Вы находитесь на странице: 1из 436

SYSTEM R-J Controller Series

Electrical Connection and


Maintenance Manual
MARMMTRBL02303E

This publication contains proprietary information of FANUC Robotics


North America, Inc. furnished for customer use only. No other uses are
authorized without the express written permission of FANUC Robotics
North America, Inc.
FANUC Robotics North America, Inc.
2000 South Adams Road
Auburn Hills, Michigan 483262800
The descriptions and specifications contained in this manual were in effect
at the time this manual was approved for printing. FANUC Robotics
North America, Inc, hereinafter referred to as FANUC Robotics, reserves
the right to discontinue models at any time or to change specifications or
design without notice and without incurring obligations.
FANUC Robotics manuals present descriptions, specifications, drawings,
schematics, bills of material, parts, connections and/or procedures for
installing, disassembling, connecting, operating and programming FANUC
Robotics products and/or systems. Such systems consist of robots,
extended axes, robot controllers, application software, the KAREL
programming language, INSIGHT vision equipment, and special tools.
FANUC Robotics recommends that only persons who have been trained in
one or more approved FANUC Robotics Training Course(s) be permitted
to install, operate, use, perform procedures on, repair, and/or maintain
FANUC Robotics products and/or systems and their respective
components. Approved training necessitates that the courses selected be
relevant to the type of system installed and application performed at the
customer site.

WARNING
This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in
accordance with the instruction manual, may cause
interference to radio communications. As temporarily
permitted by regulation, it has not been tested for
compliance with the limits for Class A computing devices
pursuant to subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such
interference. Operation of the equipment in a residential
area is likely to cause interference, in which case the user,
at his own expense, will be required to take whatever
measure may be required to correct the interference.

FANUC Robotics conducts courses on its systems and products on a


regularly scheduled basis at the companys world headquarters in Auburn
Hills, Michigan. For additional information contact
FANUC Robotics North America, Inc.
Training and Documentation Department
2000 South Adams Road
Auburn Hills, Michigan 483262800
Tel: (810)3777234
FAX: (810)3777367 or (810)3777362
Copyright 1995, 1996 by FANUC Robotics North America, Inc.
All Rights Reserved

The information illustrated or contained herein is not to be reproduced,


copied, translated into another language, or transmitted in whole or in part
in any way without the prior written consent of FANUC Robotics North
America, Inc.

AccuStat, ArcTool, DispenseTool, FANUC LASER DRILL,


KAREL, INSIGHT, INSIGHT II, PaintTool, PaintWorks,
PalletTool, SOCKETS, SOFT PARTS SpotTool,
TorchMate, and YagTool, are Registered Trademarks of FANUC
Robotics.

FANUC Robotics reserves all proprietary rights, including but not limited
to trademark and trade name rights, in the following names:
AccuFlow
ARC Mate
ARC Mate Sr.
IntelliTrak
LaserTool
MotionParts
PaintWorks II
PalletMate
SureWeld
TurboMove
FANUC Robotics Hotline

For a PRODUCTION robot that is DOWN


call 24 hours a day, 7 days a week
810-377-7159

For all other Troubleshooting and Technical Support


contact your local distributor or call the Hotline
Monday Friday, 8:00 A.M. 5:00 P.M. Eastern Time

BEFORE YOU CALL please have your Maintenance and Troubleshooting manual, and the
following information, ready.

INFORMATION DETAILS
Customer Information Include
 your companys name
 callers name
 phone number where caller can be reached, including
area code and extension
Robot type On the arm of the robot.
(A, L, M, P, or S, & 3-digit number)
Controller style Ask your supervisor.
(RA, RB, RC, RF, RG, RG2, RH, RJ, RJ2)
F Number On the identification tag on the robot and controller, near
the cable connection.
Robot serial number On the identification tag located near the cable connection.
(if no F Number is available)
Controller serial number On the controller tag located on the doors.
(if no F Number is available)
Software edition and revision numbers Shown on the CRT or teach pendant status screen during
the power-up sequence.
List of error messages Include
 error message number
 message following error message number
 any numbers following error message
List of diagnostic LEDs Note the PCB where the LED is located and the LED name
or designation.
History of problem Description of events leading up to the problem.
Application software List
 any application software running the system
 the line number where the program halted
 a description of what is happening on that line
MARMMTRBL02303E Preface vii

Purpose of this Manual The SYSTEM R-J Controller Series Electrical Connection and
Maintenance Manual provides specific information regarding FANUC
Robotics electrical hardware. The information contained within the
manual has been arranged so that it can answer specific questions quickly
and accurately.

How to Use this Use this table to locate specific information in the manual.
Manual
If you want to Refer to

Find information about a specific topic Table of Contents

Identify the components of the SYSTEM R-J Chapter 1, Overview


controller

Use diagnostic and controller initialization Chapter 2, Diagnostic


utilities Screens

View status information on teach pendant Chapter 3, Lights and LEDs


screens and using other indicators

Perform troubleshooting procedures and Chapter 4, Troubleshooting


identify specific errors

Look at fuse information or replace a fuse Chapter 5, Replacing a Fuse

Release the brakes Chapter 6, Brake Release

Turn outputs on or off and simulate inputs Chapter 7, Controlling I/O

Master the robot Chapter 8, Mastering

Replace controller components Chapter 9, Replacing


Components

Adjust switch settings and potentiometers Chapter 10, Board


on printed circuit boards Adjustments

Find controller connection schematics and Chapter 11, Connections


connector configurations

Find connection information and Chapter 12, Complete Wiring


Input/Output specifications Diagrams

Find complete schematics of the controller Chapter 13, Prints


circuitry

Use controller transportation and installation Appendix A, Transportation


information and Installation
viii PREFACE MARMMTRBL02303E

Conventions Used in This manual includes information essential to the safety of personnel,
this Manual equipment, software, and data. This information is indicated by headings
and boxes in the text.

WARNING
Information appearing under WARNING concerns the
protection of personnel. It is boxed and in bold type to set
it apart from other text.

CAUTION
Information appearing under CAUTION concerns the protection
of equipment, software, and data. It is boxed to set it apart
from other text.

NOTE Information appearing next to NOTE concerns related information


or useful hints.
MARMMTRBL02303E Table of Contents ix

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxv

Chapter 1
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 BACKPLANE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.2 MAIN CPU PRINTED CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3 AXIS CONTROL PRINTED CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
1.4 POWER SUPPLY UNIT PRINTED CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
1.5 EMERGENCY STOP CONTROL PRINTED CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . 113
1.6 SERVO AMPLIFIERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
1.7 DCR AND DBR UNIT A05B-2302-C080 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
1.8 DISCHARGE UNIT A05B-2312-C100 FOR M-500 A05B-2313-C100 FOR S-900 . . . . . . . 122
1.9 MULTI-TAP TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
1.10 INTERFACE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
1.10.1 Modular I/O Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
1.10.2 Process I/O Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
1.10.3 ABRIO and Genius I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
1.11 FUSED FLANGE DISCONNECT AND CIRCUIT BREAKER . . . . . . . . . . . . . . . . . . . . . . . 134
1.12 USER TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
1.13 OPERATOR PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
1.14 TEACH PENDANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
1.15 HEAT EXCHANGE AND FANS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

Chapter 2
DIAGNOSTIC SCREENS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.1 SAFETY SIGNAL STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.2 POSITION STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3 ROBOT AXES STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.4 ALARM LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.5 VERSION IDENTIFICATION STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
2.6 MEMORY STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213

Chapter 3
LIGHTS AND LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.1 TEACH PENDANT DIAGNOSTIC LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.2 OPERATOR PANEL DIAGNOSTIC LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3 CIRCUIT BOARD DIAGNOSTIC LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.3.1 Emergency Control Board (EMG) Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
x TABLE OF CONTENTS MARMMTRBL02303E

3.3.2 Power Supply Unit (PSU) Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


3.3.3 Axis Control Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.3.4 Main CPU Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
3.3.5 Servo Amplifier Diagnostic LED (7-Segment Display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
3.3.6 Modular I/O LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
3.3.7 (Optional) Process I/O Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
3.3.8 R-H MAP INTERFACE LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
3.3.9 R-H ABRIO LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317

Chapter 4
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.1 CLASS 1 FAULT TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.2 CLASS 2 FAULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
4.3 CLASS 3 FAULT TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 418
4.3.1 SRVO-001 ER_SVAL1 Operator Panel EStop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
4.3.2 SRVO-002 ER_SVAL1 Teach Pendant Estop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
4.3.3 SRVO-003 ER_SVAL1 Deadman switch released . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
4.3.4 SRVO-004 ER_SVAL1 Fence open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
4.3.5 SRVO-005 ER_SVAL1 Robot Overtravel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428
4.3.6 SRVO-006 ER_SVAL1 Hand Broken . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
4.3.7 SRVO-007 ER_SVAL1 External emergency stops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
4.3.8 SRVO-008 ER_SVAL Brake fuse blown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
4.3.9 SRVO-011 ER_SVAL1 TP Released While Enabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
4.3.10 SRVO-012 ER_SVAL1 Power Failure Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
4.3.11 SRVO-014 Fan Motor Abnormal (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
4.3.12 SRVO-015 ER_SVAL1 System Over Heat (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . 442
4.3.13 SRVO-021 ER_SVAL1 SRDY off (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
4.3.14 SRVO-022 ER_SVAL1 SRDY on (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
4.3.15 SRVO-023 ER_SVAL1 Stop Error Excess (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . 445
4.3.16 SRVO-024 ER_SVAL1 Move Error Excess (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . 445
4.3.17 SRVO-026 ER_WARN Motor Speed Limit (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . 445
4.3.18 SRVO-027 ER_WARN Robot Not Mastered (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . 445
4.3.19 SRVO-033 ER_WARN Robot Not Calibrated (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . 445
4.3.20 SRVO-035 ER_WARN Joint Speed Limit (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . 446
4.3.21 SRVO-036 Imposition Time Over (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
4.3.22 SRVO-037 ER_SVAL1 IMSTP Input (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
4.3.23 SRVO-038 PULSE MISMATCH (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
4.3.24 SRVO-042 ER_SVAL2 MCAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
4.3.25 SRVO-043 ER_SVAL2 DCAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
4.3.26 SRVO-044 ER_SVAL2 HVAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
4.3.27 SRVO-045 ER_SVAL2 HCAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
MARMMTRBL02303E TABLE OF CONTENTS xi

4.3.28 SRVO-046 ER_SVAL2 OVC Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451


4.3.29 SRVO-047 ER_SVAL2 LVAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
4.3.30 SRVO-049 ER_SVAL2 OHAL1 Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . 453
4.3.31 SRVO-050 ER_SVAL1 CLALM Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . 453
4.3.32 SRVO-051 ER_SVAL2 CUER Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
4.3.33 SRVO-061 ER_SVAL2 CKAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
4.3.34 SRVO-062 ER_SVAL2 BZAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
4.3.35 SRVO-063 ER_SVAL2 RCAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
4.3.36 SRVO-064 ER_SVAL2 PHAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
4.3.37 SRVO-065 ER_WARN BLAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
4.3.38 SRVO-066 ER_SVAL2 CSAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
4.3.39 SRVO-067 ER_SVAL2 OHAL2 Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . 457
4.3.40 SRVO-068 ER_SVAL2 DTERR Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . 458
4.3.41 SRVO-069 ER_SVAL2 CRCERR Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . 458
4.3.42 SRVO-070 ER_SVAL2 STBERR Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . 459
4.3.43 SRVO-071 ER_SVAL2 SPHAL Alarm (Group:i Axis:j) . . . . . . . . . . . . . . . . . . . . . . . . . . 459
4.3.44 SRVO-081 ER_WARN EROFL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . 459
4.3.45 SRVO-082 ER_WARN DAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
4.3.46 SRVO-083 ER_WARN CKAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
4.3.47 SRVO-084 ER_WARN BZAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
4.3.48 SRVO-085 ER_WARN RCAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
4.3.49 SRVO-086 ER_WARN PHAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
4.3.50 SRVO-087 ER_WARN BLAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.51 SRVO-088 ER_WARN CSAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.52 SRVO-089 ER_WARN OHAL2 Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.53 SRVO-090 ER_WARN DTERR Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.54 SRVO-091 ER_WARN CRCERR Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.55 SRVO-092 ER_WARN STBERR Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . 461
4.3.56 SRVO-093 ER_WARN SPHAL Alarm (Track encoder:n) . . . . . . . . . . . . . . . . . . . . . . . . . . 461

Chapter 5
REPLACING A FUSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.1 MULTI-TAP TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.2 SERVO AMPLIFIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.3 POWER SUPPLY UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.4 EMERGENCY STOP CONTROL PC BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.5 PROCESS INPUT/OUTPUT PC BOARDS AA, AB, CA, CB, AND DA . . . . . . . . . . . . . . . . 56
5.6 PROCESS INPUT/OUTPUT PC BOARDS BA AND BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.7 MODULAR I/O UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.8 AC OUTLET UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
xii TABLE OF CONTENTS MARMMTRBL02303E

Chapter 6
BRAKE RELEASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Chapter 7
CONTROLLING I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
7.1 FORCING OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.2 SIMULATING INPUTS AND OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.3 SOP I/O STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Chapter 8
MASTERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
8.1 MASTERING TO A FIXTURE (FIXTURE POSITION MASTER) . . . . . . . . . . . . . . . . . . . . . 82
8.2 ZERO DEGREE MASTERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.3 SINGLE AXIS MASTERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
8.4 QUICK MASTERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 811

Chapter 9
REPLACING COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.1 REPLACING THE BATTERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.2 REPLACING A RELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.3 REPLACING A PRINTED CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.3.1 Replacing the Backplane Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.3.2 Replacing a Component on the Backplane Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . 97
9.4 REPLACING A MODULE ON THE MAIN CPU OR AXIS CONTROL BOARD . . . . . . . . . 98
9.5 REPLACING THE PROCESS INPUT/OUTPUT PRINTED CIRCUIT BOARD
AA, AB, BA OR BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 911
9.6 REPLACING COMPONENTS OF THE MODULAR INPUT/OUTPUT UNIT
REFER TO CHAPTER 1 FOR PART NUMBERS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 912
9.6.1 Replacing the Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 912
9.6.2 Replacing a Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914
9.7 REPLACING THE MULTI-TAP TRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916
9.8 REPLACING A SERVO AMPLIFIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 917
9.9 REPLACING THE OPERATOR PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 918
9.10 REPLACING THE FAN MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 919
9.11 REPLACING THE DISCHARGE RESISTOR (DCR) AND DYNAMIC BRAKE (DBR)
UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 921
9.12 REPLACING THE REGENERATIVE DISCHARGE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 923
9.13 REPLACING THE OPTIONAL WARNING LIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 924
9.14 REPLACING A SERIAL PULSE CODER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 925
MARMMTRBL02303E TABLE OF CONTENTS xiii

Chapter 10
BOARD ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.1 AXIS CONTROL BOARD JUMPERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.2 PROCESS I/O BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10.2.1 Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
10.2.2 Potentiometers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
10.2.3 Output Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
10.3 BUILTIN CRT/KB UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
10.4 EMG BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010

Chapter 11
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
11.1 MECHANICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
11.1.1 Robot Connection Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
11.1.2 Connecting the Input Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
11.1.3 Connecting the External Power Supply ON/OFF Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 1110
11.1.4 External Emergency Stop Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111
11.2 PERIPHERAL DEVICE, ARC WELDING, AND END EFFECTOR INTERFACES . . . . . . 1113
11.2.1 Peripheral Device Interface Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1115
11.2.2 Process I/O Printed Circuit Board AA or AB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1116
11.2.3 Process I/O Printed Circuit Board BA or BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1117
11.2.4 Process I/O Printed Circuit Board CA or CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1118
11.2.5 Process I/O Printed Circuit Board DA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
11.2.6 Process I/O Printed Circuit Board with the Modular I/O Unit . . . . . . . . . . . . . . . . . . . . . . . 1120
11.2.7 Two or More Process I/O Boards with the Modular I/O Unit . . . . . . . . . . . . . . . . . . . . . . . . 1121
11.2.8 Peripheral Device and Control Unit Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1122
11.2.9 Mechanical Unit and End Effector Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1139
11.2.10 Control Unit and Welder Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1142
11.2.11 Peripheral Device Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1146
11.2.12 End Effector Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1148
11.2.13 Arc Welding Interface Process I/O AA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1149
11.2.14 Modular I/O Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1151
11.2.15 Modular I/O Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1155
11.3 SPECIFICATIONS OF THE CABLES USED FOR PERIPHERAL DEVICES
AND WELDERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1165
11.3.1 Peripheral Device Interface A Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1165
11.3.2 Peripheral Device Interface B Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1165
11.3.3 Arc Welding Interface Connection Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1166
11.4 CABLE CONNECTION FOR THE PERIPHERAL DEVICES, END EFFECTORS,
AND ARC WELDERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167
11.4.1 Peripheral Device Connection Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167
xiv TABLE OF CONTENTS MARMMTRBL02303E

11.4.2 Arc Welding Interface Connection Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1168


11.4.3 Peripheral Device Cable Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1169
11.4.4 End Effector Cable Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1172
11.4.5 Recommended Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1174

Chapter 12
COMPLETE WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

Chapter 13
PRINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Appendix A
TRANSPORTATION AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
A.1 TRANSPORTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
A.2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
A.2.1 Installation Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
A.2.2 Assembly During Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3
A.2.3 Installation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
A.2.4 Adjustment and Checks at Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A5
A.2.5 Resetting Overtravel and Emergency Stop at Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . A6

List of Procedures
Procedure 21 Displaying Safety Signal Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Procedure 22 Displaying Position Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Procedure 23 Displaying the Axis Status Pulse Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Procedure 24 Displaying the Alarm Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Procedure 25 Displaying the Version Identification Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Procedure 26 Displaying Memory Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Procedure 61 Releasing the Brakes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Procedure 71 Forcing Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Procedure 72 Simulating and Unsimulating Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 74
Procedure 73 Displaying and Forcing SOP I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Procedure 81 Mastering to a Fixture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Procedure 82 Mastering to Zero Degrees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Procedure 83 Mastering a Single Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Procedure 84 Recording the Quick Master Reference Position . . . . . . . . . . . . . . . . . . . . . . . . . . 811
Procedure 85 Quick Mastering the Robot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 813
Procedure 91 Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Procedure 92 Replacing the SPC Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Procedure 93 Replacing the Backplane Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Procedure 94 Replacing a Component on the Backplane Printed Circuit Board . . . . . . . . . . . . 97
MARMMTRBL02303E TABLE OF CONTENTS xv

Procedure 95 Replacing the Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 912


Procedure 96 Replacing the Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914
Procedure 97 Replacing an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914
Procedure 98 Replacing the Multi-Tap Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916
Procedure 99 Replacing a Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 917
Procedure 910 Replacing the Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 918
Procedure 911 Replacing the Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 919
Procedure 912 Replacing the Discharge Resistor (DCR) and Dynamic Brake Resistor (DBR) unit 921
Procedure 913 Replacing the Regenerative Discharge Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 923
Procedure 914 Replacing the Optional Warning Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 924
Procedure 915 Replacing a Serial Pulse Coder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 925

List of Figures
Figure 11. Cabinet Exterior, B-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12. Cabinet Exterior, B-Size Controller with Regenerative Discharge Unit . . . . . . . . . . . 12
Figure 13. Cabinet Exterior, B-Size Controller with Optional Side Cabinet . . . . . . . . . . . . . . . . . 13
Figure 14. Cabinet Exterior, C-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 15. Cabinet Interior, B-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 16. Cabinet Interior, C-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 17. Backplane with R-H Style Extended Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 18. Main CPU Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 19. Axis Control Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Figure 110. Power Supply Unit Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Figure 111. Emergency Stop Control Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Figure 112. Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Figure 113. Mounting Locations of Servo Amplifiers Robot with 6-amplifiers . . . . . . . . . . . . 115
Figure 114. Mounting Locations of Servo Amplifiers for the A-510 . . . . . . . . . . . . . . . . . . . . . . 116
Figure 115. Mounting Locations of Servo Amplifiers for the Arc Mate/ Arc Mate 100/S-6,
Arc Mate Sr./S-5/S-10 and L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Figure 116. Mounting Locations of Servo Amplifiers for the S-500/S-700 and M-400 . . . . . . . . 117
Figure 117. Mounting Locations of Servo Amplifiers for the S-420 and S-800 . . . . . . . . . . . . . . 117
Figure 118. Mounting Locations of Servo Amplifiers for the S-420 and the DCR & DBR Unit . 118
Figure 119. Mounting Locations of Servo Amplifiers for the M-500 . . . . . . . . . . . . . . . . . . . . . . 118
Figure 120. Mounting Locations of Servo Amplifiers for the S-900 . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 121. DCR and DBR Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 122. Discharge Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 123. Multi-Tap Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Figure 124. Multi-Tap Transformer A80L00260013#A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 125. Modular I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Figure 126. Process I/O Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Figure 127. Fused Flange Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Figure 128. Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Figure 129. User Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
xvi TABLE OF CONTENTS MARMMTRBL02303E

Figure 130. Operator Panel, B-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138


Figure 131. Operator Panel, C-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Figure 132. Teach Pendant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Figure 133. Heat Exchange System, B-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Figure 134. Heat Exchange System, C-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Figure 21. Default PowerUp Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 22. Alarm Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 31. Teach Pendant LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 32. Operator Panel LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 33. Circuit Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 34. Emergency Control Board (EMG) Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 35. Power Supply Unit (PSU) Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 36. Axis Control Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 37. Main CPU Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Figure 38. Modular I/O LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Figure 39. Process I/O Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Figure 310. RH MAP LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Figure 311. R-H ABRIO LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Figure 41. 24 Volt (24E) Power Distribution Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410
Figure 42. 24 Volt (24V) Power Distribution Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
Figure 43. Operator Panel E-Stop Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Figure 44. Teach Pendant E-Stop Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Figure 45. Deadman Switch Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Figure 46. Fence Open Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
Figure 47. Robot Overtravel Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
Figure 48. Hand Broken Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
Figure 49. External Emergency Stop Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
Figure 410. Brake Fuse Blown Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Figure 411. Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
Figure 412. System Over Heat Circuitry Drawing 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Figure 413. System Over Heat Circuitry Drawing 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
Figure 51. Replacing a Fuse of the Transformer Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 52. Replacing the Fuse of a Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 53. Replacing a Fuse of the Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 54. Replacing the Fuse on the Emergency Stop Control PC Board . . . . . . . . . . . . . . . . . . 55
Figure 55. Replacing the Fuse of the Process Input/Output PC Board AA, AB, CA, CB, or DA 56
Figure 56. Replacing the Fuse of the Process Input/Output PC Board BA or BB . . . . . . . . . . . . 57
Figure 57. Replacing the Fuse of the AC Outlet Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 91. Replacing the Battery (1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 92. Replacing a Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 93. Replacing the Backplane Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Figure 94. Replacing Printed Circuit Boards on the Backplane Printed Circuit Board . . . . . . . . . 97
MARMMTRBL02303E TABLE OF CONTENTS xvii

Figure 95. Moving the Latches on the End of the Module Socket . . . . . . . . . . . . . . . . . . . . . . . . 98
Figure 96. Installing a New Module at an Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Figure 97. Pushing in the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 98. Mounting Locations of the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 910
Figure 99. Replacing the Process Input/Output Printed Circuit Board AA, AB, BA, or BB . . . . 911
Figure 910. Replacing the Base Unit of the Modular Input/Output Unit . . . . . . . . . . . . . . . . . . . 913
Figure 911. Removing and Replacing a Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 915
Figure 912. Removing and Replacing a Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 915
Figure 913. Replacing the Multi-Tap Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916
Figure 914. Replacing a Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 917
Figure 915. Replacing the Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 918
Figure 916. Replacing the Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 920
Figure 917. Discharge Resistor (DCR) and Dynamic Brake Resistor (DBR) Unit . . . . . . . . . . . . 922
Figure 918. Replacing the Regenerative Discharge Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 923
Figure 919. Removing the Pulse Coder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 926
Figure 101. Axis Control Board Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 102. Process I/O Board AA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Figure 103. Process I/O Board AB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Figure 104. Process I/O Board BA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 105. Process I/O Board BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 106. Process I/O Board CA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Figure 107. Process I/O Board CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Figure 108. Process I/O Board DA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 109. Front View Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 1010. Jumper Setting CRT/KB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 1011. EMG board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010
Figure 111. Block Diagram of Electrical Interface Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Figure 112. Mechanical Connection Diagram for S-420, S-500, S-700, S-800, and M-400 . . . . . 112
Figure 113. Mechanical Connection Diagram for ARC Mate, ARC Mate 100/S-6, ARC Mate Sr.,
A-510, and L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Figure 114. Mechanical Connection Diagram, Common Part . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Figure 115. Connection to Servo Amplifiers and Mechanical Unit for S-420 . . . . . . . . . . . . . . . . 114
Figure 116. Connection to Servo Amplifiers and Mechanical Unit for S-420, S-420D, ARC Mate,
S-5, ARC Mate 100/S-6, ARC Mate Sr., S-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Figure 117. Connection to Servo Amplifiers and Mechanical Unit for S-500 . . . . . . . . . . . . . . . . 115
Figure 118. Connection to Servo Amplifiers and Mechanical Unit for S-700 . . . . . . . . . . . . . . . . 115
Figure 119. Connection to Servo Amplifiers and Mechanical Unit for S-800 . . . . . . . . . . . . . . . . 116
Figure 1110. Connection to Servo Amplifiers and Mechanical Unit for A-510 . . . . . . . . . . . . . . 116
Figure 1111. Connection to Servo Amplifiers and Mechanical Unit for M-400 and M-500 . . . . . 117
Figure 1112. Connection to Servo Amplifiers and Mechanical Unit for L-1000 . . . . . . . . . . . . . 117
Figure 1113. Input Power Supply Connection, Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 1114. Input Power Supply Connection, Fused Flange Disconnect . . . . . . . . . . . . . . . . . . . 119
xviii TABLE OF CONTENTS MARMMTRBL02303E

Figure 1115. External Power Supply ON/OFF Switch Connection . . . . . . . . . . . . . . . . . . . . . . . . 1110


Figure 1116. External Emergency Stop Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111
Figure 1117. External Emergency Stop Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1112
Figure 1118. Locations of Peripheral Device Interfaces, B-Size Controller . . . . . . . . . . . . . . . . . 1113
Figure 1119. Locations of Peripheral Devices, C-Size Controller . . . . . . . . . . . . . . . . . . . . . . . . . 1114
Figure 1120. Peripheral Device Interface Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1115
Figure 1121. Process I/O Printed Circuit Board AA or AB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1116
Figure 1122. Process I/O Printed Circuit Board BA or BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1117
Figure 1123. Process I/O Printed Circuit Board CA or CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1118
Figure 1124. Process I/O Printed Circuit Board DA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
Figure 1125. Process I/O Printed Circuit Board with Modular I/O . . . . . . . . . . . . . . . . . . . . . . . . 1120
Figure 1126. Two or More Process I/O Boards and the I/O Unit (Model A) . . . . . . . . . . . . . . . . 1121
Figure 1127. Peripheral Device and Control Unit Connection -A1/A2 . . . . . . . . . . . . . . . . . . . . . 1125
Figure 1128. Peripheral Device and Control Unit Connection -A3/A4 . . . . . . . . . . . . . . . . . . . . . 1126
Figure 1129. Peripheral Device and Control Unit Connection - B1/B2 . . . . . . . . . . . . . . . . . . . . 1127
Figure 1130. Peripheral Device and Control Unit Connection -C1 . . . . . . . . . . . . . . . . . . . . . . . . 1128
Figure 1131. Peripheral Device Interface Control for A1, A2, A3, and A4 . . . . . . . . . . . . . . . . . 1129
Figure 1132. Peripheral Device Interface for A1, A2, A3, and A4 . . . . . . . . . . . . . . . . . . . . . . . . 1130
Figure 1133. Peripheral Device Control Interface B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1131
Figure 1134. Peripheral Device Control Interface B2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1132
Figure 1135. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1133
Figure 1136. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1134
Figure 1137. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1135
Figure 1138. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1136
Figure 1139. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1137
Figure 1140. Peripheral Device Control Interface C1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1138
Figure 1141. Mechanical Unit and End Effector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1139
Figure 1142. End Effector Pin Configuration Arc Mate/S-5, Arc Mate Sr/S-10, S-420, S-500,
S-700, S-800, S-900, M-400 and M-500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1140
Figure 1143. End Effector Pin Configuration Arc Mate 100/S-6 . . . . . . . . . . . . . . . . . . . . . . . . 1140
Figure 1144. End Effector Pin Configuration A-510 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1141
Figure 1145. End Effector Pin Configuration L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1141
Figure 1146. Control Unit and Welder Connection - CRW1/CRW2 . . . . . . . . . . . . . . . . . . . . . . . 1142
Figure 1147. Control Unit and Welder Connection - CRW1 Analog Signal Assignment . . . . . . . 1143
Figure 1148. Control Unit and Welder Connection - CRW1 Digital Signal Assignment . . . . . . . 1144
Figure 1149. Control Unit and Welder Connection - CRW2 Analog Signal Assignment . . . . . . . 1145
Figure 1150. Peripheral Device Interface A Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1165
Figure 1151. Peripheral Device Interface B Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1165
Figure 1152. Arc Welder Connection Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1166
Figure 1153. Peripheral Device Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167
Figure 1154. Arc Welder Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1168
Figure 1155. Peripheral Device Cable Connector for A and B(Honda Tsushin Kogyo) . . . . . . . . 1169
MARMMTRBL02303E TABLE OF CONTENTS xix

Figure 1156. Peripheral Device Connector for A and B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1170


Figure 1157. Peripheral Device Interface Cable C Connector (Phoenix Contact) . . . . . . . . . . . . 1171
Figure 1158. Elbow Type Connector S-5, S-10, S-420, S-500, S-700, S-800, M-400, M-500,
ARC Mate, ARC Mate 100/S-6, ARC Mate Sr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1172
Figure 1159. Connector L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1173
Figure 121. Internal Connection Diagram S-420, S-800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 122. Internal Connection Diagram S420 with three Servo Amplifiers, S420D) . . . . . . . 123
Figure 123. Internal Connection Diagram ARC Mate, ARC Mate Sr., ARC Mate 100/S-6, S-5,
and S-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Figure 124. Internal Connection Diagram S-500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 125. Internal Connection Diagram S-700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Figure 126. Internal Connection Diagram S900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Figure 127. Internal Connection Diagram A-510 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Figure 128. Internal Connection Diagram M-400 (5-axes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Figure 129. Internal Connection Diagram M400 (4 axes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1210
Figure 1210. Internal Connection Diagram M500 (5 axes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1211
Figure 1211. Internal Connection Diagram M500 (4 axes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1212
Figure 1212. Internal Connection Diagram L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1213
Figure 1213. Internal Connection Diagram Emergency Stop Control PCB . . . . . . . . . . . . . . 1214
Figure 1214. Internal Connection Diagram Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . 1215
Figure 1215. Internal Connection Diagram - Main CPU; Axis Control Board . . . . . . . . . . . . . . . 1216
Figure 1216. Internal Connection Diagram Servo Amplifier Connection S-420, ARC Mate/S-5,
ARC Mate Sr./S-10, ARC Mate 100/S-6, S-500, S-700, and S-800 . . . . . . . . . . . . . . 1217
Figure 1217. Internal Connection Diagram Servo Amplifier Connection A-510, L-1000,
and M-400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1218
Figure 1218. Internal Connection Diagram Servo Amplifier Connection S-900 and M-500 . . . 1219
Figure 1219. Internal Connection Diagram Modular I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1220
Figure 1220. Internal Connection Diagram Teach Pendant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1221
Figure 1221. Internal Connection Diagram Main CPU Interface . . . . . . . . . . . . . . . . . . . . . . . . 1222
Figure 1222. Internal Connection Diagram Axis Control Board Interface . . . . . . . . . . . . . . . . . 1223
Figure 1223. Internal Connection Diagram ARC Mate/S-5, ARC Mate Sr./S-10,
ARC Mate 100/S-6, S-420, S-500 and S-800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1224
Figure 1224. Internal Connection Diagram S-700 and A-510 . . . . . . . . . . . . . . . . . . . . . . . . . . 1225
Figure 1225. Internal Connection Diagram M-400 and L-1000 . . . . . . . . . . . . . . . . . . . . . . . . . 1226
Figure 1226. Internal Connection Diagram - M400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1227
Figure 1227. External Connection Diagram M-500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1228
Figure 1228. External Connection Diagram S-900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1229
Figure 1229. External Connection Diagram Process I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1230
Figure 1230. External Connection Diagram Process I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1231
Figure 1231. External Connection Diagram Teach Pendant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1232
Figure 1232. Motor Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1233
Figure 131. R-J Control Signal and Power Distribution Overview . . . . . . . . . . . . . . . . . . . . . . . . 133
Figure 132. Main AC Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
xx TABLE OF CONTENTS MARMMTRBL02303E

Figure 133. AC Power Distribution With Optional 115VAC Secondary . . . . . . . . . . . . . . . . . . . . 137


Figure 134. Power Supply Unit (PSU) With Power ON/OFF Circuit . . . . . . . . . . . . . . . . . . . . . . 139
Figure 135. EMG Stop & Brake Connection 100 VAC E-Stop Circuit 100 VDC Brake
Circuit (1 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1311
Figure 136. EMG Stop and Brake Connection 100 VDC Brake Circuit (2 of 2) . . . . . . . . . . . . . 1313
Figure 137. EMG Stop and Brake Connection 24 VDC E-Stop Circuit (1 of 2) . . . . . . . . . . . . . 1315
Figure 138. EMG Stop and Brake Connection 24VDC E-Stop Circuit (2 of 2) Modular
I/O Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1317
Figure 139. Overheat and Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1319
Figure 1310. Single Axis Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1321
Figure 1311. Dual Axis Servo Amplifier (With Dynamic Brakes) . . . . . . . . . . . . . . . . . . . . . . . . 1323
Figure 1312. Dual Axis Servo Amplifier (Without Dynamic Brakes) . . . . . . . . . . . . . . . . . . . . . . 1325
Figure 1313. Discharge Resistor and Dynamic Brake Unit (For Amp With No Dynamic Brake) 1327
Figure 1314. LSI Module All Servo Amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1329
Figure 1315. DV-M Module Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1331
Figure 1316. ALM-M Module Servo Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1333
Figure 1317. Teach Pendant Power And Data Signal Interconnection . . . . . . . . . . . . . . . . . . . . . 1335
Figure A1. Transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Figure A2. Installation Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Figure A3. Assembly During Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3
Figure A4. Peripheral Device Interface Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6

