Академический Документы
Профессиональный Документы
Культура Документы
Abstract This paper presents calculation and simulation of a three phase short circuit,
single line to ground fault and lightning stroke transients on a 110 kV cable-overhead
transmission line that connects the new 110/20 kV transformer station Djakovo 3 with the
existing TS 400/110 kV Ernestinovo and TS 220/110 kV Djakovo. Calculation and simulation
of short-circuit transients are made using the EMT DIgSILENT Power Factory module.
Simulations of a lightning stroke are compared using the ATP-EMTP software and EMT
DIgSILENT module. Using the composite DSL (DIgSILENT Simulation Language) model, the
Direct lighting stroke has been represented as the Double-exponential function and the return
stroke as the Heidler function. Using the ATP-EMTP model, the lightning stroke has been
represented as the Heidler function. Lighting stroke simulations are made with and without
the presence of ZnO polymer-housed surge arrester model in both simulation tools.
Keywords: Short circuit, lightning stroke, cable, overhead transmission line, simulation,
DIgSILENT software, ATP-EMTP software.
1 Introduction
A new transformer station 110/20 kV Djakovo 3 has been incorporated in the Slavonian
transmission system between the existing TS 400/110 kV Ernestinovo and TS 220/110 kV
Djakovo. Conjunction with the 6- phase 110 kV Ernestinovo-Djakovo overhead line is
realized with two parallel 110 kV NEXANS type cables lying in the same canal. The
DIgSILENT model used in the simulation includes the whole Slavonian transmission system
with the newly incorporated facilities, while the ATP-EMTP model includes a detailed
overview of new facilities. According to IEC (published in 2001) norm, short-circuit RMS
and EMT values have been calculated and simulated on every 10% of length of the
considered lines and cables. A lightning stroke has been simulated at the conjunction point of
the 6-phase overhead line and two parallel 110 kV cables.
Short circuit values and diagrams have been calculated and simulated using the EMT
DIgSILENT module, while the lighting stroke has been simulated using the same EMT
module incorporating the DSL composite model.
400/110 kV
ERNESTINOVO
POLE 57
NEW TS 110/20 kV
DJAKOVO 3
220/110 kV
DJAKOVO
Figure 2.1 A new transformer station incorporated in the existing Slavonian transmisson
network, one-line diagram in DIgSILENT
Direct ligthing stroke has been modeled within the DSL composite model as the Double-
exponential function :
I(t)= A ( e- + e )
I (t ) A H (t , A , A ) B H (1, B , B )
2 1 2 1
2
t
1
2
-t
H (1, , ) e 1
2 1
2
1 t
2
2 2
1
e
Figure 2.3 Heidler function 8/20 s used for returning lightning stroke
Three 1000 A current sources behind the reactances of 20 mH that represent a lighting stroke
reactance are also involved in the DSL model.
The calculated residual voltage for current impulse 10 kA, 8/20 s entered in the DIgSILENT
surge arrester model is represented in Table 2.2.
Table 2.2 The calculated residual voltage for 10 kA, 8/20 s impulse according
to manufacturers data
I [kA] V [kV] I [kA] V [kV] I [kA] V [kV] I [kA] V [kV] I [kA] V [kV]
0,10 176,26 0,40 187,57 0,80 193,22 4,00 212,43 30,00 264,40
0,20 183,06 0,50 189,83 1,00 194,35 7,00 221,46 40,00 277,97
0,30 185,32 0,60 190,96 2,00 203,40 10,00 226,00 50,00 289,26
0,40 187,57 0,70 192,09 3,00 207,92 20,00 248,60 60,00 298,32
The residual voltage of 226.00 kV for current impulse 10 kA, 8/20 s is a lighting protective
level obtained with this surge arrester. The highest withstanding lightning voltage for the 110
kV facility (according to VDE) is 550 kV, the ratio of the highest withstanding lightning
voltage for the 110 kV facility and the residual voltage on the surge arrester is 550 kV/226 kV
= 2.43 (>1.4) which provides appropriate overvoltage protection.
4 Simulation results
The calculated three phase short-circuit RMS current values along the 110 kV line between
the new 110/20 kV transformer station Djakovo 3 and 400/110 kV transformer station
Ernestinovo are presented in Table 4.1 and Figure 4.1.
Table 4.1 Three phase short-circuit RMS current values along the 110 kV line ''Ernestinovo-
Djakovo3''
Sk3'' Ik3'' angle
Line location [MVA] [kA] []
10% 3156,36 16,57 -80,15
20% 2722,19 14,29 -78,72
30% 2443,28 12,82 -77,79
Ernestinovo -Djakovo 3 40% 2259,75 11,86 -77,16
(pole 57) 50% 2141,19 11,24 -76,74
60% 2071,41 10,87 -76,47
27,441 km 70% 2042 10,72 -76,32
80% 2049,68 10,76 -76,27
90% 2095,28 11,00 -76,33
100% 2182,92 11,46 -76,48
Figure 4.1 Distribution of 3 phase short-circuit currents along the 110 kV line
''Ernestinovo-Djakovo3''
Single line to ground fault analysis considers calculation and distribution of RMS current
values along the 110 kV lines nearby the new facilities, as well as the EMT simulation.
The calculated single phase to ground RMS current values along the 110 kV line between the
new 110/20 kV transformer station Djakovo 3 and 400/110 kV transformer station
Ernestinovo are presented in Table 4.2 and Figure 4.2.
