Вы находитесь на странице: 1из 12

1798 IEEE Transactions on Power Dclivery, Vol. 11, No.

4, October 1996

Impact of Shunt Capacitor Banks on Substation Surge Environment


and Surge Arrester Applications

Report by Working Group 3.4.17 of the IEEE


Surge Protective Devices Committee

Abstract ---The introduction of high voltage shunt 2. SCOPE


capacitor banks on a power system can result in a number
of overvoltage problems that tend to be associated with The intent of this paper is to provide an explanation of some
capacitor switching. Proper application of surge arresters basic overvoltage mechanisms associated with the installation
near a shunt capacitor bank requires careful analysis of and switching of shunt capacitor banks. The paper is written
the power system, the switching devices and their primarily for utility personnel to provide assistance in
arrangements, the insulation level of nearby equipment, assessing the application and selection of surge arresters when
the type of grounding, and the arrester energy dissipation used in combination with shunt capacitor banks for
duty. overvoltage protection.

Keywords: Shunt capacitor banks, metal oxide arrester In this paper it is assumed that all surge arrester applications
applications, surge arresters, surge protection, overvoltage are of the metal oxide type. However, existing surge arresters
protection, insulation coordination. at a station may consist of gapped silicon carbide, metal oxide,
or a combination of both. If so, the ratings of both types must
1. INTRODUCTION be taken into consideration to ensure proper coordination.

Autility survey, followed by a working group report in 1991 The subject matter is broad and has many complexities. It is
[l], indicated the need for better information on the selection not possible in this limited space, to cover all aspects of
of, and duty imposed on surge arresters located near shunt switched shunt capacitor banks, nor to offer solutions to
capacitor banks. Existing standards and application guides specific problems that may be associated with a particular
[2,3,4,5,6], relating to shunt capacitor banks and surge installation. In some cases reference material may provide the
arresters, are useful in explaining the rating structure and necessary details. In other cases it may become necessary to
capabilities, including the basic applications and procedures. model a part of the power system near the capacitor bank and
However, many important and specific details, as well as carry out a transient analysis using a transient network
system considerations, for the application of surge arresters in analyzer (TNA), [7] or a digital simulation program such as the
combination with shunt capacitor banks are lacking. Electromagnetic Transients Program (EMTP) [SI.

The number of applications of high voltage shunt capacitor 3. GENERAL CONSIDERATIONS FOR SHUNT
banks in substations has increased significantly over the past CAPACITOR BANKS
decade. This is primarily due to voltage regulation problems
associated with increasing loading levels on existing 3.1 Capacitor Bank Installations
transmission systems. In many applications shunt capacitor
banks are often switched on a daily basis to maintain control In many utilities there is a growing trend to use shunt capacitor
of system voltage levels during load changes. As a banks to provide voltage support due to the lack of an adequate
consequence, the switching of shunt capacitor banks has often power transmission system. Shunt capacitor banks are usually
become the most common source of transient voltages on installed on the transmission system at major buses to provide
many power systems. Certain switching operations can also voltage support for a large area. The size and location of the
present some potentially hazardous overvoltage conditions, not banks are usually based on load flow and stability studies of
only to the capacitor bank, but to other nearby equipment such the transmission network. As indicated from the survey
as circuit breakers and transformers. referred to above, shunt capacitors are being applied at all
voltage levels up to 500 kV, with bank sizes ranging from a
few Mvar to more than 300 Mvar.
96 WM 014-1 PWRI) A paper recommended and approved by the IEEE
Surge Protective Devices Committee of the lEEE Power Engineering Society As more capacitor banks are added to the power system there
for presentation at the 1996 IEEE/PES Winter Meeting, January 21-25, 1996,
will likely be installations with more than one bank on the
Baltimore, MD. Manuscript submitted August 8, 1995; made available for
printing November 13, 1995.

0885-8977/96/$05.00 0 1996 IEEE


1709
same bas. Series reactors are usually installed in these cases to shunt capacitor banks. There are two reasons for this
limit inirush currents during back-to-back switching, and to phenomenon. First, fitting vacuum interrupters with either
limit ontrush currents during close-in system faults. closing or opening resistors is difficult. Secondly, since
vacuum interrupters can interrupt high frequency currents, they
Since there is no basic technical restriction, shunt capacitor can produce a train of transients on closing due to multiple
banks c,anbe installed in three basic configurations: grounded- prestrikes. If a restrike should occur on opening the ability of
wye, ungrounded-wye, and delta. Wye-connected banks are vacuum circuit breakers to interrupt the high frequency current
used almost exclusively in the higher voltage ranges since this can produce significantly higher transient overvoltages than
configuration is less expensive and less complicated to other types of switchgear [13].
construct than a delta-connected bank. Utilities that choose
ungrounded-wye often do so to avoid the problems associated 3.3 Interconnected System and Other Equo'ment
with high transient inrush currents in existing station
grounding systems, but must deal with the higher level of Shunt capacitor banks are often switched on during peak loatd
transient overvoltages that will be encountered in this or low voltage conditions and switched off during light load or
arrangement. high voltage conditions. In many locations this means that the
capacitor banks are switched at least twice per day, "on" in the
3.2 Capacitor Bank Switchgear morning and "off' in the evening.