List of Tables
Table 11. Main CPU Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Table 12. Axis Control Board Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Table 13. Servo Amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table 14. Multi-Tap Transformer Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Table 15. Selecting Transformer Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Table 16. Selecting Transformer Taps for Transformer A80L00260013#A . . . . . . . . . . . . . . 125
Table 17. Digital Input Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table 18. Digital Output Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table 19. I/O Module Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Table 110. Process I/O Board Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Table 111. Circuit Breaker, B-Size Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Table 112. Circuit Breaker and Fused Flange Disconnect Switch, C-Size Cabinet . . . . . . . . . . 136
Table 113. Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Table 114. Teach Pendant Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Table 21. Safety Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 22. Axis Status Pulse Screen Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 23. Version Identification Status Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Table 24. Memory Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Table 31. Teach Pendant Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
MARMMTRBL02303E TABLE OF CONTENTS xxi

Table 32. Standard Operator Panel C-Size Controller Status Indicators . . . . . . . . . . . . . . . . . . . 33


Table 33. Emergency Control Board (EMG) Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 34. Troubleshooting Axis Control Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . 39
Table 35. Troubleshooting Main CPU Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . 312
Table 36. Servo Amplifier LED Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Table 37. Modular I/O LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Table 38. Process I/O Board Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Table 39. R-H MAP LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Table 310. R-H ABRIO LED Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Table 41. Troubleshooting Procedure 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 42. Troubleshooting Procedure 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 43. Troubleshooting Procedure 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 44. Troubleshooting Procedure 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 45. Troubleshooting Procedure 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Table 46. Troubleshooting Procedure 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Table 47. Class 2 Faults Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
Table 48. SRVO-001 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Table 49. SRVO-002 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
Table 410. SRVO-003 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Table 411. SRVO-004 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
Table 412. SRVO-005 Troubleshooting Procedure 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428
Table 413. SRVO-005 Troubleshooting Procedure 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
Table 414. SRVO-006 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
Table 415. SRVO-007 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
Table 416. SRVO-008 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Table 417. SRVO-014 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Table 418. SRVO-015 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Table 419. SRVO-021 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Table 420. SRVO-022 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Table 421. SRVO-023 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
Table 422. SRVO-036 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
Table 423. SRVO-038 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Table 424. SRVO-042 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Table 425. SRVO-043 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
Table 426. SRVO-044 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Table 427. SRVO-045 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Table 428. SRVO-046 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451
Table 429. SRVO-047 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
Table 430. SRVO-049 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Table 431. SRVO-050 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Table 432. SRVO-051 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
Table 433. SRVO-061 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
xxii TABLE OF CONTENTS MARMMTRBL02303E

Table 434. SRVO-062 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455


Table 435. SRVO-063 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Table 436. SRVO-064 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Table 437. SRVO-065 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Table 438. SRVO-066 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Table 439. SRVO-067 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Table 440. SRVO-068 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Table 441. SRVO-071 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Table 442. SRVO-081 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Table 443. SRVO-082 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
Table 51. Multi-Tap Transformer Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 52. Power supply unit for four-slot backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 53. Power supply unit for six-slot backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 54. Modular I/O Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 71. Standard Operator Panel Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Table 72. Standard Operator Panel Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Table 81. Mastering Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Table 91. Relay Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Table 101. Axis Control Board Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table 102. Process I/O Board Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Table 103. Process I/O Board Potentiometer Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Table 104. Output Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Table 105. SBK Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010
Table 111. Example of Leakage Current Circuit Breaker for Inverters . . . . . . . . . . . . . . . . . . . 118
Table 112. External Emergency Stop Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111
Table 113. External Emergency Stop Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1112
Table 114. Peripheral Device Interface Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1113
Table 115. Process I/O Printed Circuit Board AA or AB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1116
Table 116. Process I/O Printed Circuit Board BA or BB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1117
Table 117. Process I/O Printed Circuit Board CA or CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1118
Table 118. Process I/O Printed Circuit Board DA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
Table 119. Process I/O Printed Circuit Board DA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1120
Table 1110. Two or More Process I/O Boards and the I/O Unit (Model A) . . . . . . . . . . . . . . . . 1121
Table 1111. Process I/O Printed Circuit Board Signals, DI Signals . . . . . . . . . . . . . . . . . . . . . . 1122
Table 1112. Process I/O Printed Circuit Board Signals, DO Signals . . . . . . . . . . . . . . . . . . . . . 1123
Table 1113. Applicable Process I/O Printed Circuit Board - A1/A2 . . . . . . . . . . . . . . . . . . . . . 1125
Table 1114. Applicable Process I/O Printed Circuit Board - A3/A4 . . . . . . . . . . . . . . . . . . . . . 1126
Table 1115. Applicable Process I/O Printed Circuit Board - B1/B2 . . . . . . . . . . . . . . . . . . . . . . 1127
Table 1116. Applicable Process I/O Printed Circuit Board - C1 . . . . . . . . . . . . . . . . . . . . . . . . 1128
Table 1117. Applicable Process I/O Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1142
Table 1118. Peripheral Device Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1146
Table 1119. End Effector Control Interface Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1148
MARMMTRBL02303E TABLE OF CONTENTS xxiii

Table 1120. Arc Welding Interface Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1149


Table 1121. Input Modules AID32A and AID32B, Nonisolated . . . . . . . . . . . . . . . . . . . . . . . 1151
Table 1122. Input Modules AID16C and AID16D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1152
Table 1123. Input Modules AID32E and AID32F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1153
Table 1124. Input Module AIA16G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1154
Table 1125. Output Module AOD32A, Non-isolated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1155
Table 1126. Output Modules AOD08C and AOD08D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1156
Table 1127. Output Modules AOD16C and AOD16D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1157
Table 1128. Output Module AOD32C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1158
Table 1129. Output Module AOD32D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1159
Table 1130. Output Modules AOA05E and AOA08E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1160
Table 1131. Output Module AOA12F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1161
Table 1132. Output Modules AOR08G and AOR16G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1162
Table 1133. Output Module ADA02A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1163
Table 1134. Analog Input Module AAD04A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1164
Table 1135. Peripheral Device Cable Connector for A and B . . . . . . . . . . . . . . . . . . . . . . . . . . 1169
Table 1136. Symbols Used in Figure 1155 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1169
Table 1137. Peripheral Device Cable Connector for A and B . . . . . . . . . . . . . . . . . . . . . . . . . . 1170
Table 1138. Symbols Used in Figure 1156 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1170
Table 1139. Peripheral Device Interface Cable C Connector Specifications . . . . . . . . . . . . . . . 1171
Table 1140. Connection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1171
Table 1141. Recommended Cable for Peripheral Device Connection . . . . . . . . . . . . . . . . . . . . 1174
Table 1142. Recommended Cable for End Effector Connection . . . . . . . . . . . . . . . . . . . . . . . . 1174
Table A1. Installation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
Table A2. Adjustment and Checks at Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A5
SAFETY

Page2
MARMMTRBL02303E Safety xxv

FANUC Robotics is not and does not represent itself as an expert in safety
systems, safety equipment, or the specific safety aspects of your company
and/or its work force. It is the responsibility of the owner, employer, or
user to take all necessary steps to guarantee the safety of all personnel in
the workplace.
The appropriate level of safety for your application and installation can
best be determined by safety system professionals. FANUC Robotics
therefore, recommends that each customer consult with such professionals
in order to provide a workplace that allows for the safe application, use,
and operation of FANUC Robotic systems.
Additionally, as the owner, employer, or user of a robotic system, it is your
responsibility to arrange for the training of the operator of a robot system
to recognize and respond to known hazards associated with your robotic
system and to be aware of the recommended operating procedures for your
particular application and robot installation.
FANUC Robotics therefore, recommends that all personnel who intend to
operate, program, repair, or otherwise use the robotics system be trained in
an approved FANUC Robotics training course and become familiar with
the proper operation of the system. Persons responsible for programming
the systemincluding the design, implementation, and debugging of
application programsmust be familiar with the recommended
programming procedures for your application and robot installation.
The following guidelines are provided to emphasize the importance of
safety in the workplace.
xxvi SAFETY MARMMTRBL02303E

CONSIDERING Safety is essential whenever robots are used. Keep in mind the following
factors with regard to safety:
SAFETY FOR YOUR
 The safety of people and equipment
ROBOT  Use of safety enhancing devices
INSTALLATION  Techniques for safe teaching and manual operation of the robot(s)
 Techniques for safe automatic operation of the robot(s)
 Regular scheduled inspection of the robot and workcell
 Proper maintenance of the robot

Keeping People and The safety of people is always of primary importance in any
Equipment Safe situation. However, equipment must be kept safe, too. When
prioritizing how to apply safety to your robotic system, consider
 People
 External devices
 Robot(s)
 Tooling
 Workpiece

Using Safety Always give appropriate attention to the work area that surrounds the
Enhancing Devices robot. The safety of the work area can be enhanced by the installation of
some or all of the following devices:
 Safety fences, barriers, or chains
 Light curtains
 Interlocks
 Pressure mats
 Floor markings
 Warning lights
 Mechanical stops
 EMERGENCY STOP buttons
 DEADMAN switches

Setting Up a Safe A safe workcell is essential to protect people and equipment. Observe the
Workcell following guidelines to ensure that the workcell is set up safely. These
suggestions are intended to supplement and not replace existing federal,
state, and local laws, regulations, and guidelines that pertain to safety.

 Sponsor your personnel for training in approved FANUC Robotics


training course(s) related to your application. Never permit untrained
personnel to operate the robots.

 Install a lockout device that uses an access code to prevent


unauthorized persons from operating the robot.

 Use antitiedown logic to prevent the operator from bypassing safety


measures.

 Arrange the workcell so the operator faces the workcell and can see
what is going on inside the cell.
MARMMTRBL02303E SAFETY xxvii

 Clearly identify the work envelope of each robot in the system with
floor markings, signs, and special barriers. The work envelope is the
area defined by the maximum motion range of the robot, including any
tooling attached to the wrist flange that extend this range.

 Position all controllers outside the robot work envelope.

 Never rely on software as the primary safety element.

 Mount an adequate number of EMERGENCY STOP buttons or


switches within easy reach of the operator and at critical points inside
and around the outside of the workcell.

 Install flashing lights and/or audible warning devices that activate


whenever the robot is operating, that is, whenever power is applied to
the servo drive system.

 Wherever possible, install safety fences to protect against unauthorized


entry by personnel into the work envelope.

 Install special guarding that prevents the operator from reaching into
restricted areas of the work envelope.

 Use interlocks.

 Use presence or proximity sensing devices such as light curtains, mats,


and capacitance and vision systems to enhance safety.

 Periodically check the safety joints or safety clutches that can be


optionally installed between the robot wrist flange and tooling. If the
tooling strikes an object, these devices dislodge, remove power from
the system, and help to minimize damage to the tooling and robot.

 Make sure all external devices are properly filtered, grounded,


shielded, and suppressed to prevent hazardous motion due to the
effects of electromagnetic interference (EMI), radio frequency
interference (RFI), and electrostatic discharge (ESD).

 Make provisions for power lockout/tagout at the controller.

 Eliminate pinch points. Pinch points are areas where personnel could
get trapped between a moving robot and other equipment.

 Provide enough room inside the workcell to permit personnel to teach


the robot and perform maintenance safely.

 Program the robot to load and unload material safely.

 If high voltage electrostatics are present, be sure to provide appropriate


interlocks, warning, and beacons.

 If materials are being applied at dangerously high pressure, provide


electrical interlocks for lockout of material flow and pressure.
xxviii SAFETY MARMMTRBL02303E

Staying Safe While Advise all personnel who must teach the robot or otherwise manually
Teaching or Manually operate the robot to observe the following rules:
Operating the Robot
 Know whether or not you are using an intrinsically safe teach pendant
if you are working in a hazardous environment.

 Before teaching, visually inspect the robot and work envelope to make
sure that no potentially hazardous conditions exist. The work
envelope is the area defined by the maximum motion range of the
robot. These include tooling attached to the wrist flange that extends
this range.

 The area near the robot must be clean and free of oil, water, or debris.
Immediately report unsafe working conditions to the supervisor or
safety department.

 FANUC Robotics recommends that no one enter the work envelope of


a robot that is on. However, if you must enter the work envelope, be
sure all safeguards are in place, and check the teach pendant
DEADMAN switch for proper operation. Take the teach pendant with
you, turn it on, and be prepared to release the DEADMAN switch.
Only the person with the teach pendant should be in the work
envelope.

 Know the path that can be used to escape from a moving robot; make
sure the escape path is never blocked.

 Isolate the robot from all remote control signals that can cause motion
while data is being taught.

 Test any program being run for the first time in the following manner:

WARNING
Stay outside the robot work envelope whenever a program
is being run. Failure to do so can result in injury.

Using a low motion speed, single step the program for at least one
full cycle.

Using a low motion speed, test run the program continuously for
at least one full cycle.

Using the programmed speed, test run the program continuously


for at least one full cycle.

 Make sure all personnel are outside the work envelope before running
production.
MARMMTRBL02303E SAFETY xxix

Staying Safe During Advise all personnel who operate the robot during production to observe
Production Operation the following rules:

 Know the entire workcell area. The workcell includes the robot and its
work envelope, plus the area occupied by all external devices and
other equipment with which the robot interacts.

 Understand the complete task the robot is programmed to perform


before initiating production operation.

 Make sure all personnel are outside the work envelope before
operating the robot.

 Never enter or allow others to enter the work envelope during


production operation of the robot.

 Know the location and status of all switches, sensors, and control
signals that could cause the robot to move.

 Know where the EMERGENCY STOP buttons are located on both the
robot control and external control devices. Be prepared to press these
buttons in an emergency.

 Never assume that a program is complete if the robot is not moving.


The robot could be waiting for an input signal that will permit it to
continue activity.

 If the robot is running in a pattern, do not assume it will continue to


run in the same pattern.

 Never try to stop the robot, or break its motion, with your body. The
only way to stop robot motion immediately is to press an
EMERGENCY STOP button located on the controller panel, teach
pendant, or emergency stop stations around the workcell.

Staying Safe During When inspecting the robot, be sure to


Inspection
 Turn off power at the controller.

 Lock out and tag out the power source at the controller according to
the policies of your plant.

 Turn off the compressed air source and relieve the air pressure.

 If robot motion is not needed for inspecting the electrical circuits,


press the EMERGENCY STOP button on the operator panel.

 If power is needed to check the robot motion or electrical circuits, be


prepared to press the EMERGENCY STOP button, in an emergency.
xxx SAFETY MARMMTRBL02303E

Staying Safe During When performing maintenance on your robot system, observe the
Maintenance following rules:

 Never enter the work envelope while the robot or a program is in


operation.

 Before entering the work envelope, visually inspect the workcell to


make sure no potentially hazardous conditions exist.

 Consider all or any overlapping work envelopes of adjoining robots


when standing in a work envelope.

 Test the teach pendant for proper operation before entering the work
envelope.

 If it is necessary for you to enter the robot work envelope while power
is turned on, you must be sure that you are in control of the robot. Be
sure to take the teach pendant with you, press the DEADMAN switch,
and turn the teach pendant on. Be prepared to release the DEADMAN
switch to turn off servo power to the robot immediately.

 Whenever possible, perform maintenance with the power turned off.


Before you open the controller front panel or enter the work envelope,
turn off and lock out the 3phase power source at the controller.

WARNING
Lethal voltage is present in the controller WHENEVER IT IS
CONNECTED to a power source. Be extremely careful to
avoid electrical shock.

Turning the disconnect or circuit breaker to the OFF


position removes power from the output side of the device
only. High voltage is always present at the input side
whenever the controller is connected to a power source.

 Release or block all stored energy. Before working on the pneumatic


system, shut off the system air supply and purge the air lines.

 Isolate the robot from all remote control signals. If maintenance must
be done when the power is on, make sure the person inside the work
envelope has sole control of the robot. The teach pendant must be
held by this person.

 Make sure personnel cannot get trapped between the moving robot and
other equipment. Know the path that can be used to escape from a
moving robot. Make sure the escape route is never blocked.

 Use blocks, mechanical stops, and pins to prevent hazardous


movement by the robot. Make sure that such devices do not create
pinch points that could trap personnel.
MARMMTRBL02303E SAFETY xxxi

WARNING
Do not try to remove any mechanical component from the
robot before thoroughly reading and understanding the
procedures in the appropriate manual. Doing so can result
in serious personal injury and component destruction.

 Be aware that when you remove a servomotor or brake, the associated


axis will fall if it is not supported or resting on a hard stop.
 When replacing or installing components, make sure dirt and debris do
not enter the system.
 Use only specified parts for replacement. To avoid fires and damage
to parts in the controller, never use nonspecified fuses.
 Before restarting a robot, make sure no one is inside the work
envelope; be sure that the robot and all external devices are operating
normally.

KEEPING MACHINE Certain programming and mechanical measures are useful in keeping the
machine tools and other external devices safe. These measures are
TOOLS AND outlined below.
EXTERNAL
DEVICES SAFE
Programming Safety Implement the following programming safety measures to prevent damage
Precautions to machine tools and other external devices.
 Backcheck limit switches in the workcell to make sure they do not
fail.
 Implement failure routines in programs that will provide appropriate
robot actions if an external device or another robot in the workcell
fails.
 Use handshaking protocol to synchronize robot and external device
operations.
 Program the robot to check the condition of all external devices during
an operating cycle.

Mechanical Safety Implement the following mechanical safety measures to prevent damage to
Precautions machine tools and other external devices.
 Make sure the workcell is clean and free of oil, water, and debris.
 Use software limits, limit switches, and mechanical hardstops to
prevent undesired movement of the robot into the work area of
machine tools and external devices.
xxxii SAFETY MARMMTRBL02303E

KEEPING THE Observe the following operating and programming guidelines to prevent
damage to the robot.
ROBOT SAFE
The following measures are designed to prevent damage to the robot
Operating Safety during operation.
Precautions  Use a low override speed to increase your control over the robot when
jogging the robot.
 Visualize the movement the robot will make before you press the jog
keys on the teach pendant.
 Make sure the work envelope is clean and free of oil, water, or debris.
 Use circuit breakers to guard against electrical overload.

Programming Safety The following safety measures are designed to prevent damage to the robot
Precautions during programming:
 Establish interference zones to prevent collisions when two or more
robots share a work area.
 Make sure that the program ends with the robot near or at the home
position.
 Be aware of signals or other operations that could trigger operation of
tooling resulting in personal injury or equipment damage.
 In dispensing applications, be aware of all safety guidelines with
respect to the dispensing materials.

NOTE Any deviation from the methods and safety practices described in
this manual must conform to the approved standards of your company. If
you have questions, see your supervisor.
MARMMTRBL02303E SAFETY xxxiii

ADDITIONAL Process technicians are sometimes required to enter the paint booth, for
example, during daily or routine calibration or while teaching new paths to
SAFETY a robot. Maintenance personal also must work inside the paint booth
CONSIDERATIONS periodically.
FOR PAINT ROBOT Whenever personnel are working inside the paint booth, ventilation
INSTALLATIONS equipment must be used. Instruction on the proper use of ventilating
equipment usually is provided by the paint shop supervisor.
Although paint booth hazards have been minimized, potential dangers still
exist. Therefore, todays highly automated paint booth requires that
process and maintenance personnel have full awareness of the system and
its capabilities. They must understand the interaction that occurs between
the vehicle moving along the conveyor and the robot(s), hood/deck and
door opening devices, and highvoltage electrostatic tools.
Paint robots are operated in three modes:
 Teach or manual mode
 Automatic mode, including production and exercise operation
 Diagnostic mode
During both teach and automatic modes, the robots in the paint booth will
follow a predetermined pattern of movements. In teach mode, the process
technician teaches (programs) paint paths using the teach pendant.
In automatic mode, robot operation is initiated at the System Controller
Center (SCC), Manual Control Panel (MCP), if available, or Manual Paint
Station (MPS), if available, and can be monitored from outside the paint
booth. All personnel must remain outside of the booth or in a designated
safe area within the booth whenever automatic mode is initiated at the
SCC, MCP, or MPS.
In automatic mode, the robots will execute the path movements they were
taught during teach mode, but generally at production speeds.
When process and maintenance personnel run diagnostic routines that
require them to remain in the paint booth, they must stay in a designated
safe area.
xxxiv SAFETY MARMMTRBL02303E

Paint System Safety Process technicians and maintenance personnel must become totally
Features familiar with the equipment and its capabilities. To minimize the risk of
injury when working near robots and related equipment, personnel must
comply strictly with the procedures in the manuals.
This section provides information about the safety features that are
included in the paint system and also explains the way the robot interacts
with other equipment in the system.
The paint system includes the following safety features:

 Most paint booths have red warning beacons that illuminate when the
robots are armed and ready to paint. Your booth might have other
kinds of indicators. Learn what these are.

 Some paint booths have a blue beacon that, when illuminated,


indicates that the electrostatic devices are enabled. Your booth might
have other kinds of indicators. Learn what these are.

 EMERGENCY STOP buttons are located on the Manual Control


Panel (MCP), or Manual Paint Station (MPS) panel, if supplied, inside
the booth, or on the System Controller Center (SCC) outside the
booth. Also, EMERGENCY STOP buttons are located near the
interior corners of each booth, and on the robot controller and teach
pendant. Become familiar with the locations of all ESTOP buttons.

 An intrinsically safe teach pendant is used when teaching in hazardous


paint atmospheres.

 A DEADMAN switch is located on each teach pendant. When this


switch is held in, power is applied to the robot servo system. If the
engaged DEADMAN switch is released during robot operation, power
is removed from the servo system, all axis brakes are applied, and the
robot comes to an EMERGENCY STOP. Safety interlocks within the
system might also ESTOP other robots.

WARNING
An EMERGENCY STOP will occur if the DEADMAN switch
is released on a bypassed robot.

 Overtravel by robot axes is prevented by software limits. All of the


major and minor axes are governed by software limits. Limit switches
and hardstops also limit travel by the major axes.
MARMMTRBL02303E SAFETY xxxv

 EMERGENCY STOP limit switches and photoelectric eyes might be


part of your system. Limit switches, located on the entrance/exit doors
of each booth, will EMERGENCY STOP all equipment in the booth if
a door is opened while the system is operating in automatic or manual
mode. For some systems,signals to these switches are bypassed when
the switch on the SCC is in teach mode.

When present, photoelectric eyes are sometimes used to monitor


unauthorized intrusion through the entrance/exit silhouette openings.

 System status is monitored by computer. Severe conditions result in


automatic system shutdown.

Staying Safe While When you work in or near the paint booth, observe the following rules, in
Operating the Paint addition to all rules for safe operation that apply to all robot systems.
Robot
WARNING
Observe all safety rules and guidelines to avoid injury.

WARNING
OPTIONAL SAFETY DEVICE
Your robot may have a red flashing warning light. This is
an optional operator warning. It indicates:
D The robot is powered on
D The robot is armed (servo power on) and can move at
any time.
FANUC Robotics recommends that no one enter the work
envelope of a robot that is on. However, if you must enter
the work envelope, be sure all safeguards are in place, and
check the teach pendant DEADMAN switch for proper
operation. Take the tach pendant with you, turn it on, and
be prepared to release the DEADMAN switch. Only the
person with the teach pendant should be in the work
envelope.

 Know the work area of the entire paint station (workcell).

 Know the work envelope of the robot and hood/deck and door opening
devices.

 Be aware of overlapping work envelopes of adjacent robots.

 Know where all red, mushroomshaped EMERGENCY STOP buttons


are located.

 Know the location and status of all switches, sensors, and/or control
signals that might cause the robot, conveyor, and opening devices to
move.
xxxvi SAFETY MARMMTRBL02303E

 Make sure that the work area near the robot is clean and free of water,
oil, and debris. Report unsafe conditions to your supervisor.

 Become familiar with the complete task the robot will perform
BEFORE starting automatic mode.

 Make sure all personnel are outside the paint booth before turning on
power to the robot servo system.

 Never enter the work envelope or paint booth before turning on power
to the robot servo system.

 Never enter the work envelope during automatic operation unless a


safe area has been designated.

 Never wear watches, rings, neckties, scarves, or loose clothing that


could get caught in moving machinery.

 Remove all metallic objects, such as rings, watches, and belts, before
entering a booth when the electrostatic devices are enabled.

 Stay out of areas where you might get trapped between a moving
robot, conveyor, or opening device and another object.

 Be aware of signals and/or operations that could result in the triggering


of guns or bells.

 Be aware of all safety precautions when dispensing of paint is


required.

 Follow the procedures described in this manual.

Staying Safe During When you perform maintenance on the painter system, observe the
Maintenance following rules, and all other maintenance safety rules that apply to all
robot installations. Only qualified, trained service or maintenance
personnel should perform repair work on a robot.

 Paint robots operate in a potentially explosive environment. Use


caution when working with electric tools.

 When a maintenance technician is repairing or adjusting a robot, the


work area is under the control of that technician. All personnel not
participating in the maintenance must stay out of the area.

 For some maintenance procedures, station a second person at the


control panel within reach of the EMERGENCY STOP button. This
person must understand the robot and associated potential hazards.

 Be sure all covers and inspection plates are in good repair and in place.

 Always return the robot to the home position before you disarm it.
MARMMTRBL02303E SAFETY xxxvii

 Never use machine power to aid in removing any component from the
robot.

 During robot operations, be aware of the robots movements. Excess


vibration, unusual sounds, and so forth, can alert you to potential
problems.

 Whenever possible, turn off the main electrical disconnect before you
clean the robot.
xxxviii SAFETY MARMMTRBL02303E

 When using vinyl resin observe the following:

Wear eye protection and protective gloves during application and


removal

Adequate ventilation is required. Overexposure could cause


drowsiness or skin and eye irritation.

If there is contact with the skin, wash with water.


 When using paint remover observe the following:

Eye protection, protective rubber gloves, boots, and apron are


required during booth cleaning.

Adequate ventilation is required. Overexposure could cause


drowsiness.

If there is contact with the skin or eyes, rinse with water for at
least 15 minutes.
MARMMTRBL02303E 1 OVERVIEW

The SYSTEM R-J Robot and controller consists of software, a robot, and
11

the SYSTEM R-J controller. The application software runs on the R-J
controller and is written to perform a specific task.
The SYSTEM RJ controller contains the computer that operates the
robot. It executes a user-defined program to perform the following
functions:

 Supply drive power to the servomotors of an attached robot and, in


some cases, to motor-driven auxiliary devices to move the robot
through a series of program motions.

 Supply drive power to the servomotors of an attached robot and, in


some cases, to motor-driven auxiliary devices comprising additional
axes, such as door openers, and/or hood/deck openers used in
conjunction with robot programs.

 Send control signals to process devices and other peripheral


equipment.

 Initiate and monitor the purge system of the robot and sometimes
associated opening devices.
The controller consists of modular circuit boards and components housed
in a cabinet. The controller is housed in either a B-size or C-size cabinet.
The controller consists of modular circuit boards and components housed
in a C-size cabinet.
Figure 11, Figure 12, and Figure 13 illustrate an external view of the
B-size cabinet and Figure 14 illustrates an external view of a C-size
cabinet. Figure 15 illustrates an internal view of a B-size cabinet and
Figure 16 illustrates an internal view of a C-size cabinet.
Figure 14 illustrates an external view of a C-size cabinet. Figure 17
illustrates an internal view of a C-size cabinet.
1. OVERVIEW
MARMMTRBL02303E
12

Figure 11. Cabinet Exterior, B-Size Controller















Teach
pendant

Figure 12. Cabinet Exterior, B-Size Controller with Regenerative Discharge Unit

Regenerative
Discharge




Unit










Teach
pendant
1. OVERVIEW

MARMMTRBL02303E 13

Figure 13. Cabinet Exterior, B-Size Controller with Optional Side Cabinet




Optional Side Cabinet









Teach
pendant
1. OVERVIEW
MARMMTRBL02303E
14

Figure 14. Cabinet Exterior, C-Size Controller










Teach
pendant





1. OVERVIEW

MARMMTRBL02303E 15

Figure 15. Cabinet Interior, B-Size Controller

Regenerative discharge unit


Servo amplifier 4 Fan 1
Additional cabinet Servo amplifier 3

Operators panel
Main CPU printed
circuit board
Axis control printed
circuit board
Power supply unit

Printed circuit board for


emergency stop control
Process I/O printed
circuit board or
I/O unit model A

Circuit breaker

Fan 2

Transformer or
Fan 3 Servo amplifier 1 line filter unit
Servo amplifier 2
Servo amplifier 6
Teach pendant
Servo amplifier 5

Fan 4

Fan 5

Components for all models are placed in identical places except for the
servo amplifier. Refer to Section 1.6 for information on the servo
amplifiers locations for different robot models.
1. OVERVIEW
MARMMTRBL02303E
16

Figure 16. Cabinet Interior, C-Size Controller


Operator panel









Modular I/O rack or
Extended Process I/O rack
Back plane

Power disconnect

Servo amplifier #1

Servo amplifier #2 Main CPU


Fuses FL13
Servo amplifier #3
Axis control board
Power supply unit

Servo amplifier #4 and #5 Emergency stop


control board
Servo amplifier #6 Option 1 and 2 slots

User transformer

Multitap transformer
1. OVERVIEW

MARMMTRBL02303E 17

Figure 17. Cabinet Interior, C-Size Controller


Operator panel





Contact Signal
Transducer
STAHL Extended
Servo Amplifiers ISBs Back plane STBI Term Strip
Purge 24V DC
Power Supply

Power disconnect

Main CPU
Fuses FL13
Transit Board Axis control board
Power supply unit

Emergency stop
control board
Option 1 and 2 slots

BDX
ISB Unit
ALC
Relay

SPC Battery
Unit

Multitap transformer

User transformer
1. OVERVIEW
MARMMTRBL02303E
18

1.1 The control unit printed circuit boards are mounted on the backplane
printed circuit board. The backplane provides the bus structure for
BACKPLANE
communication between the various printed circuit boards in the controller.
4-Slot A20B-1004-0420 or A thermostat for sensing the temperature in the controller is mounted on
A20B-2000-0800 the backplane. If the internal temperature exceeds specifications (65C),
the controller will generate a system overheat alarm.
6-Slot A20B-1004-0590 or Two different backplane printed circuit boards are available both for the 4-
A20B-2000-0920 and 6-slot printed circuit board. Either of these printed circuit boards are
interchangeable.

The RH style extended backplane is available for using R-H style printed
R-H Style Extended circuit boards, such as MAP 3.0 and ABRIO. Figure 18 shows the
Backplane backplane with the R-H style extended backplane attached.

A20B-1004-0510
Figure 18. Backplane with R-H Style Extended Backplane
CNBV1

CNBV2

CNB15
CNAV1

CNAV2

CNA15

CNA14

JNAT

NOTE The A20B-2000-0800 and the A20B-2000-0920 printed circuit


boards have an additional connector that is not used in robot applications.
1. OVERVIEW

MARMMTRBL02303E 19

1.2 The main CPU printed circuit board is mounted on the backplane in the
slot marked MAIN. It contains the CPU and the volatile and non-volatile
MAIN CPU PRINTED
memory used by the controller.
CIRCUIT BOARD
The Main CPU printed circuit board also acts as the interface between the
A16B-2200-0840 to controller and the operator and attached devices, through connections to:
A16B-2200-0843  The I/O unit(s)
 The teach pendant
 One or more generalpurpose serial communication ports
 An optional built-in or remote computer terminal (CRT/KB)
 The operator panel lights and pushbuttons
A super capacitor on the Main CPU printed circuit board maintains voltage
to the CMOS RAM for short periods of time (less than an hour) if
removed from the backplane. A connector, BAT-VBAT, is supplied to
connect the battery from the Power Supply Unit to the Main CPU printed
circuit board when the Power Supply Unit or Main CPU is removed from
the controller for an extended period of time. This will supply voltage to
the CMOS memory so the stored data is not lost.
The main CPU consists of a main motherboard with several daughter
modules installed perpendicular to it. The modules are small printed
circuit boards with components surface-mounted on both sides. The
modules are installed in sockets, allowing them to be changed quickly and
easily.
 Flash ROM Module contains System and Application Software.
 CMOS RAM Module stores user programs, system variables, I/O
configuration files, and mastering data.
 SLC2 Module controls I/O communication.
 M32i Module controls communication between the flash ROM,
CMOS, micro processor and boot ROM chip.
 SCC Module controls communication with the operator panel.
 Optional SCC Module communicates with any optional serial ports.
Figure 19 shows the board layout. Table 11 lists the part numbers for
the modules attached on the board.
1. OVERVIEW
MARMMTRBL02303E
110

Figure 19. Main CPU Board Layout

Flash ROM module Optional SCC module

CMOS RAM module (option) SLC2 module

CMOS RAM module (option) M32i module

CMOS RAM module (standard) SCC module


CMOS RAM module (standard)

NOTE Options are shown in phantom print.


1. OVERVIEW

MARMMTRBL02303E 111

Table 11. Main CPU Modules

Name Part Number Remarks


CMOS RAM module A20B-2900-0500, 0501
Flash ROM module A20B-2900-0480, 0482
M32I module A20B-2900-0450 MAIN CPU printed circuit board
SCC module A20B-2900-0430
SLC2 module A20B-2900-0440, 0442
Optional SCC module A20B-2900-0490, 0491, 0492

NOTE CMOS RAM modules are replaced in pairs (two standard modules
or two optional modules).
1. OVERVIEW
MARMMTRBL02303E
112

1.3 The axis control printed circuit board is mounted on the backplane in the
slot marked AXIS. It performs the following functions:
AXIS CONTROL
 Receives command signals from the main CPU board, and receives
PRINTED CIRCUIT axis position and velocity signals from the serial pulse coders.
BOARD  Compares the command signal with the axis position signal and
A16B-2200-0852 to generates pulse-width-modulated axis drive signals. These signals
A16B-2200-0855 switch the drive transistors on the servo amplifiers on and off applying
power to the servo motors.
 Monitors the status of the hand breakage and axis overtravel switches
in the mechanical unit.
 Is the interface for the Robot Input (RI) and Robot Output (RO) I/O
signals.
Figure 110 shows the axis control board layout. Table 12 lists the part
numbers for the modules attached on the board.
Figure 110. Axis Control Board Layout

Servo control module (for axis 9 and 10)


Servo control module (for axis 7 and 8)
Servo control module (for axis 5 and 6)
Servo control module (for axis 3 and 4)
Servo control module (for axis 1 and 2)
Servo interface module (for axis 5 and 6)

Servo interface module (for axis 3 and 4) Servo interface module (for axis 9 and 10)

Servo interface module (for axis 1 and 2) Servo interface module (for axis 7 and 8)

NOTE Options are shown in phantom print.


