-0F/Btu (0.000018 m2-0C/W).
As fouling factor is increased, unit capacity decreases and power input increases. For unit selection at other fouling factors, apply
appropriate correction factor from the table provided in this catalog.
These chillers are suitable for operation with well maintained water systems. Using unclean and untreated water may
result in scale and deposit formation causing reduced cooler efficiency or heat transfer and corrosion or pitting leading to
possible equipment damage. The more scale forming material and suspended solids in the system water, the greater the
chances of scale and deposit formation and fouling. These include calcium, magnesium, biological growth (algae, fungi
and bacteria), dirt, silt, clays, organic contaminants (oils), silica, etc. which should be kept to the minimum to retard scale
and deposit formation. In order to prevent corrosion and pitting, the pH value of the water flowing through the cooler must
be kept between 7 and 8.5. Zamil recommends that a water treatment specialist is consulted to provide and maintain
water treatment, this is particularly critical with glycol systems.

EFFECT OF ALTITUDE ON UNIT CAPACITY


The tabulated performance data provided in this catalog are for use at or near sea level altitude application. At altitudes
substantially above sea level, the decreased air density will reduce condenser capacity and therefore unit capacity. For unit
selection at these higher altitudes, apply appropriate correction factor from the table provided in this catalog.

HIGH AMBIENT CONSIDERATION


These chillers are designed for year round operation over a range of ambient temperatures. As a standard, these chillers
can start and operate satisfactorily up to 1250F (520C) ambient temperature at rated nominal voltage.

WATER FLOW RATES AND COOLER PRESSURE DROP


The maximum and minimum water flow rates for all unit models and the pressure drop chart are provided in this catalog.
The design water flow rate must be within this range. Design flow rates below the minimum limits will result in laminar
flow causing freeze-up problems, stratification and poor control and flow rates beyond the maximum limits cause exces-
sive pressure drop and severe tube erosion.
During unit operation, water flow rate must not vary more than 5% from the design flow rate. The water flow switch should be
calibrated accordingly. The piping and pumping layout should be right for the application and must assure proper water return
and circulation. When using glycol solution, flow rate and pressure drop are higher than with water, therefore care must be
taken not to exceed the limits. In such applications, consult Zamil Air Conditioners for specific recommendations.

35
COOLER FLUID (WATER OR GLYCOL) TEMPERATURES RANGE
Unit can start and pull down from 950F (350C) entering fluid temperature. The design leaving chilled fluid temperature
(LCWT) range as mentioned earlier in the tabulated performance data is 40 to 500F. The design entering chilled fluid
temperature range is 50 to 600F. The design cooler temperature drop (T) range is 5 to 150F.
The tabulated performance data provided in this catalog is based on a chilled water temperature drop of 100F. Units may
be operated at any desired temperature drop within the range of 5 to 150F as long as the temperature and flow limits are
not violated and appropriate correction factors are applied on the capacity and power input. The Zamil electronic selec-
tion program can be very handy in selecting equipment at different temperature drops.
It should be noted that temperature drop outside the aforesaid range is not permitted as it is beyond the optimum range of
control and could adversely affect the functioning of microprocessor controller and may also prove to be detrimental for the
equipment.

FLOW RATES AND/OR WATER TEMPERATURES OUT OF RANGE


Certain applications (particularly process cooling jobs) call for flow rates and/or water temperatures that are outside the
above mentioned limits/range. Our chillers can be utilized for these applications by selecting the chiller based on the
specific process load and making a suitable piping and mixing arrangement in order to bring the flow rates and/or water
temperatures relevant to the chiller within acceptable limits.
Example 1:
An application requires 240 GPM of water at 450F and the return water temperature is 650F.
A standard chiller can be used for this application as shown in the following basic schematic layout (single mixing arrange-
ment).
45F 45F
500 GPM 240 GPM

200 TR
Chiller 45F Load
260 GPM 200 TR

54.6F
500 GPM

65F
240 GPM
Example 2:
An application requires 192 GPM of water at 650F and the return water temperature is 800F.
A standard chiller can be used for this application as shown in the following basic schematic layout (dual mixing arrangement).