The type of switchgear used to switch high voltage shunt When a capacitor bank is energized or de-energized, the
capacitor banks can have a significant effect on the nature and fundamental system voltage level will change according to the
magnitude of the transient overvoltages produced [9,10,11,12]. bank size and the available short circuit impedance at the bus
location. Although the steady state voltage change is usually
For many years oil circuit breakers were commonly used to limited to 2-4 %, it is not uncommon for the operating voltage
switch shunt capacitor banks. Capacitive switching poses a level to change 10% or more for shoirt periods, while
particularly difficult problem for most oil circuit breakers. adjustments are being made to the new operating conditions.
The interrupters in these circuit breakers require several cycles Since the maximum continuous operating voltage is an
of arcing prior to successful interruption of fault current. important consideration in the application of metal oxide surge
However, these same interrupters can easily interrupt the low arresters, these system operating conditions ,and voltage 1eve:ls
level of capacitive current at the first zero crossing. This should be recognized in the selection of surge arrester voltage
usually occurs before the contacts have achieved sufficient ratings.
separation distance to establish the high dielectric strength
required to withstand the peak recovery voltages associated The switching duty imposed on existing circuit breakers that
with capacitor switching. In this situation the oil circuit may become involved 'in capacitor switching operations ( e.;!.,
breaker can restrike resulting in high transient overvoltages. local breaker backup) can be severe. Since: the magnitude of
the capacitor current being interrupted and the initial recovery
Although oil breakers are still being used by some utilities for voltages are low, the current is usually interrupted at the first
capacitor switching, these circuit breakers can lead to severe current zero crossing after contact parting. However, the
overvoltage problems and arrester energy dissipation. transient recovery voltage (TRV) on the first pole to clear
reaches 2 per unit @U) on grounded banks and 2.5 pu on
Fortunately, gas circuit breakers (e.g., air blast and SFJ, which ungrounded banks, one-half cycle after current interruption.
have become much more common throughout the industry, If the breaker fails to withstand this TR'V, current will be
have a much better capability for capacitor switching and are reestablished due to a dielectric breakdown across the contact
now used almost exclusively to switch capacitor banks at the gap, (termed a reignition or a restrike depending on the delay
higher voltage levels. Since gas breakers can easily cope with between initial interruption and the subsequent breakdown).
high recovery voltages without restrikes, the de-energization
of a capacitor bank usually results in harmless switching The steep-fronted surges associated with all energizing
transients. On the other hand, it becomes expensive to install operations and restrikes will be impressed not only on all local
closing resistors in gas breakers at the higher voltage levels - equipment but will propagate outwardly on all lines
so closing transients may still present problems. terminating on the station bus. This can cause severe
overvoltage stresses on low voltage equipment in the
Although vacuum switchgear is commonly used to switch substation and to power transformers, particularly if connected
capacitors in the lower voltage ranges, they have been known to the end of radially fed lines. Excessive phase-to-phase
to produce significant transient overvoltages when switching transient voltages and transformer part-winding resonance ,are
1800
two of the well-known problems that have occurred. capacitor banks (C) are being planned, the possibility of
resonance conditions must be considered. This is true for linear
The oscillatory portion of the capacitor switching transient can resonance as well as ferroresonance. The occurrence o f either
have a significant impact on low voltage equipment. Large condition can impose severe duties on surge arresters if the
voltage transients may be impressed across primary and overvoltages under such conditions are high enough to cause
secondary current transformer windings as well as on low surge arresters to operate.
voltage power supply and metering circuits. Ferroresonance conditions have been reported on some
ungrounded-wye capacitor banks. One such condition involves
The presence of series reactors introduces several additional two phases of the capacitor bank in series with one phase of a
considerations during the study of surge protection for shunt grounded neutral transformer bank. It can occur due to
capacitor banks. First, some provision must be made to protect significant differences in pole interruption times of the
the reactor from transient overvoltage stresses that will be switching device [9].
impressed since it will appear as a high impedance.
Additionally, depending on the size of the reactor and the 3.5 Existing Surge Arresters
capacitor bank, the arrester may have to discharge a large
amount of energy during faults near the capacitor bank. It is not uncommon for shunt capacitor banks to be installed at
a substation that contains equipment already protected by
The switching of shunt capacitor banks on a station bus will surge arresters. The rating of all existing surge arresters must
generate voltage and current transients that can create be taken into consideration to ensure that the duty imposed
problems for nearby equipment and other parts of the during capacitor switching operations will not exceed their
interconnected system [14]. While these transients are capabilities. This applies particularly to gapped silicon carbide
generally comparable to those encountered with other (Sic) surge arresters that can be severely damaged if a
switching operations, the transients will occur more often since sparkover occurs during capacitor switching. Sometimes they
capacitor banks are likely to be switched on a daily basis. In may have to be replaced with metal oxide arresters while in
addition, if the breaker is not restrike-free, the magnitude of other cases it may be possible to coordinate the ratings so the
the transient overvoltages will be significantly higher, duty from capacitor switching will be placed only on metal
typically by a factor of two. oxide arresters.

Ungrounded capacitor banks often incorporate a potential 3.6 Lightning Surges


device, connected from the neutral of the bank to ground. This
device is used to provide unbalance protection for the bank in There is a paucity of information available on the subject of
the event of can failures. The potential device can be exposed overvoltage protection of shunt capacitor banks exposed to
to severe voltage stresses during opening of the capacitor bank lightning surges [15]. Due to the low surge impedance o f
due to delayed pole operation of the switchgear. Furthermore, shunt capacitor banks adding additional surge arresters beyond
if the neutral grounding device consists of a potential that which already exist at the station may not be necessary.
transformer, the overvoltage can result in saturation and Nevertheless, a detailed analysis should be carried out to
possible damage. One method of reducing the voltage on the determine if the bank is adequately protected from incoming
. neutral and therefore protecting the potential transformer is to lightning surges.
use surge arresters connected from the neutral of the capacitor
bank to ground. The increase in capacitor bank voltage from a lightning surge
does not depend on the rate-of-rise of the surge as it does with
Consideration must also be given to the size, configuration, transformers and other inductive equipment, but depends on
and location of all nearby shunt capacitor banks whenever the charge absorbed. The protection of a shunt capacitor bank
surge arresters are applied at a substation for overvoltage against lightning surges is, therefore, an exercise in
protection. Capacitor banks can store considerable amounts of determining the overvoltage resulting from the charge
energy during temporary overvoltage conditions, and in absorbed. If excessive, arresters must be installed to discharge
particular during circuit breaker restriking events. This must be some energy and so limit this overvoltage.
considered in determining the energy absorption capability of
any nearby surge arresters. Some capacitor banks may be self-protecting. Depending on
the capacitance (C) of the bank and the charge (Q) contained
3.4 Resonance and Ferroresonance in the incoming wave, the capacitor bank may absorb the surge
energy without resulting in an excessive overvoltage.
Whenever new installations of shunt reactors (L) or shunt Moreover, if arresters are protecting other equipment located
1801