Table 12. Axis Control Board Modules
Name Part Number Remarks
Servo interface module A20B-2900-0380 Axis control printed circuit board
Servo control module A20B-2900-0160
1. OVERVIEW

MARMMTRBL02303E 113

1.4 The power supply unit printed circuit board is mounted on the backplane
in the slot marked PSU.
POWER SUPPLY UNIT
PRINTED CIRCUIT The power supply unit printed circuit board is supplied with 210 VAC
BOARD from the multi-tap transformer and produces the following DC voltages:
4-Slot Backplane  +24V used
A16B-12120471 For inputs, outputs receivers, drivers, and relays.
6-Slot Backplane
A16B-1212-0531 As the power source for the teach pendant power supply circuitry.
 +15, 15, +5 used for logic circuitry within the controller.
The power supply unit printed circuit board also contains the ON/OFF
logic circuits used by the controller.

CAUTION
The CMOS RAM backup battery is mounted on the power
supply unit printed circuit board. If the board is removed from
the controller for longer than 30 minutes, all software in the
controller might be lost.

Figure 111. Power Supply Unit Printed Circuit Board

PSU PSU

F1 and F2:
Fuses for AC input
F5: 0.3A fuse for 10-A for 6-slot backplane
7.5A for 4-slot backplane
auxiliary
power supply
PIL: green LED
for indicating the AC
Battery cover power supply status
Battery

ALM: Red LED


for indicating
an alarm

F4:5Afuse for +24E

F3: Fuse for +24V


5-A slow blow for
6-slot backplane
3.2A slow blow for
4-slot backplane (with battery cover removed)
1. OVERVIEW
MARMMTRBL02303E
114

1.5 The emergency stop control printed circuit board is mounted on the
backplane in the slot marked EMG. It contains the circuits that:
EMERGENCY STOP
CONTROL PRINTED  Supply 100VAC to the servo amplifiers magnetic control contactors
CIRCUIT BOARD (MCCs) during normal operation.

A16B-1212-0540  Turn off 100VAC for the MCC during fault conditions such as:

A16B-1212-0730  Turn off 100VAC for the MCC during fault conditions such as:
Emergency stop
Axis overtravel
Safety fence open
Teach pendant DEADMAN switch
Hand breakage detection
 Supply power to the motor brakes to release them during normal
operation. Brake power is turned off (applying motor brakes) during
major alarm conditions, or when regulated by the software.

 Supply power to the motor brakes to release them during normal


operation. Brake power is turned off (applying motor brakes) during
major alarm conditions, or when regulated by the software. There is a
second brake circuit that is manually operated by a front panel key
switch. This key switch operated circuit provides a method to move
the robot manually should servo power fail, or when mastering is
required.

 Monitor and control the purge system through a piggy-back style PCB,
purge control A16B16000520. This PCB is mounted internally
within the EMG PCB.

 Supply 24VDC required for SPC encoder operation through the 24 to


5VDC converter unit located within the robot base and switched on
through the purge complete relay contacts of RL-1 for protection from
explosive gases.
Figure 112 shows the emergency stop control printed circuit board
layout.
1. OVERVIEW

MARMMTRBL02303E 115

Figure 112. Emergency Stop Control Printed Circuit Board

EMG
PCB
1. OVERVIEW
MARMMTRBL02303E
116

Figure 113. Emergency Stop Control PC Board

DS2

F1
DS1
F2
RL16 RL1 RL2

FUSE RL4
CRR5

RL3 LED M1

LED M2

RL2 RL1

RL4 TIMER
RL3
RL6
RL5
RL8
RL7

RL9 CRT
CNPG CRX

Purge Control PCB


1. OVERVIEW

MARMMTRBL02303E 117

1.6 The servo amplifiers are mounted on the back wall of the controller. The
servo amplifier amplifies the drive signal from the axis control printed
SERVO AMPLIFIERS
circuit board and supplies it to the servomotor.
Refer to Table 13 for Servo amplifiers are supplied in single, double or triple-axis
part numbers. configurations. Several different models of each configuration are used in
various FANUC robot controllers.

CAUTION
While two servo amplifiers might look identical, they might have
quite different output power capabilities. If you replace a servo
amplifier, make sure that the new unit has the same part
number as the old one. Otherwise, the servo amplifier or
servomotor might be damaged or destroyed.

See Figure 114 for a servo amplifier.

Figure 114. Servo Amplifier

LED
Terminal board T1
Circuit breaker
1. OVERVIEW
MARMMTRBL02303E
118

MCC Coil Each servo amplifier has its own DC power supply, which is supplied
3-phase 210 VAC from the multi-tap transformer. The power lines
supplying the DC power supply are switched on and off by a magnetic
contactor (relay) called the Magnetic Control Contractor (MCC).
The MCC coil is energized by 100 VAC from the emergency stop control
printed circuit board. The MCC coil voltage is turned off during major
fault conditions or when regulated by the software.
When the MCC is turned off, its normally-closed contacts connect the
motor power leads together through low-resistance, high-power resistors,
stopping the motor immediately.

Circuit Breaker The servo amplifier circuitry is protected by a circuit breaker. The reset
lever for the circuit breaker is visible on the front panel of the servo
amplifier. Refer to Section 1.9 for more information on the multi-tap
transformer.
Fault Detection Each servo amplifier has fault detection circuits that detect such conditions
as excessive motor current and servo amplifier power supply failure.
A pair of terminals on the servo amplifier can be connected to a
temperature-sensing switch in the multi-tap transformer. If the switch
opens, the controller will signal a SRVO0043 DCAL alarm.
Servo Amplifier Table 13 lists the servo amplifiers for several FANUC robots.
Configuration Figure 115 shows the mounting locations of the servo amplifiers.
Servo Amplifier Table 13 lists the servo amplifiers for the P-155 robot and optional
Configuration auxiliary devices.. Figure 123 shows the mounting locations of the servo
amplifiers.

Figure 115. Mounting Locations of Servo Amplifiers Robot with 6-amplifiers

SLOT 4 SLOT 5 SLOT 6

SLOT 1 SLOT 2 SLOT 3


1. OVERVIEW

MARMMTRBL02303E 119

Figure 116. Mounting Locations of Servo Amplifiers for the A-510

Figure 117. Mounting Locations of Servo Amplifiers for the Arc Mate/
Arc Mate 100/S-6, Arc Mate Sr./S-5/S-10 and L-1000
1. OVERVIEW
MARMMTRBL02303E
120

Figure 118. Mounting Locations of Servo Amplifiers for the S-500/S-700 and
M-400

Figure 119. Mounting Locations of Servo Amplifiers for the S-420 and S-800
1. OVERVIEW

MARMMTRBL02303E 121

Figure 120. Mounting Locations of Servo Amplifiers for the S-420 and the DCR &
DBR Unit

(S420) With 3 2-Axis Servo Amplifiers; S420D

Figure 121. Mounting Locations of Servo Amplifiers for the M-500


1. OVERVIEW
MARMMTRBL02303E
122

Figure 122. Mounting Locations of Servo Amplifiers for the S-900

Figure 123. Mounting Locations of Servo Amplifiers.

Amp 1 Amp 2 Amp 3


Axis 1 Axis 2 Axis 3
Axis 4 Axis 5 Axis 6

Amp 4 Amp 5
Axis 7 Axis 8
Axis 9
1. OVERVIEW

MARMMTRBL02303E 123

NOTE In Table 13, the part number of the specific amplifier is


A06B-6066-HXXX.

Table 13. Servo Amplifiers


Machine Type Servo Servo Servo Servo Servo Servo
Amplifier 1 Amplifier 2 Amplifier 3 Amplifier 4 Amplifier 5 Amplifier 6
ARC Mate H281 H223 H223
S-5 L;Axis 4/ L;Axis 5/ L;Axis 6/
M;Axis 1 M;Axis 2 M;Axis 3
ARC Mate H234 H224 H223
100/S-6 L;Axis 4/ L;Axis 5/ L;Axis 6/
M;Axis 1 M;Axis 2 M;Axis 3
ARC Mate Sr. H234 H234 H233
S-10 L;Axis 4/ L;Axis 5/ L;Axis 6/
M;Axis 1 M;Axis 2 M;Axis 3
P-155 H235 H235 H235 H005
Axes 1 & 4 Axes 2 & 5 Axes 3 & 6 Axis 7
Door Opener H233
Axes 8 & 9
Hood & Deck H244
Axes 8 & 9
S-420 H011 H006 H006 H244 H004
(with five amplifiers) Axis 1 Axis 2 Axis 3 L;Axis 5/ Axis 6
M;Axis 4
S-420 and S-420D H291 H291 H291 DCR & DBR
(with three 2-axis L;Axis 4/ L;Axis 5/ L;Axis 6/ Unit
amplifiers) M;Axis 1 M;Axis 2 M;Axis 3
S-500 H011 H006 H234 H233
Axis 1 Axis 2 L;Axis 4/ L;Axis 6/
M;Axis 3 M;Axis 5
S700 H012 H006 H234 H233
Axis 1 Axis 2 L;Axis 4/ L;Axis 6/
M;Axis 3 M;Axis 5
S-800 H011 H006 H006 H260 H006
Axis 1 Axis 6 Axis 3 L;Axis 5/ Axis 6
M;Axis 4
S900 H008 H006 H008 H006 H008 H006
Axis 1 Axis 4 Axis 2 Axis 5 Axis 3 Axis 6
M-400 H006 H011 H234 H003
Axis 1 Axis 2 L;Axis 4/ Axis 5
M;Axis 3
M-500 H008 H006 H244 H004
Axis 1 Axis 3 L;Axis 4/ Axis 5
M;Axis 2
A-510 H233 H223
L;Axis 3/ L;Axis 4/
M;Axis 1 M;Axis 2
L-1000 H234 H234 H003
L;Axis 4/ L;Axis 5/ Axis 3
M;Axis 1 M;Axis 2
1. OVERVIEW
MARMMTRBL02303E
124

1.7 The Discharge Resistor (DCR) and Dynamic Brake Resistor (DBR) unit is
used in R-J controllers with three 2-axis amplifiers. It contains the
DCR AND DBR UNIT
dynamic braking resistors and regenerative discharge resistors built into
A05B-2302-C080 the other model servo amplifiers. At the loss of either MCON (Motor
Control Connected) signal from the axis control module to the servo
amplifier, that amplifier turns off the 100C signal to the DBR (Dynamic
Braking) and DCR (Discharge Resistor) unit and its associated MCC.
This turns off the MCC contactor (one for each major and minor axis on
the DBR and DCR unit) for that amplifier, and engages the dynamic
brakes through the normally closed contacts of the corresponding MCC.
At the loss of the 100VAC from the emergency stop circuit, all of the
MCC contactors are turned off, engaging all of the dynamic brakes.
When the MCC deenergizes, it opens its normally open contact, relaying
no interlock (INTL).
The regenerative discharge resistor and its associated thermal switch, for
each amplifier, is mounted to the back of the DBR and DCR unit.
The thermal switches of transformer TF1, is also connected to the DBR
and DCR unit.

Figure 124. DCR and DBR Unit


1. OVERVIEW

MARMMTRBL02303E 125

1.8 A discharge unit, mounted on top of the controller, is used with the M-500
and S-900 robot models. This unit is connected to axis 1 on the M-500
DISCHARGE UNIT
and axes 1, 3, and 5 on the S-900.
A05B-2312-C100 for M-500
A05B-2313-C100 for S-900 The unit consists of low-resistance high-power resistors used to dissipate
the counter electromotive force generated by the servo motors when they
are shut off. Thermo overload switches connected to the overheat
terminals on the servo amplifiers are also in the discharge unit. Fans in the
discharge unit are used to cool the unit.

Figure 125. Discharge Unit


1. OVERVIEW
MARMMTRBL02303E
126

1.9 The multitap transformer is located on the floor of the controller on the
right side.
MULTI-TAP
TRANSFORMER The multi-tap transformer is supplied 3phase AC from the main
disconnect or circuit breaker. This supply voltage can be from 220 575
Refer to Table 14 for part volts. To accommodate the various levels of supply, tap selections are
numbers. provided on the primary side of the transformer.
The transformer supplies the following output voltages:
 3phase 210 VAC for the servo amplifiers
 1phase 210 VAC for the backplanemounted components
 1phase 210 VAC for the IBRC module
 1phase 210 VAC for the 24VDC Purge Power Supply
 1phase 100 VAC for the brakes and servo amplifiermounted MCCs
NOTE Transformer A80L00260013#A also supplies 115VAC for the
user receptacle.

Two seriesconnected thermostats are mounted on the transformer. They


are connected to fault detection circuitry in one servo amplifier. If the
transformer overheats, the controller will signal a SRVO0043 DCAL
alarm.
Figure 126 and Figure 127 show the transformers, and Table 14,
Table 15, and Table 16 lists the information necessary for selecting a
proper primary tap.
Figure 126 shows the transformers, and Table 14, and Table 15 lists
the information necessary for selecting a proper primary tap.
Table 14. Multi-Tap Transformer Part Numbers
Transformer Type Part Number
7.5kVA A80L00260010#A
S-420, S-500, S-800, A80L-0026-0010#A
M-500
ARC Mate Sr., S-700, A80L-0024-0010#A
M-400, L-1000, S-10
ARC Mate, Arc Mate A80L-0022-0007#A
100/S-6, A-510, S-5
S-420 with 3 2-axis A80L-0026-0013#A
Servo Amplifiers; S-420D
S-900 A80L-0026-0010#A Main cabinet
A80L-0024-0011#A Side cabinet
1. OVERVIEW

MARMMTRBL02303E 127

Figure 126. Multi-Tap Transformer


1
575V
2
550V 3
500V 4
480V
5
460V
6
240/415V
7
220V/380V
F4 F5 F1 F2 F3
7.5 7.5
8
0V
9
575V 10
550V 11
500V
12
480V
13
460V
14
A1 A2 240/415V
15
13 23 220V/380V

16
0V
31 1 3 5 41 17
575V 18
550V 19
32 2 4 6 42 500V
20
480V
21
460V
22
14 24 240/415V
23
220V/380V

24
0V

Table 15. Selecting Transformer Taps

Primary Tap
S pply Voltage
Supply Connection Type
L1 L2 L3 Jumper
220 7 15 23 7-24, 15-8, 23-16

240 6 14 22 6-24, 14-8, 22-16
380 7 15 23
415 6 14 22
460 5 13 21
480 4 12 20 8-16-24 Y
500 3 11 19
550 2 10 18
575 1 9 17
1. OVERVIEW
MARMMTRBL02303E
128

Figure 127. Multi-Tap Transformer A80L00260013#A


1
575V
2
480V 3
220V/380V

4
0V
F4 F5 F6 F7 F1 F2 F3
5A 5A
5
575V
6
480V
7
220V/380V

8
TOH2
TOH1
100V
100V

220
115
220

52
51
47
46
44
43
42

A1 A2
41

9
13 23 575V 10
480V
11
220V/380V
31 1 3 5 41

32 2 4 6 42
12
0V
14 24

Table 16. Selecting Transformer Taps for Transformer


A80L00260013#A

Primary Tap
S pply Voltage
Supply Connection Type
L1 L2 L3 Jumper
220 3 7 11 4-7, 8-11, 12-3 
380 3 7 11
480 2 6 10 4, 8, 12 Y
575 1 5 9
1. OVERVIEW

MARMMTRBL02303E 129

1.10 The interface between the controller and peripheral devices is provided by
input and output signals from one or more of the following:
INTERFACE DEVICES
 Modular I/O Unit

 Process I/O printed circuit board

 A printed circuit board specializing in communicating with a logic


controller, which includes
ABRIO for communication to an Allen-Bradley PLC
Genius I/O for communication to a GE Fanuc programmable
controller
 Digital I/O to/from the robot through the axis control board.
1. OVERVIEW
MARMMTRBL02303E
130

1.10.1 The modular I/O unit provides communication between the controller and
Modular I/O Unit various peripheral devices. See Figure 128.
Figure 128. Modular I/O

Interface Module I/O Module

Modular I/O Rack


(Backplane)

Slot 2
Slot 1 I/O Module
Slot I/F

Interface Module

The modular I/O unit uses the following communication modes:


 Discrete (On or Off) input and output signal lines at 24VDC or
120VAC. Outputs can be sink or source outputs.
 Analog signal lines, which can vary from 10VDC to +10VDC
The modular I/O unit consists of the following:
 The base unit
 The interface module
 Various discrete input and output (I/O) modules
The control can use as many as 64 modular I/O modules concatenated
(daisychained) together on multiple racks.
A single modular I/O unit is referred to as rack 1. The I/O modules are
located in slots 1 to 5 or 1 - 10, depending on the model used.

Base Unit The base unit is the backplane for the modular I/O unit. The interface
5 I/O Module Slot module and the I/O modules plug into it.
A03B-0807-C002 The base unit has no LEDs, fuses, or electrical connections, except for the
module sockets.
10 I/O Module Slot
A03B-0807-C001 The first slot to the left (I/F) always contains the interface module. The
other slots are used for the I/O modules.
1. OVERVIEW

MARMMTRBL02303E 131

Interface Module The interface module transfers data between the main CPU and the I/O
With 1 Rack modules.
A03B-0807-C011
The interface module is connected to the JD4 connector on the main CPU
For Additional Rack printed circuit board through connector JD1B. The interface module is
A03B-0807-C012 always mounted in the I/F (first) slot.

Discrete Input Modules Discrete input modules receive 24VDC or 120VAC signals on their
Refer to Table 17 and terminals and relay the data to the interface module.
Table 19 for specifications
and part numbers.
Discrete Output Modules Discrete output modules transmit 24VDC or 120VAC signals on their
Refer to Table 18 and terminals under command of the interface module.
Table 19 for specifications
and part numbers.
1. OVERVIEW
MARMMTRBL02303E
132

Table 17. Digital Input Module Specifications


Module Rated Rated Response External
Input Type Polarity* Points LED Display
Name Voltage Current Time Connection
Non-isolated AID32A 24VDC 7.5 mA Both Maximum 32 Connector No-display
DC input 20 ms
AID32B 24VDC 7.5 mA Both Maximum 32 Connector No-display
2 ms
Optically AID16C 24 VDC 7.5 mA NEG Maximum 16 Terminal block Provided
isolated 20 ms
DC input
inp t AID16D 24VDC 7.5 mA POS Maximum 16 Terminal block Provided
20 ms
AID32E 24VDC 7.5 mA Both Maximum 32 Connector No-display
20 ms
AID32F 24VDC 7.5 mA Both Maximum 32 Connector No-display
2 ms
AC input AIA16G 100~ 10.5 mA ON Max 35 ms 16 Terminal block Provided
120VAC (120VAC) OFF Max 45 ms
* Polarity is defined as follows: Negative: 0 V common (current source type); ON when input is at low level.
Positive: 24 V common (current sink type); ON when input is at high level.

Table 18. Digital Output Module Specifications


Output Module Rated Maximum Points/ External LED
Polarity* Points Fuses
Type Name Voltage Current Common Connection Display
Not fused AOD332A 5~ 0.3A NEG 32 8 Connector Not Not fused
DC output 24 VDC provided
Fused AOD08C 12 ~ 2A NEG 8 8 Terminal block Provided Fused
DC output 24 VDC (Sink)
AOD08D 2A POS 8 8 Terminal block Provided Fused
(Source)
Not-Fused AOD16C 0.5 A NEG 16 8 Terminal block Provided Not fused
DC output (Sink)
AOD16D 0.5 A POS 16 8 Terminal block Provided Not fused
(Source)
AOD32C 0.3 A NEG 32 8 Connector Not Not fused
(Sink) provided

AOD32D 0.3 A POS 32 8 Connector Not Not fused


(Source) provided
AC output AOA05E 100 ~ 2A 5 1 Terminal block Provided Fused
240 VAC
AOA08E 1A 8 4 Terminal block Provided Fused
AOA12F 100 ~ 0.5 A 12 6 Terminal block Provided Fused
120 VAC
Relay AOR08G Maximum 4A 8 1 Terminal block Provided Not fused
output 250 VAC
AOR16G /30 VD 2A 16 4 Terminal block Provided Not fused

* Polarity is defined as follows: Negative:0 V common (current sink type); output is at low level when ON.
Positive: 24 V common (current source type); output is at high level when ON.
1. OVERVIEW

MARMMTRBL02303E 133

Table 19. I/O Module Part Numbers


Name Part Number
DC input Non-isolated 32 points AID32A A03B-0807-C101
module 20 ms
32 points AID32B A03B-0807-C102
2 ms
Optically 16 points AID16C A03B-0807-C103
isolated NEG
16 points AID16D A03B-0807-C104
POS
32 points AID32E A03B-0807-C105
20 ms
32 points AID32F A03B-0807-C106
2 ms
AC input module AIA16G A03B-0807-C107
16 points
DC output Not fused 32 points A0D32A A03B-0807-C162
module NEG
Fused 8 points AOD08C A03B-0807-C151
NEG
8 points AOD08D A03B-0807-C152
POS
Not fused 16 points AOD16C A03B-0807-C153
NEG
16 points AOD16D A03B-0807-C154
POS
32 points AOD32C A03B-0807-C155
NEG
32 points AOD32D AO3B-0807-C156
POS
AC output module 5 points, 2 A AOA05E A03B-0807-C157
8 points AOA08E A03B-0807-C158
1A
12 points AOA12F A03B-0807-C159
0.5 A
Relay output module 8 points AOR08G A03B-0807-C160
4A
16 points AOR16G A03B-0807-C161
2A
Analog input module AAD04A A03B-0807-C051
Analog output module ADA02A A03B-0807-C052
1. OVERVIEW
MARMMTRBL02303E
134

1.10.2 The process I/O printed circuit board provides communication between the
Process I/O Board R-J controller on various peripheral devices.
Refer to Table 110 for The process I/O board uses:
part numbers.
 Discrete input lines - Inputs are 24 volt sensing receivers. Common
voltage can be selected as +24VDC or ground.

 Discrete output lines - Outputs are 24 volt sinking or sourcing


devices.

 Analog input lines - Analog inputs are A D converters sensing an


analog signal 10VDC to 0V or 0V to +10VDC, providing a digital
signal to the processor.

 Analog output lines - Analog outputs are D A converters that


output an analog signal 10VDC to 0V or 0V to +10VDC based on a
command from the processor.

Figure 129. Process I/O Printed Circuit Board


1. OVERVIEW

MARMMTRBL02303E 135

Figure 130. Process I/O Printed Circuit Board

Refer to Chapter 10, Board Adjustments, for the location of the output
drivers.
1. OVERVIEW
MARMMTRBL02303E
136

Table 110. Process I/O Board Part Numbers


Number of I/O
No. Name Part Number Points Remarks
DI DO D/A A/D
1 Process I/O printed circuit board AA A16B-2200-0780 40 40 2 4 Standard (with welding interface)
2 Process I/O printed circuit board AB A16B-2200-0782 40 40 Standard (without welding interface)
3 Process I/O printed circuit board BA A16B-2201-0510 32 32 2 4 Source type DO (with welding
(weld interface) interface)
A20B-2000-0540
4 Process I/O printed circuit board BB A16B-2201-0510 32 32 Source type DO (without welding
interface)
5 Process I/O printed circuit board CA A16B-2201-0470 40 40 2 4 Backplane installation type (with
welding interface)
6 Process I/O printed circuit board CB A16B-2201-0472 40 40 Backplane installation type (without
welding interface)
7 Process I/O printed circuit board DA A16B-2201-0480 96 96 Backplane installation type (without
welding interface)
1. OVERVIEW

MARMMTRBL02303E 137

1.10.3 The ABRIO and Genius I/O printed circuit boards use serial
ABRIO and Genius I/O communication to interface to a programmable controller. These printed
circuit boards are used for communicating control information between the
ABRIO SYSTEM R-J controller and the programmable controller.
R-H style: A16B-2200-0430
(requires R-H adapter Refer to the following manuals for information on these boards.
backplane)  A Users Guide to the FANUC Robotics Remote I/O Interface for an
R-J style: A05B-2300-J120 Allen-Bradley PLC
and A05B-2300-J130  A Users Guide to the FANUC Robotics Genius Network Interface for
(requires R-J six-slot GEFanuc (R-H Style Board in R-J Controller)
backplane)
Genius I/O
A16B-2200-0310 (requires
R-H adapter backplane)
1. OVERVIEW
MARMMTRBL02303E
138

1.11 The SYSTEM R-J controller is supplied with either a fused flange
disconnect or a circuit breaker.
FUSED FLANGE
DISCONNECT AND
CIRCUIT BREAKER

1.12 The SYSTEM R-J controller is supplied with a fused flange disconnect.
FUSED FLANGE
DISCONNECT
Fused Flange Disconnect The fused flange disconnect provides overcurrent protection supply
through three fuses; one for each leg of the 3phase supply. See
Refer to Table 112 for fuse Figure 131.
sizes, current rating, and part
numbers.

Circuit Breaker The circuit breaker provides overcurrent protection to the controller and
the supply. The circuit breaker is available with or without ground fault
protection. See Figure 132.
Refer to Table 111 and The fused flange disconnect and the circuit breaker also provide a means
Table 112 for current rating for shutting off power to the controller and locking the power out.
and part numbers.

WARNING
Lethal voltage is present in the controller WHENEVER IT IS
CONNECTED to a power source. Be extremely careful to
avoid electrical shock.

Turning the disconnect or circuit breaker to the OFF


position removes power from the output side of the device
only. High voltage is always present at the input side
whenever the controller is connected to a power source.

WARNING
Lethal voltage is present in the controller WHENEVER IT IS
CONNECTED to a power source. Be extremely careful to
avoid electrical shock.

Turning the disconnect to the OFF position removes power


from the output side of the device only. High voltage is
always present at the input side whenever the controller is
connected to a power source.
1. OVERVIEW

MARMMTRBL02303E 139

Figure 131. Fused Flange Disconnect

MAIN
DISCONNECT Fuse Block
FL1 FL2 FL3

Figure 132. Circuit Breaker


1. OVERVIEW
MARMMTRBL02303E
140

Table 111. Circuit Breaker, B-Size Cabinet

Input Circuit Breaker Circuit Breaker with Ground


Voltage
g Fault
Current Part Number Current Part Number
220 A60L-0001-0347
50A 30A A60L-0001-0306 #BA
240 #B030S
380
416
460 A60L-0001-0347
30A 20A A60L-0001-0306 #AA
480 #B015S
500
550
575 A60L-0001-0258
15A Not Available
#SA538-15

Table 112. Circuit Breaker and Fused Flange Disconnect Switch, C-Size
Cabinet
Circuit Breaker Circuit Breaker with Ground Fused Flange Disconnect Switch
Input Fault
Voltage Fuse
Current Part Number Current Part Number Part Number
Size
A60L0001-0181 #175
220
50A A60L0001-0308 #F050 50A A60L0001-0306 #DA 5A Fuse A60L0001-0042
240
#JG2-50
380
416
460 A60L0001-0347 A60L0001-0307
30A 30A A60L0001-0181 #175
480 #B030S #B20B3
500 30A Fuse A60L0001-0042
550 #JG1-30
A60L0001-0258
575 20A Not Available
#SA53H-20

Table 113. Fused Flange Disconnect Switch, C-Size Cabinet


Fused Flange Disconnect Switch
Inputt
Inp
Voltage Fuse
Part Number
Size
220 A60L0001-0181 #175
50A
240 Fuse A60L0001-0042 #JG2-50
380
416
460
480 A60L0001-0181 #175
30A
500 Fuse A60L0001-0042 #JG1-30
550
575
1. OVERVIEW

MARMMTRBL02303E 141

1.13 C-size controllers might contain an optional user transformer. It supplies


120VAC single-phase power to a NEMA outlet receptacle. It is located on
USER TRANSFORMER
the lower left side of the controller.

A80L-0001-0520

Figure 133. User Transformer

User Transformer
TF2

1.14 Pushbuttons and LEDs on the Operator Panel are used to control the robot
and to indicate robot status. It might be equipped with one or both of the
OPERATOR PANEL
following:
Refer to Table 112 for part
numbers.
 Remote CRT/KB port for connecting a terminal to the controller.

 DB25 connector for serial interface (external disk drive, for example)

 Disconnectable teach pendant port with a switch so the robot can be


operated without the teach pendant connected.
1. OVERVIEW
MARMMTRBL02303E
142

An emergency stop button on the operator panel places the robot into the
emergency stop condition. The operator panel LED functions are
described in Chapter 3, Lights and LEDs.
Figure 134 shows the operator panel on a B-size controller. Figure 135
shows the operator panel on a C-size controller.
Figure 136 shows the operator panel on a C-size controller.

Figure 134. Operator Panel, B-Size Controller


TEACH PENDANT

BATTERY



ENABLED FAULT ALARM ON




HOUR METER


RS232C CRT/KB FAULT RESET HOLD CYCLE START
OFF




USER LED#1 USER LED#2 REMOTE


EMERGENCY
STOP


USER PB#1 USER PB#2 REMOTE

LOCAL

Figure 135. Operator Panel, C-Size Controller



BATTERY
ALARM


CYCLE START ON



TEACH PENDANT
ENABLED



HOLD OFF

FAULT


FAULT RESET USER LED#1 REMOTE



REMOTE
USER PB#1


LOCAL

USER LED#2


USER PB#2

HOUR METER

RS232C CRT/KB


EMERGENCY STOP


1. OVERVIEW

MARMMTRBL02303E 143

Figure 136. Operator Panel, C-Size Controller


BATTERY
ALARM CYCLE START
ON


TEACH PENDANT


ENABLED
HOLD OFF


FAULT


FAULT RESET


PURGE
COMPLETE REMOTE


PURGE ENABLE REMOTE


LOCAL


PURGE
FAULT


BRAKE ENABLE
ON


HOUR METER
OFF

RS232C CRT/KB TEACH PENDANT


CONNECT/
DISCONNECT Optional


EMERGENCY STOP



Table 114. Part Numbers
Controller Without Disconnectable With Disconnectable Teach
Teach Pendant Pendant
B-Size A05B-2302-C020 A05B-2302-C021
C-size with Built-In A05B-2301-C001 A05B-2301-C003
CRT/KB
C-size with A05B-2301-C002 A05B-2301-C004
Remote CRT/KB

Table 115. Part Numbers


Controller Without Disconnectable With Disconnectable Teach
Teach Pendant Pendant
C-size with Built-In A05B-2308H190 A05B-2308H192
CRT/KB
C-size with A05B-2308H191 A05B-2308H193
Remote CRT/KB
1. OVERVIEW
MARMMTRBL02303E
144

1.15 The teach pendant is a hand held device used for operating and
programming the robot. Keys on the teach pendant are used to enter data,
TEACH PENDANT
jog the robot, and to display menus.
Refer to Table 117 for The pendant has a liquid crystal display 16 lines long by 40 characters
part numbers. wide. The teach pendant also has an emergency stop button that places the
robot into an emergency stop condition.
A deadman switch is mounted on the back of the teach pendant. It must be
held in while the teach pendant is turned on. If it is released while the
teach pendant is turned on, the robot will enter a fault condition similar to
emergency stop.

WARNING
The robot will become fully functional and capable of being
started at the operator panel if the teach pendant is turned
off and the fence circuit is not installed or closed. When
working in the robot envelope, ALWAYS CARRY THE
TEACH PENDANT and ALWAYS HAVE THE TEACH
PENDANT ENABLED.

Seven of the keys on the teach pendant provide different functions


depending on the software in the controller. Eleven LEDs display status of
the system. LEDs are different based on software operating in the
controller. When a nonintrinsic safe teach pendant is used, there are
eleven LEDs that display status of the system. LEDs are different based
on software operating in the controller.
Refer to Chapter 3, Lights and LEDs, for an explanation of the LEDs.
The teach pendant used with the P-155 robot is an Intrinsically Safe
device. It is powered by 8VDC, converted from 24VDC by the Intrinsic
Barrier unit, part number A20B-1005-0240, mounted on the rear of the
enclosure front door.
1. OVERVIEW

MARMMTRBL02303E 145

Figure 137. Teach Pendant

LCD Display

LEDs
Emergency Stop
Button

DEADMAN
Switches

Application-Dependant Keys

Table 116. Teach Pendant Part Numbers


Application Part Number
Intrinsically Safe A05B-2308-H300
NonIntrinsically Safe A05B-2301-H305

CAUTION
The intrinsically safe teach pendant and the non-intrinsically
safe teach pendant are not interchangeable and will damage
the controller, teach pendant cable, and teach pendant if the
incorrect model is attempted to be used.

Teach Pendant Intrinsically The teach pendant Intrinsically Safe Barrier PCB is mounted to the inside
Safe Barrier PCB of the cabinet door. The two main connectors, CRS1 and CRS2 join the
A05B2308C040 intrinsically safe teach pendant with the Main CPU. It is used to ensure
that there not be enough energy to induce a spark within the teach pendant.
This is accomplished by lowering the voltage and limiting current to the
teach pendant through the use of Intrinsically Safe Barriers (refer to
Section 1.19) and opto-isolation chips.