45F 45F 65F


340 GPM 82.2 GPM 192 GPM

120 TR
Chiller 80F Load
45F
257.8 GPM 109.8 GPM 120 TR
53.4F
340 GPM

53.4F 80F 80F


340 GPM 82.2 GPM 192 GPM

36
COOLER FREEZE PROTECTION
If the unit is located in an area where ambient temperatures fall below 320F (00C), cooler protection in the form of Ethylene
Glycol Solution is required to protect the cooler and fluid piping from low ambient freeze-up. This glycol solution must be
added to the water system loop to bring down the freezing point of water to a difference of 150F (8.30C) below minimum
operating ambient temperature.

Using this glycol solution causes a variation in unit performance, flow rate and pressure drop, therefore appropriate
correction factors from the aforementioned table in this catalog should be applied.

MULTIPLE CHILLER ARRANGEMENT OR PLANT CONFIGURATION


A multiple chiller system has two or more chillers connected by parallel or series piping to a common distribution system.
Multiple chiller arrangements offer the advantage of operational flexibility, standby capacity and less disruptive mainte-
nance. Also, they offer some standby capacity if repair work must be done on a chiller from a set of duty chillers. Starting
in-rush current is reduced, as well as power costs at partial-load conditions.

A multiple chiller arrangement should be provided if the system load is greater than a single chiller capacity, standby
capability is desired, large temperature drop (greater than 150F) is desired or application calls for splitting the total
capacity for better part load operation.

In designing a multiple chiller plant, units of same size should be preferred over different sizes to facilitate balanced water
flow. It is mandatory that cooler flow rates must be balanced to ensure proper flow to each chiller based on its respective
capacity. As mentioned above, two basic multiple chiller systems are used: parallel and series chilled water flow.

In the parallel arrangement, liquid to be chilled is divided among the liquid chillers; the multiple chilled streams are
combined again in a common line after chilling. Water temperatures (EWT or LWT) can be used to cycle units On and Off
based on the cooling demand. Parallel arrangements permit adding chillers in the future for plant expansion with the
appropriate considerations beforehand.

In the series arrangement, the chilled liquid pressure drop may be higher unless coolers with fewer liquid-side passes or
baffles are used. No over chilling by either unit is required, and compressor power consumption is lower than it is for the
parallel arrangement at partial loads. It is also possible to achieve higher overall entering to leaving temperature drops,
which may in turn provide the opportunity for lower chilled water design temperature, lower design flow and resulting
installation and operational cost savings. Series chiller arrangements can be controlled in several ways based on the
water temperatures depending on cooling demand.

A valved piping bypass is suggested around each chiller to facilitate future servicing as it gives the personnel an option
for service without a complete shutdown.

Zamil recommends the parallel arrangement for design temperature drops (T) up to 150F and the series arrangement
beyond that i.e., 16 to 200F. Complete design details on these parallel and series chilled water flow arrangements can be
found in the ASHRAE handbooks and other design literature which should be referred by the designer in preparing his
detailed designs.

PIPING ARRANGEMENTS AND PLANT LAYOUT


Our chillers are suitable for incorporating in Two Pipe single temperature systems or Four Pipe independent load
systems. The system piping circuit (load distribution circuit) should be basically parallel piping either Direct Return or
Reverse Return system with a good pumping arrangement.

The method of circuiting and pumping is a judgment decision by the designer. The designer must weigh the pros and
cons of cost, nature of load and configuration of building, energy economics, flexibility, installation requirements and
others to determine the best arrangement for his project. In all cases, it must be ensured that the design water flow is
constantly maintained through the chillers at all stages of operation. Some suggested arrangements with basic sche-
matic layouts are as follows:

37
A. Single or multiple chillers with constant water flow through chillers and load system:

CHWS

Chiller Load Load

3-Way 3-Way
Valve Valve

CHWR

Constant Speed Pump

In this type of arrangement, constant water flow through the chillers and load distribution piping circuit is maintained.
Before proceeding further, a brief explanation on the operation of a typical chilled water system / valves which is funda-
mental to the design or analysis of a system.

