System Psychrometrics for AROMA RE MUZN

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

August DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 45.8 0.02038 0 400 0 0
Vent - Return Mixing Outlet 24.1 0.00861 3205 2312 - -
Central Cooling Coil Outlet 12.6 0.00840 3205 2312 44202 1976
Supply Fan Outlet 12.7 0.00840 3205 2312 297 -
Cold Supply Duct Outlet 12.8 0.00840 3173 2312 - -
Zone Air - 23.6 0.00861 3173 2312 41049 1975
Return Plenum Outlet 24.2 0.00861 3173 2312 2442 -
Duct Leakage Air Outlet 12.7 0.00840 32 2312 - -
Return Duct Outlet 24.1 0.00861 3205 2312 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 41361 Cooling 41049 23.6 3173 2312 0 0

Hourly Analysis Program v4.50 Page 1 of 2


System Psychrometrics for AROMA RE MUZN
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 12.0 0.00682 0 400 0 0
Vent - Return Mixing Outlet 17.8 0.01103 3205 800 - -
Central Cooling Coil Outlet 17.7 0.01103 3205 800 0 0
Supply Fan Outlet 17.8 0.01103 3205 800 297 -
Cold Supply Duct Outlet 17.8 0.01103 3173 800 - -
Zone Air - 17.8 0.01103 3173 800 -181 0
Return Plenum Outlet 17.8 0.01103 3173 800 0 -
Duct Leakage Air Outlet 17.8 0.01103 32 800 - -
Return Duct Outlet 17.8 0.01103 3205 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -2746 Deadband -181 17.8 3173 800 0 0