Вы находитесь на странице: 1из 7

Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20,

2006 (pp62-68)

Stability analysis of natural circulation systems


HEIMO WALTER and WLADIMIR LINZER
Institute for Thermodynamics and Energy Conversion
Vienna University of Technology
Getreidemarkt 9, A-1060 Vienna
AUSTRIA

Abstract: In natural circulation systems with unequally heated risers which are connected by a header the static
instability, namely reverse flow, can occur. This paper presents different possibilities to determine the mass flow
distribution in the tube network of such systems. To calculate the mass flow distribution a graphical and the numerical
analysis (stationary and dynamical) was used. The investigation was done for a two-pass boiler under variable
operating pressures and heat loads. The dependence of the critical heat absorption ratio Vcrit from the pressure is
discussed. A lower boundary for the part load operation of the analysed natural circulation steam generator was
determined. Modifications of the boiler geometry were analysed and the calculation results were presented and
discussed.

Key-Words: Natural circulation, Reverse flow, Stability analysis, Steam generator, Two-pass boiler

1 Introduction unheated.
Natural circulation steam generators have many In the present study two different boiler designs are
advantages compared to forced- and once-through analysed:
circulation boilers. The main advantage of the natural 1. The tubes of both riser systems are connected with
circulation system is the simple design which results in the drum (design case 1). No intermediate headers
an unproblematic operation. The part load operation of and riser relief tubes (displayed with broken lines in
such a boiler is possible without special auxiliary Fig. 1) are implemented in this case.
equipment. Compared with the forced circulation boilers 2. The unheated part of both riser systems is replaced
the power for the feed water pump is lower. by an intermediate header and riser relief tubes
The steam quality of the water/steam mixture in the (design case 2). The ratio of the cross section area of
evaporator tubes of natural circulation steam generators the riser tubes to the relief tubes is 3.05.
is in the normal operation case not higher than
approximately 30 %. Therefore film boiling respectively Steam to superheater
critical heat flux can only occur under unfavorable PD
conditions. 20 m
Steam generators with natural circulation consist of a Drum
Riser relief tube
more or less complicated tube network. To avoid
instable circulation certain design criteria must be taken Intermediate header
into consideration. Unstable conditions can be the result 15 m Feed
of static [1]-[4] (e. g. reverses flow) and/or dynamic water
instabilities [5]-[7] (e. g. density wave oscillation).
In this paper the static instability, namely the reverse .
m0
.
m1
.
m2
flow, will be illustrated. Flow reversal can occur in
systems with unequal heated tubes which are connected
by a header (see Fig. 1). The investigation to identify .
q1
.
q2
reverse flow in a natural circulation system can be done
Riser system 1

Riser system 2
Downcomer

with the aid of a graphical and a numerical analysis.

2 Investigated boiler 0m
Figure 1 shows a sketch of the investigated two-pass
natural circulation steam generator. The higher heated Lower header
riser system 2 corresponds to the furnace and the lower
heated riser system 1 represents the tubes of the wall in Fig. 1: Design of the two-pass boiler
the second pass. The large diameter downcomer is
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