nearby, additional arresters may not be needed. If the existing protection of shunt capacitor banks. The median impulse
station arresters are rated for lightning surge discharge duty, charge for the fast rising negative impulse component (ai) is
then they will adequately protect the capacitor bank for approximately 5 coulombs for the first stroke and 1 couloinb
lightning surges providing shielding is in place. If the bank is for each subsequent stroke [ 161.
not self-protecting or if the nearby arrester locations and/or
duties are not adequate, additional arresters must be installed. 3.6.2 Shielding Failure - Shielding failures tend to be caused
by low current first-stroke events. Some shielding failures will
In most cases, determining capacitor bank protection will cause a flashover of line insulation to ground, and cannot be
require a simulation study that rakes into consideration details treated in the same manner as backflashoverai. The main danger
of the complete station layout, including equipment bus to capacitor banks would be caused by a shielding failure that
connections, and surge arrester locations as well as the type of does not result in a line flashover. Some 10% of lightning
bank, its size, configuration and exposure to lightning surges. strokes have current durations that exceed1 100 ms, resultilng
The frequency and magnitude of the acceptable overvoltages from low-amplitude (100 A) long duratioln (200 ms) events
also must be determined. The lines entering the station must be between retum strokes. The continuing current component can
evaluated for the number of lightning strokes to the line, the inject a charge (Qc) of typically 25 couloimbs into the phase
origin of the surge (shielding failure or backflash), the line conductor. The distribution of this charge into the power
critical flashover voltage, and the waveshape and attenuation system should be computed to establish the portion of ithe
of the surge entering the station. A detailed analysis can be charge that will lead to a voltage rise on the capacitor bank
done using the Electromagnetic Transients Program (EMTF'). [161*

The range of overcurrents and overvoltages that a capacitor 4.OVERVOLTAGES ASSOCIATED WITH CAPACITOR
may be expected to withstand during its lifetime depends on BANK SWITCHING
the magnitude, duration and frequency of occurrence. The
tables in Section 8.3.2 of the IEEE Standard for Shunt Power The switching of any capacitor bank produces overvoltages.
Capacitors [4] are intended to provide some guidelines for this Transient overvoltages will always occur dluring energization
evaluation. and will only occur during de-energization if restrikes occur
in the switching device [17]. Arresters located in the substat ion
An analysis of the charge content of the stroke is necessary to to protect transformers and other equipment from overvoltages
detemiine whether a capacitor bank is self-protecting and to can be severely stressed from an energy dissipation standpalint
calcu1,ate the required arrester discharge duty. The capacitor during capacitor switching because of the large amount of
voltage will depend on the charge absorbed. In general, the energy stored in a capacitor bank. The ability of all nearby
voltage rise in the capacitor bank is determined by the arresters to withstand the energy dissipated during capacitor
following equation: switching is therefore an important consideration.

v = cvc 4.1 Energization Transients

where: At the instant of switching on a capacitor bank the source side


voltage collapses instantaneously as if closing in on a shiort
V is ithe capacitor voltage in volts circuit. After this sudden drop in voltage the capacitor bank
Q is ithe charge in coulombs begins to draw inrush current through the source impedance.
C is the capacitance in farads The charging of the capacitor bank in this IC circuit produces
an overshoot in the voltage wave followed by a damped
3.6.1 Backflashovers - According to the standard definition oscillatory transient that is determined by the system
[3] a lightning surge rises to its peak in 1 . 2 and
~ ~decays to inductance, circuit losses and the capacitance of the bank.
half value in 50 p. The critical flashover level (CFO) for
many insulation systems is considered to be obtained in the Fig. 1 illustrates the transient voltage appearing on the 'bus
fist 10-15 p. An insulation failure from a lightning stroke to when a capacitor bank is being energized. The transient is
a grounded tower or station structure will thus normally occur typical for energizing any isolated capacitor bank. In
early in the duration of the lightning surge. The peak current, evaluating the effect of these transients om the nearby power
however, may spread into adjacent grounded elements. This system, the key characteristics are the fast-front that occurs
will rapidly reduce the magnitude of the long duration tail initially, due to breakdown of the contact gap, and the
current. Therefore, it is conservative to apply statistics on the oscillatory wave that follows.
total charge in the retum stroke when determining the surge
-
1802

steep- f ron t surge


vj - vc 1-7pu can, under certain conditions, create severe overvoltages both
phase-to-ground and phase-to-phase at remote locations.