Where multiple zones of control are required, the various load devices are controlled first; then the source (chillers)
system capacity is controlled to follow the capacity requirement of the loads. Control valves are commonly used to control
loads. These valves control the capacity of each load by varying the amount of water flow through the load device.
Control valves for these applications are two-way (straight-through) and three-way valves. The effect of either valve is to
vary the amount of water flowing through the load device. With a two-way valve, as the valve strokes from full-open to full-
closed, the quantity of water flowing through the load gradually decreases from design flow to no flow. The three-way
mixing valve has the same effect on the load as the two way valve - as the load reduces, the quantity of water flowing
through the load decreases in proportion to the load and the difference amount is directed through a bypass.

In terms of load control, a two-way valve and a three-way valve perform identical functionsthey both vary the flow
through the load as the load changes. The fundamental difference between the two-way valve and the three-way valve is
that as the source or distribution system sees the load, the two-way valve provides a variable flow load response and the
three-way valve provides a constant flow load response.

Referring to the foregoing schematic layout, this is a conventional system and is not as energy efficient as the two-way
valve systems especially on the pumping side due to constant water circulation in the system. On multiple chiller instal-
lations, pumps are required to operate continuously and the sequencing of chillers is dependent on water temperatures.

38
B. Single or multiple chillers with constant water flow through chillers and variable water flow through load system:
FM-1
CHWS

Bypass
Line

Chiller Bypass Load Load


Control
Valve
P

FM-2
2-Way 2-Way
Valve Valve

Variable Speed Pump

CHWR

System
Controller

In this type of arrangement, constant water flow through the chillers is maintained, however the quantity of water flowing
through the load distribution piping system decreases in proportion to the load and the difference amount is directed
through a bypass pipe that connects the supply and return headers. Brief sequence of operation is as follows:

The bypass with its control valve and flow meter provides the design flow required through the chillers. Flow meter FM1
measures the actual flow to the chilled water system. The system flow is compared with the required flow for the chillers.
The difference is made up through the bypass and is monitored by flow meter FM2. This flow meter controls the bypass
valve to maintain the desired flow in the bypass based on the set points in the system controller (the valve is positioned
by sum of flow meters FM1 and FM2).

The speed of the chiller pumps is controlled by the differential pressure sensor/transmitter, maintaining the desired
differential pressure (P) across the cooling coils, their control valves and the branch piping. The pump speed is modu-
lated within a certain range in order to reduce the pumping head and not to alter the water flow rate (the duty flow rate of
the pumps remains constant). Each chiller-pump combination operates independently from the remaining chillers and
each pump is shutdown when the respective chiller is stopped. Instead of using water temperature as an indicator of
demand, the sequencing of chillers is dependent on water flow. The chillers are rated in gallons per minute; the actual
flow to the system determines the number of chillers that should be in operation.

Energy is saved because the system head is reduced appreciably when there are light cooling loads on the system and
due to cycling of pumps.

Note: Some designers may consider installing constant speed pumps and utilize pressure relief bypass control valves
controlled by a differential pressure sensor/controller to maintain a fixed differential pressure between the supply and
return mains of the chilled water system in order to accommodate for the required chiller flow and to achieve some form
of variable volume system. This method is not recommended as its a wasteful practice because a considerable amount
of energy is lost, an almost constant volume system results and the pumping energy remains substantially that required
at full system flow and head.

Also, the problem with this system is improper control of the bypass valve which does not guarantee proper flow through
the chillers and high differential pressures in the control valves on the cooling coils when the system friction subsides at
low loads which can cause lifting of the valve stems or wire cutting of the valve seats. Further, as all the water must be
pumped at a head equal to or greater than the design head, the pump or pumps are forced to run up the pump head
capacity curve, which increases the overpressure on the system and also increases the wear on the pumps, since they
are forced to operate with high radial thrusts.

