Characteristics: Technical Data:


General Description: Supply:
The single channel Isolating Repeater D5072S-087 accepts a 2-3-4 wire 24 Vdc nom (18 to 30 Vdc) reverse polarity protected,
resistance/RTD or 2-wire transmitting potentiometer sensor, up to 400 , ripple within voltage limits 5 Vpp, 2 A time lag fuse internally protected.
located in Hazardous Area, and repeats the resistance, with isolation, to Safe Area. Current consumption @ 24 V: 33 mA typical.
Power dissipation: 0.8 W with 24 V supply voltage.
Mounting on standard DIN-Rail, with or without Power Bus , in
Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Isolation (Test Voltage):
Zone 2. I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V.
Choice between 2, 3 or 4 wires Input is accomplished via dedicated DIP Switch.
Among all possible sensors, typical are: Input:
IEC: Pt50, Pt100 2-3-4 wire RTD/Resistance or 2-wire transmitting Potentiometer.
Integration time: 250 ms for 2-wire sensors; 500 ms for 3,4-wire sensors.
ANSI 0.3916: Pt100 Resolution: 1 m.
DIN43760: Ni100, Ni120 Input range: 0 to 400 .
Measuring RTD current: 0.15 mA.
GOST6651 russian standard: Pt46, Pt50, Pt100 ,Cu50, Cu53, Cu100
Cu9.035 (or Cu10) Burnout Fault:
Output reflects fault condition via highscale (440 ) value forcing.
Fault Detection: Fault condition is also signaled via BUS and red LED on front panel.
D5072S-087 module is able to detect the breakage of any Input sensor line (Burnout). Output:
This situation is signaled via dedicated red LED on front panel, open collector transistor 2-3-4 wires Resistance.
on Fault bus and highscale (440 ) forcing of output resistance. Transfer characteristic: linear.
Response time: 20 ms (10 to 90 % step).
Functional Safety Management Certification: Output range: 0 to 400 .
G.M. International is certified by TUV to conform to IEC61508:2010 Excitation current (Ie): 0.1 to 5 mA.
part 1 clauses 5-6 for safety related systems up to and included SIL3.
Performance:
Ref. Conditions 24 V supply, 23 1 C ambient temperature, 4-wires RTD.
Input:
Calibration and linearity accuracy: 100 m.
Temperature influence: 20 m / C, typical.
Output:
Front Panel and Features: Calibration and linearity accuracy:
< 150 m typical (Excitation Current 1 mA);
< 250 m typical (0.5 mA Excitation Current < 1 mA).
Temperature influence: 10 m / C, typical (Excitation Current 0.5 mA).
5 6 Input from Zone 0 (Zone 20) / Division 1,
3 4 Compatibility:
1 2 installation in Zone 2 / Division 2. CE mark compliant, conforms to Directives:
94/9/EC Atex, 2004/108/CE EMC, 2006/95/EC LVD, 2011/65/EU RoHS.
2 or 3 or 4 wire resistance/RTD or
Environmental conditions:
2 wire transmitting potentiometer Input Signal. Operating: temperature limits 40 to + 70 C, relative humidity 95 %, up to 55 C.
Storage: temperature limits 45 to + 80 C.
Burnout Fault detection.
Safety Description:
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2,
ATEX: II 3(1) G Ex nA [ia Ga] IIC T4 Gc, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
EN61000-6-4, EN61326-1, EN61326-3-1 IECEx: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I,
associated apparatus and non-sparking electrical equipment.
PWR for safety systems. Uo/Voc = 7.2 V, Io/Isc = 23 mA, Po/Po = 40 mW ,
FLT Ui/Vmax = 12.8 V, Ii/Imax = 28.7 mA, Ci = 0 nF, Li = 0 nH at terminals 7-8-9-10.
ATEX, IECEx, INMETRO Certifications. Um = 250 Vrms, -40 C Ta 70 C.
Approvals:
TV Functional Safety Certification. BVS 12 ATEX E 053 X conforms to EN60079-0, EN60079-11, EN60079-15, EN60079-26,
IECEx BVS 12.0050X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26.
Type Approval Certificate DNV and KR for TV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to
IEC61508:2010 Ed.2, for Management of Functional Safety.
maritime applications. DNV Type Approval Certificate No.A-13625 and KR No.MIL20769-EL002 Certificates for
maritime applications.
Simplified installation using standard DIN-Rail
Mounting:
and plug-in terminal blocks, with or without T35 DIN-Rail according to EN50022, with or without Power Bus.
Weight: 125 g.
Power Bus. Connection: by polarized plug-in disconnect screw terminal blocks to accommodate
D5072
terminations up to 2.5 mm2.
-087 250 Vrms (Um) max. voltage allowed to the Location: installation in Safe Area or Zone 2, Group IIC T4.
Protection class: IP 20.
7 8 instruments associated with the barrier. Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
9 10

Ordering Information:

Model: D5072S-087 Power Bus and DIN-Rail accessories:


Connector JDFT049
Cover and fix MCHP196
Terminal block male MOR017
Terminal block female MOR022

G.M. International DTS0434-4 Page 1/2 - PRELIMINARY INFORMATION www.gmintsrl.com


Parameters Table: Image:
Safety Description Maximum External Parameters
Group Co/Ca Lo/La Lo/Ro
Cenelec (F) (mH) (H/)
D5072S-087:Terminals 7-8-9-10 IIC 13.5 67 875
Uo/Voc = 7.2 V IIB 240 268 3500
Io/Isc = 23 mA IIA 1000 537 7000
Po/Po = 40 mW I 1000 882 11480
Ui/Vmax = 12.8 V IIIC 240 268 3500
Ii/Imax = 28.7 mA
Ci = 0 nF, Li = 0 nH

Function Diagram:

HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4

MODEL D5072S-087

2 wires 2-3-4 wires 5+


=
Potentiometer RTD / Resistance = Supply 24 Vdc
6-
9 =
10 Ohm 1+
7 2+
=
8
3-
4-

2-3-4 wires

In Out

F - +
Fault and Power Bus

G.M. International DTS0434-4 Page 2/2