3 Graphical Analysis The characteristic curve for the downcomer is


The graphical analysis is used to study the mass flow illustrated in Fig. 2 by the full line and that for the riser
distribution under steady state conditions. For the system 1 and 2 by the doted lines. Dependent on the
determination of the mass flow rate in the individual flow direction of riser system 1 the mass flow for the
tubes of the boiler it is necessary to combine the unequally heated riser systems must be added or
different tube characteristics. The characteristic curve for subtracted at constant pressure difference pDH (In case
a tube can be obtained by plotting the total pressure of reverse flow in the lower heated riser system the
difference between the drum and the lower header pDH characteristic curve for m & 1 < 0 must be subtracted (see
against the mass flow rate (see Fig. 2). The total pressure arrows in Fig. 2) from the characteristic m & 2 > 0). This
difference pDH can be calculated by results in a circulation characteristic (broken lines)
pDH = pFric + pH + pAccel. (1) dependent on the flow direction of riser system 1.
pFric includes the pressure loss to friction as well as It can be seen that the circulation characteristic for
the pressure loss to e. g. in- and outflow and bends. The upward flow direction in both riser systems (signed with
pressure difference due to acceleration pAccel is identical m& 1 > 0 and m& 2 > 0) has only one intersection point with
to zero in case of an unheated tube. pH describes the
the characteristic of the downcomer (point A). In this
pressure difference of the static head.
intersection point equation (2) and (3) are fulfilled. The
For the graphical analysis the total pressure difference
pDH for every individual tube must be equal (equation associated circulation mass flow m & 0 , m& 1 and m& 2 as well
(2)) and also the mass balance for the lower header as pDH can be read from the axis. In case of reverse
(equation (3)) must be fulfilled. flow in riser system 1 the circulation characteristic
pDH1 = pDH2 = pDH3 (2) (signed with m & 1 < 0 and m& 2 > 0) has two intersection
m& 0 = m& 1 + m& 2 (3) points with the graph for the downcomer (point B and
The negative sign in equation (3) is used if the mass C). Only solution B is stable.
flow in the lower heated tube is directed downward. The Higher heat absorption at the lower heated system 1
counterclockwise flow direction is counted positive. moves the circulation characteristic for reverse flow in
Figure 2 should help to explain the procedure for the direction of lower mass flow rate and pDH. This leads to
graphical determination of the mass flow distribution in the consequence that the solutions B and C move
the tubes of the boiler design 1. At the horizontal axis of together. The point where B and C are merged represents
Fig. 2 the mass flow and at the vertical axis pDH is the limit of univocal flow direction in the riser system
outlined. with the lower heat absorption. For further increase of
the heat flow q&1 the downcomer characteristic does not
cross the graph for the circulation characteristic with the
0 m1

mass flow m & 1 < 0 and m& 2 > 0. In this case only upward
e
m. s ys t
DH

Do
wn flow is possible in both riser tubes.
p

1 >
se r

co The graphical solution is very illustrative but also


Ri

m
m > em 2

er
very time-consuming. Therefore a numerical simulation
0

is preferable to find design criteria to prevent reverse


. t
r s ys

flow. In the following paragraphs the results of such


2
R i se

numerical analysis (stationary and dynamical) will be


B presented.
C
0, . is ti c
m. ra c t e r o n

2 >
0
ti
ch a rc u l a

4 Stationary Analysis
e r is tic
0

The evaluation of the stationary behavior of steam


Ci
. s te m 1

1 >
c h a r a ct o n
1 < 0, m >

generators is a standard procedure for the design of


2
ti
.
Ci r c u l a
m1 < 0

heating surfaces. Many computer programs e. g. NOWA


R ise r s y

A [8] were developed in the past to calculate the stationary


operation conditions of steam generators. The data for
.m

the geometry (e.g. tube diameter and lengths, wall


thickness, etc.), the system pressure as well as the heat
absorption profile for the heated tubes are necessary for
Mass flow the input of such a code. The temperature-, density-,
pressure- or mass flow distributions in the tube network
Fig. 2: Graphical solution of the boiler are the result of such a calculation.
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

2
q 2= 75 kW/m
50 .
m2 .
p = 80 [bar] m1[kg/s]
D
40 . 10
m2

320
3 00

20 0

1 00
30 0 0
Solution A
.
q [kW/m2]
M ass flow [kg/s]

1 D
20 Solution B -10 75
100
Solution C
10 . -20
m1 q 2 = 320 kW/m2
200
0
1 5 10 20 30 40 50
. .
V= q2/q1
-10 C 300
.
m0
A V=1 V=2 V=5 V=10
320