As a consequence of this phenomenon, voltages up to 2.7 pu


phase-to-ground have been recorded at remote stations with
some circuit configurations [9]. Transformers at the end of
radial lines have been known to fail under such conditions.
Similarly, the switching of lines from buses that have shunt
capacitor banks connected can initiate steep-fronted waves on
the line being switched. Consequently, the overvoltage
protection of equipment, such as transformers at the ends of
Fig.1. Voltage Transients on capacitor bank energization remote lines, must be examined whenever shunt capacitor
banks are applied to a bus from which those lines are switched.
The fast-front portion of the transient, which normally does
not exceed 1 pu, nevertheless raises concerns about surge 4.1.2 Oscillatory Transients - The oscillatory part of
protection for transformers and low voltage equipment. capacitor switching transient is the result of energy exchange
Transformer failures associated with capacitor switching have between the inductive and capacitive elements in the circuit.
been documented in the literature [MI. Energy stored in the capacitor elements (% CVz)will flow into
the inductive elements (% LIZ). The frequency of the
Switching an isolated, grounded-wye capacitor bank from a oscillation can be estimated from the normal expression
predominantly inductive source can result in a transient 1 I 2 n m The oscillatory portion raises concerns about the
overvoltage approaching 2.0 pu on the station bus with a possibility of part-winding resonance in transformers, [18,19]
dominant frequency between 300-600 Hz. In most cases and the transfer of high per unit overvoltages and energy to
circuit damping will limit the overvoltage to the range of 1.5 secondary circuits.
to 1.7 pu. Energizing an ungrounded-wye capacitor bank can
result in slightly higher transient overvoltages because of Low frequency oscillations, ranging typically from about 300
unequal pole closing. In general, however, the overvoltages to 600 Hz,result from interaction of the capacitor bank with
associated with normal closing are similar for grounded and the source. Medium frequency transients in the 2 to 10 lcHz
ungrounded banks [9]. range are encountered if the capacitor bank is switched in
parallel with another bank (back-to-back switching) or other
The energization of shunt capacitor banks without prestriking capacitive elements such as power cables. High frequency
transients does not usually endanger station equipment at the oscillations in the 10 kHz range can occur as a result of the
bus location. However, it has been observed on networks with steep-fronted voltage surge impressed on the station bus.
several lines connected that the initial wave front can result in
higher voltages on other equipment, such as transformers 4.1.3 Voltage Magnification - Capacitor switching transients
connected at remote locations. Studies and measurement have can be magnified in certain installations. One that appears to
shown that reflections from these fast-front waves, coupled be most commonly associated with this phenomenon occurs
with superpositions on the low frequency oscillations, can when capacitors are being switched from a bus which supplies
produce transients approaching 3 pu [9]. If multiple prestrikes a step-down transformer that has shunt capacitors installed on
occur during the energization of a capacitor bank, significantly the secondary side [20,21,22]. Energizing the primary loop
higher overvoltages can result. This occurs if the switch is able will excite the natural modes of oscillation in both the primary
to clear the prestrike current at one of the high frequency and secondary loops. If the natural frequency of oscillation of
current zeroes. These phenomena have been known to occur the secondary loop is close to that of the primary then a
with vacuum switchgear. "beating" effect can occur. Since many factors play a part in
determining the amplitudes involved, each case must be
4.1.1 Steep-fronted Surges - The energization of a shunt analyzed separately. An example of an installation that may
capacitor bank on a station bus generates steep-fronted waves produce voltage magnification effects is shown in Fig. 2.
on all three phases, with magnitudes approaching 1 pu. These
steep-fronted waves propagate away from the station on all Whenever capacitors are installed at multiple voltage levels,
transmission lines connected to the station bus. As they reflect the equipment at the lower voltage level may be subjected to
from points of discontinuity, and travel back to the station they severe overvoltages (>3 pu) even when the tuning is not exact
change polarity due to the low surge impedance of the &Cl = Lj2.J. These surges may cause the arresters to dissipate
capacitor bank. As they propagate away the second time they significant amounts of energy. The magnitudes of these surges
1803
and therefore the arrester energy can be greatly reduced by equipment connected to the line. Transfomiers, in particular,
using closing resistors in the switching device. may be vulnerable due to phase-to-phase surges or
part-winding resonance.

4.2 De-energization Transients - If there is a successful


interruption of the capacitor current at the first zero crossing
and the switching device withstands the TRV there are 130
significant transients on de-energizing a caplacitor bank (apart
from the small transient associated with the steady state drop
7' c1 in the bus voltage due to removal of the capacitor bank).

The occurrence of reignitions during breaker opening is of


minimal consequence since the resulting vldtage and current
Fig. 2 Capacitor installation that may lead to voltage magnification transients are usually smaller than those produced on closing.
Restrikes on the other hand, will produce transient voltage a:nd
4.1.4 :?urge Transfer to Low Voltage System - Equipment at currents significantly larger in magnitude than those occurring
lower voltage levels can often be exposed to dangerous during closing. Since restrikes can occur when there is a
transient overvoltages from capacitor switching on the high charge remaining on the capacitor bank it is possible for
side of step-down transformers. The steep-fronted portion of restrikes to generate transient overvoltages that are much
the wave will transfer capacitively through the transformer and higher in magnitude than on closing.
thus thle magnitude of the surge on the secondary will depend
on the ratio of capacitance and not on the ratio of tums. On the 4.2.1 Restrike of Switching Device -When de-energizing a
other hand the low frequency oscillations (400-600 Hz)will grounded-wye capacitor bank, a trapped charge of 1pu is left
transfer through the winding according to the tums ratio. This on the capacitors. The recovery voltage across the switching
may create a problem of insulation coordination on the low device reaches 2 pu one-half cycle after opening. If a single
voltagle system. restrike occurs at this maximum recovery voltage, the transient
overvoltage will approach 3 pu (Fig-3).
4.1.5 Phase-to-Phase Overvoltages - The surges produced
on the substation bus where the capacitor bank is energized
will propagate along any transmission line connected to that
ADPrOKM) Jw --
bus. If the end of the line is an open circuit or is terminated
with a transformer, then the surge may double at that point. If
the surges produced on two phases by energizing the capacitor
bank are of opposite polarity, then the transformer can
experience severe phase-to-phase surges [23,24]. Arresters on
the tramformer (normally connected phase-to-ground) will
limit the phase-to-ground components on each phase to the
switching surge protective level of the arrester. However, the
phase-to-phase stress can be twice this level and may be a Fig.3 Capacitance switching with a restrike at peak voltage
problem for the transformer. It may be more economical to
Multiple restrikes may produce higher overvoltages. While
consider closing resistors or inductors in the capacitor bank
selecting a switching device that rarely restrikes is desirable,
switchgear to reduce the phase-to-phase surges at remote
designing the arrester protection is prudent, such that it can
transformers.
withstand the resulting overvoltage if a restrike occurs.
Althoiugh steep-fronted waves are generated and propagate
Any nearby arrester will dissipate a significant amount of
along the line whenever transmission lines are energized, the
energy if a restrike occurs. Also, because of the high current
magnitude of such surges can be increased by having capacitor
magnitudes involved in the arrester discharge, the arrester's
banks on the bus. The reason for these phenomena is that the
energy absorption capability may be different from ihe
capacitor bank presents a much stiffer source than a normal
standard value as published by arrester manufacturers. For a
bus arid the bus voltage does not drop significantly when the
S i c arrester the energy discharge duty is usually more severe
line is energized. Consequently, the line voltage will jump to
than for metal oxide arresters. This is due to the partial
the bus voltage level at the instant of closure. For certain
discharge of the capacitor through the arrester, which occurs
lengths of line this can pose a problem for any terminal
1804