Table 117. Teach Pendant Part Numbers


Application Part Number Comment
Spot Welding A05B-2301-C300 Japanese
Material Handling A05B-2301-C301
Arc Welding A05B-2301-C302
Sealing A05B-2301-C303
General Use A05B-2301-C305
1. OVERVIEW
MARMMTRBL02303E
146

Table 117. (Contd) Teach Pendant Part Numbers


Application Part Number Comment
Spot Welding A05B-2301-C310 English
g
Material Handling A05B-2301-C311
Arc Welding A05B-2301-C312
Sealing A05B-2301-C313
General Use A05B-2301-C315
1. OVERVIEW

MARMMTRBL02303E 147

1.16 The temperature in the controller is kept within operating range through
the use of an air-to-air heat exchange system. The controller is sealed to
HEAT EXCHANGE AND
prohibit outside air from entering. Internal controller air is circulated by
FANS fans around the inside of the controller and downward through the internal
side of the heat exchange unit. Outside air is circulated upward through
Refer to Figure 139 for the external side of the heat exchange unit also by using a fan. This
part numbers process cools the inside air.
Fans are provided on the printed circuit board racks mounted on the
backplane to circulate air over the printed circuit boards.
Cooling fins connected to the servo amplifiers are within the heat
exchange unit to keep the heat generated by the servo power circuits out of
the controller.
Figure 138 shows the heat exchange system for a B-size controller.
Figure 139 shows the heat exchange system for a C-size controller.
Figure 139 shows the heat exchange system for a C-size controller.

Figure 138. Heat Exchange System, B-Size Controller

FAN 1
Fan Unit
A05B-2302-C901
FANS Fan (Alone)
A90L-0001-0219 #A

AIR FLOW
INTERNAL AIR

OUTSIDE AIR

FAN 3 FAN 2
Fan Unit Fan Unit
A05B-2302-C902 A05B-2302-C900
Fan (Alone) Fan (Alone)
A90L-0001-0213 #A OUTSIDE AIR IN A90L-0001-0213 #A
1. OVERVIEW
MARMMTRBL02303E
148

Figure 139. Heat Exchange System, C-Size Controller

Fan (Alone) FAN 1


A90L-0001-0378 Fan Unit
A05B-2301-C901
Fan (Alone)
A90L-0001-0219 #A

AIR FLOW
INTERNAL
AIR
OUTSIDE
AIR
FANS

FAN 2
Fan Unit
A05B-2302-C900
Fan (Alone)
A90L-0001-0213#A

FAN 3 OUTSIDE AIR IN


Fan Unit
A02B0056-C904
Fan Alone
A90L-0001-0219 #A

1.17 The IBRC is an intrinsically safe barrier unit that is used as part of the
purge system required in the P-155 robot. It has ten photo-isolated relays.
PURGE SYSTEM
It provides an intrinsically safe barrier for the following signals:
IBRC
 PS-1 Pressure Switch #1 (used for the robot purge system)
A15200010020  FS1 Flow Switch #1 (used for the robot purge system)
 FS2 Flow Switch #2 (used for opening device purge system)
 ROT/FOT Robot Overtravel Switches (FOT is not applicable)
 PS3 Pressure Switch #3 (used for opening device purge system)
 EOAT 1 & 2 Not presently used
 AUX HBLD Auxiliary Hand Broken (used with Color Trak System)
 HBKD Hand Broken (used when a collision detect device is installed)
 TPCO Teach Pendant Connect/Disconnect (used when a remote
pendant port is installed in the paint booth. Connected to a
connect/disconnect switch mounted on the pendant port)
1. OVERVIEW

MARMMTRBL02303E 149

The IBRC requires 210VAC from a secondary winding of TF1 to operate.


Internal circuitry provides 20VDC to the hazardous side terminals which
are isolated from the safe side terminals and their voltage of 24VDC.
There are ten red LEDs, one for each device used in the field. There are a
pair of terminals, labeled Px and Nx, for each hazardous signal, while the
corresponding safe side terminals have Ax, Bx, and Cx. Cx is the 24VDC
input, and Ax and Bx are the normally open and normally closed contact
outputs respectively. When voltage is being applied to the field switch
device contacts and they are closed, the IBRC LED will be illuminated for
that particular contact. Should a jumper be installed across the P and N
terminals, the LED for those terminals will be illuminated.
With plant air supplied to the robot, and power available to the IBRC
through the disconnect switch in the ON position, PS-1 LED should be
illuminated.

1.18 The Purge Unit Power Supply is a 24VDC auxiliary power supply used
exclusively for the purge system. It is mounted alongside the IBRC unit.
PURGE UNIT POWER
It provides voltage necessary to energize the purge solenoid valve within
SUPPLY the robot and opening devices when applicable. It also provides 24VDC to
A05B2308C040 the relay coils mounted on the piggy-back Purge Control PCB in the EMG
module.
It requires 210VAC supplied by TF1 and is internally fused by two fuses
mounted on the power supply PCB itself, F-11 and F-12.

1.19 The Intrinsically Safety Barriers (ISB) are mounted to the left of the IBRC
unit. They are used in the purge system similar to the IBRC unit, in that
INTRINSICALLY SAFE
they restrict power that may cause a spark. The solenoid of the purge
BARRIERS (STAHL) valve requires 24VDC, and is internally located within the robot cavity.
The internal atmosphere is to be considered hazardous prior to purging,
ISBM890131280XX therefore an Intrinsically SafeBarrier device is used to prevent possible
sparking. Two of these devices will be used if opening devices are also
incorporated with the robot; one for the robot purge solenoid valve, and
the other for the opening device purge solenoid.
They are similar to a fuse. If one should be found defective, it must be
replaced by a known good Intrinsically Safe Barrier, discarding the
defective one.
1. OVERVIEW
MARMMTRBL02303E
150

WARNING
When replacing this Stahl Intrinsically Safe Barrier device, pay
careful attention to exact model or part number. Many models
appear physically identical, but have different power ratings.

Also, careful observance of which end of the device is


considered to be the SAFE side, or the HAZARDOUS side
is critical. Typically the end with the Blue colored cap should
be connected to the device located in the HAZARDOUS zone.

1.20 The Transit Board is a PCB mounted on the internal side of the R-J
controller cabinet, equipped only with connectors and associated cabling
TRANSIT BOARD
that route control signals and data to various locations within the P-155
A05B2308C030 R-J controller. It is a passive device used for interfacing purposes.
MARMMTRBL02303E 2 DIAGNOSTIC SCREENS

21

Various builtin diagnostic screens reveal important information regarding


the status of the SYSTEM R-J Controller. These screens with
explanations of the screen data are presented in this section.

Figure 21. Default PowerUp Screen

UTILITY Hints JOINT 10 %


MENUS Provides a list of all menus.
FCTNS Provides helpful functions.
SELECT, EDIT, DATA, POSN, I/O, STAT
Displays menus with those names.
Function keys with [] show more
choices.
F1 [ TYPE ] function key lists related
screens with a menu.

[ TYPE ] HELP
OFF ON

DATA Key
Examine and change
MENUS Key data register contents
Used to select the
teach pendant menus
EDIT Key
Used to edit a
particular program
SELECT Key
Used to SELECT and
create programs

The UTILITY Hints screen, shown in Figure 21, is the first screen to
appear in the menu structure; this is the starting level to the rest of the
diagnostic screens. Most operations begin by pressing MENUS. The F1,
[TYPE] function key will show submenus within any menu shown on the
screen.
This chapter contains information about the following diagnostic screens:
 Safety signals
 Position display
 Robot Axes motion
 Alarm log
 Version IDs
 Memory
2. DIAGNOSTIC SCREENS

22 MARMMTRBL02303E

2.1 The STATUS Safety signal screen displays the status of safety-related
control signals coming into the controller.
SAFETY SIGNAL
STATUS The safety signal screen displays the current state (TRUE or FALSE) of
each safety signal. You cannot change the condition of the safety signal
using this screen. Table 21 lists and describes each safety signal. Use
Procedure 21 to display safety signal status.

Table 21. Safety Signals

SAFETY
DESCRIPTION
SIGNAL

SOP E-Stop Indicates whether the EMERGENCY STOP button on the operator panel has been pressed. The
status is TRUE if the operator panel EMERGENCY STOP button has been pressed.
TP E-Stop Indicates whether the EMERGENCY STOP button on the teach pendant has been pressed. The
status is TRUE if the teach pendant EMERGENCY STOP button has been pressed.
Ext E-Stop Indicates whether an external emergency exists. The status is TRUE if the external emergency stop
contacts are open on the emergency control PCB (EMG) and the following conditions exist:
 SOP E-STOP is FALSE
 TP E-Stop is FALSE
 Hand Broken is FALSE
 Overtravel is FALSE
If any one of these conditions is TRUE, Ext EStop is displayed as FALSE even though the external
emergency stop switch could be open.
Fence Open Indicates whether the safety fence switch is open. The status is TRUE if the safety fence terminals
are open on the emergency control (EMG) PCB. This does not require the teach pendant to be
enabled.
TP Deadman Indicates when either the left or right teach pendant DEADMAN switch is pressed. The status is
TRUE if either DEADMAN switch is pressed.
TP Enable Indicates whether the teach pendant ON/OFF switch is ON. The status is TRUE when the teach
pendant ON/OFF switch is ON.
Overtravel Indicates whether the robot has moved beyond its overtravel limits. The status is TRUE when the
robot has moved beyond its overtravel limits tripping the overtravel switch.
Low Air Alarm Indicates whether the air pressure has decreased below the acceptable limit. Low Air Alarm is
usually connected to an air pressure sensing device. The status is TRUE when the air pressure is
below the acceptable limit. You must set the $PARAM_GROUP[1].$PPABN_ENBL system variable
to TRUE to use this signal.
2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 23

Procedure 21 Displaying Safety Signal Status

Step 1 Press MENUS.


2 Select STATUS.
3 Press F1, [TYPE].
4 Select Safety Signal. You will see a screen similar to the following.

STATUS Safety JOINT 10 %


SIGNAL NAME STATUS 1/10
1 SOP EStop:
SOP EStop: TRUE
2 TP EStop: FALSE
3 Ext EStop: FALSE
4 Fence Open: FALSE
5 TP Deadman: FALSE
6 TP Enable: FALSE
7 Hand Broken: FALSE
8 Overtravel: FALSE
9 Low Air Alarm FALSE
10 Belt Broken: FALSE

[ TYPE ]
2. DIAGNOSTIC SCREENS

24 MARMMTRBL02303E

2.2 The POSITION screen displays positional information in joint angles or


Cartesian coordinates. The positional information on this screen is
POSITION STATUS
updated continuously when the robot moves. You cannot change the
displayed information using this screen.

NOTE E1, E2, and E3 indicate extended axis positional information if


extended axes are installed in your system.

Joint The joint screen displays positional information in degrees for each robot
axis. Tool indicates the number of the active tool frame.

User The user screen displays positional information in Cartesian coordinates


based on the user frame. Tool indicates the number of the active tool
frame. Frame indicates the number of the active user frame.

World The world screen displays positional information in Cartesian coordinates


based on the world frame. Tool indicates the number of the active tool
frame.
Use Procedure 22 to display position status.
2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 25

Procedure 22 Displaying Position Status

Step 1 Press MENUS.


2 Select POSITION.
3 Select the appropriate coordinate system.
 For joint, press F2, JNT. You will see a screen similar to the
following.

POSITION JOINT 10 %
Joint Tool: 1

J1: .001 J2: 10.028 J3: 35.025


J4: .000 J5: 34.998 J6: .001
E1: .001 E2: .001 E3: .001

[ TYPE ] JNT USER WORLD

NOTE E1: , E1:, and E3 are displayed only if you have extended axes.

 For user, press F3, USER. You will see a screen similar to the
following.

POSITION USER 10 %
User Frame: 0 Tool: 1

Configuration: F, 0, 0, 0
x: 1906.256 y: .041 z: 361.121
w: 178.752 p: 89.963 r: 1.249
E1: .001 E2: .001 E3: .001

[ TYPE ] JNT USER WORLD


2. DIAGNOSTIC SCREENS

26 MARMMTRBL02303E

 For world, press F4, WORLD. You will see a screen similar to
the following.

POSITION WORLD 10 %
World Tool: 1

Configuration: F, 0, 0, 0
x: 1906.256 y: .041 z: 361.121
w: 178.752 p: 89.963 r: 1.249
E1: .001 E2: .001 E3: .001

[ TYPE ] JNT USER WORLD


2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 27

2.3 The robot axes status screen displays information for each robot axis. This
information is continually updated. Use this information when you call
ROBOT AXES STATUS
the FANUC Robotics Hotline if a problem occurs with your robot.
The Axis Status Pulse screen displays information about axis motion.
Table 22 lists and describes each kind of information displayed on this
screen.
Use Procedure 23 to display the axis status pulse screen.

Table 22. Axis Status Pulse Screen Items

ITEM DESCRIPTION

Motion Displays the desired value of the Absolute Pulse Coder (APC) when the robot gets to the position
Command commanded by the controller.
Machine Pulse Shows the actual APC count as read by the controller.
Position Error Displays the difference between the commanded APC count versus the actual APC count.

You cannot change any information on this screen except for the group
number. Group number only applies if you have multiple groups;
otherwise, it remains as 1.

Procedure 23 Displaying the Axis Status Pulse Screen

Step 1 Press MENUS.


2 Select STATUS.
3 Press F1, [TYPE].
4 Select Axis.
5 Display the status screen you want:
 For Pulse, press F4, PULSE.

STATUS JOINT 10 %

GRP [ 1]
Position Machine Motion
J1: Error Pulse Command
J1: 0 00000000 0
J2: 0 00000000 0
J3: 0 00000000 0
J4: 0 00000000 0
J5: 0 00000000 0
J6: 0 00000000 0

[ TYPE ] STATUS1 STATUS2 PULSE GRP# >


2. DIAGNOSTIC SCREENS
MARMMTRBL02303E
28

2.4 The Alarm Log displays a list of the 100 most recent alarms. Figure 22
shows an example of the Alarm Log.
ALARM LOG
Figure 22. Alarm Log
1 SRVO049 OHAL 1 alarm (Group=1 Axis=6)
PROGRAM LINE 4
2 Alarm JOINT 10%
1/100 4
1 SRVO049 OHAL 1 alarm (Group:1 Axis:6)
3 2 SRVO042 MCAL 1 Alarm (Group:1 Axis:6)
3 R E S E T

[ TYPE ] CLEAR HELP

The areas of the Alarm Log are as follows:

1. This is the most recent alarm message. This message will be


displayed in this line regardless of the screen you choose.

2. Indicates the program name and line number of program last having
been acted upon.

3. Lists all of the alarm messages, up to 100, with the most recent alarm
on the top of the list. When the RESET key is pressed, a RESET is
logged on the alarm message screen.

4. Indicates the line number the cursor is on in proportion to how many


lines numbers available.
Use Procedure 24 to display the Alarm Log.
2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 29

Procedure 24 Displaying the Alarm Log

Condition  An error has occurred.


Step 1 Press MENUS.
2 Select ALARM.
3 Press F1, [TYPE].
4 Select Alarm Log. The alarm log will be displayed. This lists all
errors. See the following screen for an example.

SRVO002 Teach pendant emergency stop


TEST1 LINE 15 ABORTED
Alarm WORLD 100 %
1/100
1 SRVO002 Teach pendant emergency sto
2 SRVO001 Operator panel emergency st
3 R E S E T
4 SRVO029 Robot calibrated (Group:1)
5 SRVO001 Operator panel emergency st
6 SRVO012 Power fail recovery
7 INTP127 Power fail detected
8 SRVO047 LVAL alarm (Group:1 Axis:5)
9 SRVO047 LVAL alarm (Group:1 Axis:4)
10 SRVO002 Teach pendant emergency sto

[ TYPE ] CLEAR HELP


The most recent error is number 1.
5 To display the motion log, which lists only motion-related errors,
press F1, [TYPE], and select Motion Log.
6 To display the system log, which displays only system errors, press
F1, [TYPE], and select System Log.
7 To display the application log, which displays only
application-related errors, press F1, [TYPE], and select Appl Log.
8 To display more information about an error, move the cursor to the
error and press F5, HELP. The error help screen displays information
specific to the error you selected. When you are finished viewing the
information, press PREV.
9 To remove all of the error messages displayed on the screen, press
F4, CLEAR.
2. DIAGNOSTIC SCREENS

210 MARMMTRBL02303E

2.5 The STATUS Version IDs screen displays information specific to your
controller. Use this information when you call the FANUC Robotics
VERSION
Hotline if a problem occurs with your controller. You cannot change the
IDENTIFICATION information displayed on this screen. Table 23 lists and describes the
STATUS version identification status information.
Table 23. Version Identification Status Items

VERSION ID ITEM DESCRIPTION

Appl/Tool The name of the application package.


Appl/Tool ID The version number of the application package.
Robot Model The robot model name, the torque on the wrist, and the type of wrist.
S/W Serial Number The software order number for the disk set.
Core Name The name of the core software.
Core ID The version number of the core software.
Library Name The name of the robot library.
Library ID The version number of the robot library.
Servo Code ID The version of servo parameters installed.
Mot Param ID The software version for the software that controls motion
Update #110 The name and software version for which a post-release software update has been
installed.
Build ID Internal software version information.

Use Procedure 25 to display version identification status.


2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 211

Procedure 25 Displaying the Version Identification Status

Step 1 Press MENUS.


2 Select STATUS.
3 Press F1, [TYPE].
4 Select Version ID. You will see a screen similar to the following.

STATUS Version ID JOINT 10 %


ITEM: SOFTWARE:
1 Appl/Tool: Std System Core
2 Appl/Tool ID: V3.06P
3 Robot Name: S500INLN
4 S/W Serial Number: F00000
5 Core Name: Std System Core
6 Core ID: V3.06
7 Library Name: Std Robot Library
8 Library ID: V3.06P
9 Servo Code ID: J03.00
10 Mot Param ID: V1.00
11 Update #1: Uninitialized

20 Update #10: Uninitialized


21 Build ID: V3.06 02/13/9X

[ TYPE ] SOFTWARE MOT_ID MOT_INF SER_PAR

5 Press the key that corresponds to the version ID status screen you want
to display:
 To display software version information, press F2,
SOFTWARE.
 To display motor types for each axis, press F3, MOT_ID. You
will see a screen similar to the following.

STATUS Version IDs JOINT 10 %


GRP: AXIS: MOTOR ID: 1/16
1
1: 1 1 AC20
2: 1 2 AC20F
3: 1 3 AC20F
4: 1 4 AC10
5: 1 5 AC10
6: 1 6 AC10
7: * * Uninitialized
8: * * Uninitialized
9: * * Uninitialized
10: * * Uninitialized

[ TYPE ] SOFTWARE MOT_ID MOT_INF SER_PAR


2. DIAGNOSTIC SCREENS

212 MARMMTRBL02303E

 To display the motor information for each axis, press F4,


MOT_INF. You will see a screen similar to the following.

STATUS Version IDs JOINT 10 %


GRP: AXIS: MOTOR INFO: 1/16
11: 1 1 H1 DSP1L
2: 1 2 H2 DSP1M
3: 1 3 H3 DSP2L
4: 1 4 H4 DSP2M
5: 1 5 H5 DSP3L
6: 1 6 H6 DSP3M
7: * * Uninitialized
8: * * Uninitialized
9: * * Uninitialized
10: * * Uninitialized

[ TYPE ] SOFTWARE MOT_ID MOT_INF SER_PAR

 To display the servo parameters for each axis, press F5,


SER_PAR. You will see a screen similar to the following.

STATUS Version IDs JOINT 10 %


GRP: AXIS: SERVO PARAM ID: 1/16
1
1: 1 1 PO1.00
2: 1 2 PO1.00
3: 1 3 PO1.00
4: 1 4 P01.00
5: 1 5 PO1.00
6: 1 6 P01.00
7: * * Uninitialized
8: * * Uninitialized
9: * * Uninitialized
10: * * Uninitialized

[ TYPE ] SOFTWARE MOT_ID MOT_INF SER_PAR


2. DIAGNOSTIC SCREENS

MARMMTRBL02303E 213

2.6 The STATUS Memory screen displays information about controller


memory. Table 24 lists and describes each memory status item. Use
MEMORY STATUS
Procedure 26 to display memory status.

Table 24. Memory Status

MEMORY STATUS DESCRIPTION

User Indicates the amount of memory for user programs: teach pendant programs and KAREL
programs.
 Total indicates the original size of the memory area.
 Free indicates how much memory is available.
 Largest Free indicates the largest contiguous segment of available memory.

System Indicates the amount of memory for system information: FDICT (dictionary files that
define what is displayed on the screens), F-PROG (application, operating system, and
option files), and C-WORK (temporary memory used for system operations).
 Total indicates the original size of the memory area.
 Free indicates how much memory is available.
 Largest Free indicates the largest contiguous segment.

Hardware Indicates the total amount of memory in FROM and CMOS RAM.

Procedure 26 Displaying Memory Status

Step 1 Press MENUS.


2 Select STATUS.
3 Press F1, [TYPE].
4 Select Memory. You will see a screen similar to the following.

STATUS Memory JOINT 100 %


USER TOTAL FREE LRGST FREE
KAREL 2921.0KB 2062.0KB 1939.9KB
TPE 150.0KB 71.2KB 70.1KB
SYSTEM
F-DICT 320.0KB 18.2KB 18.2KB
FPROG 512.0KB 91.3KB 91.3KB
CWORK 1023.9KB 552.8KB 547.6KB
HARDWARE
FROM 2.0MB
CMOS 4.0MB
[ TYPE ]
MARMMTRBL02303E 3 LIGHTS AND LEDS

31

This chapter describes the lights and LEDs you can use for diagnostics:
 Teach pendant LEDs
 Operator panel LEDs
 Circuit board diagnostic LEDs
3. LIGHTS AND LEDS
MARMMTRBL02303E
32

3.1 The non-intrinsically safe teach pendant has several LEDs to assist you in
determining the status of the controller. Figure 31 shows the teach
TEACH PENDANT
pendant LEDs. Table 31 lists and describes the teach pendant LEDs.
DIAGNOSTIC LEDS The LEDs whose labels are blank vary depending on the particular
application.
On the Intrinsically Safe Teach Pendant, these LEDs are simulated by
symbols on the teach pendant display.
Refer to the Setup and Operations Manual for your application for
information on application-specific LEDs.

Figure 31. Teach Pendant LEDs


FAULT


HOLD


STEP
BUSY


RUNNING
Application-


Specific


LEDs
JOINT


OFF
XYZ
TOOL
ON

Table 31. Teach Pendant Status Indicators

INDICATOR DESCRIPTION

FAULT Indicates that a fault condition has occurred.


HOLD Indicates that the robot is in a hold condition. HOLD is not on continuously during a hold condition.
STEP Indicates that the robot is in step mode.
BUSY Indicates that the controller is processing information.
RUNNING Indicates that a program is being executed.
JOINT Indicates that the current jog coordinate system is JOINT.
XYZ Indicates that the current jog coordinate system is WORLDFRAME, JOGFRAME, or USERFRAME.
XYZ Indicates that the current jog coordinate system is JOG frame or WORLD.
TOOL Indicates that the current jog coordinate system is TOOL.
3. LIGHTS AND LEDS

MARMMTRBL02303E 33

3.2 The operator panel has several LEDs to assist you in determining the
status of the controller. Figure 32 shows the operator panel LEDs.
OPERATOR PANEL
Table 32 lists and describes the operator panel LEDs.
DIAGNOSTIC LEDS
Figure 32. Operator Panel LEDS


BATTERY
ALARM
CYCLE START ON


TEACH PENDANT


ENABLED


HOLD OFF
FAULT


FAULT RESET



USER LED#1 REMOTE


USER PB#1 REMOTE


LOCAL


USER LED#2


USER PB#2

HOUR METER

RS232C CRT/KB


EMERGENCY STOP



3. LIGHTS AND LEDS
MARMMTRBL02303E
34

Figure 33. Operator Panel LEDS

BATTERY


ALARM CYCLE START
ON


TEACH PENDANT


ENABLED
HOLD OFF


FAULT



PURGE
FAULT RESET COMPLETE REMOTE




PURGE ENABLE REMOTE


LOCAL

PURGE


FAULT


BRAKE ENABLE
ON

HOUR METER
OFF

RS232C CRT/KB TEACH PENDANT


CONNECT/
DISCONNECT Optional


EMERGENCY STOP



Table 32. Standard Operator Panel C-Size Controller Status Indicators
INDICATOR DESCRIPTION
BATTERY ALARM Indicates that the backup battery voltage is low. Replace the battery, using
Procedure 9-1.
TEACH PENDANT ENABLED Indicates that the teach pendant is enabled and has motion control.
FAULT Indicates a fault condition has occurred.
REMOTE Indicates that robot motion can only be started by a PLC or other remote device. The
operator panel cycle start pushbutton cannot cause robot motion. This is determined
by the position of the REMOTE/LOCAL keyswitch.
USER LED #1 User-defined and accessible from a KAREL program or macros.
USER LED #2 User-defined and accessible from a KAREL program or macros.
PURGE COMPLETE Identifies that the robot cavities have been purged and are presently at the prescribed
pressure as outlined in the P-155 Mechanical Service Manual.
This LED must be illuminated in order to turn power on to the R-J controller.
PURGE FAULT Indicates a fault exists with the purge system.
PURGE ENABLE PUSHBUTTON Indicates that the purge cycle has started. You can now release the pushbutton if you
are holding it.
POWER ON PUSHBUTTON LED Indicates that the robot is powered on.
CYCLE START PUSHBUTTON LED Indicates that the robot is currently running a program
HOLD Indicates that the robot is in a software hold condition.
3. LIGHTS AND LEDS

MARMMTRBL02303E 35

3.3 The RJ Controller contains several diagnostic LEDs within the controller.
They are on the circuit boards that plug into the backplane, on the servo
CIRCUIT BOARD
amplifiers, and on the modular I/O unit. Figure 34 shows an overview of
DIAGNOSTIC LEDS the circuit board diagnostic LEDs. Refer to the sections that follow for
descriptions of the following circuit board diagnostic LEDs:
 Emergency control board (EMG)
 Power supply unit (PSU)
 Axis control board
 Main CPU board
 Servo amplifier
 Contact signal transducer (IBRC)
 Modular I/O (optional)
 Process I/O board (optional)
 RH MAP Interface (optional)
 ABRIO printed circuit board (optional)
3. LIGHTS AND LEDS
MARMMTRBL02303E
36

Figure 34. Circuit Board Diagnostic LEDs

OPTIONAL OPTIONAL I/O


INTERFACE MODULE LEDS
MODULE LEDS Section 3.3.7
Section 3.3.7

OPTIONAL AXIS
PROCESS I/O MAIN CPU PSU BOARD EMG BOARD
CONTROL
BOARD LEDS BOARD LEDS LEDS LEDS
BOARD LEDS
Section 3.3.8 Section 3.3.4 Section 3.3.2 Section 3.3.1
Section 3.3.3

SERVO
AMPLIFIER
DIAGNOSTIC
LED (7SEG)
Section 3.3.5
3. LIGHTS AND LEDS

MARMMTRBL02303E 37

Figure 35. Circuit Board Diagnostic LEDs

INTERFACE
MODULE LEDS
Section 3.3.7 IBRC LEDS

I/O
MODULE LEDS
Section 3.3.7

OPTIONAL AXIS
KRIO/GEF/MAP MAIN CPU PSU BOARD EMG BOARD
CONTROL
MODULES BOARD LEDS LEDS LEDS
BOARD LEDS
Sections 3.3.10 Section 3.3.4 Section 3.3.2 Section 3.3.1
Section 3.3.3
and 3.3.11

SERVO
AMPLIFIER
DIAGNOSTIC
LED (7SEG)
Section 3.3.5
3. LIGHTS AND LEDS
MARMMTRBL02303E
38

3.3.1 Figure 37 shows the emergency control board (EMG) diagnostic LEDs.
Emergency Control Table 34 lists and describes each LED.
Figure 36. Emergency Control Board (EMG) Diagnostic LEDs
Board (EMG)
Diagnostic LEDs

SON BRKL

BRK1 BRK4

BRK2 BRK5

BRK3 BRK6

FALM
3. LIGHTS AND LEDS

MARMMTRBL02303E 39

Figure 37. Emergency Control Board (EMG) Diagnostic LEDs

BRK4 NOT USED

BRK5 BRK6

FALM

BRK1 SON

BRK2 BRK3

Table 33. Emergency Control Board (EMG) Diagnostic LEDs


LED Name Description
SON Servo on When this LED lights, 100 VAC is supplied to the
(Green) servo amplifier MCC coils.
BRK 1* Brake Circuit 1 When this LED lights, axis 1 brake is energized.
(Green) Release
BRK2* Brake Circuit 2 When this LED lights, axis 2 and 3 brakes are
(Green) Release energized.
BRK3* Brake Circuit 3 When this LED lights, axis 4, 5, and 6 brakes are
(Green) Release energized.
FALM Fuse alarm of This LED lights if the brake-fuse is blown or a
(red) the brake circuit voltage spike has occurred. Refer to Servo Alarm
SRVO-008.
BRK4* Brake Circuit 4 When this LED lights, auxiliary axis are energized.
(Green) Release
BRK5* Brake Circuit 5 When this LED lights, auxiliary axis are energized.
(Green) Release
3. LIGHTS AND LEDS
MARMMTRBL02303E
310

Table 33. (Contd) Emergency Control Board (EMG) Diagnostic LEDs


LED Name Description
BRK6* Brake Circuit 6 When this LED lights, auxiliary axis are energized.
(Green) Release
BRKL Manual Brake Brakes are released by the front panel keyswitch
Release
Table 34. Emergency Control Board (EMG) Diagnostic LEDs
LED Name Description
SON Servo on When this LED lights, 100 VAC is supplied to the
(Green) servo amplifier MCC coils.
BRK 1* Brake Circuit 1 When this LED lights, brake circuit 1 is energized.
(Green) Release
BRK2* Brake Circuit 2 When this LED lights, brake circuit 2 is energized.
(Green) Release
BRK3* Brake Circuit 3 When this LED lights, brake circuit 3 is energized.
(Green) Release
FALM Fuse alarm of This LED lights if the 100 VAC brake-fuse is blown
(red) the brake circuit or a voltage spike has occurred. Refer to Servo
Alarm SRVO-008.
BRK4* Brake Circuit 4 When this LED lights, brake circuit 4 is energized.
(Green) Release
BRK5* Brake Circuit 5 When this LED lights, brake circuit 5 is energized.
(Green) Release
BRK6* Brake Circuit 6 When this LED lights, brake circuit 6 are energized.
(Green) Release
* Refer to robot-specific electrical maintenance for brake connections.
3. LIGHTS AND LEDS

MARMMTRBL02303E 311

3.3.2 Figure 38 shows each power supply unit (PSU) diagnostic LED.
Power Supply Unit
Figure 38. Power Supply Unit (PSU) Diagnostic LEDs
(PSU) Diagnostic LEDs
PSU

Power Input LED (PIL) LED


This LED lights if 200 VAC is being supplied to the PSU
from Transformer TF1 (Main disconnect is on), if fuses
F1, F2, or F5 (on circuit board) are not blown, and the
power supply internal circuitry is okay.

ALM (Fuse Alarm) LED


This LED will light if fuse F3 is blown and/or there
are any DC power circuit malfunctions.
3. LIGHTS AND LEDS
MARMMTRBL02303E
312

3.3.3 The four green status LEDs will also light on the axis control printed
Axis Control Board circuit board at power on and then change during software initialization.
See Figure 39.
Diagnostic LEDs
Figure 39. Axis Control Board Diagnostic LEDs

1 2 3 4
STATUS
ALARM

Table 35 contains supplementary troubleshooting information.


3. LIGHTS AND LEDS

MARMMTRBL02303E 313

Table 35. Troubleshooting Axis Control Board Diagnostic LEDs


LEDs Remarks Procedure
1 2 3 4 Normally, all four green LEDs 1. Replace the axis control board.
STATUS come on when the robot is
ALARM 2. Test FROM* and CMOS from the BMON screen and
turned on. They then turn off
replace as necessary.
and come back on as software
loads and circuits are tested. 3. Reload software if a defective FROM or CMOS is found,
This procedure should only be otherwise replace the main CPU and then reload
used when the four LEDs software.
come on and stay on without
turning off or FLASH.
1 2 3 4 Lights go out and initialization 1. Check the power supply output voltages. Replace if
STATUS of each printed circuit board necessary.
ALARM begins.
2. Replace the axis control board.
3. Test FROM* and CMOS from the BMON screen and
replace as necessary.
4. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Timer initialization 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of communication 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Replace the axis control printed circuit board.
STATUS
ALARM
3. LIGHTS AND LEDS
MARMMTRBL02303E
314

Table 35. (Contd) Troubleshooting Axis Control Board Diagnostic LEDs


LEDs Remarks Procedure
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Communication to teach 1. Replace the teach pendant.
STATUS pendant
ALARM 2. Replace the teach pendant cable.
3. Replace the main CPU.
4. Reload software.
1 2 3 4 Communication to process I/O Turn off controller power. Disconnect the cable from
STATUS or modular I/O connector JD4 of the main CPU and cold start the controller.
ALARM If the light pattern is normal, replace the device that the cable
connects to: process I/O module or modular I/O interface unit.
Otherwise:
1. Replace the I/O connection cable.
2. Replace the main CPU.
3. Reload software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Initialization of software 1. Test FROM* and CMOS from the BMON screen and
STATUS replace as necessary.
ALARM
2. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Teach pendant banner page 1. Replace the teach pendant.
STATUS displayed
ALARM
1 2 3 4 Initialization of software 1. Replace the axis control board.
STATUS
ALARM 2. Test FROM* and CMOS from the BMON screen and
replace as necessary.
3. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.
1 2 3 4 Robot is working fine
STATUS
ALARM
3. LIGHTS AND LEDS

MARMMTRBL02303E 315

Table 35. (Contd) Troubleshooting Axis Control Board Diagnostic LEDs


LEDs Remarks Procedure
1 2 3 4 Servo alarm on Axis Control 1. Replace the Axis Control printed circuit board.
STATUS printed circuit board.
ALARM
1 2 3 4 (SYSFAIL) 1. If the controller has an ABRIO board or a MAP board,
STATUS Voltage level too low on *EN turn off controller power. Remove the two boards and
ALARM signal cold start the controller. If the light pattern is normal,
replace the ABRIO or MAP board device that the cable
connects to: process I/O module or modular I/O
interface unit.
2. Check the power supply output voltages. Replace if
necessary.
3. Replace the axis control board.
4. Test FROM* and CMOS from the BMON screen and
replace as necessary.
5. Reload software if a defective FROM or CMOS is found,
otherwise replace the main CPU and then reload
software.