-20
.
m .
q [kW/m2]
1 0 1 2 2
-30
.
m0 B,C
-40

-50 0 1 2
Fig. 4: Mass flow m& 1 at different heat absorption ratios
V as 3-dimensional surface [2]
Fig. 3: Mass flow distribution at different heat
absorption ratios V [2] The static analysis has shown that both stable
solutions (A and B) for the mass flow distribution can be
Figure 3 shows as a result of a static stability analysis found. But a static analysis can only find the solution
the mass flow distribution in the tubes of the steam under stationary conditions. As shown in [2] the correct
generator. The calculations are done for the boiler design static results alone are not a guaranty for a safe operation
shown in Fig. 1 without the riser relief tubes and the of a natural circulation system with unequally heated
intermediate headers (design case 1). The heat flux for risers under all conditions. Therefore the prediction of
the transient behavior of the boiler e. g. under hot start-
riser system 2 with q& 2 = 320 kW/m2 was kept constant
up conditions or heavy load changes must be done by a
while the heat flux for q&1 decreases. A negative sign in dynamic analysis.
Fig. 3 describes a flow direction from the drum to the
lower header.
Up to a heat absorption ratio of V = q& 2 / q&1 = 7 only 5 Dynamic Analysis
one solution (A) with upward flow direction in both riser The one-dimensional mathematical model for the flow in
systems can be found. With a heat absorption ratio the tubes, which was used for all calculations in this
higher than 7 two stable (A and B) and one unstable (C) paragraph, includes a homogeneous equilibrium model
solutions are possible for the circulation mass flow. The for the two phase flow and applies a correction factor for
solution C in Fig. 3 was found with the help of the the two phase pressure loss according to Friedel [10].
graphical method presented in the paragraph above. The The collectors and distributors respectively are assumed
heat absorption ratio of 7 represents the critical value to be points. The steam, which enters the header, is
Vcrit between a stable upward flow in both riser systems evenly distributed to the outlet tubes. A detailed
and a possible operation condition with reverse flow in description of the computer code is given in [11].
the lower heated riser system 1.
A complete solution for the mass flow in the lower 5.1 Boundary and initial conditions
heated riser system 1 m & 1 for all possible heat absorption The following initial conditions are used for the dynamic
ratios is presented in Fig. 4. The Fig. shows that reverse simulations:
flow is possible for a heat absorption ratio V > 7 (point the steam generators are filled with water near
C) at the constant heat flux for riser system 2 with boiling condition
q& 2 = 320 kW/m2. The critical heat absorption ratio Vcrit the pressure distribution of the fluid is due to gravity
and the velocity of the working fluid in the tube
decreases with lower total heat flux. This can be seen for network of the evaporator is zero and
the curve for q& 2 = 75 kW/m2 (point D). the fluid temperature in the evaporator of the boiler
is equivalent to the boiling temperature at drum
pressure.
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

The drum pressure of the steam generator is constant mass flow starts to slow down. Approximately 500
during the whole simulation. The heat fluxes to the two seconds after the start of the simulation the flow
riser systems of the two-pass boiler are boundary direction of the riser system 1 changes rapidly to upward
conditions for the simulation. The water level was flow. Following the change of the flow direction, the
controlled at the drum centerline. mass flow tends after a short peak to a much lower mass
The system pressure will be varied in steps between flow. After about 600 seconds the mass flows in the
80 bars and 12 bars (80 bar, 65 bar, 50 bar, 40 bar, downcomer and both riser systems have achieved the
30 bar 20 bar and 12 bar). steady state values.
The heating ramp for the simulated hot start-up was
selected according to [9] and is shown in Fig. 5. It can be 60.0
seen that in the first period of the simulation the heat Riser System 2
40.0

M ass flow [kg/s]


flow increases up to 30 % of the full load. Between 30 s
and 150 s after the ignition of the burner the load is Downcomer
20.0
constant. During the time period between 150 s and
400 s the ramp-like heat input reaches the full load. The 0.0
Riser System 1 p = 80 [bar]
total time for the simulation is 10000 s. D
Q = 4.8 MW
-20.0
6000.0 V=9
V = 9.5
-40.0
0.0 200.0 400.0 600.0 800.0
Time [s]
H eating [kW ]