when the arrester sparks over. The current magnitude and These differences may be the result of arc duration or timing.
duration are of primary concem for S i c arresters. It may be An example of this circuit condition is shown in Fig. 5.This
possible to apply metal-oxide arresters in a station to protect ferroresonance condition can impose significant duty on surge
existing Sic arresters from the surges associated with arresters [ 9 ] .
restriking during the de-energization of a capacitor bank.
I- 1.1 c (**I VOLTAGES:
Simplified methods can be used to make a preliminary *XWRCE
assessment of the energy dissipation duty that an arrester may
experience during the de-energbation of a capacitor bank.
R + SOURCE
However, a detailed computer simulation is usually needed to VOLTAGE
determine the arrester energy rating. 8 + VOLTAGES
CAPACITOR

When de-energizing ungrounded capacitor banks, the


u\y v \SOURCE
CAPACITOR
NEUTRAL
switching device experiences even higher recovery voltages V 0L TA GE
than those associated with de-energizing grounded capacitor
banks. The recovery voltage will reach 2.5 to 3.0 pu in
one-half cycle and under certain stuck pole conditions can
exceed 4 pu. If a restrike occurs on one phase, the recovery
voltages will be increased across one of the other phases. This OXIDE
tn A ARRESTER
can result in a two-phase restrike. The two-phase restrike can CURRENTS
be used as a conservative analysis of the duty that an arrester
may see when located near an ungrounded capacitor bank.
Fig.4 Switching ungrounded 230 kV 192 Mvar capacitor bank with
independent pole operated breaker -W (D intentionally delayed
The transient voltages on a capacitor bank and the recovery
voltages across a switching device can be reduced during a
restrike by installing arresters on the capacitor side of the
switching device. Arresters connected phase-to-ground on
ungrounded capacitor banks will limit the recovery voltage but
do not necessarily limit the voltages trapped on capacitors
during restrikes. Arresters are sometimes connected from
phase-to-neutral to limit the trapped voltages to lower levels,
thus reducing switch recovery voltage and minimizing the
possibility of multiple restrikes.