* The Flash ROM test checks for cleared FROM. If you test FROM you must first
clear the FROM.

NOTE 1: After replacing the main CPU printed circuit board, CMOS RAM modules,
or FROM module, you must perform a complete software load.
NOTE 2: If Axis Control alarm LEDs occur with LEDs on the Main CPU,
troubleshoot the Main CPU alarm LEDs first.

CAUTION
While working with the power supply unit, Main CPU, and axis
control modules, be advised of the following:
 There are static-sensitive devices on the Main CPU and
axis control modules. Wear a grounded wrist strap devices
and observe anti-static safety precautions when handling
this equipment.
 When removing the power supply unit or main CPU, the
battery backup is disconnected and must be reconnected
within 30 minutes or a loss of memory will occur.
3. LIGHTS AND LEDS
MARMMTRBL02303E
316

3.3.4 The Main CPU printed circuit board alarm LEDs are shown in
Main CPU Board Figure 310. Table 36 provides supplementary troubleshooting
information.
Diagnostic LEDs
Figure 310. Main CPU Board Diagnostic LEDs

1 2 3 4
STATUS
ALARM

Table 36. Troubleshooting Main CPU Board Diagnostic LEDs


LEDs Remarks Procedure
1 2 3 4 Parity alarm on CMOS 1. Test CMOS from the BMON screen and replace as necessary.
STATUS RAM in the Main CPU.
ALARM 2. Reload software.
3. Replace the main CPU.
1 2 3 4 The battery voltage that Replace the battery, using Procedure 91.
STATUS backs up the MAIN CPU
ALARM CMOS RAM memory is
low.
1 2 3 4 An error is encountered Turn off the controller. Disconnect the cable from connector JD4 of the
STATUS in the serial link. main CPU and cold start the controller. If the light pattern is normal,
ALARM replace the device that the cable connects to: process I/O module or
modular I/O interface unit.
Otherwise:
1. Test FROM and CMOS from the BMON screen and replace as
necessary.
2. Reload software.
3. Replace the main CPU.
1 2 3 4 Normal status Controller should be operational.
STATUS
ALARM
3. LIGHTS AND LEDS

MARMMTRBL02303E 317

3.3.5 Table 37 shows and describes each servo amplifier diagnostic LED.
Servo Amplifier
Diagnostic LED
(7-Segment Display)
Table 37. Servo Amplifier LED Functions
Name Indication Description
Overvoltage(HV) An abnormally high DC voltage was detected in the power supply of the main circuit
of the servo amplifier.

Refer to Error code: SRVO-044 for troubleshooting information.


Insufficient voltage of the An abnormally low voltage was detected in the control power supply of the servo
control power supply amplifier. (Rating: +5V)
(LV5V)
Refer to Error code: SRVO-047 for troubleshooting information.
Insufficient DC link An abnormally low DC voltage was detected in the power supply of the main circuit
voltage (LVDC) of the servo amplifier.

Refer to Error code: SRVO-047 for troubleshooting information.


Faulty regenerative The regenerative energy discharge was too large for a short time. This alarm occurs
control circuit (DCSW) when the regenerative energy discharge circuit is defective.

Refer to Error code: SRVO-043 for troubleshooting information.


Excessive regenerative The average regenerative energy discharge was too large. This alarm occurs when
discharge (DCOH) the frequency of acceleration and deceleration exceeds a predetermined value.

Refer to Error code: SRVO-043 for troubleshooting information.


Servo amplifier overheat The thermostat in the servo amplifier operated. (Thermostat contact opened)
(OH)
Refer to Error code: SRVO-049 for troubleshooting information.
Welded electromagnetic The contacts of the MCC contactor in the servo amplifier are stuck together.
contactor (MCC)
Refer to Error code: SRVO-042 for troubleshooting information.
Overcurrent (HCL) An overcurrent was detected in the oneaxis servo amplifier or the Laxis circuit of
the twoaxis servo amplifier.

Refer to Error code: SRVO-045 for troubleshooting information.


Overcurrent (HCM) An overcurrent was detected in the Maxis circuit of the twoaxis servo amplifier.

Refer to Error code: SRVO-045 for troubleshooting information.


Overcurrent (HCLM) An overcurrent was detected in both the Laxis and Maxis circuit of the twoaxis
servo amplifier.

Refer to Error code: SRVO-045 for troubleshooting information.


Servo amplifier not ready The MCC contactor in the servo amplifier is turned off. The amplifier is unarmed and
cannot drive the motor. See teach pendant display for error code information.
Servo amplifier ready The MCC contactor in the servo amplifier is turned on. The amplifier is armed and
can drive the motor.

NOTE Refer to Chapter 4, Troubleshooting, for more information.


3. LIGHTS AND LEDS
MARMMTRBL02303E
318

3.3.6 The LEDs associated with the IBRC are indicators that input terminals P
Contact Signal and N have been closed in the circuit loop for that LEDs channel.
Figure 311 shows the IBRC.
Transducer (IBRC)
Figure 311. IBRC
3. LIGHTS AND LEDS

MARMMTRBL02303E 319

3.3.7 The LEDs associated with module I/O are on the interface module printed
Modular I/O LEDs circuit board and on each I/O module. Figure 312 shows the modular I/O
LEDs. Table 38 describes each modular I/O LED.

Figure 312. Modular I/O LEDs

LEDS

PWR LINK A0 1 2 3 4 5 6 7
BAI LEDS
B0 1 2 3 4 5 6 7
BAO

AIF0IA

JD1B JD1A

CP32 JD2

INTERFACE MODULE I/O MODULE

Table 38. Modular I/O LEDs


LED Location Description
PWR Interface ON: The interface module is supplied with
module 24 VDC power.
Link Interface ON: The I/O Link is operating properly.
module Normally, this LED lights several seconds
after the power is turned on.
BA1 Interface These LEDs indicate that a fault has
module occurred in the modular I/O system.

BA0 Interface
module

A01234567 I/O Module Indicates if the input or output is on.


B01234567
3. LIGHTS AND LEDS
MARMMTRBL02303E
320

3.3.8 Figure 313 shows the process I/O board diagnostic LEDs. Table 71
(Optional) Process I/O shows and describes each process I/O board diagnostic LED.
Board Diagnostic LEDs
Figure 313. Process I/O Board Diagnostic LEDs

CB, DA Process I/O AA, AB, BB, BA, CA Process I/O Board
Board (side view) (front view)
ALM0

FALM
1 2 3 4
STATUS
ALARM

Table 39. Process I/O Board Diagnostic LEDs


AA, AB, BB, BA, CA CB, DA Color Description
ALM0
Red A communication alarm occurred between the
Process
I/O PCB main CPU and process I/O board. Check
cabling from Main CPU to I/O board. Replace I/O
ALM0 board.
FALM 1 2 3 4
STATUS
ALARM

ALM0
Red A fuse (FUSE 1) in the process I/O board blew.
Process Replace fuse. If fuse blows again, replace board.
I/O PCB

FALM FALM
1 2 3 4
STATUS
ALARM

Green Indicates the operations status of the process I/O


Process board.
I/O PCB

1 2 3 4
STATUS
ALARM
3. LIGHTS AND LEDS

MARMMTRBL02303E 321

3.3.9 Table 310 shows and describes each process I/O board diagnostic LED.
(Optional) Process I/O
Board Diagnostic LEDs Table 310. Process I/O Board LEDs

Process A communication alarm


I/O PCB occurred between the
main CPU and process
RED input/output. Check
1 2 3 4
cabling from Main CPU to
1 2 3 4 STATUS
ALARM I/O board. Replace I/O
STATUS board.
ALARM

Process
I/O PCB A fuse (FUSE 1) in the
process input/output blew.
RED Replace fuse. If fuse
1 2 3 4
blows again, replace
STATUS
ALARM board.

Process
I/O PCB
Indicates the operations
GREEN status of the Process I/O
1 2 3 4
Board.
STATUS
ALARM
3. LIGHTS AND LEDS
MARMMTRBL02303E
322

3.3.10 Figure 314 shows each RH MAP Interface LED. Table 311 describes
R-H MAP INTERFACE each LED.
LEDs
Figure 314. RH MAP LEDs

A D

B C

Table 311. R-H MAP LEDs


LED Meaning Status
A System fail This LED is briefly turned on during power up/down by the
(RED) MAP interface board. This LED is turned on when a system
failure has occurred in the MAP interface board or other
subsystems in the controller. Therefore, the problem might
not exist with the MAP interface board.
B Not used
C Not used
D Not used
3. LIGHTS AND LEDS

MARMMTRBL02303E 323

3.3.11 Figure 41 shows and Table 312 describes the R-H ABRIO LEDs.
R-H ABRIO LEDs Figure 41. R-H ABRIO LEDs

POWER

ACTIVE
INTERBRD
FAULT
PC COMM
FAULT
PROC
FAULT

Table 312. R-H ABRIO LED Descriptions


LED On Flashing Off
POWER (green) There is power to the ABRIO board. Not applicable There is no power
to the ABRIO
board.
ACTIVE (green) The ABRIO board is communicating with the  The PLC is in PROGRAM or In conjunction
PLCs remote I/O scanner and the PLC is in TEST mode and the input and with one of the
run mode. Input and output data in the ABRIO output data to the interface is other red LEDs
board is being updated. being updated. being on or
 A No Update condition is flashing indicates
indicated by the PLC remote I/O an interface fault.
scanner. There is no
 Indicates an error in the rack communication
address setup. Error is possibly with the PLCs
an invalid value or an invalid remote I/O
combination of starting module scanner.
group and rack size settings.
INTERBOARD Communication between the ABRIO board and  An error in communications Normal operation
COMMUNICATION the R-J controller has been broken. This might between the ABRIO board and
FAULT (red) be due to the inability of the ABRIO board to the R-J controller has occurred.
gain access to the Common RAM or a Communication with the PLCs
checksum error in the R-J output data. remote I/O scanner is stopped.
Communication with the PLCs remote I/O  The ABRIO board did not
scanner is stopped. detect the R-J controllers
operational code after power up
or reset.
PC ABRIO board is not communicating properly Not applicable Normal operation
COMMUNICATIONS with the PLC remote I/O scanner. The remote
FAULT (red) I/O scanner might be faulted or a problem
might exist on the serial channel.
PROCESSOR This LED is normally on for to 2 seconds This LED flashes along with the No faults exist
FAULT (red) during initialization to indicate that the ABRIO ACTIVE LED to indicate that an with the remote
board is performing its power up diagnostics. invalid rack address has been I/O CPU or
The LED is turned off after diagnostics have set up via the DIP switches on related circuitry.
been completed successfully and the R-J the ABRIO board.
controllers operation code has been set. If,
after initialization, this LED is on, this indicates
a fault in the ABRIO board hardware (RAM
integrity, EPROM checksum, or CPU watchdog
timeout). Communication with the PLCs
remote I/O scanner and with the R-J controller
has been stopped. When this LED is on, all
other LEDs except Power should be off.
MARMMTRBL02303E 4 TROUBLESHOOTING

41

This chapter describes the steps used to repair electrical faults in the robot.

WARNING
The procedures described in this section require you to
work with high voltage circuits. Carelessness or
inattention can kill you. Do not attempt any of these
procedures unless you are trained and experienced in
electrical repair.

Electrical faults are divided into three classes of symptoms:

 A Class 1 Fault is a malfunction that prevents the controller from


operating. The main contactor might or might not be energized. No
text is displayed on the teach pendant.

 A Class 2 Fault is a malfunction that prevents the bootROM from


turning the system over to the application software. Text will be
displayed on the the teach pendant, but the teach pendant display will
be frozen and will not respond to keypad entries.

 A Class 3 Fault is a malfunction that prevents the robot from


operating normally, even though the application software is running.
A numbered alarm message will be displayed on the teach pendant.
You can access teach pendant menus and diagnostic screens during a
Class 3 fault.
If your robot has a class 1 fault, refer to Section 4.1.
If your robot has a class 2 fault, refer to Section 4.2.
If your robot has a class 3 fault, refer to Section 4.3.
4. TROUBLESHOOTING
MARMMTRBL02303E
42

4.1 To enable the user with a quick reference guide to powering on a P-155
controller, the following steps and events should be followed:
POWER ON
SEQUENCE

Procedure 41 Purge Sequence

Step 1 With the main disconnect ON, you should observe:


 Purge complete LED out
 Purge enable pushbutton (purging) lamp out
 ON pushbutton lamp out
 Purge fault LED on
2 Push and hold the purge enable pushbutton. You should observe
 Purge solenoid engages when minimum pressure requirements are
met.
 Purge fault LED goes out
 Purging lamp (behind purge enable pushbutton) lights.
At this point you can release the purge enable pushbutton, no change
should occur.
3 At the end of the 5 minute purge, the purging lamp (behind the purge
enable pushbutton) will go out and the purge complete LED lights.
Also, the purge solenoid shuts off.

Procedure 42 Enabling Power

Step 1 With purge complete, you should observe:


 Purge complete LED on
 Purge enable pushbutton (purging) lamp out
 ON pushbutton lamp out
 Purge fault LED out
2 Push the ON pushbutton. You should observe:
 ON pushbutton lamp lights
 Main CPU and axis control PCBs go through internal diagnostics
At the end of diagnostics the MCC contactor on all servo amplifiers will
energize and click. The teach pendant should be energized and the
controller ready to operate manually.
4. TROUBLESHOOTING

MARMMTRBL02303E 43

4.2 This section contains troubleshooting information for Class 1 Faults.


A Class 1 fault prevents the controller from operating. The main ALC
CLASS 1 FAULT
contactor might or might not be energized. The Purge Complete light
TROUBLESHOOTING might or might not be on. No text is displayed on the teach pendant or
CRT.

How to use the This section contains several tables. Each table provides procedures to
Troubleshooting Tables correct the fault. To troubleshoot a Class 1 fault, always start at
Table 44. Perform the procedures in order. You will either correct the
fault using Table 44 or it will refer you to another table in this section.
Use the other tables only when Table 44 refers you to them.

Class 1 Fault Condition If the following conditions are true, follow the steps in Table 44.
 The main disconnect is UP (on).
 The ON button has been pushed.
 The power on sequence (Section 4.1) has been attempted.
 The controller does not operate.
4. TROUBLESHOOTING
MARMMTRBL02303E
44

Without turning off the main disconnect, open the controller door:
Release the disconnect latch by turning the screw to the lower right of the
disconnect handle.
Table 41. Troubleshooting Procedure 1
Troubleshooting Procedure Illustration Chapter 13
Print Reference



1. Find the Purge Complete light on the SOP. 0806



 The light is on indicating that the purge cycle was successful.
If the light is on  go to Table 45.



H
OL
D
If the light is off  continue.


Purge


Complete
Light






2. Find the Purge Fault LED on the SOP.
0806


If the LED is on  go to Step 4.


If the light is out  continue. H
OL

Purge


Fault




4. TROUBLESHOOTING

MARMMTRBL02303E 45

Table 41. (Contd) Troubleshooting Procedure 1


Troubleshooting Procedure Illustration Chapter 13
Print Reference


3. Press and hold the Purge Enable pushbutton on the SOP until it 0805


lights (1 5 seconds) and then release. 0806
 After the purge cycle is completed, the Purge Complete light 0810


H
should come on. OL
D


If the Purge Complete light comes on  test the controller for


proper operation.


If the Purge Enable (purging) or Purge Complete light does
not come on and/or the Purge Fault light comes on  Purge


continue. Fault
Light




4. Turn off the power disconnect handle.
5. Connect jumper wires between terminals P1 and N1, and 0821
between terminals P2 and N2 on the IBRC. 0822
 These terminals are the inputs for the robot-mounted air 0834
pressure and air flow switches. 0835
 If opening devices are used, you will also need to jumper 0825
between P3 and N3, and P5 and N5. These auxiliary 0826
inputs are for the pressure switch and flow switch for an
opener.
6. Turn on the power disconnect handle.
7. Press and hold the Purge Enable pushbutton on the SOP until 0805
it lights (1 5 seconds) and then release.
 If the purge circuit is cycling, the purge enable lamp (purging) 0808
should stay lit until the 5 minute purge is complete. The
Purge Fault LED will be out.
 If the purge enable (purging) lamp does not stay lit, replace
the purge control PCB (piggy-back to EMG control PCB).
 If the purge enable (purging) lamp will not light, go to Table
42. 0811
 If, during the purge cycle, the Purge Fault LED lights, go to
Table 42. 0806
 If, after the 5 minute purge cycle, the Purge Complete light
comes on, locate and repair the break in the air pressure
and/or air flow switch circuits to the robot.
0943
 If the purge is too long or too short, the timer on the purge
control PCB is incorrectly set or damaged. Repair or replace
it.
4. TROUBLESHOOTING
MARMMTRBL02303E
46

Table 42. Troubleshooting Procedure 2


Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Observe on the IBRC Unit that:
 Red lights on the IBRC panel indicate that 200 VAC is
supplied to it.
If all of the lights are off  continue.
If one or more of the lights are on  go to Table 43.

2. Measure the AC voltage coming into the IBRC unit. 0710


 You should see 200 240 VAC. TF1
If the voltage is OK  replace the IBRC Unit. 43 44

R S 1 2
If there is no voltage  troubleshoot the AC power distribution FRA
circuit shown at the right.
G R S
CONTACT SIGNAL
TRANSDUCER IBRC

20VDC PSU
15ma MAX.
(+) ()

Table 43. Troubleshooting Procedure 3


Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Observe the LEDs of channels 1 and 5 on the IBRC unit. If 0819
either of these LEDs are out it implies that one or more cavities of
the robot is missing minimum air pressure. In the case of channel 0826
5, if there are no auxiliary pressure switches, it could be that the
jumper across terminals P5 and N5 has come loose.
 Check that there is sufficient maintenance air at the robot.
 Check cables between robot and controller.
If LEDs 1 and 5 are lit  continue.
If either LED 1 and 5 are out  go to Step 8.

2. Turn off the power disconnect handle.


3. Reseat the following connectors: 0819 thru
 Contact signal transducer (IBRC) connector CRX 0843
 Purge transit board connector CRX3
 Purge transit board connector CRX1 0925 thru
 Purge control PCB (mounted with EMG control PCB) 0950
connector CRX.
4. Turn on the power disconnect handle.
4. TROUBLESHOOTING

MARMMTRBL02303E 47

Table 43. (Contd) Troubleshooting Procedure 3


Troubleshooting Procedure Illustration Chapter 13
Print Reference


5. Observe on the SOP that: 0810


 Purge fault LED is lit


H
OL
D





Purge
Fault




6. Re-initiate the purge sequence. See Section 4.1.

If the controller does not operate properly, continue.


7. Measure the DC voltage between the white and black wires in 0815
the wiring harness at connector CRX5 (A1 and A2) of the Transit
Board.
 You should see 24 VDC.
If the voltage is OK  go to Step 10.
If there is no voltage  replace the Purge Power Supply Board
(PSU2).
Note: The Purge Power Supply Board (PSU2) contains two
fuses that can be checked after the board is removed from the
controller.
If you wish, you can perform the following steps after the board
is removed:
1. Check the fuses.
2. If a fuse is bad, replace it and reinstall PSU2.
3. If a fuse blows again, replace PSU2.
8. If, on the IBRC unit, channel 5 LED is out, jumper terminals P5 0825
to N5 and observe if the LED lights.
If the LED does not light  replace the IBRC unit.
If the LED lights  repair the auxiliary flow switch or wiring for
proper operation or replace the jumper when auxiliary flow
switch is not used.
4. TROUBLESHOOTING
MARMMTRBL02303E
48

Table 43. (Contd) Troubleshooting Procedure 3


Troubleshooting Procedure Illustration Chapter 13
Print Reference
9. If channel 1 LED is out, jumper terminals P1 to N1 and observe 0821
if the LED lights.
If the LED does not light  replace the IBRC unit.
If the LED lights  repair the flow switch or wiring for proper
operation.
10. Repair or replace the following in the order shown:
 Purge enable switch
 IBRC unit
 Purge control PCB (mounted piggy-back on the EMG control
PCB)
 Cable 2003-T526 (1.6M) between SOP (CRX) and transit
board (CRX2)
 Cable 2003-T233 (2M) between purge control PCB and
IBRC unit.

Table 44. Troubleshooting Procedure 1


Table 45. Troubleshooting Procedure 4
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Find the green PIL light in the center of the PSU module. PSU Module 0218
 The light is on indicating 200VAC to PSU through F5.
0216
If the light is on  go to Table 43.
02-19
If the light is off  continue.
F1 and F2: 10-A fuses
for AC input

PIL: Green LED


for indicating the AC
power supply status

2. Check fuses F1 and F2 in the top center of the PSU module. If PSU Module 0208
no flag shows, turn off power. Pull fuses F1 and F2 from the PSU
and check the fuse with an ohmmeter. 0210
 A white flag in the center of the fuse indicates it is bad. F1 & 02-8
2 monitor incoming 200VAC to PSU.
If fuse(s) are good, go to step 4, otherwise continue. 02-10
F1 and F2: 10-A
fuses for AC
input
4. TROUBLESHOOTING

MARMMTRBL02303E 49

Table 45. (Contd) Troubleshooting Procedure 4


Troubleshooting Procedure Illustration Chapter 13
Print Reference
3. If one or both of the fuses are bad  0218 thru
a. Turn off power at the main disconnect switch. 0223
b. Unplug CP2 and CP3.
0219
c. Replace any bad fuse(s).
d. Turn the main disconnect switch on, but do not press the 02-18 thru 02-22
ON button.
If the fuse(s) blow again  Replace the PSU.
If the PIL light comes on  go to step 8.

4. Disconnect CP1 at the top of the PSU module. Measure the PSU Module 0208 thru 0210
voltage coming into the PSU on the two red wires in the harness 02-08
connector (S and R).
CP1
 You should see 200VAC. 3 G
If the voltage is ok  Continue. 2 S
1 R
If no voltage  go to Table 42.

5. Turn the main disconnect off, pull the PSU module out and PSU Module 0215
remove the fuse, F5, (located near the middle of the printed circuit 02-16
board).

F5: 0.3-A Fuse


for auxiliary
power supply

6. Using an ohmmeter, check fuse. 0215


If the fuse is good  Replace the PSU. 02-16
If the fuse is bad  Continue.
7. Replace fuse F5, insert the PSU module, and turn on the con- PSU Module
troller.
If the class1 fault is still present  replace the PSU

F5: 0.3-A Fuse


for auxiliary
power supply
4. TROUBLESHOOTING
MARMMTRBL02303E
410

Table 45. (Contd) Troubleshooting Procedure 4


Troubleshooting Procedure Illustration Chapter 13
Print Reference
8. If the PIL light is on, PSU Module 02-19
Turn off the main disconnect switch and, using an ohmmeter, 0218 thru
test for a short in the wiring harness at CP2 and CP3. 0223
02-18 thru 02-22

F1 and F2: 10-A


fuses for AC
input

9. If no short is evident, reconnect CP2 and CP3 and turn the


main disconnect switch on. Press the Power ON pushbutton and
check for proper operation.
10. If the PIL light goes out, fuse(s) F1 and/or F2 have blown 0209
again due to a short in one of the following: 0126
 Wiring harness to ALC relay coil 0209
0203 thru
 ALC relay coil 0208
 Wiring harness to fans (check in particular where cable and
front door hinge point meet).
 Fan motor shorted. 02-08
Repair short, replace fuse(s) and go to Step 9. 01-26
If the PIL light stays on, check controller for proper operation.
02-08

02-22
4. TROUBLESHOOTING

MARMMTRBL02303E 411

Table 46. Troubleshooting Procedure 2


Table 47. Troubleshooting Procedure 5
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Measure the AC voltage between Multitap transformer termi- Multi-Tap Transformer 01-22
nals 43 and 44 of TF1.
43 44
 You should see 200 VAC.
If voltage is present  Replace or repair harness between
PSU and transformer.
F4 F5
If voltage is not present or incorrect  Continue. 5A 5A

2. Check transformer tap settings. 01-14


 As shown in Section 1.9. (Should be Plant 3-phase voltage)
If the tap settings are incorrect  Correct.
If the tap settings are correct  Continue.

3. Check AC voltage between transformer primary terminals. 01-14


 Plant 3-phase voltage.
If voltage proper is present  Replace multi-tap transformer.
If incorrect or no voltage is present  Continue.
4. Check AC voltage between bottom terminals of FL1, FL2, & Fuse Block 01-05,
FL3. FL1 FL2 FL3 01-07,
 Plant 3-phase voltage. 01-09
If voltage is present  Replace or repair wiring harness
between transformer and fuse unit.
If voltage is not present  Continue.
5. Check AC voltage between top terminals of FL1, FL2, and FL3. 01-05,
 Plant 3-phase voltage. 01-07,
01-09
If voltage is present  F1, F2, F3 is/are blown. Replace bad
fuse. If it blows again, replace the multitap transformer.
If voltage is not present  Continue.
6. Check AC voltage between terminals at bottom of main discon- 01-05,
nect switch. Main 01-07,
 Plant 3-phase voltage. Disconnect 01-09
If voltage is present  Replace or repair wiring harness Switch
between fuse unit and main disconnect switch.
If voltage is not present  Continue.
7. Check AC voltage between terminals at top of disconnect. 01-05,
FL1, FL2, FL3
 Plant 3-phase voltage. 01-07,
01-09
Replace main disconnect switch if voltage is present;
otherwise, contact plant maintenance.
4. TROUBLESHOOTING
MARMMTRBL02303E
412

Table 48. Troubleshooting Procedure 3


Table 49. Troubleshooting Procedure 6
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Check the red alarm light in the center of the PSU module. PSU Module 02-14
 The alarm light should be off.
If the light is ON  Go to Table 410.
If the light is ON  Go to Table 411.
If the light is OFF  Continue. ALM: Red LED

F4: 5-Afuse for +24E

F3: 5-AS slowblow


fuse for +24V
2. Check the LED displays on the servo amplifier. 08-24 thru 08-26
If any LED is on  Go to Table 413 . 09-23 thru 09-25
08-09 thru 08-12
If any LED is on  Go to Table 45.
09-11 thru 09-13
If no LEDs are on  Continue.
10-11 thru 10-13
4. TROUBLESHOOTING

MARMMTRBL02303E 413

Table 49. (Contd) Troubleshooting Procedure 6


Troubleshooting Procedure Illustration Chapter 13
Print Reference
3. Listen and look for main cabinet cooling fans to be running. 02-02 thru 08-08
 Fans should be running indicating 200VAC to ALC relay. 02-02 thru 02-08
If fans are not running  Continue. FAN 1
FRONT REAR
If fans are running  Go to step 5.

FAN 2

FAN 3

CONTROLLER SIDE VIEW

4. Check for 200 VAC at CP2 or CP3. PSU Module 02-18 thru
 You should see 200 VAC 10VAC. 02-21
If there is 200VAC  Repair the wiring to the fans and the ALC 02-18 thru 02-22
relay and check the controller for proper operation.
If there is not 200VAC  Go to step 8.

5. Check for 200VAC at ALC relay on A1 & A2. 01-25, 01-27


 You should see 200VAC 10VAC. A1 A2
If voltage is not correct or missing  Repair the wiring
harness coil between the PSU and the coil of the ALC relay.
Check the controller for proper operation. 1 3 5
If voltage is present  Continue. ALC
2 4 6
4. TROUBLESHOOTING
MARMMTRBL02303E
414

Table 49. (Contd) Troubleshooting Procedure 6


Troubleshooting Procedure Illustration Chapter 13
Print Reference
6. Check for 200VAC at the ALC relay between 2 & 4, 4& 6, and 2 Multi-Tap Transformer 01-27
& 6. 01-22
 You should see 200 VAC. 01-27
If voltage is not correct or missing  Check fuses F1, F2,
and F3. If the fuses are ok, replace the multitap transformer.
If voltage is present  Turn power off and repair wiring F1 F2 F3
between ALC contactor and servo amplifiers.

A1 A2
13 23

31 1 3 5 41
ALC
32 2 4 6 42

14 24

7. Check the connector CRR4 on the EMG module for jumpers 02-06
between terminals 10 (EX-COM) and 12 (EX-OFF) and terminals 02-28 thru 02-33
14 (DIL1) and 16 (DIL2).
 If you use an external OFF button or door interlock, there will CRR4
be a wire on each terminal. 1 100OUT3
2 EMGOU2
If the terminals are connected with a jumper wire check for no 3 100OUT4
loose screws and good contact. 4 EMGOUTC
5 FENCE1
If an external OFF button or door interlock is used  Test for 6 EMGOUT1
continuity of the external OFF, and DIL circuits, and repair it if 7 FENCE2
8 EX-ON
necessary. 9 0V
10 EX-COM
11 0V
12 EX-OFF
13 5v
14 DIL1
15 15V
16 DIL2
17 -15V
18 EMGB1
19 +24V
20 EMGB2
4. TROUBLESHOOTING

MARMMTRBL02303E 415

Table 49. (Contd) Troubleshooting Procedure 6


Troubleshooting Procedure Illustration Chapter 13
Print Reference
7. Check the connector on the EMG module for jumpers between 02-28 thru 02-33
terminals 32 (EX-COM) and 31 (EX-OFF) and terminals 30 (DIL1)
and 29 (DIL2).
 If you use an external OFF button or door interlock, there will
be a wire on each terminal.
If the terminals are connected with a jumper wire check for
loose screws and good contact.
If an external OFF button or door interlock is used  Test for
continuity of the external OFF, and DIL circuits, and repair it if
necessary.

29 32
8. On the EMG board, connect 10 (Ex-COM) to ground with a 02-28 thru 02-33
jumper wire; then momentarily connect 8 (ExON) to
10 (Ex-COM).
 Controller should turn on.
If the controller turns on  There is a break in the on/off
switch circuit. Repair or replace.
If the controller does not turn on  Replace the PSU module.
PSU 02-16
9. On the Power Supply Unit, momentarily jumper the following
connections:
 CP4 connector terminal 1 (ON) to CP4 connector terminal 3
(COM)
 CP4 connector terminal 3 (COM) to ground
 The controller should turn on.
If the controller turns on  there is a break on the ON/OFF
switch circuit. Repair or replace.
If the controller does not turn on  continue.
4. TROUBLESHOOTING
MARMMTRBL02303E
416

Table 410. Troubleshooting Procedure 4


Table 411. Troubleshooting Procedure 7
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Check fuse F3 at the bottom of the PSU. PSU Module 02-24
 A white flag in the center of the fuse indicates it is bad and 02-23
that 24 power is missing.
If the fuse is blown  There might be a short circuit in one of
the following:
ALM: Red LED
Backplane for indicating an
24VDC Cooling Fans for module card cage alarm
Process I/O 24 VDC supply
CRT/KB
Main CPU Module F4: 5-Afuse for +24E
Axis Module
Modular I/O 24 VDC supply
Option #1 F3: 5-AS slow-blow
fuse for +24V
Option #2
Extended Backplane
 Isolate the short and repair it.
If the fuse is good  Continue. See NO TAG.
2. Turn off the controller. Measure the resistance between the 06-24 thru 06-36
following terminals of CRR4 on the EMG module:
Terminal 9 (0V) and Terminal 15 (+15)
Terminal 9 (0V) and Terminal 17 (15)
Terminal 9 (0V) and Terminal 13 (+5) CRR4
1 100OUT3
 Look for greater than 100 ohms at each measurement. 2 EMGOU2
If all readings are ok  Replace the PSU. 3 100OUT4
4 EMGOUTC
If all readings are not ok  Continue. 5 FENCE1
6 EMGOUT1
7 FENCE2
NOTE A low reading means shorted power to ground 8 EX-ON
9 0V
through or because of an EMG, Main CPU, PSU, Fence, 10 EX-COM
or Axis board. Remove them one at a time until you get 11 0V
12 EX-OFF
a normal reading. Replace the defective board. 13 5v
14 DIL1
15 15V
16 DIL2
17 -15V
18 EMGB1
19 +24V
20 EMGB2
4. TROUBLESHOOTING

MARMMTRBL02303E 417

Table 411. (Contd) Troubleshooting Procedure 7


Troubleshooting Procedure Illustration Chapter 13
Print Reference
2. Turn off the controller. Measure the resistance between the
following terminals on the EMG module: EMG 0934
Ground and Terminal 39 (15) 0932
Ground and Terminal 38 (+15) 0931
Ground and Terminal 40 (+5)
 Look for greater than 100 ohms at each measurement.
If all readings are ok  Replace the PSU.
If all readings are not ok  Continue.

NOTE A low reading means shorted power to ground 40


39
through or because of the Main CPU, PSU, Fence, or 38

Axis board EMG. Remove them one at a time until you


get a normal reading. Replace the defective board.
4. TROUBLESHOOTING
MARMMTRBL02303E
418

Figure 51. 24 Volt (24E) Power Distribution Chart


4. TROUBLESHOOTING

MARMMTRBL02303E 419

Table 412. Troubleshooting Procedure 5


Table 413. Troubleshooting Procedure 8
Troubleshooting Procedure Illustration Chapter 13
Print Reference


1. Turn the power disconnect switch on and press the power on 06-25
pushbutton. Check the lights on the operator panel. 06-29
 Any light on indicates 24E to the operator panel. This can


H
O
also be checked by measuring for 24VDC between terminals L


D
5 and 9 of the EMG connector CRR4.
If any light is on  Go to Table 414.
If the lights are not on  Continue.




1. Turn the power disconnect switch on and press the power on


pushbutton. Check the lights on the operator panel.


