Mode Structure

Boot Camp for New Employees

Jul
23

Permitted and Actual Mode


Categories:

Control Design & Commissioning,


Distributed Control Systems (DCS),
Education,
Process Control,
Standards

by Terry Blevins

The input parameters of are function block are used by the algorithm in conjunction with the state of the function
block application to determine if the algorithm can achieve the target mode of operation established for it. The
target mode attribute as origianlly defined by ISA50 is the part of the mode parameter that indicates what mode
of operation is desired for the block. Under certain operating condition, a block may not be able to function in
http://modelingandcontrol.com/2012/07/permitted-and-actual-mode/ 1/4
5/8/2017 Permitted and Actual Mode Modeling and Control

the requested mode. In such cases, the actual mode attribute reflects the mode of operation it is able to achieve.
Comparison of the actual against the target indicates whether the target was achieved.

As detailed in Control Loop Foundation, the allowed target mode values for an instance of a block are defined
by the permitted mode attribute of the mode parameter. Thus, the modes available for controlling a block may
vary with each block instance and are assigned during block configuration. Interface devices and temporary
devices may use the permitted mode to limit operator changes in target mode. Function blocks limit changes in
target mode to those allowed by the permitted mode attribute. To help an operator select the normal mode of
operation from those available, a normal mode attribute is provide in the mode parameter. This attribute may be
used by a human interface application to help guide the operator in setting the operation mode of a block.

The operator modes for the PID block and the impact of the mode selection on the source of setpoint and output
are summarized in table below

The Actual mode attribute may take on a value other than that specified by the Target mode attribute. This
occurs when an internal condition or input status indicates that the mode of operation requested by the operator
through the Target mode attribute cannot be achieved. Under normal operating conditions, the Target and Actual
mode attributes match. The Actual mode attribute changing to Local Override (LO) indicates that the output
tracking or an internal application, such as auto-tuning, is setting the block output. Similarly, if the path to the
process is lost, then the Actual mode attribute will change to Initialization Manual (IMan) as summarized
below.

When the Actual mode of a PID is shown as IMan, this indicates that the path to the process is not complete.
The path to the process can be broken if a downstream block is taken out of Cascade mode. For example, in a
single- loop application, the path of the PID output to the process will be broken by changing the mode of the
analog output block from Cascade to Automatic. The path to the process may also be broken by a physical

http://modelingandcontrol.com/2012/07/permitted-and-actual-mode/ 2/4
5/8/2017 Permitted and Actual Mode Modeling and Control

condition such as the failure of an actuator that is manipulated by the PID. When the Actual mode of the PID is
IMan, the PID cannot adjust the manipulated process input. Under this condition, the PID output follows the
value provided by the downstream block through the back calculation input.

Tags: "permitted mode", "Supported mode", Control, mode, PID, setpoint

Search

Search Search

Select by Contributor

Terry Blevins
Mark Nixon

Archives

Archives Select Month

Subscribe

Enter your email:


Subscribe
Subscribe to RSS feed

Translate

Select Language
Pow ered by Translate

Categories

Advanced Control (134)


Control Design & Commissioning (413)
Distributed Control Systems (DCS) (188)
Education (265)
Fieldbus (26)
Final Control Elements (112)
Human Machine Interfaces (24)
Measurements (192)
Metrics (44)
Mobile Worker (3)
Process Control (352)
Simulation (92)
http://modelingandcontrol.com/2012/07/permitted-and-actual-mode/ 3/4
5/8/2017 Permitted and Actual Mode Modeling and Control

Standards (54)
Uncategorized (20)
Unit Operation Control (114)
Virtualization (5)
Wireless (121)

About This Blog

Welcome Message
Website Feedback

Our Community

Emerson Exchange 365

Disclaimer

The opinions expressed here are the personal opinions of Terry Blevins and Mark Nixon. Content published
here is not read or approved by Emerson before it is posted and does not necessarily represent the views and
opinions of Emerson. 2006-2012 Terry Blevins, Mark Nixon. All rights reserved.

Copyright

2017 Modeling and Control.

Return to top

Powered by WordPress and the Graphene Theme.

http://modelingandcontrol.com/2012/07/permitted-and-actual-mode/ 4/4

Вам также может понравиться