4.2.2 Stuck Pole on Switching Device - If an independent pole


operated (IPO) circuit breaker is de-energizing a capacitor
bank, then stuck pole conditions may occur. Depending on
pole opening sequence, this can give rise to recovery voltages
across the circuit breaker contacts exceeding 4.0 pu. The
installation of metal oxide surge arresters to limit the
phase-to-ground voltage to about 1.7 pu will prevent the Fig. 5 Single pole rmnance involving W-@ breaker pole when switching an
ungrounded capacitor bank with a grounded neutral transformer
occurrence of these high recovery voltage levels and tend to
keep the switching duty within the capability of the circuit
breaker. As a consequence of the stuck pole only one phase of
4.3 Control of Overvoltages
the ungrounded capacitor bank remains to be disconnected by
the upstream general purpose breaker. In this case severe
Overall, overvoltage protection should be considered whenever
energy dissipation requirements may be imposed on the surge
shunt capacitor banks are installed on the system. Several
arresters. An example of this condition is shown in Fig. 4 [9].
methods are available for reducing energizing transients,
however, not all are practical or economical [25,26,27].
4.2.3 Ungrounded Capacitor Bank with Transformer - This
condition involves two phases of the ungrounded capacitor
4.3.1 Surge Arresters - Although surge arresters are not
bank and the windings of an adjacent transformer and occurs
normally used at stations to control the transient overvoltages
because of the significant differences in interruption times that
during energization of local capacitor banks, they are
can appear among the three poles of the switching device.
1,905
frequently used to reduce the transient recovery voltages on consequences, are the low impedance and the high stoIed
opening and thus the probability of restrikes, or on the energy associated with shunt capacitor banks.
capacitor bank to limit the overvoltage should restrikes occur.
Metal oxide surge arresters can be used to reduce the Consequently when selecting metal oxide surge arresters for
possibility of restrikes occurring in the switching device and shunt capacitor installations it is necessary to consider 'the
to protect transformers. However, studies are usually required following:
to determine arrester ratings and energy requirements.
0 Maximum operating voltage on the system
4.3.2 Alternatives - Both preinsertion resisters and inductors Amplitude and waveshape and duration of possible
have been used by circuit breaker manufacturers to reduce overvoltages
voltage and current transients during the energization of high Energy absorbed by the arrester if the expected
voltage shunt capacitor banks. The difficulty with these overvoltages exceed the maximum continuous operating
devices however, is in providing sufficient energy absorption voltage (MCOV)of the arrester
capability that greatly increases the complexity and cost of
the circuit breaker.
5.2.1 MCOV(Maximum Continuous Operating Voltage) - The
Synchronous closing is another means of reducing energizing MCOV rating of a metal oxide surge arrester is the maximum
transients. However, reliability requirements of the sensing RMS value of power frequency voltage that may be applied
device coupled with mechanical variations in the switching continuously between the terminals of the arrester. In selectilng
device under a wide range of operating conditions have the MCOV for surge arresters located near high voltage shunt
delayed developments. Renewed activity in the development capacitor banks the first consideration, therefore, is to
of synchronous closing circuit breakers for high voltage shunt determine the maximum operating voltage at the arrester
capacitor banks appears to be taking place due to increasing location. According to the survey [l]the maximum permissi'ble
conceims of the voltage and current transients generated during operating voltage where the capacitor banlk is installed under
energiization [28,29]. normal system conditions is 5-10% above the nominal voltage
level.
5. APPLICATION O F SURGE ARRESTERS
The minimum required MCOV rating for the application of
5.1 Location of Surge Arrester phase-ground arresters on a solidly (directly) grounded
system is the maximum phase-ground voltage (maximum
Surge arresters can be connected phase-ground, phase-phase systemvoltage divided by J3). It can usually be assumed that
or phase-neutral depending on the actual system the neutral of a power system will be directly connected1 to
configuration. Obviously the selection of voltage rating of a ground at large shunt capacitor installations. If the system
surge arrester must take these factors into consideration. cannot be considered solidly grounded, then the system
configuration and operating practices should be reviewed. If
If the primary aim of installing surge arresters is to protect the phase-phase arresters are considered, the required MCOV is
capacitors in the capacitor bank, their physical location with the maximum phase-phase operating voltiige.
respect to other elements will also be important. For example,
if a series reactor is installed, the placing of arresters in front An arrester must also be capable of withstanding the maximum
of the reactor will not protect the capacitor. In this situation anticipated temporary overvoltage (T0.V) at the arrester
the voltage on the capacitor may be much higher than at the location. TOV requirements must take into account both the
arrester location. magnitude and duration of the anticipated overvoltage, If the
system voltage is distorted, the MCOV of the arrester should
If the purpose of the surge arrester is to protect the switching be higher than or equal to the expected crest voltage divided
device or a transformer, studies will be required to assess the by J2.
best location and physical arrangement.
5.2.3 Energy Absorption Duty - Any discharge of a capacitor
5.2 Selection of Surge Arrester bank through a surge arrester results in high currents. Thus,
energy absorption becomes a critical factor in selecling
Baseid on the above presentation it is important to recognize suitable surge arresters installed in the vicinity of shunt
that surge arresters can be exposed to very high stresses when capacitor banks. Switching surges of different origins can
used to limit the overvoltages on shunt capacitor banks. The occur, but overall a restrike in a circuit breaker will 1ik.ely
inherent parameters, which are primarily responsible for these result in the highest arrester energy duty.
1806
The high energy requirement can be demonstrated by 7. ACKNOWLEDGMENTS
considering the following example. Assume a temporary
overvoltage of 2.5 pu (where 1 pu = V,x J U J 3 ) and the Present and former members of WG 3.4.17 who contributed to
rating of the arrester has been chosen to limit overvoltages to this paper:
2.0 pu. The energy involved in this voltage reduction can be C. C. Erven - Chairman
estimated from the following expression.
M. M. Bostic R. T. Leskovich G A Pillmore
E = 1/2 c ( v,Z - vA2) joules M. G. Comber A. L. Lim D. E. Seay
H. Huynh L. Lishchyna ~ J. P. Skliutas
where: B. Johnnerfelt H. G. Mathews K. B. Stump
R. A. Jones Y. I. Musa E. J. Tarasiewicz
C is the bank capacitance G. E. Lee V. Pargaonkar R. S. Thallum
V, and V, are the voltages before and after the arrester
application, respectively. 8. REFERENCES

On a 230 kV system, with an installed shunt capacitor bank [l] IEEE, PES Surge Protective Devices Committee, WG
of 200 Mvar, the energy dissipated in the arrester would be 3.4.17, "Surge Protection of High Voltage Shunt Capacitor
about 400 kJ. For a selected arrester with an MCOV rating of Banks on AC Power Systems - Survey Results and
144 kV this would represent 2.2 kJ per kV of duty cycle rating. Application Considerations," IEEE Trans. Power Delivery,
Vol. 6, no. 3, July 1991, pp. 1065-1072.
As indicated previously stuck pole conditions on a circuit
breaker clearing an ungrounded capacitor bank can lead to [2] IEEE/ANSI (262.2-1987, "Guide for the Application of
much higher temporary overvoltages and must be given careful Gapped Silicon-Carbide Surge Arresters for AC Systems.
consideration in the application of metal oxide surge arresters.
In many cases single column station class arresters will be [3] IEEE/ANSI C62.22-1992, "Guide for the Application of
adequate but in some cases using arresters with additional Metal-Oxide Surge Arresters for Alternating-Current
parallel columns to handle the energy involved may be Systems. I'
necessary. If so a routine test should be used to ensure current
sharing tolerances are acceptable over the range of currents [4] ANSVIEEE STD 18-1992, "IEEE Standard for Shunt
anticipated. Power Capacitors."

