Notes:

1- You must follow the steps from 1 to 5.


2- Cable tray sizing based on NEC code section 392.22.
3- The allowable fill ratio of multi core cables approximately used for single core cables.
4- The cable sizes (in mm2) as per the IEC standard.
5- The input data of the LV cables as per 2kv rating & non-armoured type.
6- The input data of the MV cables as per 22kv rating & armoured type.

STEP-1 STEP-2 STEP-3 STEP-4


Low Voltage NO. of
OR Cable Data Automatic calcu
Cables
MV Cables
1 1 Multi core 300 mm2
MV NO. OF PARALLEL
2 1 Multi core 300 mm2
CABLE TRAYS
3 Multi core mm2
4 Multi core mm2
5 Multi core mm2 1
6 Multi core mm2
7 Multi core mm2 STEP-5
8 Multi core mm2
9 Multi core mm2
Manual calcul
(SELECT TRAY WIDT
10 Multi core mm2
11 Multi core mm2
12 Multi core mm2
NO. OF PARALLEL
CABLE TRAYS
13 Multi core mm2
14 Multi core mm2
15 Multi core mm2 1
16 Multi core mm2
17 Multi core mm2
18 Multi core mm2
Warning t
19 Multi core mm2
20 Multi core mm2
21 Multi core mm2
22 Multi core mm2
Please check the c
23 Multi core mm2
(till now you
24 Multi core mm2
25 Multi core mm2

By: Eng. Mohamed Sleem moh.aly.sleem@gmail.com


on 392.22.
s approximately used for single core cables.
andard.
rating & non-armoured type.
kv rating & armoured type.

STEP-4

Automatic calculation

NO. OF PARALLEL WIDTH (mm)


CABLE TRAYS

1 200

STEP-5
Manual calculation
(SELECT TRAY WIDTH BEFORE)

NO. OF PARALLEL WIDTH (mm)


CABLE TRAYS

1 300

Warning text:

Please check the cells in white


(till now you are ok)

.sleem@gmail.com
Notes:
1- You must follow the steps from 1 to 5.
2- Conduit sizing based on NEC code chapter.9_table.1.
3- The cable sizes (in mm2) as per the IEC standard.
4- The input data of the LV cables as per 2kv rating & non-armoured type.
5- The input data of the MV cables as per 22kv rating & armoured type.

STEP-1 STEP-2 STEP-3 ST


Low Voltage NO. of
OR Cable Data Automati
Cables
MV Cables
1 4 Multi core 50 mm2
LV NO. OF PARALLEL
2 4 Multi core 2.5 mm2
CONDUITS
3 Multi core mm2
4 Multi core mm2
5 Multi core mm2 1
6 Multi core mm2
7 Multi core mm2 ST
8 Multi core mm2
9 Multi core mm2
Manual
(SELECT COND
10 Multi core mm2
11 Multi core mm2
12 Multi core mm2
NO. OF PARALLEL
CONDUITS
13 Multi core mm2
14 Multi core mm2
15 Multi core mm2 4
16 Multi core mm2
17 Multi core mm2
18 Multi core mm2
Warn
19 Multi core mm2

20 Multi core mm2


21 Multi core mm2
Please check t
22 Multi core mm2
(till now
23 Multi core mm2
24 Multi core mm2
25 Multi core mm2

By: Eng. Mohamed Sleem moh.aly.sleem@gmail.com


e.1.

& non-armoured type.


ng & armoured type.

STEP-4

Automatic calculation

NO. OF PARALLEL DIA (mm)


CONDUITS

1 100

STEP-5
Manual calculation
(SELECT CONDUIT DIA BEFORE)

NO. OF PARALLEL DIA (mm)


CONDUITS

4 50

Warning text:

Please check the cells in white


(till now you are ok)