39
C. Single or multiple chillers with constant water flow through chillers and variable water flow through load
system (primary/secondary pumping arrangement):
A CHWS

Variable
Speed Secondary Pump

Chiller Load Load

Flow Sensor
P

2-Way 2-Way
Valve Valve

Constant Speed
Primary Pump

B CHWR

System
Controller

This system is called a Primary Secondary System and in this arrangement, the generation zone is separated from the
transportation or distribution zone. In this type of arrangement also, constant water flow through the chillers is main-
tained, however the quantity of water flowing through the load distribution pump/piping system decreases in proportion to
the load and the difference amount is directed through a bypass pipe that connects the supply and return headers. This
bypass pipe forms a Hydraulic Coupling between the points A B and is also called as Common Bridge or Decoupling
Line. The sequence of operation is similar as the foregoing system with the following explanation:

The speed of the secondary chiller pump is controlled by the differential pressure sensor/transmitter, maintaining the
desired differential pressure (P) across the cooling coils, their control valves and the branch piping. This pump speed is
modulated within a broad range in order to reduce the pumping head and alter the water flow rate based on the changing
load conditions.

The primary pumps are constant speed pumps and the design flow rate through the chillers remains constant. Each
chiller-pump combination operates independently from the remaining chillers and each pump is shutdown when the
respective chiller is stopped. The sequencing of chillers is dependent on water flow. If greater flow is demanded than that
supplied by the chiller-pumps, return water is forced through the bypass into the supply header. This flow indicates a
need for additional chiller capacity and another chiller-pump starts. Excess bypass flow with reference to the set points in
the system controller in the opposite direction i.e., into the return header indicates overcapacity and the chiller-pumps are
turned off.

Energy is saved because the system head and water flow rate are reduced on the Secondary Pump when there are
partial cooling loads on the system and due to cycling of Primary Pumps.

UNIT LOCATION AND INSTALLATION


These chillers are designed for outdoor installation and can be installed at ground level or on a suitable rooftop location.
In order to achieve good operation, performance and trouble-free service, it is essential that the proposed installation
location and subsequent installing procedures meet the following requirements:

The most important consideration while deciding upon the location of air cooled chillers is the provision for supply of
adequate ambient air to the condenser and removal of heated discharge air from the condenser. This is accomplished
by maintaining sufficient clearances which have been specified in this Catalog around the units and avoiding obstruc-
tions in the condenser air discharge area to prevent the possibility of warm air circulation. Further, the condenser fans
are propeller type and are not recommended for use with ductwork or other hindrances in the condenser air stream.
Where these requirements are not complied, the supply or discharge airflow restrictions or warm air recirculation will
cause higher condensing temperatures resulting in poor unit operation, higher power consumption and possible even-
tual failure of equipment.

40
The units longitudinal axis should be parallel to the prevailing wind direction in order to ensure a balanced air flow
through the condenser coils. Consideration should also be given to the possibility of down-drafts caused by adjacent
buildings, which may cause recirculation or uneven unit airflow. For locations where significant cross winds are ex-
pected, an enclosure of solid or louver type is recommended to prevent wind turbulence interfering with the unit airflow.
When units are installed in an enclosure, the enclosure height should not exceed the height of the unit.
The location should be selected for minimum sun exposure and away from hot air sources, steam, exhaust vents and
sources of airborne chemicals that could attack the condenser coils and steel parts of the unit. Avoid locations where
the sound output and air discharge from the units may be objectionable.
If the location is an area which is accessible to unauthorized persons, steps must be taken to prevent access to the unit
by means of a protective fence. This will help to prevent the possibility of vandalism, accidental damage or possible
harm caused by unauthorized removal of panels or protective guards exposing rotating or high voltage components.
The clearance requirements prescribed above are necessary to maintain good airflow and provide access for unit
operation and maintenance. However, it is also necessary to consider access requirements based on practical consid-
erations for servicing, cleaning and replacing large components.
The unit must be installed on a ONE-PIECE, FLAT and LEVELLED {within 1/2'' (13 mm) over its length and width} /
CONCRETE BASE that extends fully to support the unit. The carrying or supporting structure should be capable of
handling complete operating weight of the unit as given in the Physical Data tables in this Catalog.
For ground level installations, it must be ensured that the concrete base is stable and does not settle or dislocate upon
installation of the unit which can strain the refrigerant lines resulting in leaks and may also cause compressor oil return
problems. It is recommended that the concrete slab is provided with appropriate footings. The slab should not be
connected to the main building foundation to avoid noise and vibration transmission.
For rooftop installations, choose a place with adequate structural strength to safely support the entire operating weight
of the unit. The unit shall be mounted on a concrete slab similar to ground installations. The roof must be reinforced for
supporting the individual point loads at the mounting isolator locations. It must be checked and ensured that the
concrete base is perfectly horizontal and levelled, especially if the roof has been pitched to aid in water removal. It
should be determined prior to installation if any special treatment is required to assure a levelled installation else it
could lead to the above mentioned problems.
Vibration isolators are necessary for installing these chillers in order to minimize the transmission of vibrations. The
two types of vibration isolators generally utilized for mounting these units are Neoprene Pads and Spring Isolators.
Neoprene Pads are recommended for ground level normal installations jobs where vibration isolation is not critical and
job costs must be kept to a minimum. Spring Isolators are recommended for ground level installations which are noise-
sensitive areas or exposed to wind loads and all roof top installations. For critical installations (extremely noise and
vibration sensitive areas), follow the recommendations of structural and acoustical consultants.
Based on the specific project requirements, choose the type of vibration isolators best suited for the application.
Carefully select the vibration isolators models / configuration based on the respective point loads and place each
mount in its correct position following the Load Distribution Data and Mounting Drawings provided in this Catalog.
Refer to the Schematic Mounting Layout drawings provided in the IOM manual of these chillers for further details in this
regard.