 Any light on indicates 24E to operator panel. This can also H
O
be checked by measuring for 24VDC between terminals 62



L
D
and Ground of the EMG control PCB.


If any light is on  Go to Table 415.


If the lights are not on  Continue.



2. Check fuse F4 at the bottom of the PSU module. If no flag PSU Module 02-23
shows, check the fuse with an ohmmeter. 02-31
 White flag in the center of the fuse indicates it is bad. 02-23
If the fuse is good  Replace the PSU 06-25
06-29
If the fuse is bad  Continue.
ALM: Red LED for
indicating an alarm

F4: 5-Afuse for +24E

F3: 5-AS slow-blow


fuse for +24V
4. TROUBLESHOOTING
MARMMTRBL02303E
420

Table 413. (Contd) Troubleshooting Procedure 8


Troubleshooting Procedure Illustration Chapter 13
Print Reference
3. Turn off power, disconnect fence circuit or remove jumper, and 09-50
connect an ohmmeter between Fence1 terminal 36 and Ground EMG
on the EMG module.
 If it does not show continuity (greater than 500 ohms),
replace fuse F4 and check the controller for proper
operation.
 If it does show continuity (less than 10 ohms), a
component is shorted, loading the 24E voltage supply.

0V 56
0V 55
36

3. Turn off power, disconnect fence circuit or remove jumper, and 06-25
connect an ohmmeter between Fence1 and 0V (CRR4 pin5 & 9 or
11) on EMG module.
 If it does not show continuity (greater than 500 ohms), CRR4
replace fuse F4 and check the controller for proper 1 100OUT3
operation. 2 EMGOU2
3 100OUT4
 If it does show continuity (less than 500 ohms), a 4 EMGOUTC
component is shorted, loading the 24E voltage supply. 5 FENCE1
6 EMGOUT1
7 FENCE2
8 EX-ON
9 0V
10 EX-COM
11 0V
12 EX-OFF
13 5v
14 DIL1
15 15V
16 DIL2
17 -15V
18 EMGB1
19 +24V
20 EMGB2
4. To find the shorted component, watch the ohmmeter while you
disconnect or remove the following parts in order:
 Main CPU
 Axis
 Option #1
 Option #2
 EMG
 Cards on the extended backplane one at a time
 If the ohmmeter shows greater than 500 ohms, the part is
OK. If the ohmmeter shows under 500 ohms, the part is
defective.
If it still does not work  Follow the short out to the failed
component and replace. See Figure 52.
4. TROUBLESHOOTING

MARMMTRBL02303E 421

Figure 52. 24 Volt (24V) Power Distribution Chart


4. TROUBLESHOOTING
MARMMTRBL02303E
422

Figure 53. Tracing a Short on 24E


4. TROUBLESHOOTING

MARMMTRBL02303E 423

Table 414. Troubleshooting Procedure 6


Table 415. Troubleshooting Procedure 9
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Press the OFF button. Press and hold USER PB1 and USER Operator Panel
PB2 and press the ON button.
If the BMON> prompt appears  Treat the problem as a




Class 2 Fault; otherwise, continue. ON



H
O
L OFF
D

USER


PB1

USER
PB2


1. Press the OFF button. Press and hold PURGE ENABLE Operator Panel 08-05


press the ON button. ON 02-13


If the BMON> prompt appears  Treat the problem as a
Class 2 Fault; otherwise, continue.


H
OL
D


Purge


Enable
Button





4. TROUBLESHOOTING
MARMMTRBL02303E
424

Table 415. (Contd) Troubleshooting Procedure 9


Troubleshooting Procedure Illustration Chapter 13
Print Reference
2. If you have not done so already, measure the 24E voltage at
the EMG module connector CRR4 on terminals 5 (FENCE1) and 06-25
9 (0VDC) for 24VDC (10%). If the 24VE voltage is missing or out 06-29
of tolerance, go to Table 412.
CRR4
1 100OUT3
2 EMGOU2
3 100OUT4
4 EMGOUTC
5 FENCE1
6 EMGOUT1
7 FENCE2
8 EX-ON
9 0V
10 EX-COM
11 0V
12 EX-OFF
13 5v
14 DIL1
15 15V
16 DIL2
17 -15V
18 EMGB1
19 +24V
20 EMGB2
2. If you have not done so already, measure the 24E voltage at 0950
the EMG module on terminals 36 and Ground. for 24VDC (10%). EMG
If the 24VE signal is missing or out of tolerance, go to Table 413.

0V 56
0V 55
36
4. TROUBLESHOOTING

MARMMTRBL02303E 425

Table 415. (Contd) Troubleshooting Procedure 9


Troubleshooting Procedure Illustration Chapter 13
Print Reference
3. On the teach pendant, look for any lit LEDs or screen display.
If there is no display  the 24T power supplying the teach 05-23
pendant ISB unit is most likely missing. Visually check the
teach pendant cable K0402003T908 (10/20M) for damage.
If the 24T signal is missing or out of tolerance the following will
correct the problem. Replace the following, in order, one at a
time:
3 Replace the teach pendant cable.
4 Replace the ISB unit.
5 Replace the EMG module.
6 Replace the Main CPU printed circuit board.
7 Replace the backplane.
4. If there are LEDs or a screen display, there is a communication
fault between the Main CPU printed circuit board and the teach
pendant.
Replace the following in order, one at a time.
 Teach pendant cable
 Teach pendant
 Main CPU module
4. TROUBLESHOOTING
MARMMTRBL02303E
426

4.3 A Class 2 Fault is indicated by frozen text (letters or numbers) displayed


on the teach pendant. This situation is an indication of a problem with the
CLASS 2 FAULTS
Main CPU printed circuit board caused by either the memory, processor,
the board itself, or a bad teach pendant cable.

Table 416. Class 2 Faults Troubleshooting Procedure


Troubleshooting Procedure
1. Is the Battery light on the main CPU module on?
If the Battery light is on  replace the battery. Refer to Procedure 91.
1 2 3 4
STATUS
ALARM

Battery Light

2. Perform a cold start of the controller.


3. Is a red light on the axis control board turned on?
If a red light is on  replace the axis control board.
4. Are all four green LEDs on the axis control board turned on?
If all four green LEDs are on  go to step 5.
If all four green LEDs are not on  troubleshoot the controller using Table 35 in Chapter 3, Lights and LEDs.
5. Turn the controller off. Hold down Purge Enable pushbutton and press the ON button.
 Check the teach pendant cable by swapping it with a known working cable or by doing a continuity test.
 Does the BMON> prompt appear on the teach pendant? If it does not appear, replace the main CPU printed circuit
board and reload software.

CAUTION
Continuing beyond this point will erase all software stored in the controller
including all taught positions in your application. It will also require a software
reload which will take at least two hours. Do not do this unless your controller
actually has a Class 2 fault.
4. TROUBLESHOOTING

MARMMTRBL02303E 427

Table 416. (Contd) Class 2 Faults Troubleshooting Procedure


Troubleshooting Procedure
6. Perform the following steps on the teach pendant:
a. Press the NEXT key twice.
b. Press F2, DIAG.
c. Press ENTER.
The prompt changes to DIAG> (diagnostic monitor).
d. Press the NEXT key.
e Press F3, TEST.
f. Press F1, CMOS.
g. Press ENTER.
The teach pendant will display a message that gives you an opportunity to exit without destroying the contents of CMOS
memory.
h. Press 1 if you want to continue with the test.
7. The CMOS memory test will take a few minutes to run. If an error is encountered, an address and good and bad data are
displayed on the teach pendant or CRT/KB. Record the address and refer to following to determine the board that failed.

Error Code Replace Board


F1000000 F10FFFFF 7MK1 (RAM MODULE) (STANDARD)
F1100000 F11FFFFF MJ1 (RAM MODULE) (STANDARD)
F1200000 F12FFFFF MH1 (RAM MODULE) (OPTION)
F1300000 F13FFFFF MG1 (RAM MODULE) (OPTION)

Replace defective memory boards as necessary and reload software. If the CMOs memory test passes, continue.
8. Perform the following steps on the teach pendant:
a. Press the NEXT key.
b. Press F1, EXIT.
c. Press ENTER.
d. Press the NEXT key.
e. Press F1, CLEAR.
f. Press F2, FROM.
g. Press ENTER.
h. Press the NEXT key.
i. Press F1, EXIT.
j. Press the NEXT key twice.
k. Press F2, DIAG.
l. Press ENTER.
m. Press F3, TEST.
n. Press F4, FROM.
o. Press ENTER.
The teach pendant will display a message that gives you an opportunity to exit without destroying the
contents of Flash ROM memory.
p. Press 1 if you want to continue with the test.
The Flash ROM memory test will take a few minutes to run. If an error is encountered, replace the Flash
ROM board and reload software. Otherwise, continue.
9. The hardware in your controller is OK. Reload your system application software.
4. TROUBLESHOOTING
MARMMTRBL02303E
428

4.4 This section contains troubleshooting information for Class 3 Faults. You
are here if the teach pendant displays a fault message on the teach pendant
CLASS 3 FAULT
screen.
TROUBLESHOOTING
1. Press the MENU key on the teach pendant.
2. Select ALARM from the menu.
3. Refer to the appropriate subsection in this section and follow the
troubleshooting procedure. The subsections that follow are arranged
in numerical error code order.
4. TROUBLESHOOTING

MARMMTRBL02303E 429

4.4.1 The operator panel emergency stop push button is pressed.


SRVO-001 ER_SVAL1
Remedy: Twist the operator panel emergency stop push button clockwise
Operator Panel EStop to release. Press reset.

If the problem still exists, it is caused by an open circuit in the emergency


stop circuit or a bad Main CPU. Perform the troubleshooting procedure in
the following table.
Table 417. SRVO-001 Troubleshooting Procedure
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Remove and reconnect: Main CPU Printed Circuit Board 03-17
 CN1 on the Operator Interface board 03-28
 CN5 on the Operator Interface board
 JRM5 on the Main CPU
Check for proper operation.
If the problem still exists  go to step 2.

JRM5 connector

Operator Interface Printed Circuit Board

Operator panel,
rear face

CN1 connector

CN3 connector
4. TROUBLESHOOTING
MARMMTRBL02303E
430

Table 417. (Contd) SRVO-001 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
2. Perform the following steps: 03-17
a. Turn off the controller.
b. At the operator panel emergency stop button,
remove the two blue wires and connect (strap) them
together.
c. Turn on the controller.
If the error message is cleared  replace the
emergency stop button.
If the error message reappears  go to step 3.

ESTOP REAR VIEW


3. Perform the following steps: Main CPU Printed Circuit Board 03-25
a. Replace the cable between connector JRM5 at the
Main CPU module and the operator interface printed
circuit board.
b. Turn on the controller.
If the error message is cleared  check the
controller for proper operation.
If the error message reappears  replace the Main
CPU module.

JRM5 connector

PIN 1

PIN 26

PIN 25

PIN 50
4. TROUBLESHOOTING

MARMMTRBL02303E 431

Figure 54. Operator Panel E-Stop Circuitry


4. TROUBLESHOOTING
MARMMTRBL02303E
432

4.4.2 The teach pendant emergency stop push button is pressed.


SRVO-002 ER_SVAL1
Remedy: Twist the teach pendant emergency stop push button clockwise
Teach Pendant Estop to release. Press reset.
If the problem still exists, it is caused by the loss of 24VDC to the teach
pendant relay RLY2 or the 5 VDC signal to the matrix decoding from the
normally closed contact of the teach pendant relay RLY2.
Any of the following can cause this problem:
 A defective teach pendant emergency stop switch.
 A defective component on the teach pendant printed circuit board.
 Loss of 24VDC to the E-STOP switch (not part of the teach pendant
power).
This loss of power can be caused by a bad teach pendant emergency
stop switch, a broken wire in the teach pendant cable, or a bad EMG
module on relay RL-10. In most cases, you can fix it by replacing the
teach pendant.
If you want to troubleshoot the problem further, perform the following
troubleshooting procedure:

Table 418. SRVO-002 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
Perform the following steps:
a. Turn off power to the controller.
b. Remove the seven screws holding the teach pendant back in place.
c. Remove the teach pendant back cover.
d. Slide the E-stop wiring connector half way off connector CNEMG1.
e. Carefully energize the teach pendant and measure the DC voltage of CNEMG1 and 15-33
either of the GND test points on the teach pendant.
At pin 2, if there is 24VDC (5 VDC)  Measure pin 1. If 0VDC, go to step f.
At pin 1, if there is no 24VDC (5 VDC)  Replace the teach pendant emergency stop
switch.
If voltage is found  Replace the teach pendant.
f. If no voltage is found, replace the teach pendant cable, and test for proper operation. Figure 55
g. If the problem still exists, replace the EMG module.
4. TROUBLESHOOTING

MARMMTRBL02303E 433

Figure 55. Teach Pendant E-Stop Circuitry

JRS1 MAIN (RS422/TEACH PENDANT) HONDA High Density


10 +24T 20 +24T
9 TPDSC 19
8 EMGB2 18 EMGTP
7 EMGB1 17
6 0V 16 EMGDM
5 15
4 *TXTP 14 EMGEN
3 TXTP 13
2 *RXTP 12 0V
1 RXTP 11

4 3 2 1
*RXTP RXTP *TXTP TXTP
10 9 8 7 6 5
+24T +24T
16 15 14 13 12 11
EMGB2 EMGB1 EMGEN EMGDM EMGTP
20 19 18 17
0V 0V TPDSC

Teach Pendant
External Connector CN1
Male HIROSE
4. TROUBLESHOOTING
MARMMTRBL02303E
434

4.4.3 The teach pendant deadman switch is released while the teach pendant is
SRVO-003 ER_SVAL1 enabled.
Deadman switch Remedy: Press and hold the teach pendant deadman switch. Press reset.
released
If the problem still exists, it is caused by:
 A defective teach pendant deadman switch
 A defective component on the teach pendant printed circuit board
 A possible break in the circuitry between the teach pendant and the
Main CPU.
In most cases, you can fix it by replacing the teach pendant.
If you want to troubleshoot the problem further, perform the following
troubleshooting procedure:

Table 419. SRVO-003 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Perform the following steps:
a. Remove power from the controller.
15-25
b. Remove the seven screws holding the teach pendant back in place. 15-30
c. Remove the teach pendant back but leave all electrical connectors in place.
d. Press each deadman switch bar while watching the switch body inside the teach pendant.
e. Make sure that the copper strip presses the switch actuator all the way into the switch body.
You should be able to hear and feel it click into place.
If the actuator is frozen or will not click sharply  replace the switch.
2. Perform the following steps for each deadman switch:
a. Slide the wiring connector half way off the circuit board connector. 15-25
15-30
b. Measure the resistance between:
 Pins 1 and 2
 Pins 3 and 4
When the deadman switch is not pressed, there is continuity between pins 1 and 2 and no
continuity between pins 3 and 4
When the deadman switch is pressed, there is no continuity between pins 1 and 2 and
continuity between pins 3 and 4.
If one or more measurements are bad  replace the deadman switch assembly.
If the measurements are good  replace the teach pendant.
4. TROUBLESHOOTING

MARMMTRBL02303E 435

Figure 56. Deadman Switch Circuitry


4. TROUBLESHOOTING
MARMMTRBL02303E
436

4.4.4 The motion command after the ramping algorithm in the servo software
SRVO-041 exceeded one word. Contact the FANUC Robotics Hotline for more
information. DO NOT INCLUDE IN MANUAL!!!!!!
MOFAL Alarm
(Group:i Axis:j)
4. TROUBLESHOOTING

MARMMTRBL02303E 437

4.4.5 The safety fence gate is open.


SRVO-004 ER_SVAL1 Remedy: Close the gate. Several gates in the workcell might be
Fence open involved.
If the problem still exists, perform the following troubleshooting
procedure:
Table 420. SRVO-004 Troubleshooting Procedure
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Perform the following steps to determine if a safety fence is 06-24 thru 06-26
installed:
a. Look at terminals 5 and 7 on the EMG module connector
CRR4. CRR4
b. Check for a jumper connecting the terminals or a wire on 1 100OUT3
2 EMGOU2
each terminal. 3 100OUT4
If a jumper is present  go to step 2. 4 EMGOUTC
5 FENCE1
If two wires are present  go to step 3. 6 EMGOUT1
7 FENCE2
8 EX-ON
9 0V
10 EX COM
EX-COM
2. Measure the resistance between the two terminals. 11 0V
If there is continuity  replace the EMG module. If the 12 EX-OFF
13 5v
problem still exists, replace the axis control printed circuit 14 DIL1
board. 15 15V
16 DIL2
If there is no continuity  repair or replace the jumper. 17 -15V
18 EMGB1
19 +24V
20 EMGB2
3. Measure the resistance between the two wires.
If there is continuity  replace the EMG module. If the
problem still exists, replace the axis control printed circuit
board.
If there is no continuity  locate and repair the break in the
safety fence switch circuit between the two terminals.
4. TROUBLESHOOTING
MARMMTRBL02303E
438

Figure 57. Fence Open Circuitry


4. TROUBLESHOOTING

MARMMTRBL02303E 439

4.4.6 An overtravel error occurs when one or more of the robot axes move
SRVO-005 ER_SVAL1 beyond the software motion limits, tripping an overtravel limit switch.
Robot Overtravel
Table 421. SRVO-005 Troubleshooting Procedure 1
Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. If you have not already done so, continuously press and hold 05-08 thru 05-20
the DEADMAN switch and turn the teach pendant ON/OFF switch
to ON.
2. Hold down the SHIFT key and press RESET.
3. Press COORD until you select the JOINT coordinate system.
4. Jog the axis in overtravel off of the overtravel switch.
If you cannot jog the robot off of the overtravel switch  the
wrong motion inhibit flag has been set; therefore, continue to
the next step. Otherwise, the axis (or axes) are no longer in
overtravel and you can end the procedure now.
5. Cold start the controller and go to Step 1 in this procedure. If
the overtravel still cannot be cleared, continue to Step 6.
NOTE In some instances, the screen will indicate a FALSE for a
given axis when a TRUE should be set because of the way
overtravel is read in software. It is best to perform the following
procedure on all of the axes.
6. Press MENUS.
7. Select MANUAL FCTNS.
8. Press F1, [TYPE].
9. Select OT Release. See the following screen for an example.
10. Move the cursor to the OT PLUS or OT MINUS value of the
axis in overtravel. The status of OT PLUS or OT MINUS for that
axis is TRUE.
11. Press and hold SHIFT and press F2, RELEASE.
12. Press and hold SHIFT and press RESET.
13. Press COORD until you select the JOINT coordinate system.
14. Continuously press and hold the DEADMAN switch and turn
the teach pendant ON/OFF switch to ON.
15. Jog the axis off of the overtravel switch.
16. Turn the teach pendant ON/OFF switch OFF and release the
DEADMAN switch.
4. TROUBLESHOOTING
MARMMTRBL02303E
440

If the problem still exists, it is caused by an open circuit in the overtravel


switch circuit or by a defective axis control board or EMG module.
Try the following steps in order, checking for proper operation after each.

Table 422. SRVO-005 Troubleshooting Procedure 2

Troubleshooting Procedure Reference


1. Remove all connectors from the axis control board and reseat them, starting with connector CRM1.
2. If spare boards are available, temporarily replace the EMG board and axis control board.
3. Using the schematic drawings and an ohmmeter, check the overtravel switches in the robot and their
wiring for continuity.
4. Replace the cable between axis control board connector CRM1 and the robot.

Figure 58. Robot Overtravel Circuitry


4. TROUBLESHOOTING

MARMMTRBL02303E 441

4.4.7 A hand breakage error occurs when the hand (wrist) breakage detection
SRVO-006 ER_SVAL1 switch or aux hand breakage detection switch is tripped.
Hand Broken Remedy:

If you are not using the hand broken function, ensure that the HBK
jumper on the axis control printed circuit board is set to the A side.

If you are using the hand broken function, perform the following steps:

1. If you have not already done so, continuously press and hold the
DEADMAN switch and turn the teach pendant ON/OFF switch to ON.

2. Hold down the SHIFT key and press RESET. The robot can now be
moved.

3. Jog the robot to a safe position off of the limit switch.

4. Turn the teach pendant ON/OFF switch to OFF and release the
DEADMAN switch.
4. TROUBLESHOOTING
MARMMTRBL02303E
442

If the problem still exists, perform the following troubleshooting


procedure:

Table 423. SRVO-006 Troubleshooting Procedure


Troubleshooting Procedure Illustration Reference
1. Remove power from the controller by
turning off the disconnect switch.

2. Test the end effector switch and its wires at


the robot for continuity.
If there is no continuity  replace or repair
the switch or its wires.
If there is continuity  continue.

3. Set the HBK jumper on the axis control


board to the A side and test the robot for
proper operation.
If the fault is fixed  replace the cable
between axis control board connector
CRM1 and the robot. Be sure to reset the
HBK jumper on the axis control board to the
B side.
If the fault is not fixed  replace the axis
control board.
NOTE: When replacing the axis control
module, ensure that the on-board jumpers
on the replacement board match those on
the original board.
A COM B B HBK A
JUMPER JUMPER

Figure 59. Hand Broken Circuitry


4. TROUBLESHOOTING

MARMMTRBL02303E 443

4.4.8 An external emergency stop button somewhere in the workcell has been
SRVO-007 ER_SVAL1 pressed. External emergency stop is signaled whenever the 100V to the
servo amplifiers is not present, and the operator panel emergency stop,
External emergency teach pendant emergency stop, overtravel, and hand broken signals are not
stops asserted.

Remedy: Locate and release the external emergency stop button. Press
reset on the operator panel or teach pendant.

If the problem still exists, perform the following troubleshooting


procedure:
4. TROUBLESHOOTING
MARMMTRBL02303E
444

Table 424. SRVO-007 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Perform the following steps: CRR3
a. Locate terminals 6, 8, and 10 on connector CRR3 of the 1 100IN1
2 OP1
EMG module. 3 100IN2
4 OP2
b. Check for jumpers between: 5 100IN3 03-08, 03-09, 03-10
 6 and 8 6 EMGIN1
7 100IN4
 8 and 10 8 EMGINC
9
10 EMGIN2
or else wires attached to the terminals. Wires indicate that 11 100OUT1
an external emergency stop is EMG 12 100OUT1
13 100OUT2
connected to the controller. 14 100OUT2
15 BKP4
If there is no jumper connecting the terminals or there are 16 BKM4
no wires on each terminal  verify that no external emergency 17 BKP5
18 BKM5
stop should be installed and replace the missing jumper. 19 BKP6
20 BKM6
If a jumper is present or if wires are present  go to step 2.
2. With controller power off, on the EMG module, measure the
resistance on CRR3 between: 03-08, 03-09
 6 and 8 03-09, 03-10
 8 and 10
If there is continuity  go to step 3.
If there is no continuity  repair or replace the jumper or locate
and repair the break in the external emergency stop circuit.
3. With controller power off, on the EMG module, measure the 03-06, 03-07
resistance on CRR3 between terminals 2 and 4.
If there is continuity  go to step 4.
If there is no continuity  verify that the 100VAC contacts on
the operator panel emergency stop button are operating
properly.
4. With controller power on, on the EMG module, measure the AC 03-04
voltage on CRR3 between terminals 1 and 3.
Is the voltage 100VAC  10%?
If the voltage is within tolerance  replace EMG
If the voltage is not within tolerance  go to step 5.
5. With controller power on, measure the AC voltage at transformer Multi-Tap Transformer 01-33, 01-34
TF1, terminals 41 and 42, for
100VAC  10%. 41 42
If the voltage is within tolerance  repair or replace the wiring
between TF1 terminals 41 and 42 and EMG module CRR3
terminals 1 and 3. F4 F5
5A 5A
If voltage is out of tolerance  continue.
4. TROUBLESHOOTING

MARMMTRBL02303E 445

Table 424. (Contd) SRVO-007 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
6. At the ALC relay, terminals 23 and 13, measure again for Multi-Tap Transformer 01-26
100VAC  10%.
If the voltage is within tolerance  check for proper operation A1 A2
of the ALC relay. 13 23

31 1 3 5 41
32 2 4 6 42

14 24

7. Remove power from the controller, and with an ohmmeter test Multi-Tap Transformer 01-23
fuses F4 and F5.
If F4 and F5 are good  transformer TF1 is not outputting 41 42
100VAC on its secondary legs and needs replacing.

F4 F5
5A 5A
4. TROUBLESHOOTING
MARMMTRBL02303E
446

Figure 510. External Emergency Stop Circuitry


4. TROUBLESHOOTING

MARMMTRBL02303E 447

4.4.9 Indicates one of two symptoms:


SRVO-008 ER_SVAL  The 5A brake fuse on the EMG module has blown.
Brake fuse blown  A momentary surge of high current was detected in the brake circuit.
The FALM LED on the EMG module will be lit.
Remedy: By turning power off momentarily and then back on you will
reset the circuit and the LED will go out if the fault is caused by a current
surge.

If the fault does not reset or if it reoccurs frequently, perform the


following troubleshooting procedure:

Table 425. SRVO-008 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
1. Turn off the controller at the main disconnect and open
the cabinet door.
2. Remove all of the connectors on the front of the EMG
module and pull out the module.
3.Check the 5A fuse and replace it if necessary. EMG 03-19
PCB

4. Place the EMG control printed circuit board back in its


slot and plug all connectors back into it.
4. TROUBLESHOOTING
MARMMTRBL02303E
448

Table 425. (Contd) SRVO-008 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
5. Using an ohmmeter, test the continuity between CRR3
CRR3, terminal 19 and the following points to test for a
shorted brake coil: 1 100IN1
2 OP1
 CRR5 pins 1B, 2B, 3B, 1D, 2D, 3D 3 100IN2
4 OP2 04-10 thru 04-38
 CRR3 terminals 16, 18, and 20 (extended 5 100IN3
axes only) 6 EMGIN1
7 100IN4
A short or resistance lower than 50 ohms could cause 8 EMGINC
9
the fuse to blow or the sensor to trip. Replace the 10 EMGIN2
motor on the axis with the shorted brake coil. 11 100OUT1
12 100OUT1
If the resistance is OK  continue. 13
14
100OUT2
100OUT2
15 BKP4
16 BKM4
17 BKP5
18 BKM5
19 BKP6
20 BKM6

BRK4 NOT
USED
BRK5 BRK6

FALM
D CB A
BRK1 SON

BRK BRK2 BRK3


CRR5

1 100OUT3
2 EMGOU2
3 100OUT4
4 EMGOUTC
5 FENCE1
6 EMGOUT1
7 FENCE2
8 EX-ON
9 0V
10 EX-COM
11 0V
12 EX-OFF
13 5v
14 DIL1
15 15V
16 DIL2
17 -15V
18 EMGB1
19 +24V
20 EMGB2

CRR4
VIOLET BLUE VIOLET BLUE
BKM3 BKP3 BKM2 BKP2
BKM3 BKP3 BKM2 BKP2
BKM3 BKP3 BKM1 BKP1
6. With the controller door open and all connectors and 03-32
plugs reattached, energize the controller.
If the FALM light comes on  replace the EMG
module.
4. TROUBLESHOOTING

MARMMTRBL02303E 449

Table 425. (Contd) SRVO-008 Troubleshooting Procedure


Troubleshooting Procedure Illustration Chapter 13
Print Reference
7. Power up the robot and jog the robot to verify robot
operation.
If the FALM light comes on  replace the EMG
module.

9. If this problem occurs occasionally, change the SET EMG CONTROL MODULE
jumper from 2 to 1 on the EMG module. 0337
SENSITIVITY
JUMPER

SET
2
4. TROUBLESHOOTING
MARMMTRBL02303E
450

Figure 511. Brake Fuse Blown Circuitry


4. TROUBLESHOOTING

MARMMTRBL02303E 451

4.4.10 Teach pendant deadman switch released while enabled.


SRVO-011
Remedy: Press the deadman switch, then press RESET.
ER_SVAL1
TP Released While
Enabled

4.4.11 Normal power is on (hot start).


SRVO-012
Remedy: This message is normal and does not indicate a problem.
ER_SVAL1
Power Failure
Recovery

4.4.12 One or all of the 24VDC cooling fans in the backplane cage are not
SRVO-014 running.
Fan Motor Abnormal Each double-board board cage in the backplane has a cooling fan mounted
(Group:i Axis:j) in its top. Each fan contains a centrifugal switch that opens when the fan
is not running.

Table 426. SRVO-014 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. With power on, test whether each fan is turning by passing a strip of paper over the top of each
board cage.
All fans are turning  go to step 3.
One fan is motionless  continue.
2. Remove the circuit boards from the board cage with the motionless fan. Reconnect the four-wire
connector on the backplane behind the board cage. Reinstall the boards and power up the controller.
If the fault is not fixed  replace the fan.
3. One of the fans or the axis control board is probably defective. Determine which part is bad by
temporarily replacing it with a known-good part.
If the fault is not fixed  continue.
4.Replace the backplane.
4. TROUBLESHOOTING
MARMMTRBL02303E
452

Figure 512. Backplane

AXIS BACKPLANE
24V
CA39C
1 +24VDC

5V OPTION 1 & 2 PCB


CA39C COOLING FAN
2 +0VDC

CA39C CENTRIFUGAL
JRA2 3 ALMC
E71 13
6 *FMM ALM
RV IC13
(SVRO 014
FAN MOTOR CA39B
1 +24VDC
ABNORMAL)
AXIS & MAIN PCB
CA39B COOLING FAN
2 +0VDC

CA39B CENTRIFUGAL
IC11 3 ALMB

CA39A
1 +24VDC

EMG & PSU PCB


0V CA39A
2 +0VDC COOLING FAN

CA39A CENTRIFUGAL
IC12 3 ALMA

0V
4. TROUBLESHOOTING

MARMMTRBL02303E 453

4.4.13 The temperature in the controller is too high, or the overheat sensor
SRVO-015 located on the backplane has opened.
ER_SVAL1
System Over Heat
(Group:i Axis:j)

Table 427. SRVO-015 Troubleshooting Procedure


Troubleshooting Procedure Line No. Reference
Chapter 13
1. Clean the controller air filter, allow the controller to cool down, and cold start the controller.
2. Check the heat exchanger fans for operation.
If the fans run ok replace the axis control board. 02-02
02-04
If one or more fans do not work  continue. 02-07
3. Check the AC voltage at the terminals of the non-working fan(s).
If the voltage is 180VAC 220VAC  replace the fan(s).
If the voltage is out of tolerance  replace or repair the fan motor wiring harness.

Figure 513. System Over Heat Circuitry Drawing 1


4. TROUBLESHOOTING
MARMMTRBL02303E
454

Figure 514. System Over Heat Circuitry Drawing 2


4. TROUBLESHOOTING

MARMMTRBL02303E 455

4.4.14 The axis control board sends a signal to the servo amplifiers in order to
SRVO-021 energize the MCC contactors and turn on the servo amplifiers. When a
servo amplifier MCC coil is turned on, it sends a signal back to the axis
ER_SVAL1 control board. If the axis control board sends its signal and does not
SRDY off receive the reply within a few milliseconds, this alarm occurs.
(Group:i Axis:j)
Table 428. SRVO-021 Troubleshooting Procedure
Troubleshooting Procedure Line No. Reference
Chapter 13
1. Does the alarm occur on three or more axes? 08-17
YES  repair or replace the wiring harness between the EMG board and terminals 5 and 6 of the 09-18
servo amplifier in the far left position. 10-17
09-01 thru 09-09
NO  continue
2. Disconnect and reseat the signal cable between the axis control board and the affected servo 10-01 thru 10-18
amplifier. If necessary, continue.
3. Exchange the axis control board-to-servo amplifier cable between the affected axis and a known-
good axis. Be sure to switch both ends of the cables.

Does the fault message change to indicate a different axis?


YES  replace the bad cable.
NO  continue
4. Replace the axis control board. If the problem continues, replace the affected servo amplifier.

4.4.15 The axis control board sends a signal to the servo amplifiers in order to
SRVO-022 energize the MCC contactors and turn on the servo amplifiers. When a
servo amplifier MCC coil is turned on, it sends a signal back to the axis
ER_SVAL1 control board. If the axis control board receives the reply signal without
SRDY on having sent its request signal, this alarm occurs.
(Group:i Axis:j)
Table 429. SRVO-022 Troubleshooting Procedure
Troubleshooting Procedure Line No. Reference
Chapter 13
1. Exchange the axis control board-to-servo amplifier cable between the affected axis and a known- 09-01 thru 09-09
good axis. Be sure to switch both ends of the cables. 08-01 thru 08-18
10-10 thru 10-18
Does the fault message change to indicate a different axis?
YES  replace the bad cable.
NO  continue
2.Replace the axis control board. If the problem continues, replace the affected servo amplifier.
4. TROUBLESHOOTING
MARMMTRBL02303E
456

4.4.16 The axis position is too far from its commanded position when the robot is
SRVO-023 stopping, or the robot is stopped and it will not move. The torque
necessary to decelerate an overloaded motor could cause this alarm to
ER_SVAL1 occur.
Stop Error Excess
(Group:i Axis:j)

Table 430. SRVO-023 Troubleshooting Procedure


Troubleshooting Procedure Line No. Reference
Chapter 13
1. Is the load over the specification?
If it is over  Reduce the load.
2. Check for a binding axis. Repair if required.
If the load is within the specification and the axes are not binding  Go to step 3.
3. Is the three phase input voltage lower than the FANUC specification (170V ~253V)? 08-24, 25, 26
If it is lower  The maximum torque of the motor decreases. Increase the input voltage within the 09-23, 24, 25
rated voltage. Check transformer TF1 for proper tap settings. 10-23, 24, 25
4. Replace the servo amplifier.
If the alarm occurs again  Go to step 4.
5. Replace the motor.

4.4.17 The servo error is too big when the robot is moving, or the robot moves
SRVO-024 when it is supposed to be stopped.
ER_SVAL1 Remedy: Same as SRVO-023, Stop Error Excess.
Move Error Excess
(Group:i Axis:j)

4.4.18 The motor cannot rotate as fast as the calculated speed required for the
SRVO-026 current motion
ER_WARN Remedy: Even though this is just a warning, every attempt should be
Motor Speed Limit made to eliminate this error by modifying the programmed speed or
(Group:i Axis:j) motion.

