DISEO Y CALCULO DE ZAPATAS CONECTADAS SENTIDO Y

PROYECTO: CENTRO DE SALUD ANCAHUASI LATERAL 1(A2) CENTRAL (B2)


DATOS (FS=3) DISEO DE LA ZAPATA EXTERIOR
Esfuerzo del Terreno 1.03 kg/cm f'c = 210 kg/cm W nu = 4.26 Tn/m Mu max= 0.16 Tn-m
Altura Fondo de Zapata y NPT 1.50 m f'y= 4200 kg/cm ln = 0.275 m cuantia 0.004
Densidad promedio del suelo 1.63 Ton/m3 w = 0.08
Sobrecarga sobre el NPT 0.40 Ton/m2 Peralte Sugerido d=3.74 cm hz=50.00 cm d=45.05 cm
Longitud entre ejes columnas 4.25 m Peralte Asumido hz=30.00 cm d=25.05 cm
DIMENSIONES COLUMNAS X Y AREA DISEO POR CORTE
COLUMNA EXTERIOR 0.25 m 0.25 m 0.06 m2 Vud = -0.75 Tn Vn = -1.00 Tn
COLUMNA INTERIOR 0.25 m 0.25 m 0.06 m2 Vc = 18.43 Tn OK!
Cm Cv DISEO POR FLEXION pmin=0.33% Asmin= 6.68 cm
PESO EN COLUMNA EXTERIOR 1.93 Tn 0.90 Tn 2.83 Tn As= 6.68 cm a=1.96 cm
PESO EN COLUMNA INTERIOR 2.73 Tn 1.30 Tn 4.03 Tn Usar 3 #5 @ 15 cm As= 5.94 cm
Esfuerzo Neto del Terreno 7.86 Tn/m REFUERZO TRANSVERSAL
As-temp= 3.60 cm

PREDIMENSIONAMIENTOS Usar 2 #5 @ 25 cm
ZAPATA EXTERIOR Az = 0.43 m2 T=0.55 m
S=0.80 m DISEO DE LA ZAPATA INTERIOR
VIGA DE CONEXIN h=0.25 m b=0.25 m r=0.04 m P2 efectivo = -4.13 Tn Az= 0.53 m
DIMENSIONAMIENTOS ZAPATA EXTERIOR P2u efectivo = -6.36 Tn se usara: b = 0.80 m
Carga Distribuida de la viga 0.15 Tn/m USAR: T=0.80 m W un = 9.94 Tn/m Mu max= 0.30 Tn-m
Reaccion Neta de la Zapata Exterior 3.39 Tn Az=0.43 m S=0.80 m Lv = 0.28 m cuantia 0.004
w= 0.08
DISEO DE LA VIGA DE CONEXIN Peralte Sugerido d=5.11 cm hz=50.00 cm d=41.55 cm
P1u 2.83 Tn Peralte Asumido hz=30.00 cm d=25.05 cm
Carga Distribuida de la viga 0.15 Tn/m VERIFICACION POR PUNZAMIENTO
Reaccion Neta de la Zapata Exterior 3.41 Tn m = 0.78 m Vn = 3.34 Tn
Reaccion Distribuida Neta de la Zapata 4.26 Tn/m n = 0.50 m bo = 2.05 m
Vu = 2.50 Tn Vc = 78.92 Tn
SECCION DE MOMENTO MAXIMO (Xo<S) OK!
Xo= 0.69 m OK! VERIFICACION POR CORTE Vud = 0.20 Tn
-Mu-max= 0.62 Tn-m As= 0.76 cm a=0.22 cm Vn = 0.26 Tn
Usar 1 # 4 As= 1.27 cm OK! Vc = 15.39 Tn
REFUERZO EN LA CARA INF. As= 1.73 cm Usar 1 # 5 DISEO POR FLEXION pmin=0.33% Asmin= 6.68 cm
DISEO POR CORTE El momento para el As princ sera 1/3 Mu-max As= 6.68 cm a=1.96 cm
V1u= -0.94 Tn Vumax=13.58 Tn ok Usar 3 #5 @ 15 cm
V2u= 0.46 Tn REFUERZO TRANSVERSAL
Vc= 4.03 Tn -Vr=3.57 Tn As-temp= 5.98 cm
Estribos: 3/8'':1 @ 5, 5 @ 10 , R @ 15 #NUM! Usar 3 #5 @ 20 cm
PAG 1