Table 4.2 Single phase to ground RMS current values along the 110 kV line ''Ernestinovo-
Djakovo3''
Sk1''
Line location [MVA] Ik1'' [kA] angle [] Z0 [] I0 [kA]
The single phase to ground fault with 0 impedance has been initiated at t=100 ms, whereas
at t=300 ms the fault has been cleared. Figure 4.3 presents a single phase to ground current
diagram at the middle of the 110 kV line ''Ernestinovo-Djakovo 3''
DIgSILENT
20.00
10.00
0.00
-10.00
-20.00
-0.0010 0.0652 0.1314 0.1975 0.2637 [s] 0.3299
Ernestinovo-s tup57: 3*I0 in kA
struje_Ern_Djakovo Date: 4/21/2009
Annex: /1
Figure 4.3 The single phase to ground current diagram at the middle of the 110 kV overhead
line ''Ernestinovo-Djakovo 3''
Voltages on the end terminals of the 110 kV overhead line ''Ernestinovo-Djakovo 3'' follow
the current waveforms during the fault. Peak voltage sags values are up to 30 kV.
DIgSILENT
120.00
100.00
80.00
60.00
40.00
20.00
-0.0010 0.0652 0.1314 0.1975 0.2637 [s] 0.3299
Stup 57 DJK: Voltage Phasor, Magnitude in kV
120.00
100.00
80.00
60.00
40.00
20.00
-0.0010 0.0652 0.1314 0.1975 0.2637 [s] 0.3299
Stup 57 ERN: Voltage Phas or, Magnitude in kV
naponi2 Date: 4/21/2009
Annex: /6
Fig. 4.4 Voltages on the end terminals of the 110 kV overhead line ''Ernestinovo-Djakovo 3''
The single phase to ground fault current phase A simulated at the middle of the cable from
''Pole 57 Djakovo 3 (section from TS Ernestinovo) is presented in Figure 4.5.
DIgSILENT
30.00
20.00
10.00
0.00
-10.00
-20.00
-0.0010 0.0692 0.1394 0.2096 0.2798 [s] 0.3500
Stup57-Djakovo3-Ern: 3*I0 in kA
Ernestinovo_Djakovo3-kabel Date: 4/21/2009
Annex: /5
Figure 4.5 The single phase to ground fault current phase A simulated at the middle of the
cable from ''Pole 57 Djakovo 3 (section from TS Ernestinovo)
The single phase to ground fault peak values simulated at the middle of the cable from ''Pole
57 Djakovo 3 (section from TS Ernestinovo) are approximately 1.5 times the simulated
single phase to ground current peak values at the middle of the 110 kV overhead line
''Ernestinovo-Djakovo 3'' due to lower cable direct, inverse and zero component reactances
than overhead line reactances.
The lightning stroke has been simulated at the conjunction point 110 kV overhead line cable
(pole 57) with the ZnO surge arresters modeled on both tower terminals. According to
residual voltage-current surge arrester characteristics (Table 2.2), the 50 kA resistive current
value has been achieved on the surge arrester electrically closer to the point of lightning
stroke, while the 3 kA value has been obtained on the farther tower terminal.
DIgSILENT
4.00
3.00
2.00
1.00
0.00
-1.00
-0.0030 -0.0018 -0.0006 0.0006 0.0018 [s] 0.0030
ZNOodvodnik 1: Current Phasor, Magnitude in kA
62.50
50.00
37.50
25.00
12.50
0.00
-12.50
-0.0030 -0.0018 -0.0006 0.0006 0.0018 [s] 0.0030
ZNOodvodnik 2: Current Phasor, Magnitude in kA
udar_munje ZNO-2 Date: 5/12/2009
Annex: /3
Figure 4.6 Surge arrester resistive current values on both tower terminals
DIgSILENT
120.00
100.00
80.00
60.00
40.00
-0.0030 -0.0018 -0.0006 0.0006 0.0018 [s] 0.0030
Stup 57 DJK: Voltage Phasor, Magnitude in kV
110.00
100.00
90.00
80.00
70.00
60.00
50.00
-0.0030 -0.0018 -0.0006 0.0006 0.0018 [s] 0.0030
Stup 57 ERN: Voltage Phasor, Magnitude in kV
naponi2 Date: 5/12/2009
Annex: /2
Figure 4.8 The Heidler function as the lightning stroke model in ATP-EMTP
Figure 4.9 Voltages on the tower terminals after lighting stroke simulation
Figure 4.10 Surge arrester residual voltage- arrester further from the lightning stroke location
Figure 4.13 Voltages on the 110 kV busbars of the new TS 110/20 kV Djakovo 3 after
lighting stroke simulation
Residual voltage differences on surge arresters closer and further from the lightning stroke
location are negligible as expected due to more accurate tower geometry model in ATP-
EMTP which is the advantage of this simulation tool.
5. Conclusion
The paper presents lightning stroke simulation, as well as calculation of short circuit
transients along the 110 kV cable-overhead transmission line. Cable and overhead
transmission line has been presented as frequency-dependant model in DIgSILENT and ATP-
EMTP software. Lightning stroke model consisted of direct stroke and returning stroke
components in DIgSILENT results in somewhat different transient shape than in the ATP-
EMPT software where the same model consists only the direct stroke component including
grounding inductances and impulse resistances, as well as tower wave impedances in a few
spans nearby the conjunction point with cables. In both simulation tools, the ZNO surge
arrester has been modeled with related non-linear characteristic. The ATP-EMTP software
provides better and more accurate lightning stroke analysis results.
References
[1] IEC 60909 Standard Short-circuit Currents in Three-phase A.C. Systems - Part 0:
Calculation of Currents, IEC July 2001
[3] ABB document 1HSM 9543 13-01 en Edition Protection Characteristic of Surge
Arrester 110 kV PEXLIM-Q2, ABB, 2004-11
[4] NEXANS High Voltage Cables and Systems Cable data Al 110kV Al-PE sheath
A2XS(FL)2Y+ 1x1000RM/95 64/110 (123) kV, Nexans ref.: C110100095