SUBMITTAL AM020FNNDCH/AA
Samsung DVM S Series, Mini 4-Way Cassette (interior)

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
Cooling (Btu/h) 20,000 (15,400 SH)
Nominal Capacity
Performance Heating (Btu/h) 23,000

Condensate Pints/Hour 4.7

Voltage (/V/Hz) 1 / 208-230 / 60


Power Compatible with Samsung DVM S and Mini DVM systems:
Nominal Running Current (A) 0.5 AM***FXVA*R/AA, AM***FXVA*H/AA, AM0**FXMDCH/AA only.

Type Turbo (1) Electro-static, washable, pleated filters as standard (included with
fascia panel)
Fan Type Non Feedback SSR
Motor Built in condensate pump and check valve with maximum 29" lift
Output (W) 55
Knock-out for outside air capability ( 4.2% of total CFM with use of
Airflow CFM (UL) H/M/L 512 / 441 / 388 a booster fan)
Type R410A Fascia panel shall have LED indicator lights, IR receiver, and 4
Refrigerant
Control Method motorized louvers
Electronic Expansion Valve
High-voltage terminal block temperature sensor to disable unit in
Liquid (flare) Inches 1/4 the event overheating of power connection.
Piping
Suction (flare) Inches 1/2
Connections Construction
Drain Inches VP20 (OD 1, ID 3/4) Insulated, galvanized steel chassis and HIPS fascia panel certified to
UL94 V0.
Unit WXHXD Inches 22 5/8 X 10 1/4 X 22 5/8
Heat Exchanger
Dimensions Weight lbs. 37.5 The heat exchanger shall be mechanically bonded fin to copper tube

Model Number PC4SUSMEN Indoor Fan


Fascia Panel Indoor fan is a single turbo type
LXWXH Inches 26 1/2 X 1 3/8 X 26 1/2
(required)
Three fan speed settings and auto setting
Weight lbs. 8
Controls
Sound Level H/L dB 44 / 36 The unit shall be operated via a wireless or wired remote control with
DDC type signal
External Contact Control MIM-B14
The unit shall integrate with the Samsung NASA Controls Network
Accessories Motion Occupancy Sensor MCR-SMA
Solution
Wireless Remote Controller MR-DH00U
Controls shall integrate with a BMS system
Safety Certifications ETL & ETLc
Control wiring shall be 16 AWG shielded wire
Nominal cooling capacities are based on: Indoor temperature: 80 F DB, 67F WB. Outdoor temperature: 95 F DB, 75F WB.
Nominal heating capacities are based on: Indoor temperature: 70 F DB, 60F WB. Outdoor temperature: 47 F DB, 43F WB.
Samsung and Quietside maintains a policy of ongoing development, specifications are subject to change without notice.

www.SamsungSystemAC.com
QS-DVMS-022013A_PRELIMINARY 888-699-6067
Page 2 of 2
SUBMITTAL AM020FNNDCH/AA
Samsung DVM S Series, Mini 4-Way Cassette (interior)

11 13/16"
5 7/8"

4 3/4"
2

1 10 19/32"
4
26 3/8" 9 13/16"

6 13/16"

1 9/16"
15"

2 1/4"

5 1/8"
6 15/16"
7 11/16"
8 7/8"

26 3/8"
1 5/8"

15"
1 7/8" 3 22 5/8" 1 7/8"
4 7/16" 6
7

PC4SUSMEN Panel (ordered separately)

11 5/8"
9 7/8"

1 7/8" 22 5/8" 1 7/8"

23 - 24 13/16" Ceiling Opening

19 11/16" Suspension Point


23 - 24 13/16" Ceiling Opening
19 11/16" Suspension Point

re
or mo
m(59) No. Name Description
1500 m

1 Liquid Pipe Connection 1/4" Flare


15
00 Gas Pipe Connection 1/2" Flare
m
m
2
(59
)
or 3 Drain Pipe Connection Quick Lock, OD 1 1/4", ID 1"
m 15
or 00
e m 4 Conduit for Power & Communication Wiring -
m
(59
) 5 Air Inlet Grille -
or
m
or
e 6 Air Outlet Louver -
7 Fresh Air Intake 4 7/16"
re
or mo
m(59)
1500 m

Proper clearance must be maintained around unit for proper operation.

www.SamsungSystemAC.com
Page 1 of 2
SUBMITTAL AM053FXMDCH/AA
Samsung DVM S Eco Series Mini DVM, Heat Pump Condensing Unit

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #
System Specifications
US Ton (nominal) 4.42

Nominal Cooling 53,000


Performance Capacity (Btu/h)
Nominal Heating 61,000

System Modulation down to (Btu/h) TBA

Voltage (/V/Hz) 1 / 208-230 / 60


Nominal Cooling TBA
Running
Power Current (A) Heating TBA
Maximum Circuit Breaker
55
(MCCB/ELB/ELCB)
Minimum Circuit Ampacity (MCA) 34.0