DISEO DE VIGAS CONECTADAS PARA CENTRO DE SALUD ANCAHUASI


LATERAL 1(A2) CENTRAL (B2)
S=1.20 m b = 1.20 m
3 5/8" @ 15cm

3 5/8" @ 15cm
b = 1.20 m
T=1.20 m

1 1/2"
2 5/8" @ 25cm Obs: La long. del As refuerzo sera L/5 (L=Dist entre ejes) 3 5/8" @ 20cm
1 1/2"
Estribos: 3/8'':1 @ 5, 5 @ 10 , R @ 15 h=0.25 m
1 5/8"

3 5/8" @ 15cm 1 5/8" 3 5/8" @ 15cm b=0.25 m


hz=30.00 cm 30.00 cm
NPT:-1.50 m
10.00 cm 10.00 cm
S=0.80 m b = 1.20 m
2 5/8" @ 25cm 3 5/8" @ 20cm

4.25 m

BARRA DIAMETRO PESO AREA PERIMETRO


N PULG cm kg/m cm cm
3 3/8" 0.98 0.56 0.71 2.99
4 1/2" 1.27 0.99 1.27 3.99
5 5/8" 1.59 1.55 1.98 4.99
6 3/4" 1.91 2.24 2.85 5.98
7 7/8" 2.22 3.04 3.88 6.98
8 1" 2.54 3.97 5.07 7.98
9 1 1/8 2.86 5.03 6.41 8.98
10 1 1/4 3.18 6.21 7.92 9.97
11 1 3/8 3.49 7.51 9.58 10.97
12 1 1/2 3.81 8.94 ### 11.97
DISEO DE COLUMNAS METODO DEL CONTORNO DE CARGA Y JACOBSEN CON VERIFICACION DEL TIO BRESLER
CENTRO DE SALUD ANCAHUASI
C1 DATOS COLUMNA DISEO DE COLUMNA
h = 30.00 cm CONTORNO DE CARGA JACOBSEN Y BORIS BRESLER

b = 25.00 cm b/h= 0.83 ex = 15.50 cm


r = 4.00 cm = 0.65 ey = 18.69 cm
f'c= 210 kg/cm Mo = 1.61 Tn-m e= 27.26 cm
f'y= 4200 kg/cm Pu / Ag = 8.346667 kg/cm e/h= 0.91
Pu = 6.26 Ton Mo/(Ag x h)= 7.134473 kg/cm Pu / Ag = 8.346667 kg/cm
Mux = 0.97 Tn-m = 0.73 = 0.73
Muy = 1.17 Tn-m ABACO : 4L - 3 ABACO : 4L - 3
= 0.75 = 0.75
= 2.20% = 1.00%
ABACO : 4L - 4 ABACO : 4L - 4
= 0.90 = 0.90
= 1.00% = 1.00%
p = 2.33% p = 1.00%
As= 17.50 cm As= 7.50 cm
(14 3/4") (4 5/8")
As= 39.90 cm As= 7.92 cm
p = 5.32% p = 1.06%
VERIFICACION DE VALORES HALLADOS
Po = 164.83 Ton Po = 92.81 Ton
Pu / Po = 0.04 Ton ex / tx = 0.62
ABACO : CONTORNO DE CARGA ey / ty = 0.62
= 0.62 (Pu / Ag)x = 45.00 Ton
Mox / (Ag x h) = 120 kg/cm (Pu / Ag)y = 30.00 Ton
Moy / (Ag x b) = 120 kg/cm Pu x = 33.75 Ton
Mox = 27.00 Tn-m Pu y = 22.50 Ton
Moy = 22.50 Tn-m 1 / Pu = 0.06329892688
Mo equi = 1.67 Tn-m Pu = 15.80 Ton
ok!!! ok!!!!
CASO N (Ton) Mux (Ton-m) Muy (Ton-m)
1.5cm+1.8cv 6.26 0.00 0.09
1.25(cm+cv+csx) 4.89 0.95 0.07
1.25(cm+cv-csx) 4.89 0.97 0.07
1.25(cm+cv+csy) 4.98 0.00 1.10
1.25(cm+cv-csy) 4.80 0.00 1.17
0.9cm+1.25csx 2.35 0.95 0.03
0.9cm-1.25csx 2.35 0.97 0.02
0.9cm+1.25csy 2.44 0.00 1.10
0.9cm-1.25csy 2.26 0.00 1.15
BARRA DIAMETRO PESO AREA PERIMETRO
N PULG cm kg/m cm cm
3 3/8" 0.98 0.56 0.71 2.99
4 1/2" 1.27 0.99 1.27 3.99
5 5/8" 1.59 1.55 1.98 4.99
6 3/4" 1.91 2.24 2.85 5.98
7 7/8" 2.22 3.04 3.88 6.98
8 1" 2.54 3.97 5.07 7.98
9 1 1/8 2.86 5.03 6.41 8.98
10 1 1/4 3.18 6.21 7.92 9.97
11 1 3/8 3.49 7.51 9.58 10.97
12 1 1/2 3.81 8.94 11.40 11.97
CENTRO DE SALUD ANCAHUASI
VIGA PRINCIPAL CENTRAL V-101
f'c= 210 kg/cm Ec=0.003 0.85 f'c
fy= 4200 kg/cm 4 E'S A's x fs = 0.88 Tn
(N) : 5 2 5/8" 4.15 =c a=(B1)x(c)= 3.53

