SPECIFICATION FOR DRY-TYPE (VPI) RESIN
SHEET 1 OF 4
IMPREGNATED DISTRIBUTION TRANSFORMER

1.0 SCOPE

Design, Manufacture, testing, supplying and commissioning of Open


Ventilated dry type transformer as per specification with all the accessories
and fittings for efficient and trouble free operation.

2.0 STANDARD

Transformer shall conform to Indian Standard IS: 2026-1981(Part I to IV), IS:


11171-1985 and IEC 60076-11.

3.0 RATING

Transformer shall be suitable for continuous operation and rating available in


market varies between 400 to 2500 kVA.

4.0 CONNECTIONS AND VECTOR GROUP

Connection and vector group shall be as per the requirement.

5.0 SYSTEM OF SUPPLY

3 phase, 50 Cycles up to 33/0.415 kV supply.

6.0 TAPPINGS

6.1 Off load tap changing Link on HV side

FCAN (Full load above nominal) & FCBN (Full load below nominal) tapping to
be provided for variation on either side.

7.0 TEMPERATURE RISE

Continuously rated for full load, temperature rise not exceeding 900C
corresponding to class H type Insulation, with Ambient Temperature of 500C.

8.0 TERMINALS

Bare bushing on HT and LT side shall be suitable for XLPE cable or Bus (as
per the requirement).

9.0 COOLING

Cooling type can be taken as per the requirement (ANAN, AN, GNAN,
GNAF).

10.0 INSULATION

Resin impregnated under vacuum & pressure with C class insulation on H.V
& L.V winding conductor/strip and all other insulation with H class.

ISSUE
R0
SECTION: D
SPEC. NO.
SPECIFICATION FOR DRY-TYPE (VPI) RESIN
SHEET 2 OF 4
IMPREGNATED DISTRIBUTION TRANSFORMER

11.0 EARTHING

Two earthing terminals shall be provided at the bottom on both sides.

12.0 FITTINGS AND ACCESSORIES

The following fittings and accessories shall be provided.

a) Transformer shall be provided with 4 Nos. bi-directional rollers fitted on cross


channels to facilitate the movement of the transformer in both directions.

b) Lifting lugs.

c) Diagram and rating plate shall be provided indicating the details of


transformer, connection diagram, vector group, tap changing diagram etc.

d) Thermostats for Alarm and Trip.

e) HV Cable terminating facility for XLPE cable.

f) LV Cable terminating facility for /bus duct termination flange.

g) Winding Temperature Relay unit.

h) Winding Temperature indicator Digital type with RTD connection embedded


in winding.

i) All hardware material should be corrosion resistant preferably zinc


passivated.

13.0 IRON CORE (CRGO)

The core shall be assembled from high grade cold rolled grain oriented
(CRGO) silicon steel
Lamination which shall be perfectly insulated on both & clamped to minimize
vibration & noise.
Core fastening bolts shall be insulated to reduce losses & to avoid hot spots.
All parts of magnetic circuit are effectively connected to earth system.

14.0 WINDING

High Voltage and Low Voltage shall be made of EC GRADE copper & shall
be insulated with C class insulation & to withstand thermal & magnetic
stresses arising due to through fault current High voltage windings & low
voltage windings, shall resin completely impregnated with resin. This process
shall form the insulation system of uniform under vacuum pressure process
covering highest electrical and mechanical quality, into which windings shall
be voidlessly embedded.

ISSUE
R0