Digitrip 1150i - IEC Curves

IEC-A (Normal Inverse)

60
40

50
20

30

70
10
.7
.5
.6

.9
.8

9
4

8
7
3
2
1
10000
9000
2 HOURS

8000
7000 Circuit Breaker Time/Current Curves (Phase Current)
6000
5000 Magnum Circuit Breakers
Response: Normal Inverse & Short Delay Trip
1 HOUR

4000
This curve is for 50Hz or 60Hz applications.

3000 Notes:

1. This curve is shown as a multiple of the PICKUP setting (Ir). The TimeDial setting
2000 combined with SHORT PU and SHORT TIME setting (shown in heavy lines) depict
the IEC-A response. The Instantaneous,shown as a separate response, can be
set to OFF.

2. Curve Equation: Trip = TimeDial *[ 0.14 / ( I0.0 2-1) ] where I is a multiple of Ir.
1000 For current > 1.2xIr tolerance is [15%] or [-15%, +90 ms], whichever is larger.
900
800
TimeDial curve goes to flat response at 14xIr with a shorter time of
700
TimeDial function or SHORT TIME function prevailing if curves overlap.
600
The ShortTime function and the TimeDial function act independently and the entire
500 TimeDialcurves continue to be active even after the curves intersect.
400 3. With Zone Selective Interlocking enabled, max trip times w/o aux power are
as follows:
300
3 Phase fault
60 Hz 75ms
200 50 Hz 85ms

When only one pole is carrying current and a fault occurs, trip times increase to
90ms at 60Hz and 95ms at 50 Hz, however with Aux power these times would be
reduced by 10%
100
90 4. The actual pick up point (indicated by rapid flashing of Unit Status LED on the
80 product) occurs at 110% of the Ir, current, with a 5% tolerance. The SHORT PU
1 MINUTE

70 settings have conventional 100% 5% as their pick up point.


60
5. SHORT PU has also has a M1 setting, which may extend out where the SHORT
50 Adjustable PICKUP PU will become active.
40
0.4 to 1.0x In = Ir
with 0.05 increments Adjustable Range M1 setting
See Note 4
30 Narrow Frame:
200A through 1250A 1.5 to 14x Ir M1=14x In
1600A 1.5 to 12x Ir M1=12x In
20
2000A (IEC only) 1.5 to 10x Ir M1=12x In
Standard Frame:
Adjustable TimeDial 200A through 1250A 1.5 to 14x Ir M1=14x In
Setting 0.05 to 1.00
With 0.05 increments 1600A, 2000A, 2500A 1.5 to 12x Ir M1=12x In
10 See Note 2 3000A, 3200A 1.5 to 10x Ir M1=10x In
9 Double Wide Frame:
8 2000A, 2500A 1.5 to 14x Ir M1=14x In
7
3000A, 3200A, 4000A, 5000A 1.5 to 12x Ir M1=12x In
6
6000A, 6300A (IEC only) 1.5 to 10x Ir M1=10x In
5 See
Note 6
4 6. The end of the curve is determined by the interrupting rating of the circuit breaker.

7. SHORT TIME: FLAT only


3 Tolerance is +0/ -80 ms of setting except
1.00
0.10s setting is 0.06 to 0.13
0.90
0.15s setting is 0.10 to 0.17
2 0.80 0.20s setting is 0.15 to 0.22
0.70
8. Curve applies from -20C to +55C ambient. Temperatures above 85C cause
TIME IN SECONDS

0.60 automatic trip.


0.50 Adjustable
1 SHORT TIME 9. These curves are comprehensive for the complete family of Magnum breakers,
0.40
.9 0.10s to 0.50s including all frame sizes, ratings, and constructions. The total clearing times
.8 0.30 With 0.05 increments shown are conservative and consider the maximum response times of the trip
.7 See Note 7 unit, the circuit breaker opening, and the interruption of the current under factors
.6 that contribute to worst case conditions, like: maximum rated voltages, single
0.20 phase interruption, and minimum power factor. Faster clearing times are possible
.5 0.50 s
depending on the specific system conditions, the type of Magnum Circuit Breaker
0.15 applied, and if any arc reduction settings are employed. Contact Eaton for
.4
additional information.
.3
0.10

.2

0.05

.1
.09
.08
.07
.06
.05

.04 Adjustable SHORT PU


1.5x to 10x or 12x or 14x Ir Minimum clearing time
With 0.5 increments See Notes 9
.03
See Notes 4, 5

.02

.01
1

3
.5

100
2

30

90
20
8
4

40
.7

6
7

50
5

10

80
9

70
.6

60
.9
.8

Current in Multiples of of Pickup ( Ir )

Dwg. No.: 70C1031


July 2012