6. CONCLUSIONS [5] NEMA Standards Publication, Shunt Capacitors,


NO. CP-1-1988.
In many cases severe duties can be imposed on arresters
located next to shunt capacitor banks due to the high energy [6] CAN3-C155-M84,1984, Shunt Capacitors for AC Power
discharges during bank switching, regardless of whether the Systems, (A National Standard of Canada).
arresters were installed to protect the capacitor bank or other
station equipment. [7] S. S. Mikhail, and M. D. McGranaghan, "Evaluation of
Switching Concems Associated with 345 kV Shunt Capacitor
The application of surge arresters for the protection of shunt Applications," IEEE Trans. Power Delivery, vol. PWRD-1,
capacitor banks is essentially a matter of determining the No. 2, April 1986, pp. 221-230.
voltage level at which the arrester will limit the overvoltage
and then determining the energy absorption requirements. [8] M. F. McGranaghan, W. C. Reid, S. W. Law, and D. W.
Gresham, "Overvoltage Protection of Shunt-Capacitor Banks
Arrester ratings can vary widely and studies should be carried Using MOV Arresters," IEEE Trans. Power Apparatus and
out as an aid to selecting suitable arresters for these Systems, vol. PAS-103, no.8, August 1984, pp. 2326-2336.
applications.
[9] C . C . Erven, and A. Narang, "Switching of Large
Ungrounded Shunt Capacitor Banks on the Ontario Hydro
System," Canadian Electrical Association, 1985 Transactions
of Engineering and Operations, Vol. 24, Part 1, Paper No.
85-A-65.
1807
[lo] A. L. Janssen, and L. van der Sluis, "Controlling the [22] A. J. Schultz, J. B. Johnson, and N. R. Schultz,
Transient Currents and Overvoltages after the Interruption of "Magnification of Switching Surges," AlEE Transactwm,
a Fault near Shunt Capacitor Banks," CIGRE Paper 13-13, PAS, February 1959, pp. 1418-1426.
Pans, 1988.
[23] R.A. Jones, and H.S. Fortson Jr., "Consideration of
[ll] L.van der Sluis, A. L. Janssen, "Clearing Faults Near Phase-to-Phase Surges in the Application of Capacitor
Shunt Capacitor Banks," IEEE Trans. Power Delivery, Vol. 5, Banks," IEEE Trans. Power Delivery, Vol. PWRD-1, No. 3,
N0.3, July 1990, pp. 1346 - 1354. July 1986, pp. 240-244.

[12] T. M McCauley et al, "The Impact of Shunt Capacitor [24] L. Lishchyna, and R. H. Brierley, "Plnase-to-Phase
Installaltions on Power Circuit Breaker Application," IEEE Switching Surges Due to Capacitor Energization," Canadian
Trans. Power Apparatus and Systems, Vol. PAS-99, No. 6, Electrical Association, 1986 Transactions of Engineering arid
Nov/D<:c 1980, pp. 2210 -2218. Operations, Vol. 25, Part 4, Paper No. P86-SP-148.

[13] E. W. Boehne, S.S. Low "Shunt Capacitor Energization [25]H. M. Pflanz, and G. N. Lester, "Control of 0vervoltagr:s
with 'Vacuum Interrupters - A Possible Source of on Energizing Capacitor Banks," IEEE Transactions, PAS
Overvoltage," IEEE Trans. Power Apparatus and Systems, Vol. Vol. 92, No. 3, MayIJune 1973, pp. 907-915.
PAS-88, September 1969, pp. 1424-1443.
[26] R.P O'Leary, R.H. Hamer, "Evaluation of Methods for
[14] W. C. Reid, "Capacitor Application Considerations - Controlling the Overvoltages Produced by the Energization of
UtilityKJser Interface," Presented at T&D Conference, a Shunt Capacitor Bank," CIGRE Paper 13 - 05, Paris, 1988.
New Orleans, April 1976.
[27] L. Stenstrom, "Application Guidelines for Shunt
[15] J. Fish, and J. M. Clayton, "Lightning Protection of Shunt Capacitor Overvoltage Control," CIGRE S(3 33-93 WG (1l)
Capacitors," IEEE PES Summer Meeting, 1972, CP72560-1. 4 IWD.

[16] M. A. Uman, n e Lightning Discharge, (Orlando: [28] R. W. Alexander, "Synchronous Closing Control for
Acadernic Press), 1987. Shunt Capacitor Banks," IEEE Trans. Power Apparatus and
Systems, Vol. PAS - 104, No. 9, September 1985, pp. 2619 -
[17] A.. Greenwood, Electrical Transients in Power Systems, 2626.
John Wiley & Sons Inc., New York, 1971.
[29]J. H. Brunke, and G. G. Schockeit, "Synchronous
[18] R.S. Bayless, J. D. Selman, D. E. Truax, W.E. Reid, Energization of Shunt Capacitors at 230 kV," IEEE Paper
"Capacitor Switching and Transformer Transients," IEEE A 78 148- 9, January 1978.
Trans. .Power Delivery - PWRD, Jan 1988, pp. 349-357.
[30] A. Sabot, C. Morin, C. Guillaume, A. Pons, J.P. Taisne,
[19] L,. Lishchyna, R. H. Brierley, "Capacitor Switching G. Lo Pizzo, H.U. Morf, "A unique Multipurpose Damping
Surges and Possible Effects on Transformer Insulation," Circuit for Shunt Capacitor Bank Switching," IEEE Trans.
Canadian Electrical Association, 1983 Transactions of Power Delivery - PWRD, July 1993, pp.1173-1183.
Engineering and Operations.

[20] M. F. McGranaghan, R. M. Zavadil, G. Hensley,


T. Singh, M. Samotyj, "Impact of Utility Switched Capacitors
on Customer Systems - Magnification at Low Voltage
Capacitors," IEEE Trans. Power Delivery, Vol. 7, No. 2, April
1992, pp. 862 - 868.

[21] D. M. Dunsmore, E. R. Taylor, B. F. Wirtz, T.L.