COOLER PIPING CONNECTIONS


The following pertinent guidelines are served to ensure satisfactory operation of the units. Failure to follow these recom-
mendations may cause improper operation and loss of performance, damage to the unit and difficulty in servicing and
maintenance:
Water piping must be connected correctly to the unit i.e., water must enter from the inlet connection on the cooler and
leave from the outlet connection.
A flow switch must be installed in the field piping at the outlet of the cooler (in horizontal piping) and wired back to the
unit control panel using shielded cable. There should be a straight run of piping of at least five pipe diameters on either
side of the flow switch. Paddle type flow switches can be obtained from Zamil which are supplied as optional items.
The chilled water pump(s) installed in the piping system should discharge directly into the unit cooler. The pump(s)
may be controlled external to the unit - but an interlock must be wired to the unit control panel (as shown in the wiring
diagram) so that the unit can start only upon proof of pump operation.

41
Flexible connections suitably selected for the fluid and pressure involved should be provided as mandatory in order to
minimize transmission of vibrations to the piping / building as some movement of the unit can be expected during
normal operation. The piping and fittings must be separately supported to prevent any loading on the cooler.
The cooler must be protected by a strainer, preferably of 20 mesh, fitted as close as possible to the liquid inlet connec-
tion, and provided with a means of local isolation.
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each cooler.
Pressure gauges are recommended to check the water pressure before and after the cooler and to determine if any
variations occur in the cooler and system. When installing pressure taps to measure the amount of pressure drop
across the water side of the cooler, the taps should be located in the water piping a minimum of 24 inches downstream
from any connection (flange etc.) but as near to the cooler as possible.
Drain and air vent connections should be provided at all low and high points in the piping system to permit complete
drainage of the cooler and piping as well as to vent any air in the pipes. Hand shut-off valves are recommended for use
in all lines to facilitate servicing.
The system water piping must be flushed thoroughly before connecting to the unit cooler. The cooler must not be
exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass and
valve arrangement is installed to allow flushing of the piping system. The bypass can be used during maintenance to
isolate the cooler without disrupting flow to other units.
The following is a suggested piping arrangement at the chiller for single unit installations. For multiple chiller installa-
tions, each unit should be piped as shown:

OUT

IN

Isolating Valve - Normally Open Pressure tapping

Isolating Valve - Normally Closed Flow Switch

Balancing Valve Connection (flanged / Victaulic)

Flow meter Pipe work

Strainer Flexible connection

Note: For chillers with two coolers, the connecting pipes for entering and leaving water on one cooler must be joined to
the corresponding pipes on the other cooler before connecting to the main headers in the system piping.