Total Capacity (%) 50 - 130% Of Outdoor Capacity


Indoor Units
Maximum Indoor Unit Quantity 9

Type Twin BLDC Rotary X1


Compressor Compatibility
RLA (A) TBA
Only compatible with Samsung DVM S indoor units (AM****N*DCH/AA)
Type R410A
Refrigerant
Factory Charge (lbs.) 7.05 Construction
The unit shall be galvanized steel with a baked on powder coated finish
Pipe
Liquid X Suction 3/8 X 3/4
Connections Refrigerant pipe connections inside unit chassis with penetrations
Max. Distance - ODU to IDU (feet) 492 (574 equivalent) available on front, back, right, and bottom sides for versatile installation
Vertical ODU to IDU 164 / 131
Installation
Separation Heat Exchanger
Limitation Highest/Lowest IDU 49
(feet) The heat exchanger shall be mechanically bonded fin to copper tube.
Total Refrigerant Pipe (feet) 984

Type Propeller X 2 Controls


Fan The unit shall be operated via NASA Protocol with controls provided by
Output (CFM) 3,885
Condenser Fan Samsung
Type DC
Motor Controls shall integrate with a BMS system without additional interface
Output (W) 125 X 2 modules
WXHXD Inches 37 X 47 5/8 X 13 The unit shall integrate with the Samsung NASA Controls Network
Dimensions
Weight lbs. 227 Solution

Sound Level dB (A) Max. 51 Control wiring shall be 16 AWG X 2 shielded wire.

Operating Cooling F 23 - 118


Temperature Refrigerant System
Range Heating F -4 - 66 The compressors shall be Samsung hermetically sealed, inverter driven,
twin BLDC Rotary type.
Safety Certifications ETL & ETLc
Refrigerant flow shall be controlled by EEV (electronic expansion valve)
Intelligent logic to ensure proper operation within unit design limitations and
throughout the system.
operational parameters
Protection
Devices High pressure sensor, low pressure sensor, over-voltage protection,
compressor over-current protection, current transformer, fan motor voltage Other Features
protection, fan motor thermal protection, high voltage fuses Optional night quiet modes to reduce outdoor unit sound
Nominal cooling capacities are based on: Indoor temperature: 80 F DB, 67F WB. Outdoor temperature: 95 F
DB, 75F WB.
Nominal heating capacities are based on: Indoor temperature: 70 F DB, 60F WB. Outdoor temperature: 47 F
DB, 43F WB.

Other pipe restrictions and requirements exist. Please consult installation manuals or technical data book for
full details.

Samsung and Quietside maintains a policy of ongoing development, specifications are subject to change
without notice.

QS-DVMS-052013A www.SamsungSystemAC.com
Page 2 of 2
SUBMITTAL AM053FXMDCH/AA
Samsung DVM S Eco Series Mini DVM, Heat Pump Condensing Unit
AM053FXMDCH/AA Dimensional Drawing

24 13/32" 4 X 15/32" Anchor bolt hole

14 5/32"

15 1/8"
13"

TOP

37"

Wire terminals
47 5/8"
46 5/8"

34 7/8"
21 31/32"
22 5/16"
FRONT FRONT (W/O PANEL)
1"

BOTTOM

1 Gas refrigerant pipe opening 3 Condensate drain holes

2 Liquid refrigerant pipe opening 4 Communication conduit opening (2 X 1 3/8")

888-699-6067
www.SamsungSystemAC.com
Certificate of Product Ratings
AHRI Certified Reference Number: 5915997 Date: 9/8/2016 Exclusively for Export
Product: Variable Speed Multi-Split Heat Pump

Outdoor Unit Model Number: AM053FXMDCH


Indoor Unit Type: Non-Ducted Indoor Units
Manufacturer: SAMSUNG ELECTRONICS CO., LTD.
Trade/Brand name: SAMSUNG
Series name:

Manufacturer responsible for the rating of this system combination is SAMSUNG ELECTRONICS CO., LTD.

Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third
party testing:

Cooling Capacity (Btuh): 53000

EER Rating (Cooling): 10.30

SEER Rating (Cooling): 18.50

Heating Capacity(Btuh) @ 47 F: 61000

Region IV HSPF Rating (Heating): 8.80

Heating Capacity(Btuh) @ 17 F: 38000

CERTIFIED RATINGS FOR VARIABLE-SPEED, MINI- AND MULTI-SPLIT SYSTEMS ARE VALID FOR ALL COMBINATIONS OF INDOOR UNITS
(BASED ON COMBINATION TYPES) WITH THE SPECIFIC OUTDOOR UNIT LISTED ABOVE AND IN THE AHRI DIRECTORY OF CERTIFIED
EQUIPMENT.

VISIT WWW.AHRIDIRECTORY.ORG TO VERIFY THAT THIS COMBINATION IS AN ACTIVE LISTING AND THE DATA LISTED ON
THIS CERTIFICATE IS ACCURATE. SEARCH ON THE AHRI REFERENCE # TO QUICKLY LOCATE THIS COMBINATION IN THE DIRECTORY.
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate.

DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the users individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on Verify Certificate link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right.
2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: 131178456752446998