Академический Документы
Профессиональный Документы
Культура Документы
For many years now the International shapes producible in laboratories and acceptable as regards operating safety.
Electrotechnical Commission (IEC) has having shown satisfactory equivalence. Moreover, the gradual replacement of
been concerned with the problem of Moreover, two new concepts are dealt dischargers by arresters enables
HV insulation coordination. with in this standard: reduction of the safety margin which
longitudinal insulation (between the had become superfluous between
Insulation coordination is dealt with in
terminals of the same phase of an open arrester protection level and equipment
two main documents:
device); specified insulating voltage.
IEC 664 for LV;
IEC 71 for HV. consideration of altitude and of Determining insulation levels
installation ageing. The standard does not stipulate
IEC 71 is divided into two parts, the
second part forming an exhaustive This draft-standard distinguishes invariable withstand voltages valid in all
application guide. internal insulation, external insulation cases, but enables insulation
Product standards, including: and two voltage ranges: coordination studies to be carried out in
IEC 694 common clauses for internal insulation covers everything a number of stages:
equipment; not in ambient air (for example, liquid definition of relationships between
IEC 76 transformers; insulation for transformers, SF6 or network type and choice of its
IEC 99 surge arresters; vacuum for circuit-breakers); insulations.
comply with IEC 71 as regards specific external insulation refers to air The purpose is to establish the
withstand voltages. clearances. characteristics of the maximum
range l: from 1 kV to 245 kV inclusive possible permanent voltages and the
range ll: above 245 kV. foreseeable temporary overvoltages as
HV insulation coordination a function of:
For each of these, implementation of
as in IEC 71 insulation coordination varies slightly.
network structure and its rated
One of the objectives of this standard voltage,
A table of standardised rated withstand the neutral earthing connection
which should come into force in 93 is to
voltages exists for each range. These diagram,
explain and break down the various tables have been drawn up according the substations and rotating
factors for achievement of withstand to various criteria, and, although mostly machines present on the line,
voltages. This approach encourages empirical up to now, have been the type and position of surge
search for optimisation and even confirmed, with a few reservations, by limitation devices, if any,
reduction in voltage withstand levels. experience. Indeed, it cannot be denied and according to considerations
Standard IEC 71 proposes conventional that the levels laid down, which have common to all overvoltage classes
modelling of actual stresses by wave not been changed for years, are fully defined by the standard (see fig. 26).
f
t
100 Tf 3 ns
shape range f = 50 or 60 Hz 10 f 500 Hz 5,000 Tp 20 s 20 T1 0.1 s 0.3 f1 100 MHz
(frequency, rising front, 30 f2 300 kHz
term) Tt 3,600 s 3,600 Tt 0.03 s 20 ms T2 300 s T2 3 ms Tt
standardised shape f = 50 or 60 Hz 48 f 62 Hz Tp = 250 s T1 = 1.2 s (*)
Tt (*) Tt = 60 s T2 = 2,500 s T2 = 50 s
standardised (*) short duration switching lightning (*)
withstand test power frequency impulse test impulse test
test
(*) to be specified by the relevant product Committee
The high operating voltage involved for energy distributors (invoice losses), ferromagnetic resonance. To prevent
increases the economic importance of industrial consumers (production this, the capacitances must be reduced
this study. losses) and people (safety). by approaching, for example, the
Three criteria justify this statement: In LV transformer energising equipment.
increase of number of customers or In practice, the lower the operating Connection of a load prior to energising
of distributed power; voltage, the more limited the is useful since this load acts as a
increase of failure cost (cost of consequences of breakdown in power reducing resistance which can prevent
equipment to be replaced); distribution terms. However resonance.
the smaller relative part of the development of electronic equipment Earthing the neutral is also a solution
coordination study in total installation and systems is responsible for a large for phase/earth resonances.
cost. number of incidents further to Overvoltage caused by capacitive
overvoltages. In point of fact, current breaking
breakdown consequences disturbance withstand level is not The solution is to prevent successive
always specified or is not coordinated reignitions by increasing contact
Dielectric failure (breakdown or arcing)
with the level corresponding to its separation speed and using a good
can cause:
installation. dielectric (vacuum or SF6).
tripping of the protective devices in
the best possible case; However, these systems play an Overvoltage caused by closing off-
destruction of equipment in the worst increasingly large role in the integrity of load lines
possible case; installations, production and This is prevented on transmission
interruption of operation each time a management, and the economic networks by progressive energising,
failure occurs. consequences for the company obtained by adding insertion
concerned can be serious. resistances to the circuit-breaker.
In HV, the resulting power failure can
affect an entire town, a region or an Coordination of withstands is thus Overvoltage caused by lightning
iron and steel plant, and causes: vital, even in LV... stroke
a risk of network destabilisation; .... and the use of arresters should be There are three possibilities:
a loss of energy billed for the energy generalised. Today they are highly installation of earth cables to prevent
distributor; recommended for LV consumers direct impulses (see chapter 1);
production loss for industrial supplied by overhead lines. installation of protective devices at
consumers; vulnerable points (dischargers or,
a risk for people (e.g. in hospitals) reduction of overvoltage preferably, arresters), (see appendix 2);
and for computer data. creation of good quality earth
risks and level connections (see chapter 1).
To avoid such incidents, studies must
Simple solutions to the various
be conducted for each new installation
overvoltages looked at in chapter 1 can
to provide consistent and optimised risk
be considered as from the initial project
protection. of installation.
One solution is to increase installation
Overvoltage due to ferromagnetic
insulation level by increasing resonance
clearances. However, this results in
The only means of removing this
considerable increase in cost: doubling completely is for 1/C to be greater
these clearances means multiplying than the slope at the origin of L i.
eight times volumes and costs. However, other solutions can be
considered, in particular in MV where
an unbalance between the 3 phases
can occur in the case of protection by
In MV phase by phase controlled switch. The
The consequences of insulation faults greatest simultaneity possible must be
on MV networks are the same, on a sought on closing the 3 network phases
lesser scale, as those in HV. (omnipole equipment);
The consequences of the resulting closing an off-load transformer may
electricity failures can also be serious be the transient phenomenon causing
Insulation coordination aims at finding rules out the possibility of absolute alongside optimisation of economy and
the right balance between equipment solutions. electrical operating stresses.
reliability from a dielectric standpoint, Although the modellings chosen may Increasing use of arresters, partly due
on the one hand, and their sizing and appear somewhat arbitrary at first sight, to improvement of their characteristics
thus cost, on the other. they have been confirmed by and reliability, contributes to greater
experience. control of protection levels.
The presentation made in this
document shows the complexity of the More detailed information can be found Consideration of this aspect by
in the publications quoted for readers international standard committees, both
parameters involved in such an
wishing to examine the subject in generally and as regards product
analysis.
greater depth. The progress made in recommendations, is proof of the
Moreover, the statistical aspect of knowledge of phenomena now ensures importance of the subject and of its
behaviour to transient overvoltages increased installation reliability associated advantages.
arrester
transformer