42
CHILLED FLUID VOLUME REQUIREMENT
The volume of water in a piping system loop is critical to the smooth and proper operation of a chilled water system. If
sufficient volume of water is not there in the system, the temperature control can be lost resulting in erratic system
operation and excessive compressor cycling. Therefore, to prevent this effect of a Short Water Loop ensure that total
volume of water in the piping system loop equals or exceeds 3 Gallons per Nominal Ton of cooling capacity for standard
air conditioning applications and 6 Gallons per Nominal Ton of cooling capacity for process cooling jobs where accuracy
is vital and applications requiring operation at very low ambient temperatures and low loading conditions.

For example, chiller model ASY100 operating with a design water flow rate of 205 GPM for a standard air conditioning
application would require 100 (Nom. Cap.) x 3 = 300 Gallons of water in the piping system loop.

To achieve the aforementioned water volume requirements, it may be necessary to install a tank in the piping system
loop to increase the volume of water in the system and therefore, reduce the rate of change of return water temperature.
This tank should be provided on the return water side to the chiller and the tank should be baffled to ensure that there is
no stratification and the entering stream thoroughly mixes with the tank water. See recommended tank design schemat-
ics below:

TANK SCHEMATIC

SUGGESTIONS ON SYSTEM DESIGN AND PIPING PRACTICES


The prospective chilled water system should be designed to the specific requirements of the owner and to achieve the
most efficient system possible. Following are some recommendations:
The first decision a designer of a chilled water system must make is the selection of the temperature differential.
Temperature differential is the difference between the supply water and the return water temperatures. There is no one
temperature difference for all chilled water systems. The actual temperature difference that is selected for a specific
installation is determined by the cost of the cooling coils for various temperature differences and the effect that higher
differences may have on the operating cost of the chillers. A careful balance between energy savings and first cost
should be made by the designer. These are the decisions that must be made by the designer for each application and
only experienced designers should entertain water temperature differences in excess of 120F on chilled water sys-
tems. A number of conditions must be recognized before making the final selection of temperature differential:
a) An increase in temperature differential decreases water flow and therefore saves pumping energy.
b) An increase in temperature differential may increase the cost of cooling coils that must operate with a higher mean
temperature difference.
c) Higher temperature differentials increase the possibilities of loss of temperature difference in coils due to dirt on the
air side and chemical deposits on the water side of them.
d) Laminar flow on the water side due to lower velocities at low loads on a coil is always a concern of the water system
designer. The possibility of laminar flow is greater with higher temperature differences. Laminar flow reduces the
heat-transfer rate and should not occur in a coil at any point in its load range. Many systems operate inefficiently
because of coils that were selected at too low a friction loss through them at design load; therefore, at reduced
loads and flows, they operate with laminar flow.

43
Control of Return Water Temperature: Return water temperature is one of the most important operating values for a
chilled water system. It tells the operator just how good a job the control system and coils are doing in converting
energy from the chillers to the air or water systems that are cooling the building. This is such a basic criterion that it
should be addressed early in the design of a chilled water system. The proper method of controlling return temperature
is through the correct selection of control valves and cooling coils. In conclusion, one of the designers most important
tasks is the selection of a sound temperature differential that will provide maximum possible system efficiency. The
second step in this process is to ensure that the differential is maintained after the system is commissioned.
The water system should be configured to distribute the water efficiently with a minimum use of energy-wasting
devices. These devices are listed here:
a) Three-way temperature control valves
b) Balancing valves, manual or automatic
c) Pressure-reducing or pressure-regulating valves
The piping should be designed without
a) Reducing flanges or threaded reducing couplings
b) Bullhead connections (e.g., two streams connected to the run connections of a tee with the discharge on the branch
of the tee)
The friction for the piping should be calculated for all pipe runs, fittings and valves.
Cooling coils should be selected with a high enough water velocity in the tubes to avoid laminar flow throughout the
normal load range imposed on the coils.
Coil control valves and their actuators should be sized to ensure that they can operate at all loads on the system
without lifting the valve head off the valve seat.
Expansion tank should be provided to so that water volume changes can be accommodated. Expansion tanks are
generally connected to the suction side of the pump - lowest pressure point.
Pumps in parallel must always operate at the same speed. There may be some exceptional cases where parallel
pumps are operated at different speeds, but only experienced designers should make evaluations for such a proposed
operation. Also, it is better to use pumps of the same size when operating them in parallel. Variable speed pumps
should be controlled so that pumps operating in parallel never have more than one percent difference in actual oper-
ating speed. Mixing of constant and variable speed pumps in parallel operation is wrong and leads to disastrous
results.
Distribution pumps should be selected for maximum efficiency at the design condition and within the economic con-
straints of the project. Distribution pumps should be added and subtracted to avoid operation of pumps at points of
high thrust and poor efficiency. Pump sequencing should achieve maximum possible system efficiency.
Differential pressure control (bypass) valves should never be installed at the pump discharges.
Check valves should be provided in pump discharges when pumps are operating in parallel. Pump discharge check
valves should be center guided, spring loaded, disc type check valves and should be sized so that the check valve is
full open at design flow rate. Generally this will require the check valve to be one pipe size smaller than the connecting
piping.
Circuiting Chilled water to Multiple Chillers : There are fundamentals for the circuiting of chillers that should not be
violated in order to achieve maximum efficiency. Some of these are:
a) Design the piping arrangement so that energy consumption of chillers is not increased.
b) Arrange the piping so that all chillers receive the same return water temperature.
c) Ensure that the required design water flow through the coolers is always maintained.