4.4.19 The system variable $master_done is set to FALSE.


SRVO-027
Remedy: Master the robot.
ER_WARN
Robot Not Mastered
(Group:i Axis:j)
4. TROUBLESHOOTING

MARMMTRBL02303E 457

4.4.20 The system variable $calibrate is set to FALSE.


SRVO-033
Remedy: Calibrate the robot.
ER_WARN
Robot Not Calibrated
(Group:i Axis:j)

4.4.21 Joint cannot rotate as fast as the calculated speed required for the current
SRVO-035 motion.
ER_WARN Remedy: Even though this is just a warning, every attempt should be
Joint Speed Limit made to eliminate this error by modifying the programmed or motion
(Group:i Axis:j) speed.

4.4.22 The robot is not in position for the specified period, or the servo error is in
SRVO-036 excess of the commanded position when the robot is stopping, or the robot
is stopped and it will not move. The torque necessary to decelerate an
Imposition Time Over overloaded motor could cause this alarm to occur.
(Group:i Axis:j)

Table 431. SRVO-036 Troubleshooting Procedure


Troubleshooting Procedure Line No. Reference
Chapter 13
1. Is the load over the specification?
If it is over  Reduce the load.
2. Check for a binding axis. Repair if required.
If the load is within the specification and the axes are not binding  Go to step 3.
3. Is the three phase input voltage to the servo amplifier lower than the FANUC specification 08-24, 25, 26
(170V ~253V)? 09-23, 24, 25
If it is lower  Check transformer TF1 for the proper tap setting. 10-23, 24, 25
4. Replace the servo amplifier.
If the alarm occurs again  Go to step 4.
5. Replace the motor.

4.4.23 IMSTP (immediate stop) UOP input asserted.


SRVO-037
Remedy: If using a UOP, determine the cause and repair. If not using
ER_SVAL1 UOP, select the I/O menus and zero UOP mapping.
IMSTP Input
(Group:i Axis:j)
4. TROUBLESHOOTING
MARMMTRBL02303E
458

4.4.24 When the controller was powered up, one or more of its axes was at a
SRVO-038 different position from when it was powered off. This might occur when a
motor is replaced or when a CPU from one controller is installed in
PULSE MISMATCH another.
(Group:i Axis:j)
Remedy: Perform the following procedure:

Table 432. SRVO-038 Troubleshooting Procedure


Troubleshooting Procedure Line No. Reference
Chapter 13
1. Press MENUS.
2. Select SYSTEM.
3. Press F1, [TYPE].
4. Select System Variables.
5. Move the cursor to $MCR.
6. Press ENTER.
7. Move the cursor to $SPC_RESET.
8. Press F4, TRUE. The display will reset to false. This is normal.
9. Press RESET.
The fault condition should reset. If the controller is still faulted with additional servo-related
errors, cold start the controller.

It might be necessary to remaster the robot.

4.4.25 The servo amplifier magnetic contactor (MCC) is welded closed. If the
SRVO-042 contact of the magnetic contactor is already closed when the contactor is
turned on, this alarm circuit regards the contact as welded closed and the
ER_SVAL2 MCC alarm occurs.
MCAL Alarm
(Group:i Axis:j)
Table 433. SRVO-042 Troubleshooting Procedure
Troubleshooting Procedure Line No. Reference
Chapter 13
1. Does this alarm occur with SRVO-049? 08-24, 25, 26
If SRVO-049 occurs  Check for the absence of input three-phase voltage to the servo amplifer. 09-23, 24, 25
Correct as necessary. 10-23, 24, 25

If SRVO-049 does not occur  Go to step 2


2. Does this alarm occur with the OH1 alarm?
If OH1 alarm occurs  Turn off the controller power for fifteen seconds and turn it on again. If still
present, remove and replace the connector CN1 or CN2 of the problem axis and check its
associated cable and connector at the axis module.
If OH1 alarm does not occur  Go to step 3.
3. Replace the servo amplifier.
4. TROUBLESHOOTING

MARMMTRBL02303E 459

4.4.26 The motion command after the ramping algorithm in the servo software
SRVO-041 exceeded one word. Contact the FANUC Robotics Hotline for more
information. DO NOT INCLUDE IN MANUAL!!!!!!
MOFAL Alarm
(Group:i Axis:j)
4. TROUBLESHOOTING
MARMMTRBL02303E
460

4.4.27 The regenerative energy produced by the motor exceeded the specification.
SRVO-043
NOTE Energy feedback from motor to the amplifier is called regenerative
ER_SVAL2 energy. This occurs when the axis is being slowed down. The amplifier
DCAL Alarm discharges this energy by converting it to heat energy through the
(Group:i Axis:j) discharge resistor. If the charged energy exceeds the discharged energy,
this alarm occurs.

Remedy: Check the LED of the amplifier, then perform the following
troubleshooting procedure.

Table 434. SRVO-043 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Is 4 or 5 indicated on the servo amplifier 7-segment display?
If indicated  Go to step 2 if 4 is indicated.
Go to step 3 if 5 is indicated.
If not indicated  Check for short to ground or an open circuit in the PWMC line of the specified 08-03, 09-03
axis between the axis control printed circuit board and servo amplifier (connector JV-1 7). Swap
11-03, 12-03
the axis control printed circuit board.
2. A 4 is indicated (DCSW alarm) when the regenerative transistor is on continuously for one 11-37, 12-37
second or longer. Reduce the load of the robot. 08-37, 09-37
If the error still exists  Replace the servo amplifier.
3. 5 is indicated (DCOH alarm). The DCOH alarm is caused when the regenerative resistor 11-39, 12-39
overheats and is sensed by the thermostat or the thermostat in transformer TF1 opens. 08-39, 09-39
If the average regenerative energy is excessive  This alarm occurs when the
acceleration/deceleration frequency is high or gravity energy at the axis is large. Relax the
operating conditions.
For robots with extended axes: When a separate regenerative discharge unit or power
transformer for the servo controller is used, check the wiring for the thermostat according to the
connection diagrams for proper wiring.
If the thermostat is incorrectly wired or is defective  When a separate regenerative discharge
unit or power transformer for the servo controller is used, check the wiring for the thermostat
according to the connection diagrams.
4. TROUBLESHOOTING

MARMMTRBL02303E 461

4.4.28 The DC voltage on the main power circuit of the servo amplifier exceeded
SRVO-044 specification.
ER_SVAL2 Remedy: Check the three-phase voltage to the servo amplifier input. It
HVAL Alarm should not exceed 253 VAC phase-to-phase. Check the cabling between
(Group:i Axis:j) the servo amplifier and the axis control printed circuit board if no alarm is
indicated on the servo amplifier 7-segment display.

If the problem still exists, perform the following troubleshooting


procedure:

Table 435. SRVO-044 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Is the voltage of the threephase input servo to the amplifier higher than 253 VAC? 08-24, 25, 26
If it is higher  Check transformer TF1 taps. 09-23, 24, 25
01-38
2. Is the load of the robot within the specification? This alarm can be caused by the charge of the
regenerative energy when the load exceeds the specification.
If it exceeds the specification  Reduce the load of the robot.
3. Check the connection of the Separated Regenerative Discharge Unit. If one is being used, it should
be wired across terminals 17 and 19 of T1 and connected to terminals 1 and 2 of T3 on the discharge
unit. There should be no jumper connecting terminals 17 and 18.
If connected incorrectly  Connect correctly.
4. Check the resistance of the built-in regenerative resistor of the amplifier or that of the separate 11-39
regenerative resistor (14 ohms) across terminals 17 and 19 of T1.
If the value of the resistance is incorrect  Replace the regenerative discharge unit or servo
amplifier.
5. For robots with extended axes: The operating condition might not be appropriate for the
specification of the motor or the amplifier.
If this occurs  Relax the operating condition.
6. Replace the servo amplifier.
4. TROUBLESHOOTING
MARMMTRBL02303E
462

4.4.29 The current in the main power circuit of the servo amplifier exceeded
SRVO-045 specification. The servo amplifier LED should display 8, 9, or 6.
ER_SVAL2 Remedy: If no alarm is indicated on the servo amplifier 7-segment
HCAL Alarm display, check the cabling between the servo amplifier (CN1) and the axis
(Group:i Axis:j) control printed circuit board (JV1-10).
If the problem still exists, perform the following troubleshooting
procedure:
Table 436. SRVO-045 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Disconnect the motor power lines from the amplifier terminals and turn on the power. This alarm will 08-24, 25, 26
re-occur if 09-23, 24, 25
 The transistor module (TM) is defective. 10-23, 24, 25
 Resistor R3 has opened or raised resistance.
 The servo amplifier is defective.
If an HCAL alarm occurs  Replace these components as necessary or replace the servo
amplifier.
2. Remove the motor power lines from the amplifier terminals and check the continuity between GND 08-24, 25, 26
and each of the lines U, V, and W that go to the motor. 09-23, 24, 25
If any are short-circuited  Go to step 3. 10-23, 24, 25

If all are not shorted  Go to step 4.


3. Remove the power lines from the motor connectors (J1-6) and recheck the continuity between GND 08-24, 25, 26
and each of the lines U, V, and W to the robot motor. 09-23, 24, 25
If any are shorted  The motor is defective. Replace the motor. 10-23, 24, 25

If all are open  The power lines to the motor are defective. Replace the cable.
4. Remove the motor power lines from the amplifier terminals and measure the resistance 08-24, 25, 26
between U-V, V-W, and W-U on the servo amplifier using a measuring instrument sensitive 09-23, 24, 25
enough to detect small resistances. 10-23, 24, 25
If the three measured values are the same  Go to step 5.
If the three measured values are different  Go to step 6.
5. Remove the power lines from the motor connectors and remeasure the resistance between U-V, 08-24, 25, 26
V-W, and W-U using a measuring instrument sensitive enough to detect small resistances. 09-23, 24, 25
If the three measured values are the same  The power lines are defective. Replace the cable. 10-23, 24, 25

If the three measured values are different  The motor is defective. Replace the motor.
6. Replace the axis control printed circuit board. 08-12, 13
If the alarm occurs again  Go to step 7.
7. Replace the servo amplifier.
8. Replace the serial pulse coder on the motor.
9. Check whether you are using the robot under conditions that exceed the specification. For
example, load, duty, and so forth. If there is no mechanical reason (binding and so forth) to cause this
alarm, this alarm might occur under conditions that exceed the specification. If you are using the robot
over the specification, relax the operating conditions.
4. TROUBLESHOOTING

MARMMTRBL02303E 463

4.4.30 The average current calculated by the servo software exceeded


SRVO-046 specification.
ER_SVAL2 Remedy: Reduce the load on the robot.
OVC Alarm
(Group:i Axis:j) If the problem still exists, perform the following troubleshooting
procedure:

Table 437. SRVO-046 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Is the three-phase AC input power to the servo amplifier lower than 200 VAC? 08-24, 25, 26
If it is lower or missing  Check transformer TF1 taps and fuses. 09-23, 24, 25
10-23, 24, 25
01-15, 16

2. Replace the axis control printed circuit board. 08-11, 12, 13


If the alarm occurs again  The motor is defective.
4. TROUBLESHOOTING
MARMMTRBL02303E
464

4.4.31 The DC voltage on the main power circuit of the servo amplifier is lower
SRVO-047 than the specification even though the MCC is on.
ER_SVAL2 Remedy: If no alarm is indicated on the servo amplifier LED, check the
LVAL Alarm cabling between the servo amplifier and the axis control printed circuit
(Group:i Axis:j) board.

If the problem still exists, perform the following troubleshooting


procedure:

Table 438. SRVO-047 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Does the LED of the amplifier indicate 2? 08-23, 24, 25
a. Check for 200VAC input power to terminals 13 and 14 of the servo amplifier. If low or missing, 09-23, 24, 25
check transformer TF1 taps and fuses. 10-23, 24, 25

b. If 200VAC is present, replace the servo amplifier.


2. Does the LED of the amplifier indicate 3? A 3 indicates the DC current in the main power circuit 08-23, 24, 25
is too low 09-23, 24, 25
a. Check the three-phase 200VAC input voltage to the servo amplifier. 10-23, 24, 25

If the voltage is lower than 200VAC Check the transformer TF1 taps and fuses.
b. Did the circuit breaker on the servo amplifier trip? (If a circuit breaker trips, this alarm will occur.)
If a circuit breaker trips  Turn on the breaker. If it trips again, replace the servo amplifier.
3. Does the LED of the amplifier indicate a 7? This alarm could occur when the contact of the
magnetic contactor is melted (welded together).
Refer to the SRVO-042 MCAL Alarm.
4. TROUBLESHOOTING

MARMMTRBL02303E 465

4.4.32 The servo amplifier overheated. Servo amplifier LED indicates a 6.


SRVO-049 This alarm indicates that the thermal switch mounted on the PC board of
the specified axis has opened.
ER_SVAL2
OHAL1 Alarm Remedy: Check the fans and the heat exchange unit for proper operation.
(Group:i Axis:j)
If the problem still exists, perform the following troubleshooting
procedure:

Table 439. SRVO-049 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. If the servo amplifier 7-segment display shows , check the cabling between the servo amplifier 08-01 thru 08-08
(CN1) and axis control module (JV1-6). 09-01 thru 09-09
10-10 thru 10-18
2. Relax the operating condition.

If the alarm no longer occurs  The operating condition of the robot exceeded the specification.
3.Replace the servo amplifier.

4.4.33 The servo software detected a disturbance torque that was too high or a
collision occurred and tripped a collision detection alarm.
SRVO-050
ER_SVAL1 Remedy: Reset the robot by using the teach pendant RESET button and
CLALM Alarm jog the robot away from obstructions.
(Group:i Axis:j)
If the problem still exists, perform the following troubleshooting
procedure:

Table 440. SRVO-050 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Does the load exceed the specifications? (When the robot moves over the specifications, the esti-
mated disturbance torque might become larger and this alarm could occur.)
If the load exceeds the specifications Lower the load to within the specifications.
2. Is the three-phase AC input voltage to the servo amplifier lower than the rated voltage (200VAC)? 08-23, 24, 25
If it is lower  Check transformer TF1 taps and fuses. 09-23, 24, 25
10-23, 24, 25
01-38

3. Replace the servo amplifier.


4. TROUBLESHOOTING
MARMMTRBL02303E
466

4.4.34 The feedback current is abnormal.


SRVO-051
ER_SVAL2
CUER Alarm
(Group:i Axis:j)

Table 441. SRVO-051 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Replace the axis control printed circuit board. 08-11, 12, 13
If the alarm still occurs  Go to step 2.
2. Replace the servo amplifier. If the alarm continues, go to step 3.
3. Replace the pulse coder and master the robot.

4.4.35 The clock for the rotation counter in the pulse coder is abnormal.
SRVO-061
ER_SVAL2
CKAL Alarm
(Group:i Axis:j)

Table 442. SRVO-061 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard SRVO_061 and refer to the remedy of any of the other three alarms.
If no alarms occur  Replace the pulse coder on the specified axis and master the robot.
4. TROUBLESHOOTING

MARMMTRBL02303E 467

4.4.36 The battery voltage for the pulse coders is zero volts.
SRVO-062
ER_SVAL2
BZAL Alarm
(Group:i Axis:j)

Table 443. SRVO-062 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard the BZAL alarm and refer to the procedure for the other alarm (SRVO_68
SRVO_70).
NO  Continue
2. Did this alarm message list only one axis?
YES  Check the battery cable for the pulse coder of the axis listed in the alarm message.
Reconnect, repair, or replace as necessary. Go to Step 4.
NO  Continue
3. Press the teach pendant emergency stop button. Turn the controller on. Check the batteries behind
the black plastic hatch in the base of the controller.

Are the batteries ok?


YES  Repair or replace the battery compartment cable. Go to Step 4.
NO  Replace the batteries. Go to Step 4.
4. a. Press MENUS.
b. Select SYSTEM.
c. Press F1, [TYPE].
d. Select System Variables.
e. Move the cursor to $MCR.
f. Press ENTER.
g. Move the cursor to $SPC_RESET.
h. Press F4, TRUE. The display will reset to false. This is normal.
i. Press RESET. The fault condition should reset. If the controller is still faulted with additional
servo-related errors, cold start the controller.
It might be necessary to remaster the robot.
4. TROUBLESHOOTING
MARMMTRBL02303E
468

4.4.37 The built-in rotation counter on the pulse coder is abnormal.


SRVO-063
ER_SVAL2
RCAL Alarm
(Group:i Axis:j)

Table 444. SRVO-063 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard SRVO_063 and refer to the remedy of any of the other three alarms.
NO  Replace the pulse coder on the specified axis and master the robot.

4.4.38 The relationship between the analog signals on the pulse coder are
SRVO-064 abnormal.
ER_SVAL2
PHAL Alarm
(Group:i Axis:j)
Table 445. SRVO-064 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard SRVO_064 and refer to the remedy of any of the other three alarms.
NO  Replace the pulse coder on the specified axis and master the robot.

4.4.39 The pulse coder batteries are low.


SRVO-065
ER_WARN
BLAL Alarm
(Group:i Axis:j)
Table 446. SRVO-065 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard SRVO_065 and refer to the remedy of any of the other three alarms.
NO  Replace the APC backup batteries. Remaster the robot if necessary.
NOTE Replace the battery as soon as possible when this alarm occurs, otherwise, if the battery volt-
age goes to zero volts, the robot will require remastering.
4. TROUBLESHOOTING

MARMMTRBL02303E 469

4.4.40 The pulse coder ROM checksum data are abnormal.


SRVO-066
ER_SVAL2
CSAL Alarm
(Group:i Axis:j) Table 447. SRVO-066 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm?
YES  disregard SRVO_066 and refer to the remedy of any of the other three alarms.
If no alarms occur  Replace the pulse coder on the specified axis and master the robot.

4.4.41 The pulse coder overheated.


SRVO-067
ER_SVAL2
OHAL2 Alarm
(Group:i Axis:j) Table 448. SRVO-067 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Did a SRVO-068 DTERR, or SRVO-069 CRCERR, or a SRVO-070 STBERR occur with this alarm? 07-22
YES  disregard SRVO-067 and refer to the remedy of any of the other three alarms.
2. Does the operating condition (load, duty) exceed the specifications?
If the operating condition exceeds the specifications  Relax the operating condition within the
specification. (Reduce the load, change the program, etc.)
3. Turn off the controller and when the temperature of the motor returns to normal, turn it back on.
If the alarm immediately occurs again  The built-in thermostat in the pulse coder is defective.
Replace the pulse coder.
If the alarm occurs again, but not immediately  the motor is generating too much heat. Replace
the motor.
4. TROUBLESHOOTING
MARMMTRBL02303E
470

4.4.42 The axis control printed circuit board sent the serial data request signal to
SRVO-068 the pulse coder, but did not receive serial data from the pulse coder.
ER_SVAL2
DTERR Alarm
(Group:i Axis:j) Table 449. SRVO-068 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Check for connection and continuity of the feedback cable. Repair or replace if necessary. 08-16, 17, 18
If the alarm occurs again  Go to step 2.
2. Replace the axis control board. 08-01 thru 10
If the alarm occurs again  Go to step 3.
3. Replace the pulse coder and master the robot.

4.4.43 The serial data from the pulse coder changed during communication to the
SRVO-069 axis control printed circuit board.
ER_SVAL2 Refer to the SRVO_068 remedy.
CRCERR Alarm
(Group:i Axis:j)
4. TROUBLESHOOTING

MARMMTRBL02303E 471

4.4.44 The communication stop and start bits are abnormal.


SRVO-070
Refer to the SRVO-068 remedy.
ER_SVAL2
STBERR Alarm
(Group:i Axis:j)

4.4.45 The feedback velocity exceeds the specifications.


SRVO-071
If the problem still exists, perform the following troubleshooting
ER_SVAL2 procedure:
SPHAL Alarm
(Group:i Axis:j)

Table 450. SRVO-071 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Does this alarm occur with any other alarm?
If another alarm occurs  This alarm is caused by another alarm of the serial pulse coder. Refer to
the other alarm for details.
2. Reduce the load within the specifications.

4.4.46 Line Tracking Overflow Error.


SRVO-081
ER_WARN
EROFL Alarm
(Track encoder:n)
Table 451. SRVO-081 Troubleshooting Procedure
Troubleshooting Procedure Chapter 13
Print Reference
1. Check the connection between the controller and the line tracking device (absolute encoder or
pulse generator).
2. Check that the line speed is within the FANUC specification.
If the line speed is not within the specification  Relax the line speed.
4. TROUBLESHOOTING
MARMMTRBL02303E
472

4.4.47 Line Tracking Pulse coder is disconnected.


SRVO-082
Remedy: Check axis control printed circuit board for proper line tracking
ER_WARN cable connections.
DAL Alarm
(Track encoder:n) If the problem still exists, perform the following troubleshooting
procedure:

Table 452. SRVO-082 Troubleshooting Procedure


Troubleshooting Procedure Chapter 13
Print Reference
1. Replace the axis control printed circuit board.
2. Replace the pulse coder.

4.4.48 The clock for the rotation counter in the line tracking pulse coder is
abnormal.
SRVO-083
ER_WARN Remedy: Refer to SRVO-061 remedy.
CKAL Alarm
(Track encoder:n)

4.4.49 The battery voltage for the line tracking pulse coder is zero volts.
SRVO-084
Remedy: Refer to SRVO-062 remedy.
ER_WARN
BZAL Alarm
(Track encoder:n)

4.4.50 The built-in rotation counter on the line tracking pulse coder is abnormal.
SRVO-085
Remedy: Refer to SRVO-063 remedy.
ER_WARN
RCAL Alarm
(Track encoder:n)

4.4.51 The relationship between the analog signals on the line tracking pulse
SRVO-086 coder are abnormal.
ER_WARN Remedy: Refer to SRVO-064 remedy.
PHAL Alarm
(Track encoder:n)
4. TROUBLESHOOTING

MARMMTRBL02303E 473

4.4.52 The line tracking pulse coder batteries are low.


SRVO-087
Remedy: Refer to SRVO-065 remedy.
ER_WARN
BLAL Alarm
(Track encoder:n)

4.4.53 The line tracking pulse coder ROM checksum data is abnormal.
SRVO-088
Remedy: Refer to SRVO-066 remedy.
ER_WARN
CSAL Alarm
(Track encoder:n)

4.4.54 The line tracking pulse coder overheated.


SRVO-089
Remedy: Refer to SRVO-067 remedy.
ER_WARN
OHAL2 Alarm
(Track encoder:n)

4.4.55 The axis control printed circuit board sent the request signal, but did not
receive serial data from the line tracking pulse coder.
SRVO-090
ER_WARN Remedy: Refer to SRVO-068 remedy.
DTERR Alarm
(Track encoder:n)

4.4.56 The serial data from the line tracking pulse coder changed during
communication to the axis control printed circuit board.
SRVO-091
ER_WARN Remedy: Refer to SRVO-069 remedy.
CRCERR Alarm
(Track encoder:n)

4.4.57 The communication stop and start bits for line tracking axis are abnormal.
SRVO-092
Remedy: Refer to SRVO-070 remedy.
ER_WARN
STBERR Alarm
(Track encoder:n)

4.4.58 The feedback velocity exceeds the specification for line tracking axis.
SRVO-093
Remedy: Refer to SRVO-071 remedy.
ER_WARN
SPHAL Alarm
(Track encoder:n)
MARMMTRBL02303E 5 REPLACING A FUSE

If a fuse blows in the control unit, eliminate the cause, then replace the
51

fuse.

5.1 F2, F2, and F3 : Fuses for three-phase 200 VAC servo power
F4 and F5 : Fuses for 100 VAC
MULTI-TAP
Refer to Table 51.
TRANSFORMER
Table 51. Multi-Tap Transformer Fuses
Rated
Fuse Number Machine Part Number
Current
S-420, S-500, 30A A60L-0001-0042#JG130
S-800, S-900,
M-500
F1, F2, F3 P-155 30A A60L-0001-0042#JG130
F1, F2, F3 ARC Mate SR., 20A A60L-0001-0042#JG120
S-700, M-400,
L-1000, S-10
ARC Mate, Arc 10A A60L0001-0042#JG1-10
Mate 100, A-510,
S-5
F4, F5 P-155 7.5A A60L-0001-0101#P475H
F4, F5 S-420, S-500, 7.5A A60L-0001-0101#P475H
S-800, S-900,
M-500
ARC Mate Sr., 5A A60L-0001-0101#P450H
ARC Mate, S-5,
Arc Mate 100,
S-10, L-1000,
S-700, M-400,
A-510
F6, F7 S-420, 3-servo 10A A60L-0001-0042#JG1-10
amplifier
configuration
5. REPLACING A FUSE
MARMMTRBL02303E
52

Figure 61. Replacing a Fuse of the Transformer Unit

Fuse Fuse Fuse

Fuse

Fuse Fuse Fuse

WARNING
Before replacing a fuse, turn power off and lock out the
controller.
5. REPLACING A FUSE

MARMMTRBL02303E 53

5.2 FUSE 1 : Fuse for control power supply


Part number: A60L-0001-0175#3.2A
SERVO AMPLIFIER
FUSE 2 and 3 : Fuse for fan motors (only for one axis servo amplifier,
A06B-6066-H008)
Part number: A60L00010101#P405

Figure 62. Replacing the Fuse of a Servo Amplifier

F1

F2

F3

LED
Terminal board T1
Circuit breaker
5. REPLACING A FUSE
MARMMTRBL02303E
54

5.3 F1 and F2 : Fuses for AC input


F3 : Fuse for +24V
POWER SUPPLY UNIT
F4 : Fuse for +24E
F5 : Fuse for auxiliary power supply
Table 52. Power supply unit for four-slot backplane
Fuse number Rated current Part Number
F1, F2 7.5A A60L-0001-0245#GP75
F3 3.2A A60L-0001-0075#3.2
F4 5A A60L-0001-0046#5.0
F5 0.3A A60L-0001-0290#LM03

Table 53. Power supply unit for six-slot backplane


Fuse number Rated current Part Number
F1, F2 10A A60L-0001-0245#G100
F3 5A A60L-0001-0075#5.0
F4 5A A60L-0001-0046#5.0
F5 0.3A A60L-0001-0290#LM03

Figure 63. Replacing a Fuse of the Power Supply Unit

PSU PSU

F1 and F2:
Fuses for AC input
F5: 0.3A fuse for 10-A for 6-slot backplane
7.5A for 4-slot backplane
auxiliary
power supply
PIL: green LED
for indicating the AC
Battery cover power supply status
Battery

ALM: Red LED


for indicating
an alarm

F4:5Afuse for +24E

F3: Fuse for +24V


5-A slow blow for
6-slot backplane
3.2A slow blow for
4-slot backplane (with battery cover removed)
5. REPLACING A FUSE

MARMMTRBL02303E 55

5.4 FUSE : 5.0 A brake circuit fuse


Part number: A60L-0001-0046#5.0
EMERGENCY STOP
CONTROL PC BOARD
FUSE : F1, F2, 3.2A Manual brake circuit fuse
Part number: A60L-0001-0175#3.2A

Figure 64. Replacing the Fuse on the Emergency Stop Control PC Board

F1

F2

FUSE
5. REPLACING A FUSE
MARMMTRBL02303E
56

Figure 65. Replacing the Fuse on the Emergency Stop Control PC Board

EMG
PCB

Fuse

5.5 FUSE: F11, F12, 3.2A AC Input Line Fuses


Part Number: A60L00010175#3.2
PURGE POWER
SUPPLY
A05B2047C181
5. REPLACING A FUSE

MARMMTRBL02303E 57

Figure 66. Purge Power Supply

Cover

F12

F11

Purge Power Supply


5. REPLACING A FUSE
MARMMTRBL02303E
58

5.6 FUSE 1 : 2.0-A fuse for +24V


Part number: A60L-0001-0046#2.0
PROCESS
INPUT/OUTPUT PC Figure 67. Replacing the Fuse of the Process Input/Output PC Board AA, AB,
BOARDS AA, AB, CA, CA, CB, or DA
CB, AND DA Fuse

Fuse

Process input/output Process input/output


PC boards AA and AB PC boards CA, CB and DA
5. REPLACING A FUSE

MARMMTRBL02303E 59

5.7 FUSE 1 to 8 : 6.3 A fuses for +24V


Part number: A60L-0001-0046#6.3
PROCESS
INPUT/OUTPUT PC Figure 68. Replacing the Fuse of the Process Input/Output PC Board BA or BB
BOARDS BA AND BB

Fuse

Process input/output PC boards BA and BB


5. REPLACING A FUSE
MARMMTRBL02303E
510

5.8 The modules listed below have built-in fuses. If a fuse blows, remove the
cause, then replace the fuse with a spare.
MODULAR I/O UNIT
Table 54. Modular I/O Unit
Module Indication Rating Fuse Specification
Interface module A1F01A PWR is off 3.2A A60L-0001-0290=LN32
Interface module A1F01B PWR is off 3.2A A60L-0001-0290=LM32
Output module with 8 DC F is on 5A A60L-0001-0260=5R00
points AOD08C
Output module with 8 DC F is on 5A A60L-0001-0260=5R00
points AOD08D
Output module with 5 AC F is on 3.15A A60L-0001-0276=3.15
points AOA05E
Output module with 8 AC F is on 3.15A A60L-0001-0276=3.15
points AOA08E
Output module with 12 AC F is on 3.15A A60L-0001-0276=3.15
points AOA12F

The fuses are on the PC boards in the modules.


5. REPLACING A FUSE

MARMMTRBL02303E 511

5.9 FUSE : 2.0 A fuse for 100 VAC


Part number: A60L-0001-0101#P420H
AC OUTLET UNIT
Figure 69. Replacing the Fuse of the AC Outlet Unit

Fuse
MARMMTRBL02303E 6 BRAKE RELEASE

To perform some troubleshooting and error recovery procedures, you


61

might have to release the brakes. Use Procedure 61 to release the brakes.

Procedure 61 Releasing the Brakes

NOTE Clear all E-stops before proceeding.

Step 1 Press and release the EMERGENCY STOP button.

NOTE Do not press RESET. The servos must be off to release the
brakes.

2 Press MENUS.
3 Select NEXT PAGE.
4 Select SYSTEM.
5 Press F1, [TYPE].
6 Select Brake Ctrl. See the following screen for an example.
SYSTEM Brake Crtl JOINT 10%
AXIS SELECTED BRAKE STATE
1 NO ENGAGED
2 NO ENGAGED
3 NO ENGAGED
4 NO ENGAGED
5 NO ENGAGED
6 NO ENGAGED
7 NO ENGAGED
8 NO ENGAGED
9 NO ENGAGED

[TYPE] ENGSEL RELSEL YES NO >

7 Highlight the number of the axis you want to release or engage.

WARNING
Releasing a brake could cause the robot to move. To
STOP the robot immediately, press the EMERGENCY STOP
button or press F2, ENGSEL to engage the brake.
6. BRAKE RELEASE
MARMMTRBL02303E
62

8 To release or engage a single brake:


a Select an axis to be released or engaged; press F4, YES.

NOTE To release axis 3 you must select both axis 2 and axis 3.

b Release the brake on the selected axis; hold down the shift key
and press F3, RELSEL.
c Engage the brake on the selected axis; press F2, ENGSEL.
9 To release ALL brakes:
a Press NEXT, > to display the next page of function keys.

SYSTEM Brake Crtl JOINT 10%


AXIS SELECTED BRAKE STATE
1 NO ENGAGED
2 NO ENGAGED
3 NO ENGAGED
4 NO ENGAGED
5 NO ENGAGED
6 NO ENGAGED
7 NO ENGAGED
8 NO ENGAGED
9 NO ENGAGED

[TYPE] ENGALL RELALL GROUP >

WARNING
The following step will release all brakes even though they
have not been selected by pressing F4, YES. This could
result in robot movement. Be prepared for all brakes to be
released, as personnel could be injured, or equipment
damaged.

b Hold down the SHIFT key and press F3, RELALL to release all
of the brakes.
10 To engage ALL brakes:
a Press the F2, ENGALL to engage all of the brakes.
11 When you are finished, press RESET.

NOTE If you are unable to jog the robot after releasing the brakes, press
and release the EMERGENCY STOP button, and then press RESET to
clear the fault.
MARMMTRBL02303E 7 CONTROLLING I/O

Controlling I/O allows you to test the I/O in your system for proper
71

function during testing operation. Controlling I/O includes


 Forcing outputs
 Simulating inputs and outputs
 SOP I/O
7. CONTROLLING I/O

72 MARMMTRBL02303E

7.1 Forcing outputs is turning output signals on or off. Outputs can also be
forced within a program using I/O instructions. Use Procedure 71 to
FORCING OUTPUTS
force outputs outside of a program.
Refer to the application Specific Setup and Operations Manual for
information on using program I/O instructions.

NOTE RO[1] and RO[2] control HAND 1, and RO[3] and RO[4] control
HAND 2.

Procedure 71 Forcing Outputs

Condition  The outputs you are forcing have been configured.


Step 1 Press MENUS.
2 Select I/O.
3 Press F1, [TYPE].
4 Select the type of output you want to force: digital, analog, group,
robot, UOP, or SOP.

WARNING
Forcing digital outputs causes connected devices to
function. Make certain you know what the digital output is
connected to and how it will function before forcing it;
otherwise, injury to personnel or damage to equipment can
occur.
7. CONTROLLING I/O

MARMMTRBL02303E 73

For digital outputs for example, you will see a screen similar to the
following.

