please find attached commented fire detection & protection layout as per following main

comments

1. i have re arranged the ground floor detection drawing


2. there should be two type of heat detector (rate of rise-car park & high tem. fixed type for
kitchen)
3. please refer the general arrangement of detection of typical apartment
4. notes should be added
5. i have included typical details of detector installation & manual call point installation
6. as per 30m length restriction, i proposed 2 manual call points for typical apartment floor

7. Protection system schematic need to revised as per comments (typical one is attached for
reference)
8. pipe path in ground floor need to re-vist
9. Extinguishers shall be placed as per fire department requirement