44
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS
Hook rigging sling thru holes in base rail, as shown below.
Holes in base rail are centered around the unit center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging, to prevent the slings from damaging the unit.
CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.
MODELS: ASY050B - ASY240B

MODELS: ASY250B - ASY310B

MODELS: ASY330B - ASY500B

45
INSTALLATION CLEARANCE

WALL

MODEL NUMBER A B
ASY050B - ASY080B 2500 2000 FIGURE - 1
ASY090B - ASY310B 3000 2000 STRAIGHT WALL
ASY330B - ASY500B 3500 2500

FIGURE - 2
CORNER WALL
NOTE: 1. All dimensions are in mm.
2. Pit installations are not recommended. Re-circulation of hot condenser air in combination with surface air
turbulence can not be predicted, hot air re-circulation will severely affect unit efficiency (EER) and can
cause high pressure or fan motor temperature trips.

46
MOUNTING LOCATION
MODELS: ASY050B - ASY080B

MODELS: ASY090B - ASY140B MODEL A


ASY090B 1249
ASY100B 1249
ASY120B 1858
ASY130B 1858
ASY140B 1858

MODELS: ASY150B - ASY240B MODEL A


ASY150B 1586
ASY160B 1586
ASY170B 1586
ASY180B 2094
ASY190B 2094
ASY200B 2094
ASY215B 2094
ASY230B 2094
ASY240B 2094

MODELS: ASY250B - ASY310B

MODELS: ASY330B - ASY500B

NOTE: All dimensions are in mm.