4000.0 Riser system 2


Fig. 6: Mass flow distribution at a heat absorption ratio
of V = 9 and V = 9.5
2000.0
Riser system 1 The situation for the circulation mass flow after a
moderate change of the heat absorption ratio from V = 9
0.0
0.0 200.0 400.0 600.0 800.0 to V = 9.5 is different. The mass flow in the tubes of the
Time [s] boiler at V = 9.5 starts similar to that shown for a heat
absorption ratio of V = 9. The mass flow of the working
Fig. 5: Heating ramp fluid in riser system 1 starts in the downward direction too.
With the beginning of the steam production in the lower
The total heat absorption (i.e. the heat absorption for heated riser system 1, the mass flow starts to slow down.
both riser systems) will be varied in steps between But, compared to the case with V = 9 the heat flux to the
8 MW and 0.8 MW (8 MW, 6.4 MW, 4.8 MW, 3.2 MW riser system 1 is not high enough to change the flow
and 1.6 MW). The value of 8 MW was chosen as upper direction. Therefore the flow direction remains different in
extreme. For industrial furnaces with oil firing the both riser systems at steady state.
corresponding heat absorption can be assumed between
5 MW - 6 MW. The value of 0.8 MW can represent the 1.50
Pressure difference [bar]

condition for low load operation or special equipment in 1.40 Riser System 1
process engineering (e. g. refuse incineration plant). 1.30
pDH
1.20 pDH
5.2 Results of the dynamic analysis
1.10
Figure 6 shows as a result of the dynamic simulation the V=9
V = 9.5
mass flow in the different tubes of the boiler. The 1.00
simulation refers to the boiler design without the p = 80 [bar]
0.90 D
Q = 4.8 MW Riser System 2
intermediate headers and riser relief tubes at 80 bars, a 0.80
total heat flow of 4.8 MW and a heat absorption ratio of 0.0 200.0 400.0 600.0 800.0
V = 9 (full line) and V = 9.5 (broken line). Time [s]
In the following the results for the heat absorption ratio
of V = 9 will be described in detail: Fig. 7: Pressure difference distribution at a heat
It can be seen that the lower heated riser system 1 starts absorption ratio of V = 9 and V = 9.5
in the downward direction with a relatively high mass
flow rate. The higher heated riser system 2 starts in the Figure 7 shows the pressure difference of the static head
upward direction with approximately the double mass pH for both riser systems as well as the total pressure
flow rate as the riser system 1. With the beginning of the difference between the drum and the lower header pDH.
steam production in the lower heated riser system 1, the
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

At first the results for the heat absorption ratio of V = 9


will be described:
During the first phase of the hot start-up pDH is smaller
than the pressure difference of the static head and
therefore the mass flow in the lower heated riser system
1 is directed downward. With the beginning of the steam
production pH starts to decrease. Between 480 and 520
seconds after the start of the simulation the increasing
steam production in the riser system 1 reduces the static
head pH and crosses the graph of the pressure difference
pDH. In this period, the mass flow changes from
downward to upward direction.
The pressure difference due to height pH to the case of Fig. 9: Velocity in the tubes of riser system 2
a heat absorption ratio of V = 9.5 is always higher than
pDH (see Fig. 7). Therefore the mass flow is always The analysis of the basic design has shown that the
directed downward in the lower heated riser system 1 boiler should not operate in the pressure range < 30 bars
also at steady state. and in the very low load region, even at 80 bars.
Therefore modifications on the system geometry are
necessary. One of the most successful methods to get a
higher stability is to modify the thermo-hydraulic
behaviour of the circulation system. This can be done by
reducing the pressure loss in the downcomer or
increasing the pressure loss in the riser systems [4], [12].
The investigation on the design case 1 has also shown
that the mass flow in the higher heated tubes is higher
than necessary for cooling the tubes. Therefore a
redesigning of the unheated section of the riser systems
should be done with the aim to reduce the mass flow in
the higher heated riser system. This can be done by
replacing the unheated part of both riser systems by an
Fig. 8: Critical heat absorption ratios intermediate header and riser relief tubes (see Fig. 1) [4],
[12].
Figure 8 shows the critical heat absorption ratio Vcrit for In the following the results for design case 2 will be
the boiler design 1 at different system pressures and heat presented.
loads. The investigation for this test case is subdivided into two
A heat absorption ratio of Vcrit 5 is assumed to be a parts:
design criterion for the two-pass boiler for stable 1. The number of unheated riser relief tubes for the
operation at all heat loads. A curve with the constant lower heated system 1 is two and for the higher
heat absorption ratio of Vcrit = 5 (broken line) is included heated system 2 is four.
in Fig. 8. It can be seen that the system tends to flow 2. The number of unheated riser relief tubes for the
reversal for low heat loads even at 80 bars. lower heated system 1 is four and for the higher
Beside the overall circulation ratio the fluid velocities heated system 2 is two.
are also of important interest for the boiler design. In a At first the design case with the four riser relief tubes
certain temperature (pressure) range high velocities can implemented in the higher heated riser system 2 will be
be the reason for erosion-corrosion ([13] [14]). described.
Figure 9 shows the velocity in the higher heated tubes. It Figure 10 shows the critical heat absorption ratios Vcrit
can be seen that the velocity corresponds over a wide for the first analysed configuration of design case 2. The
range of pressures and heat loads with the usual design modifications at the unheated part of the riser systems
rules (The velocity of the steam-water mixture should be has moved the lower limit for stable upward flow of
approximately 12 m/s and the velocity in the Vcrit = 5 in direction to the lower heat loads. Therefore no
downcomer 4m/s [12]). A curve with the constant operation restriction at lower heat loads is given for the
velocity of 12 m/s is included in Fig. 9. pressure range down to approximately 60 bars.
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