As
# varillas : 0 d C= 0.63 Tn

36 cm
(N) : 5
A's
# varillas : 2
SECTOR CENTRAL

31.85

D 38636.8061 Es As fy
+ 9978.38461 +0 5/8" 16.63 Tn
- 221.62 cm 25 cm 2 5/8" Cb < C
As= 3.96 cm P (en compres) 0.44% Cb= 21.18 cm
A's= 3.96 cm _Pb= 2.13% Mn= 5.67 Tn-m SECCION
SUBREFORZADA, falla
fs= 221.62 kg/cm Pb= 2.63% Mu= 5.11 Tn-m ductil OK!. El concreto se
a= 3.53 cm P (total)= 0.88% P>Pmin? CONFORME vera afectado despues que
el acero alcance su punto
c= 4.15 cm Pmax= 2.10% P<Pmax? CONFORME
de fluencia. CUMPLE LOS
B1= 0.85 Pmin1 (ACI)= 0.28% fluye A's? CON MOMENTOS REQUISITOS!!!
P (en traccion) 0.44% Pmin2 (ACI)= 0.33% P-P'> 1.34%

f'c= 210 kg/cm Ec=0.003 0.85 f'c


fy= 4200 kg/cm 4 E'S A's x fs = 0.88 Tn
(N) : 5 +0 5/8" 4.15 =c a=(B1)x(c)= 3.53
As

# varillas : 0 2 5/8" C= 0.63 Tn


36 cm

(N) : 5
A's

# varillas : 2
SECTOR LATERAL

31.85

D 38636.8061 Es As fy
+ 9978.38461 2 5/8" 16.63 Tn
- 221.62 cm 25 cm Cb < C
As= 3.96 cm P (en compres) 0.44% Cb= 21.18 cm
SECCION
A's= 3.96 cm _Pb= 2.13% Mn= 5.67 Tn-m
SUBREFORZADA, falla
fs= 221.62 kg/cm Pb= 2.63% Mu= 5.11 Tn-m ductil OK!. El concreto se
a= 3.53 cm P (total)= 0.88% P>Pmin? CONFORME vera afectado despues que
c= 4.15 cm Pmax= 2.10% P<Pmax? CONFORME el acero alcance su punto
de fluencia. CUMPLE LOS
B1= 0.85 Pmin1 (ACI)= 0.28% fluye A's? CON MOMENTOS REQUISITOS!!!
P (en traccion) 0.44% Pmin2 (ACI)= 0.33% P-P'> 1.34%

f'c= 210 kg/cm Ec=0.003 0.85 f'c


fy= 4200 kg/cm 4 E'S A's x fs = 0.88 Tn
(N) : 5 2 5/8" 4.15 =c a=(B1)x(c)= 3.53
As