Yanchula, "Magnification of Transient Voltages in Multi-
Voltage-level, Shunt-Capacitor-Compensated, Circuits" IEEE
Trans. Power Delivery, Vol. 7, No. 2, April 1992, pp. 664-
673.
1808
Discussion Current Systems, where it will be more available to the usual
planning or substation design engineer.
John E. Harder (Applications Consultant, Bloomington IN,
USA) The Working Group has done an excellent job of Manuscript received January 30, 1996.
assembling a litany of things that can go wrong associated with
capacitor applications in substations, and some concerns over
arrester selection and location. In addition, many of the items are
supported by appropriate references. This overview should be a
valuable reference. The following comments are offered for the
consideration of the working group. C.C. Eru-en (Chairman, Working Group 3.4.17), and on
In focusing on problems which have occurred, the paper has behalf of the workiiig group: We appreciate the
an unfortunate overtone that capacitor applications and arrester comments offered by Mr. J. Harder. As indicated, the
protection in the vicinity of these banks are likely to create scope of the paper is to prohide utility personnel with
problems and that every proposed application requires in-depth information which can be used in the application of
study, perhaps including TNA or EMTP modeling. The vast surge arresters in combination with the installation of
majority of substation capacitor banks on utility and industrial shunt capacitor banks. The results of the utility sumey
systems operate without problems and do not require in-depth carried out by the working group indicated the need for
study for good application. It would be helpful in the closure of such information. In reviewing the literature on the
this paper to give a brief list of specific items to look for to subject of capacitor banks and surge arresters, the
indicate the need for investigation. working group found that many papers dealt with
Modern metal oxide arresters have very high mherent energy specific problems but found a paucity of information on
capability compared with older silicon carbide arresters. Concern the general application considerations.
for arrester energy capability is only concern for the very largest
(KVAUikV) capacitor banks, and then only if the arrester is to be While we do not wish to overemphasize the risk for
problenis occurring in practice, it is our view that
applied based on withstanding a worst case restrike of the
overvoltage protection should be considered whenever.
capacitor switcling breaker (which may be restrike free). Even in
and whei-ever shunt capacitor banks are installed,
the example of a 200 WAR,230 kV bank in the paper, 2.2 kJkV
regardless of voltage level, size, locafion, connection or
is well withm the capability of standard arresters available for this
switching arrangement. Since capacitor banks can store
application. It may be helpful to indicate in some simple way for
large amounts of energy during overvoltage conditions.
what size banks energy capability is a concern, perhaps related to
several important factors, such as system operating
arrester energy capability.
conditions, installation and switching arrangement, and
It is indicated that it may be possible to use metal oxide
equipment insulation protective levels, must be taken
arresters to protect existing silicon carbide arresters from
into account in determining the energy absorption
excessive duty from a capacitor bank. Unfortunately the requirements of all nearby surge arresters. Unfortunately,
minimum sparkover of an existing arrester may be very low. If there is no easy way to determine the amount o f studies
the silicon arrester sparks over below the protective level of the required by a utility, that will depend on many factors
metal oxide arrester, the metal oxide arrester will have little impact well beyond the scope of this paper. The following list
on the duty to the gapped silicon arrester. The use of a metal indicates some of specific application consideration
oxide arrester to protect a silicon carbide arrester associated with which may require detailed studies
a capacitor installation is generally not a good option.
The paragraphs discussing gas circuit breakers and vacuum 1 ) On the capacitoi primary and backup swtchgear to
switchgear suggest that gas circuit breakers ...have a much better limit transient recovery voltages when shunt capacitor
capability for capacitor switching... and vacuum switchgear banks are switched out This wl1 tend to reduce the
...have been known to produce been known to produce possibility of restrikes, particularly for ungrounded wye-
significant transient overvoltages.. .. The suggestion that gas is connected shunt capacitor banks
better (or worse) than vacuum for capacitor switching is probably 2) At the end of transformer termmated lines to limit
beyond the scope of this paper, and is unfortunate. Some gas phase-to-phase overvoltages resulting from capacitor
breakers and switches have unfomiiiately restruck in service and switching, or line switching in the presence of shunt
have caused damaging overvoltages. This can occur because of capacitor banks
design defects, abuse, etc. The reference [ 131 cited for the vacuum 3 ) On transformers in the presence of shunt capacitoi
switchgear relates to problems with an early version of a vacuum banks
switch (not vacuum switchgear). The switch involved was so 4) To control overvoltages due to resonance when
badly out of adjustment that some phases would bounce switching shunt capacitor banks (a) In series or parallel
completely open during the closing operation. Both technologies with transformers, (b) in the presence of other capacitor
applied properly are excellent capacitor switches. Both banks
technologies can result in problems if the application is incorrect 5 ) To control overvoltages due to voltage magnification
or there is a defect in the breaker. on an inductively coupled lower voltage system, which
It would seem desirable to incorporate some of the arrester has shunt capacitors installed, when a capacitor is
application aspects of this paper into C62.22 IEEE Guide for the swtched on the higher voltage system
Application of Metal-Oxide Surge Arresters for Alternating- 6) On the neutrals of ungrounded shunt capacitor banks
1809
This example shown to demonstrate the energy whereas oil circuit breakers are prone to restnkes on
absorption in reducing overvoltages was not intended to capacitor switching It would be prudent therefore to
show a worst case scenario. but simply to demonstrate a include a requirement for restnke-free performance in
conivenient method of estimating the energy involved in the specification for any circuit breaker to be used on
such a reduction While restnkes usually represent the capacitor switching tinfortunately most circuit breakers
highest overvoltages, stuck pole conditions, or which operate as the back-up swtching dewce on
feriroresonance condihons may involve much higher capacitor swtching are likely to be those that already
energy In some cases of ungrounded capacitor banks, exist at the substation
see for example Ref [9] in the paper, multi column metal
oxide surge arresters have been used to satisfy the energy We especially thank Mr Harder for his final comment,
absorpfion requirements under stuck pole conditions on and wsh to acknowledge his foresight The working
the switching dewce group actually started out by attempting to prepare some
material for inclusion in C62 22 IEEE Guide for the
While we agree in pnnciple that it is generally not a Application of Metal Oxide Surge Arresters for
good option to use a metal oxide surge arrester to protect Altemating Current Systems However, when it
silicon carbide arresters, it mal be lustified on an became apparent that there was so much more to the
economic basis, especially if the altemate is replacing a application considerations than could be included in this
large number of stahon class silicon carbide arresters document it was agreed that a paper would be used as a
reference document As suggested, we do intend to
We agree with Mr Harder that design defects and lack incorporate some of the apphcahon aspects of this paper
of maintenance can often jeopardize the performance of in the application guide
any switching dewce However, in principle circuit
breakers based on gas blast (SF, air ) or vacuum media
can be designed to be essentially restrike free. Manuscript received April 10, 1996.

Вам также может понравиться