Fig. 10: Critical heat absorption ratios for design case 2


with four riser relief tubes at the higher heated riser
system 2
Fig. 12: Critical heat absorption ratios for design case 2
with four riser relief tubes at the lower heated riser
The simulation result for the velocity in the riser relief
system 1
tubes of the higher heated riser system 2 is shown in Fig.
11. It can be seen that the curve with the constant
Figure 13 shows the velocity in the riser relief tubes of
velocity of 12 m/s is shifted in direction of higher
the higher heated riser system 2. In this case the curve
pressures and lower heat loads. A detailed analysis of the
for the constant velocity of 12 m/s is moved into the low
data in the pressure region between 30 bars and 50 bars
load region for all operation pressures. This is a result of
and higher heat loads has shown that the velocities are
the lower number of riser relief tubes at the riser system
close to 12 m/s. Therefore a safe operation is also given
2.
for this boiler design down to 30 bars.

Fig. 11: Velocity in the riser relief tubes at the higher Fig. 13: Velocity in the riser relief tubes at the higher
heated riser system 2 heated riser system 2

The installation of four riser relief tubes in the lower On the basis of this result the current design case can be
heated system 1 increases the critical heat absorption used only in a very restricted operation range. Therefore
ratio especially in the high pressure/high heat load a further redesign (e. g. larger dimension for the riser
region (see Fig. 12). The limit for stable upward flow of relief tubes and intermediate headers) of the boiler is
Vcrit = 5 is also moved to lower heat loads. necessary.
It can be seen that this boiler design has achieved the
highest values for Vcrit from all analysed configurations.
A comparison of the data has shown that the pressure in 6 Conclusion
the lower header for the design case 2 with four riser A stability analysis for a natural circulation system with
relief tubes at the lower heated riser system 1 was higher two unequally heated riser systems which are connected
than in the other cases while the pressure in the lower by a header with an unheated downcomer was
header of the basic design was the lowest. The higher performed. For the determination of the static instability,
pressure in the lower header moves the critical heat namely reverse flow, different methods have been
absorption ratio to higher values. This was demonstrated presented. The investigation was done for different
also in [12]. operation pressures and heat loads.
Proceedings of the 2006 WSEAS/IASME International Conference on Heat and Mass Transfer, Miami, Florida, USA, January 18-20, 2006 (pp62-68)