# varillas : 2 d C= 0.63 Tn
36 cm
RESISTENCA SIN REFUERZOS

(N) : 5
A's

# varillas : 2
31.85

D 38636.8061 Es As fy
+ 9978.38461 2 5/8" 16.63 Tn
- 221.62 cm 25 cm Cb < C
As= 3.96 cm P (en compres) 0.44% Cb= 21.18 cm
SECCION
A's= 3.96 cm _Pb= 2.13% Mn= 5.67 Tn-m SUBREFORZADA, falla
fs= 221.62 kg/cm Pb= 2.63% Mu= 5.11 Tn-m ductil OK!. El concreto se
a= 3.53 cm P (total)= 0.88% P>Pmin? CONFORME vera afectado despues que
el acero alcance su punto
c= 4.15 cm Pmax= 2.10% P<Pmax? CONFORME
de fluencia. CUMPLE LOS
B1= 0.85 Pmin1 (ACI)= 0.28% fluye A's? CON MOMENTOS REQUISITOS!!!
P (en traccion) 0.44% Pmin2 (ACI)= 0.33% P-P'> 1.34%

BARRA DIAMETRO PESO AREA PERIMETRO


N PULG cm kg/m cm cm
3 3/8" 0.98 0.56 0.71 2.99
4 1/2" 1.27 0.99 1.27 3.99
5 5/8" 1.59 1.55 1.98 4.99
6 3/4" 1.91 2.24 2.85 5.98
7 7/8" 2.22 3.04 3.88 6.98
8 1" 2.54 3.97 5.07 7.98
9 1 1/8 2.86 5.03 6.41 8.98
10 1 1/4 3.18 6.21 7.92 9.97
11 1 3/8 3.49 7.51 9.58 10.97
12 1 1/2 3.81 8.94 11.40 11.97
VIGA PRINCIPAL CENTRAL V-101

DIAGRAMA DE MOMENTOS

MY (Tm)
-2.00

-1.00

0.00

Longitud (m)
1.00
0.00 1.00 2.00 3.00 4.00 5.00

DIAGRAMA DE CORTANTES

FZ (T)
2.00

1.00

0.00

-1.00
Longitud (m)
-2.00
0.00 1.00 2.00 3.00 4.00 5.00

VALORES CRITICOS

FX (T) FZ (T) MY (T*m)


MAX para la barra 51 0.22 1.57 0.52
en el punto: 0 0 2.21
MIN para la barra 51 0.22 -1.49 -1.19
en el punto: 0 4.25 0

DESPLAZAMIENTOS:

ARMADO DE VIGA
CENTRO DE SALUD ANCAHUASI : VIGA PRINCIPAL CENTRAL V-101

zona permisible a
+0 5/8" +0 5/8"
empalme en negativos
4.25 m
2 5/8" 2 5/8"
1.42 m 1.42 m 1.42 m

40 cm 40 cm
1.63 m 40 cm

1.06 m 1.06 m 1.06 m 1.06 m


2 5/8" +0 5/8" 2 5/8"
Estribos: 3/8'':1 @ 5, 8 @ 10 , R @ 20cm zona permisible a 0.53 m
1.35 m
empalme en positivos
BARRA DIAMETRO PESO AREA PERIMETRO
N PULG cm kg/m cm cm
3 3/8" 0.98 0.56 0.71 2.99
4 1/2" 1.27 0.99 1.27 3.99
5 5/8" 1.59 1.55 1.98 4.99
6 3/4" 1.91 2.24 2.85 5.98
7 7/8" 2.22 3.04 3.88 6.98
8 1" 2.54 3.97 5.07 7.98
9 1 1/8 2.86 5.03 6.41 8.98
10 1 1/4 3.18 6.21 7.92 9.97
11 1 3/8 3.49 7.51 9.58 10.97
12 1 1/2 3.81 8.94 11.40 11.97