47
LOAD DISTRIBUTION, kg. (ALUMINUM CONDENSER COIL)
MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14
ASY050B 521 495 477 451 - - - - - - - - - -
ASY060B 681 642 602 576 - - - - - - - - - -
ASY070B 712 673 631 605 - - - - - - - - - -
ASY080B 715 679 635 609 - - - - - - - - - -
ASY090B 632 600 585 553 522 506 - - - - - - - -
ASY100B 635 603 587 554 523 507 - - - - - - - -
ASY120B 853 821 805 696 664 649 - - - - - - - -
ASY130B 880 849 833 724 692 677 - - - - - - - -
ASY140B 886 855 839 727 695 680 - - - - - - - -
ASY150B 729 702 693 684 628 601 592 582 - - - - - -
ASY160B 730 703 694 684 629 601 592 583 - - - - - -
ASY170B 750 722 713 704 646 618 609 600 - - - - - -
ASY180B 973 939 927 916 805 771 759 748 - - - - - -
ASY190B 989 955 943 932 819 785 773 762 - - - - - -
ASY200B 997 963 952 940 826 791 780 769 - - - - - -
ASY215B 1024 989 978 966 859 825 813 802 - - - - - -
ASY230B 1045 1011 999 988 888 854 842 831 - - - - - -
ASY240B 1050 1016 1005 993 891 856 845 833 - - - - - -
ASY250B 1045 1010 993 987 982 862 827 810 805 799 - - - -
ASY270B 1084 1049 1032 1026 1021 925 891 874 868 862 - - - -
ASY295B 1108 1074 1056 1051 1045 948 913 896 890 885 - - - -
ASY310B 1112 1078 1061 1055 1049 950 916 898 893 887 - - - -
ASY330B 992 973 964 955 946 941 937 823 804 795 786 777 772 768
ASY350B 1071 1052 1043 1034 1025 1020 1016 867 848 839 830 821 816 812
ASY375B 1089 1070 1061 1052 1043 1038 1034 892 874 864 855 846 841 837
ASY400B 1109 1089 1079 1069 1059 1054 1049 911 891 881 871 861 856 851
ASY420B 1124 1104 1094 1084 1074 1069 1064 925 905 895 885 875 870 865
ASY450B 1164 1144 1134 1124 1114 1109 1104 989 969 959 949 939 934 929
ASY475B 1171 1151 1141 1131 1121 1116 1111 993 973 963 953 943 938 933
ASY500B 1176 1156 1146 1136 1126 1121 1116 995 975 965 955 945 940 935

R1 R2 R1

R3 R4 R6

48
LOAD DISTRIBUTION, kg. (COPPER CONDENSER COIL)
MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14
ASY050B 552 526 508 482 - - - - - - - - - -
ASY060B 729 690 650 624 - - - - - - - - - -
ASY070B 782 743 701 675 - - - - - - - - - -
ASY080B 785 748 705 678 - - - - - - - - - -
ASY090B 685 654 638 606 575 559 - - - - - - - -
ASY100B 688 657 641 608 576 561 - - - - - - - -
ASY120B 904 873 857 747 716 700 - - - - - - - -
ASY130B 955 923 908 798 767 751 - - - - - - - -
ASY140B 961 929 913 801 770 754 - - - - - - - -
ASY150B 778 750 741 732 676 649 640 631 - - - - - -
ASY160B 778 751 742 732 677 649 640 631 - - - - - -
ASY170B 820 792 783 774 715 688 679 670 - - - - - -
ASY180B 1031 996 985 973 863 828 817 805 - - - - - -
ASY190B 1064 1030 1018 1007 894 860 848 837 - - - - - -
ASY200B 1081 1047 1035 1024 910 875 864 852 - - - - - -
ASY215B 1109 1075 1063 1052 945 911 899 888 - - - - - -
ASY230B 1141 1107 1095 1084 984 949 938 926 - - - - - -
ASY240B 1146 1112 1100 1089 986 952 940 929 - - - - - -
ASY250B 1112 1077 1060 1054 1049 929 894 877 871 866 - - - -
ASY270B 1150 1116 1099 1093 1087 992 958 941 935 929 - - - -
ASY295B 1205 1171 1153 1148 1142 1045 1010 993 987 982 - - - -
ASY310B 1209 1175 1158 1152 1146 1047 1013 995 990 984 - - - -
ASY330B 1078 1060 1051 1042 1033 1028 1023 909 891 882 873 863 859 854
ASY350B 1169 1150 1141 1132 1123 1118 1114 965 946 937 928 919 914 910
ASY375B 1187 1169 1159 1150 1141 1137 1132 990 972 962 953 944 940 935
ASY400B 1191 1171 1161 1151 1141 1136 1131 993 973 963 953 943 938 933
ASY420B 1225 1205 1195 1185 1175 1170 1165 1026 1006 996 986 976 971 966
ASY450B 1282 1262 1252 1242 1232 1227 1222 1108 1088 1078 1068 1058 1053 1048
ASY475B 1290 1270 1260 1250 1240 1235 1230 1111 1091 1081 1071 1061 1056 1051
ASY500B 1294 1274 1264 1254 1244 1239 1234 1114 1094 1084 1074 1064 1059 1054

R1 R2 R1

R3 R4 R6

49
PL-AP-ASY-10-2M-E