The study has shown that for every system pressure,


heat load and boiler configuration a special critical heat [4] Walter, H. and Linzer, W., Investigations to the
absorption ratio Vcrit exists. This critical heat absorption Stability of a Natural Circulation Two-Pass Boiler,
ratio must be determined for every configuration of such Proceedings of the ASME - ZSIS International
a boiler. The critical heat absorption ratio depends also on Thermal Science Seminar II, Bled, Slowenia 13.-16.
the thermo-hydraulic behaviour of the circulation system. June 2004, pp. 469-474.
Heating conditions which exceed this critical value can [5] Walter, H., and Linzer, W., Dynamic Flow
lead to unstable conditions including the possibility of Instability of Natural Circulation Heat Recovery
flow stagnation and or reverse flow. Steam Generators, Proceedings of the 16th
The analysis of the data has shown that all International Symposium on Transport Phenomena
modifications which lead to a higher pressure in the (ISTP-16), Prague, Czech Republic, 29. August 1.
lower header results in a higher stability. September 2005, pp. 1-11.
In boiler configurations with unequally heated tube [6] Nayak A. K., Vijayan P. K., Saha D., Raj, V. V. and
systems the number of riser relief tubes which are Aritomi M., Analytical Study of Nuclear-Coupled
connected with the lower heated tubes should be smaller Density-Wave Instability in a Natural Circulation
or equal to the number of riser relief tubes which are Pressure Tube Type Boiling Water Reactor, Nuclear
connected with the higher heated tubes. Otherwise the Engineering and Design, Vol.195, 2000, pp. 27-44.
velocity in the relief tubes can exceed the upper limit. [7] Guanghui S., Dounan J., Fukuda K. and Yujun G.,
Theoretical and Experimental Study on Density
Wave Oscillation of Two-Phase Natural Circulation
7 Nomenclature of Low Equilibrium Quality, Nuclear Engineering
m& 0 Mass flow in the downcomer [kg/s] and Design, Vol.215, 2002, pp. 187-198.
[8] Nowotny, P., A contribution to the calculation of the
m& 1 Mass flow in riser system 1 [kg/s] mass flow distribution in tube networks, Fortschritt-
m& 2 Mass flow in riser system 2 [kg/s] Berichte VDI, Series 6, No.102, VDI-Verlag,
Dsseldorf, 1982
q&1 Heat flow to riser system 1 [kW/m2] [9] Linzer, W., Das Ausstrmen von Siedewasser und
q& 2 Heat flow to riser system 2 [kW/m2] Sattdampf aus Behltern, Brennstoff-Wrme-Kraft,
V Heat absorption ratio [-] Vol.22, No.10, 1970, pp. 470-476.
Vcrit Critical heat absorption ratio [-] [10] Friedl, L., Improved Friction Pressure Drop
pAccel Pressure difference due to acceleration [bar] Correlation for Horizontal and Vertical Two-Phase
pDH Total pressure difference between the drum and Pipe Flow. European Two-Phase Group Meeting,
the lower header [bar] Ispra, Italy, 5. 8. June 1979, Paper E 2, pp. 1 - 25.
pFric Pressure difference due to friction [bar] [11] Walter, H., Modeling and Numerical Simulation of
Natural Circulation Steam Generators, Fortschritt-
p H Pressure difference of the static head [bar]
Berichte VDI, Series 6, No.457, VDI-Verlag,
Dsseldorf, 2001
[12] Walter, H. and Linzer, W., The influence of the
References:
operating pressure on the stability of natural
[1] Ledinegg, M., Instability of flow during natural and
circulation systems, Applied Thermal Engineering,
forced circulation, Die Wrme, Vol.61, No.48, 1938,
(accepted for publication).
pp. 891-898
[2] Linzer, W. and Walter, H., Flow reversal in natural [13] Loos C. and Heitz E., The mechanism of the
circulation systems, Applied Thermal Engineering, erosion corrosion in fast fluid flows. Werkstoff
Vol.23, No.18, 2003, pp. 2363-2372. und Korrosion, Vol.24, No.1, 1973, pp. 38-48
[3] Walter, H., and Linzer, W., Flow Stability of Heat [14] Kastner W., Riedle K. and Tratz H.,
Recovery Steam Generators, Proceedings of the Experimental investigation to the material
ASME Turbo Expo 2004, Power for Land, Sea and abrasion through erosion corrosion. VGB
Air, Vienna, Austria 14.-17. June 2004, Paper Nr. Kraftwerkstechnik, Vol.64, No.5, 1984, 452-465
GT2004-53040, pp. 1-9.

Вам также может понравиться