I/O Digital Out WORLD 10%


# SIM STATUS
DO[ 1] U OFF [ ]
DO[ 2] U ON [ ]
DO[ 3] U OFF [ ]
DO[ 4] U OFF [ ]
DO[ 5] U OFF [ ]
DO[ 6] U ON [ ]
DO[ 7] U OFF [ ]
DO[ 8] U OFF [ ]
DO[ 9] U OFF [ ]
DO[ 10] U OFF [ ]

[ TYPE ] CONFIG IN/OUT SIMULATE UNSIM

DO[ 4] U OFF 5 Move the cursor to the STATUS of the output you want to force.
6 Press the function key that corresponds to the value you want.
For digital, robot, UOP, and SOP outputs, press
 F4 for ON
 F5 for OFF
AO[ 4] U 12H For analog and group outputs, move the cursor to value, and use the
numeric keys to type the value. Value entry is always in decimal
format. To change the displayed value from decimal to hexadecimal,
press F4, FORMAT. Hexadecimal numbers are followed by an H
on the screen.
7. CONTROLLING I/O

74 MARMMTRBL02303E

7.2 Simulating inputs and outputs is forcing inputs and outputs without signals
entering or leaving the controller. Simulate I/O to test program logic and
SIMULATING INPUTS
motion when I/O devices and signals are not set up. You can simulate
AND OUTPUTS digital, analog, and group I/O only; you cannot simulate robot, UOP, or
SOP I/O. When you are finished simulating a signal, you can reset, or
unsimulate, it. Use Procedure 72 to simulate and unsimulate I/O.

Procedure 72 Simulating and Unsimulating Inputs and Outputs

Condition  The input or output has been configured.


Step 1 Press MENUS.
2 Select I/O.
3 Press F1, [TYPE].
4 Select the type of input or output you want to simulate: digital,
analog, or group.
For digital inputs for example, you will see a screen similar to the
following.

I/O Digital Input WORLD 10%


# SIM STATUS
DI[ 1] U OFF [ ]
DI[ 2] S ON [ ]
DI[ 3] U OFF [ ]
DI[ 4] U OFF [ ]
DI[ 5] U OFF [ ]
DI[ 6] U ON [ ]
DI[ 7] U OFF [ ]
DI[ 8] S OFF [ ]
DI[ 9] U OFF [ ]
DI[ 10] U OFF [ ]

[ TYPE ] CONFIG IN/OUT SIMULATE UNSIM

5 If you simulate a signal, you can force the status by setting it to a


value. When the signal is unsimulated, its actual status is displayed.
DO[ 4] OFF 6 Move the cursor to the SIM column of the signal you want to simulate.
 U means the signal is not simulated or unsimulated.
 S means the signal is simulated.
7 Simulate or unsimulate the signal.
 To simulate, press F4, SIMULATE.
 To unsimulate, press F5, UNSIM.
8 To unsimulate all simulated signals, press FCTN and then select
UNSIM ALL I/O.
7. CONTROLLING I/O

MARMMTRBL02303E 75

7.3 The I/O SOP screen indicates the status of the standard operator panel
signals. SOP input signals (SI) and SOP output signals (SO) correspond
SOP I/O STATUS
to internal controller software Panel Digital Input signals (PDI) and Panel
Digital Output signals (PDO). Refer to Table 71 and Table 72.
Table 71. Standard Operator Panel Input Signals
SI PDI Function Description
EMERGENCY Input signal is normally turned ON, indicating that the EMERGENCY STOP button is
0 1
STOP not being pressed.
Input signal is normally turned OFF, indicating that the FAULT RESET button is not
1 2 FAULT RESET
being pressed.
2 3 REMOTE Input signal is normally turned OFF, indicating that the controller is not set to remote.
Input signal is normally turned ON, indicating that the HOLD push button is not
3 4 HOLD
being pressed.
Input signal is normally turned OFF, indicating that the CYCLE START push button
6 7 CYCLE START
is not being pressed.
715 816 NOT USED Open for additional PDI.

Table 72. Standard Operator Panel Output Signals


SO PDO Function Description

0 1 REMOTE LED Output signal indicates the controller is set to remote.


Output signal indicates the CYCLE START button has been pressed or a program is
1 2 CYCLE START
running.
Output signal indicates the HOLD button has been pressed or a hold condition exists.
2 3 HOLD
Output signal indicates a fault has occurred.
3 4 FAULT LED
Output signal indicates the voltage in the battery is low.
4 5 BATTERY ALARM
TEACH PENDANT Output signal indicates the teach pendant is enabled.
7 8
ENABLED
815 916 NOT USED Open for additional PDO.

Use Procedure 73 to display and force SOP I/O.


7. CONTROLLING I/O

76 MARMMTRBL02303E

Procedure 73 Displaying and Forcing SOP I/O

Step 1 Press MENUS.


2 Select I/O.
3 Press F1, [TYPE].
4 Select SOP. You will see a screen similar to the following.

I/O SOP Out JOINT 10 %


# STATUS
SO[ 1] OFF
OFF [ ]
SO[ 2] OFF [ ]
SO[ 3] OFF [ ]
SO[ 4] OFF [ ]
SO[ 5] OFF [ ]
SO[ 6] OFF [ ]
SO[ 7] OFF [ ]
SO[ 8] OFF [ ]
SO[ 9] OFF [ ]
SO[ 10] OFF [ ]

[ TYPE ] IN/OUT ON OFF

To change between the display of the input and output screens, press
F3, IN/OUT.
To move quickly through the information, press and hold the SHIFT
key and press the down or up arrow keys.

NOTE You can only view the status of input signals. Input signals cannot
be forced.

5 To force an output signal, move the cursor to the output you want to
change:
 To turn on an output signal, press F4, ON.
 To turn off an output signal, press F5, OFF.
MARMMTRBL02303E 8 MASTERING

When you master a robot you define the physical location of the robot by
81

synchronizing the mechanical information with the robots positional


information. A robot must be mastered to operate properly. Robots are
usually mastered before they leave FANUC Robotics. However, it is
possible that a robot might lose its mastering data and require to be
remastered.

You can master the robot using several different methods. Refer to
Table 81 to select the method that best meets your needs.

Table 81. Mastering Methods


Robot
Mastering Method When to Use
Models
Mastering to a fixture All  When mastery was lost due to
(Fixture Position mechanical disassembly or repair.
Master)  When a quick master reference position
was not previously set.
 Method of choice for P- and A-series
robots. Used for S- and M-series robots
when extreme precision is required.
Mastering to zero M-series  When mastery was lost due to
degrees S-series mechanical disassembly or repair.
 When a quick master reference position
was not previously set.
 Method of choice for S- and M-series
robots when extreme precision is not
required.
Single axis mastering M-series When mastery was lost due to mechanical
S-series disassembly or repair of a single axis (usually
due to motor replacement).
Recording the quick All To record mastering data as a reference for
master reference future quick mastering.
position
Quick mastering All To retrieve mastering data that has been
stored as a quick master reference position
when mastery is lost due to an electrical or
software problem. Do not use if mastery was
lost due to mechanical disassembly or repair.

If you are using a FANUC Robotics A-series or P-series robot you must
use a mastering fixture to master your robot. Refer to the Mechanical
Service Manual specific to your robot model for procedures on how to set
up and use a mastering fixture.
If you are using a FANUC Robotics M-series or S-series robot you can
either master to a fixture or you can master to zero degrees. Refer to the
Mechanical Service Manual specific to your robot model for more
information on mastering using a fixture.
Quick mastering is a convenient way to master an M-series or S-series
robot after you have recorded a reference position. You cannot quick
master a robot unless the reference position was taught before mastering
was lost.
8. MASTERING
MARMMTRBL02303E
82

CAUTION
Record the quick master reference position after the robot is
installed to preserve the factory mastering settings for future
remastering.

8.1 When you master to a fixture, you use a mastering fixture to align the
robot axes and then record the position. You can master any robot to a
MASTERING TO A
fixture. If you have a P-series or A-series robot, you must master it to a
FIXTURE (FIXTURE fixture.
POSITION MASTER)
Use Procedure 81 to master to a fixture.

Procedure 81 Mastering to a Fixture

Condition  You have the appropriate mastering fixture for your robot.
Step 1 Press SYSTEM.
2 Press F1, [TYPE].
3 Select Master/Cal.
If Master/Cal is not listed on the [TYPE] menu, do the following;
otherwise, continue to Step 4.
a Select VARIABLE from the [TYPE] menu.
b Move the cursor to $MASTER_ENB.
c Press the numeric key 1 and then press ENTER on the teach
pendant.
d Press F1, [TYPE].
e Select Master/Cal. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD
8. MASTERING

MARMMTRBL02303E 83

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD RES_PCA

4 If you are resetting a pulse coder alarm,


a Press F3, RES_PCA. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%


1 FIXTURE POSITION MASTER
2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

Reset pulse coder alarm? [NO]


[ TYPE ] YES NO

b Press F4, YES. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%


1 FIXTURE POSITION MASTER
2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE
Pulse coder alarm reset!

[ TYPE ] LOAD RES_PCA

5 Refer to the Mechanical Service Manual or Mechanical Connection


and Maintenance Manual specific to your robot model for the
procedures on how to set up and use a mastering fixture.
8. MASTERING
MARMMTRBL02303E
84

6 Select Fixture Position Master.


7 Press F4, YES. Mastering will be performed automatically.
8 Continue to Step 9.
9 Select Calibrate.


10 Press F4, YES.


11 Perform a cold start.

a Turn off the robot.




b Press and continue pressing the FAULT RESET button on the

operator panel.

c While still pressing FAULT RESET, press the ON button on the


operator panel.


8. MASTERING

MARMMTRBL02303E 85

8.2 When you master to zero degrees, you position all axes at their zero degree
witness marks and record the zero degree position. You can master any
ZERO DEGREE
M-series or S-series robot to zero degrees.
MASTERING
Use Procedure 82 to master to zero degrees.

Procedure 82 Mastering to Zero Degrees

Step 1 Press SYSTEM.


2 Press F1, [TYPE].
3 Select Master/Cal.
If Master/Cal is not listed on the [TYPE] menu, do the following;
otherwise, continue to Step 4.
a Select VARIABLE from the [TYPE] menu.
b Move the cursor to $MASTER_ENB.
c Press the numeric key 1 and then press ENTER on the teach
pendant.
d Press F1, [TYPE].
e Select Master/Cal. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD
8. MASTERING
MARMMTRBL02303E
86

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD RES_PCA

4 If you are resetting a pulse coder alarm,


a Press F3, RES_PCA. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%


1 FIXTURE POSITION MASTER
2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

Reset pulse coder alarm? [NO]


[ TYPE ] YES NO

b Press F4, YES. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%


1 FIXTURE POSITION MASTER
2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE
Pulse coder alarm reset!

[ TYPE ] LOAD RES_PCA

5 Align the witness marks on the robot.


6 Select Zero Position Master.
8. MASTERING

MARMMTRBL02303E 87

7 Press F4, YES. Mastering will be performed automatically.


8 Select Calibrate.
9 Press F4, YES.

10 Perform a cold start.




a Turn off the robot.



b Press and continue pressing the FAULT RESET button on the


operator panel.
c While still pressing FAULT RESET, press the ON button on the


operator panel.
8. MASTERING
MARMMTRBL02303E
88

8.3 You can master a single axis of an M-series or S-series robot when mastery
was lost due to mechanical disassembly or repair of a single axis, usually
SINGLE AXIS
due to motor replacement.
MASTERING
Use Procedure 83 to master a single axis.

Procedure 83 Mastering a Single Axis

Step 1 Clear any servo faults that prevent you from jogging the robot.
a Press MENUS.
b Select SYSTEM.
c Press F1, [TYPE].
d Select Variables.
e Move the cursor to $MCR and press ENTER.
f Move the cursor to $SPC_RESET and press F4, TRUE.
The value will change to TRUE momentarily, and will then change to
FALSE.
g If the value does not change to TRUE momentarily, repeat
Step 1.
h Press RESET on the operator panel.
2 Using the JOINT coordinate system, jog the unmastered axis to the
zero degree position.
3 Press MENUS.
4 Select SYSTEM.
5 Press F1, [TYPE].
6 Select Master/Cal.
If Master/Cal is not listed on the [TYPE] menu, do the following;
otherwise, continue to Step 7.
a Select VARIABLE from the [TYPE] menu.
b Move the cursor to $MASTER_ENB.
c Press the numeric key 1 and then press ENTER on the teach
pendant.
d Press F1, [TYPE].
e Select Master/Cal. See the following screen for an example.
8. MASTERING

MARMMTRBL02303E 89

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD RES_PCA

7 Select 4, Single Axis Master. See the following screen for an


example.

SINGLE AXIS MASTER JOINT 10%


1/9
ACTUAL POS (MSTR POS) (SEL) [ST]
J1 0.000 ( 0.000) (0) [2]
J2 3.514 ( 35.000) (0) [0]
J3 7.164 (100.000) (0) [2]
J4 357.366 ( 0.000) (0) [2]
J5 1.275 ( 80.000) (0) [2]
J6 4.571 ( 0.000) (0) [2]
E1 0.000 ( 0.000) (0) [0]
E2 0.000 ( 0.000) (0) [0]
E3 0.000 ( 0.000) (0) [0]

[ TYPE ] GROUP EXEC

8 Move the cursor to the MSTR POS column for the unmastered axis
and press the 0 key.
9 Continuously press and hold the DEADMAN switch and turn the
teach pendant ON/OFF switch to ON.
10 Move the cursor to the SEL column for the unmastered axis and press
the numeric key 1.
11 Press ENTER.
12 Press F5, EXEC. Mastering will be performed automatically.
13 Press PREV.
14 Select Calibrate.
15 Press F4, YES.
8. MASTERING
MARMMTRBL02303E
810

16 Perform a cold start.




a Turn off the robot.


b Press and continue pressing the FAULT RESET button on the


operator panel.
c While still pressing FAULT RESET, press the ON button on the


operator panel.
8. MASTERING

MARMMTRBL02303E 811

8.4 Quick mastering allows you to minimize the time required to remaster the
robot using a reference position you established when the robot was
QUICK MASTERING
properly mastered. You cannot quick master the robot unless you have
previously recorded this quick master reference position.
Record the quick master reference position when the robot is properly
mastered. The best time to record the quick master reference position is
when the robot is still factory-mastered.
If you lose mastery due to an electrical or software problem, you can use
this reference position to master the robot in a minimum amount of time.
If you lose mastery due to mechanical disassembly or repair, you must
master to a fixture or perform zero degree mastering.
You can define a quick master reference position and perform quick
mastering on any robot model.
Use Procedure 84 to record the quick master reference position. Use
Procedure 85 to quick master the robot.

CAUTION
Record the quick master reference position after the robot is
installed to preserve the factory mastering settings for future
remastering.

Procedure 84 Recording the Quick Master Reference Position

Condition  The robot is properly mastered.


1 Align the witness marks on the robot. This is the zero position, which
will be the quick master reference position.
If you have a P-series or A-series robot, jog all robot axes to zero
degrees and scribe witness marks on each axis.
2 Press MENUS.
3 Select SYSTEM.
4 Press F1, [TYPE].
5 Select Master/Cal.
If Master/Cal is not listed on the [TYPE] menu, do the following;
otherwise, continue to Step 6.
a Select VARIABLE from the [TYPE] menu.
b Move the cursor to $MASTER_ENB.
c Press the numeric key 1 and then press ENTER on the teach
pendant.
8. MASTERING
MARMMTRBL02303E
812

d Press F1, [TYPE].


e Select Master/Cal. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD

6 Move the cursor to SET QUICK MASTER REF and press ENTER.
Set quick master ref? [NO] 7 Press F4, YES.

8 Perform a cold start.

a Turn off the robot.





b Press and continue pressing the FAULT RESET button on the
operator panel.

c While still pressing FAULT RESET, press the ON button on the


operator panel.


8. MASTERING

MARMMTRBL02303E 813

Procedure 85 Quick Mastering the Robot

Condition  The robot has lost mastery due to an electrical or software problem.
NOTE If the robot has lost mastery due to mechanical disassembly or
repair, you cannot perform this procedure. In this case, master to a fixture
or master to zero degrees to restore robot mastery.
 The quick master reference position was recorded before the robot lost
mastery.
1 Jog the robot to the quick master reference position (zero degree
position).
2 Press MENUS.
3 Select SYSTEM.
4 Press F1, [TYPE].
5 Select Master/Cal.
If Master/Cal is not listed on the [TYPE] menu, do the following;
otherwise, continue to Step 6.
a Select VARIABLE from the [TYPE] menu.
b Move the cursor to $MASTER_ENB.
c Press the numeric key 1 and then press ENTER on the teach
pendant.
d Press F1, [TYPE].
e Select Master/Cal. See the following screen for an example.

SYSTEM Master/Cal JOINT 10%

1 FIXTURE POSITION MASTER


2 ZERO POSITION MASTER
3 QUICK MASTER
4 SINGLE AXIS MASTER
5 SET QUICK MASTER REF
6 CALIBRATE

Press ENTER or number key to select.

[ TYPE ] LOAD

6 Move the cursor to QUICK MASTER and press ENTER.


Quick master? [NO] 7 Press F4, YES.
8. MASTERING
MARMMTRBL02303E
814

8 Move the cursor to CALIBRATE and press ENTER


9 Press F4, YES.

10 Perform a cold start.

a Turn off the robot.






b Press and continue pressing the FAULT RESET button on the
operator panel.

c While still pressing FAULT RESET, press the ON button on the


operator panel.


MARMMTRBL02303E 9 REPLACING COMPONENTS

This chapter describes replacement of the following items:


91

 Batteries
 Relays
 Printed Circuit Boards (PCB)
 Modules
 Process I/O Boards
 Modular I/O Components
 Transformers
 Servo Amplifiers
 Operator Panel
 Fan Motors
 Replacing the Discharge Resistor (DCR) and Dynamic Brake Resistor
(DRB) unit
 Replacing the Regenerative Discharge unit
 Replacing the Optional Warning Light
 Replacing Serial Pulse coders

NOTE To replace output drivers on the process I/O boards, refer to


Chapter 10.
9. REPLACING COMPONENTS
MARMMTRBL02303E
92

9.1 FANUC Robotics recommends that all batteries be changed immediately


prior to production start up. Change the batteries annually to assure
REPLACING THE
reliable robot performance. Use Procedure 91 to replace the battery:
BATTERY Use Procedure 92 to replace the SPC battery.

Procedure 91 Replacing the Battery

Step 1 Get the new battery. (number: A98L-0031-0007)


2 Power down and lock out the controller.

CAUTION
The battery must be replaced within 30 minutes. If the power is
turned off and the battery is removed for 30 minutes or more,
the contents of the memory on the main CPU printed circuit
board may be lost.

WARNING
Do not short circuit or incinerate a discarded battery.
Follow your companys procedures for disposing of lithium
batteries.

WARNING
Lethal voltage is present in the controller WHENEVER IT IS
CONNECTED to a power source. Be extremely careful to
avoid electrical shock.

3 Remove the battery case from the front panel of the power supply unit.
The case can be removed easily by squeezing the top and bottom of it
and pulling.
Figure 101. Replacing the Battery (1)
Front panel of the
power supply unit
BATTERY
Front panel of the Cable connector
power supply unit

Battery Battery case PC board


(ordering drawing
number:
connector Battery
A98L-0031-0007)

4 Remove the connector from the battery.


9. REPLACING COMPONENTS

MARMMTRBL02303E 93

5 Replace the battery and reconnect the connector.


6 Install the battery case.

Procedure 92 Replacing the SPC Batteries

Step 1 Get four new alkaline Dcell batteries.


2 Turn on the controller.
3 Press the operator panel Emergency Stop button and the teach pendant
Emergency Stop button.
4 Turn on the teach pendant and take it with you into the workcell.
5 Remove the black plastic battery cover on the base of the robot.
6 Remove the old batteries.
7 Insert the new batteries. The new batteries must be arranged as
follows:
Upper left positive end out.
Upper right negative end out.
Lower left negative end out.
Lower right positive end out.
8 Replace the battery cover.
9 Cold start the controller. The teach pendant might display a
SRVO065 BLAL alarm. This is normal. It will reset when you cold
start the controller.
9. REPLACING COMPONENTS
MARMMTRBL02303E
94

9.2 A relay may fail after it is used for a long time. The relay or its circuit
board must be replaced. Relays RL1-RL6 on the EMG board are
REPLACING A RELAY
replaceable.
Figure 102. Replacing a Relay

DS2

F1
DS1
F2
RL16 RL1 RL2

FUSE RL4

RL3 LED M1
LED M2

2 1

RL4 TIMER 3
6
5 TM1
8 TM2
7
9
CNPG CRX
9. REPLACING COMPONENTS

MARMMTRBL02303E 95

Figure 103. Replacing a Relay

Relay

Table 91. Relay Part Numbers


Name Part Numbers
RL1
RL2 A58L00010192#1472R
RL3
RL4
RL5, RL6 A58L00010192#1192D

Table 92. Relay Part Numbers


Name Part Numbers
RL1, RL2 A58L00010192#1472R
RL3, RL16 A58L00010192#1509A
RL4 A58L00010192#1192D
RL5, RL8, RL10,
RL15 A58L00010260#234PH24
RL5, RL6 A58L00010192#1192D
9. REPLACING COMPONENTS
MARMMTRBL02303E
96

9.2.1 Part Number: A16B16000520


Purge Control PCB Table 93. PCB Relay Part Numbers
Name Part Numbers
RL4 Timer Relay A58L00010269#B24
RL1, RL3, RL5, RL9 A58L00010260#234PH24
9. REPLACING COMPONENTS

MARMMTRBL02303E 97

9.3 When replacing a printed circuit board, take the following precautions:
REPLACING A 1. Before starting replacement, power down and lock out the controller.
PRINTED CIRCUIT
BOARD 2. When removing the printed circuit board, do not touch semiconductor
components on it and do not let the components touch other
components.

3. Wear a grounded wrist strap. Do not remove the new board from its
conductive bag until you are ready to install it.

4. Check that any jumpers on the printed circuit board to be installed are
correctly set.

5. When replacing the main CPU printed circuit board, all software
stored in the controller will be lost. Before starting replacement, back
up your user programs, mastering data, and system variable data onto a
floppy disk.

6. Connect the cables removed for replacement to the original positions.


If the cable markings are missing or unclear, retag them before
disconnecting them.
9. REPLACING COMPONENTS
MARMMTRBL02303E
98

9.3.1 Use Procedure 93 to replace the backplane printed circuit board. The
Replacing the backplane printed circuit board and the yellow board rack are removed and
replaced as one unit.
Backplane Printed
Circuit Board
Refer to Chapter 1 for part
numbers.

Procedure 93 Replacing the Backplane Printed Circuit Board

Step 1 Remove the battery from the power supply unit and plug it into the
battery connector on the front panel of the main CPU.
2 Remove all printed circuit boards from the backplane. Use
Procedure 94 .
3 Disconnect the ground wire from the backplane printed circuit board.
4 Remove the two or three mounting screws at the bottom of the rack.
5 Loosen the two or three mounting screws at the top of the rack and
remove the rack/backplane assembly.
6 Install the new rack/backplane assembly in reverse order. Be sure to
move the battery back to the power supply unit from the main CPU.
Figure 104. Replacing the Backplane Printed Circuit Board

Backplane
PC board

M5 mounting screw
9. REPLACING COMPONENTS

MARMMTRBL02303E 99

9.3.2 Use Procedure 94 to replace a component on the backplane printed


Replacing a circuit board.
Component on the
Backplane Printed
Circuit Board
Refer to Chapter 1 for part
numbers.
Procedure 94 Replacing a Component on the Backplane Printed Circuit
Board

NOTE When the main CPU is replaced, all software stored in the
controller will be lost. If possible, back up your user programs, mastering
data, and system variable data on a floppy disk before starting
replacement.
Step 1 Turn off and lock out the controller.
2 Disconnect any cables and harnesses on the component to be replaced.
3 Squeeze the latch tabs at the top and bottom of the component and pull
the component straight out.
4 Set any jumpers on the new component to match the component being
replaced.
5 Insert the new component into the proper slot of the backplane rack.
Carefully press it into the slot until the latches engage at the top and
bottom.
6 Reconnect all cables and harnesses.
Figure 105. Replacing Printed Circuit Boards on the Backplane Printed Circuit
Board

Process input/output PC board CA, CB, or DA


Main CPU board (*1)
Axis control PC board
Power supply unit (*2)
Emergency stop con-
trol PC board
9. REPLACING COMPONENTS
MARMMTRBL02303E
910

9.4 Use the following procedure to replace a module:


REPLACING A 1. Move the latches at both ends of the module socket toward the outside.
MODULE ON THE The spring of the contact tilts the module. See Figure 106.
MAIN CPU OR AXIS
CONTROL BOARD Figure 106. Moving the Latches on the End of the Module Socket

Refer to Chapter 1 for part


numbers.

2. If the tilted module touches the next module, it might be difficult to


remove it. In this case, release the latches of the next module as
described in step 1 above.

3. Now the module is free in the socket. Pull out the module carefully in
a straight line. Do not pull it out in an arc. The contacts of the socket
or module might be damaged.

4. Install a new module in the socket at an angle. Push it into the socket
until the bottom of the module reaches the bottom of the socket
groove. Be sure you have the module facing in the proper direction.
align the groove in the module with the tab as shown in Figure 107.

Figure 107. Installing a New Module at an Angle

Short Long

Fit the recess on


the module over
the tab in the
module socket.
9. REPLACING COMPONENTS

MARMMTRBL02303E 911

5. Push the module in the top edge so that the module stands upright.
See Figure 108.

Figure 108. Pushing in the Module

6. Check that the module is latched properly at both ends of the socket.
If it is insufficiently latched, the electrical contact might be improper
and a malfunction could occur.
9. REPLACING COMPONENTS
MARMMTRBL02303E
912

Figure 109 shows the mounting locations of the modules.

Figure 109. Mounting Locations of the Modules

FLASH

Flash ROM module Optional SCC module

CMOS RAM module (option) SLC2 module

CMOS RAM module (option) M321 module

CMOS RAM module (standard) SCC module


CMOS RAM module (standard)

Main CPU PC board

Servo control module (for axis 9 and 10)


Servo control module (for axis 7 and 8)
Servo control module (for axis 5 and 6)
Servo control module (for axis 3 and 4)
Servo control module (for axis 1 and 2)
Servo interface module (for axis 5 and 6)

Servo interface module (for axis 3 and 4)

Servo interface module (for axis 1 and 2)

Axis control PC board


9. REPLACING COMPONENTS

MARMMTRBL02303E 913

9.5 Part numbers: A16B-2200-0780, A16B-2200-0782, and A16B-2201-0510


REPLACING THE
PROCESS 1. Remove the cable from the process input/output printed circuit board
INPUT/OUTPUT to be replaced.
PRINTED CIRCUIT 2. Remove the two screws from the left side of the process input/output
BOARD AA, AB, BA OR printed circuit board.
BB 3. Remove the board by pulling outward to the left.
4. Replace the printed circuit board with a new one.
Refer to Chapter 1 for part 5. Replace the two screws removed in step 2.
numbers.
6. Replace the cables.

NOTE For replacing output drivers on the process I/O boards refer to
Chapter 10.

Figure 1010. Replacing the Process Input/Output Printed Circuit Board AA, AB,
BA, or BB

M4 screw
9. REPLACING COMPONENTS
MARMMTRBL02303E
914

9.6 Use the information in this section to replace the following components of
the modular I/O unit:
REPLACING
COMPONENTS OF THE
 Base Unit
MODULAR
 Modules
INPUT/OUTPUT UNIT
 Multi-Tap Transformer
Refer to Chapter 1 for part
 Servo Amplifier
numbers.  Operator Panel
 Fan Motor
 Discharge Resistor (DCR) and Dynamic Brake Resistor (DBR) Unit
 Regenerative Discharge Unit
 Optional Warning Light
 Serial Pulse Coder

9.6.1 Use Procedure 95 to replace the base unit.


Replacing the Base
Unit
Ordering code:
A03B-0807-J002

Procedure 95 Replacing the Base Unit

Step 1 Remove the I/O modules from the base unit.


2 Loosen the upper two mounting screws.
3 Remove the lower two mounting screws and replace the base unit.
9. REPLACING COMPONENTS

MARMMTRBL02303E 915

Figure 1011. Replacing the Base Unit of the Modular Input/Output Unit

M4 screw
9. REPLACING COMPONENTS
MARMMTRBL02303E
916

9.6.2
Replacing a Module

Procedure 96 Replacing the Interface Module

Removing the Interface 1 Power down and lock out the controller.
Module
2 Disconnect the signal and power cables from the interface module.
3 Press the latch on the bottom of the module and rotate the module
toward you and up.
Installing the Interface 1 Engage the hook at the top rear of the module with the bar above the
Module base unit socket.
2 Rotate the module downward until the latch engages.
3 Reconnect the signal and power cables to the interface module.

Procedure 97 Replacing an I/O Module

Removing an I/O Module 1 Power down and lock out the controller.
2 Remove the wiring harness block. (See Figure 1013.)
a Lift the latch at the lower left corner of the module window.
b Rotate the block toward you and down.
3 Press the latch on the bottom of the module and rotate the module
toward you and up. (See Figure 1012.)
Installing an I/O Module 1 Engage the hook at the top read of the module with the bar above the
base unit socket.
2 Rotate the module downward until the latch engages.
9. REPLACING COMPONENTS

MARMMTRBL02303E 917

Figure 1012. Removing and Replacing a Module

3 Install the wiring harness block.


a Engage the hook at the bottom rear of the block with the bar at the
bottom of the module.
b Rotate the block upward until the latch engages.
Figure 1013. Removing and Replacing a Terminal Block
9. REPLACING COMPONENTS
MARMMTRBL02303E
918

9.7 Use Procedure 98 to replace the multi-tap transformer.


REPLACING THE
MULTI-TAP
TRANSFORMER
Refer to Chapter 1 for part
numbers.

Procedure 98 Replacing the Multi-Tap Transformer

Condition  The controller is turned off and locked out.


Step 1 Remove the acrylic covers from the transformer and ALC relay.
2 Disconnect the wiring harnesses and ground wire from the transformer.
3 Disconnect the three wires from the bottom of the ALC relay.
4 After removing the eight screws fastening the transformer, remove the
transformer. Put a new transformer on the rail in the controller and
push it into the controller along the rail. Then reinstall the screws.
5 Reconnect the wires and harnesses.
6 Reinstall the acrylic covers.

Figure 1014. Replacing the Multi-Tap Transformer

M5 screws
9. REPLACING COMPONENTS

MARMMTRBL02303E 919

9.8 Use Procedure 99 to replace a servo amplifier.


REPLACING A SERVO
AMPLIFIER
Refer to Chapter 1 for part
numbers.

Procedure 99 Replacing a Servo Amplifier

Condition  The controller is turned off and locked out.


Step 1 Remove the five bus bars from the servo amplifier bank.
2 Disconnect the wires from the servo amplifier terminal strip. Remove
the two screws fastening the servo amplifier and remove the amplifier.
3 Set the terminal strip jumpers on the new servo amplifier to match
those of the one you removed.

4 Install the new servo amplifier by following these steps in reverse


order.

Figure 1015. Replacing a Servo Amplifier

M5 screw
9. REPLACING COMPONENTS
MARMMTRBL02303E
920

9.9 Use Procedure 910 to replace the operator panel.


REPLACING THE
OPERATOR PANEL
Refer to Chapter 1 for part
numbers.

Procedure 910 Replacing the Operator Panel

Condition  The controller is turned off and locked out.


Step 1 Remove the cable from the operator panel.
2 Remove the six nuts fastening the operator panel and replace the
operator panel.
3 When replacing only the operator panel printed circuit board, replace it
together with the metal plate.
4 After removing the cable from the operator panel printed circuit board,
remove the four nuts fastening the metal plate. Then replace the
operators panel printed circuit board.

Figure 1016. Replacing the Operator Panel

Operator panel
(rear face)

M4 nuts
(4 pieces)
9. REPLACING COMPONENTS

MARMMTRBL02303E 921

9.10 Use Procedure 911 to replace the fan motor.


REPLACING THE FAN
MOTOR
Refer to Chapter 1 for part
numbers.

Procedure 911 Replacing the Fan Motor

Condition  The controller is turned off and locked out.


Step 1 Remove the printed circuit board located below the fan motor to be
replaced, following Procedure 94 .
2 The cable connected to the fan motor is connected to the backplane
printed circuit board in the slot. Holding the connector, remove the
cable from the backplane printed circuit board.
3 Open the lid at the top of the backplane rack by placing the tip of a
flatblade screwdriver into the center hole at the front of the lid and
moving the screwdriver like a lever in the direction in Figure 1017 to
release the latch.
4 Remove the fan motor.
5 Install a new fan motor. Route the cable through the hole at the back
of the rack.
6 Close the lid until it is latched.
7 Connect the cable of the fan motor to the connector on the backplane
printed circuit board. Suspend the center of the cable on the hook in
the back of the rack.
8 Reinstall the removed printed circuit board using the procedure
described in Section 9.3.2.
9. REPLACING COMPONENTS
MARMMTRBL02303E
922

Figure 1017. Replacing the Fan Motor

(3)
(4)

Fan motor

Cable

Connector

Backplane PC board
9. REPLACING COMPONENTS

MARMMTRBL02303E 923

9.11 Use Procedure 912 to replace the discharge resistor (DCR) and dynamic
brake resistor (DBR) unit.
REPLACING THE
DISCHARGE
RESISTOR (DCR) AND
DYNAMIC BRAKE
(DBR) UNIT

Procedure 912 Replacing the Discharge Resistor (DCR) and Dynamic Brake
Resistor (DBR) unit

Condition  The controller is turned off and locked out.


Step 1 Use FANUC part number A05B-2302-C080 to replace the DCR and
DBR unit.
2 Remove the cable from the DCR and DBR unit to be replaced.
3 Remove the two screws fastening the DCR and DBR unit and replace
it.
4 Reattach the cable to the new DCR and DCR unit.
9. REPLACING COMPONENTS
MARMMTRBL02303E
924

Figure 1018. Discharge Resistor (DCR) and Dynamic Brake Resistor (DBR) Unit

M5 SCREW (2 pieces)
9. REPLACING COMPONENTS

MARMMTRBL02303E 925

9.12 Use Procedure 913 to replace the regenerative discharge unit.


REPLACING THE
REGENERATIVE
DISCHARGE UNIT

Procedure 913 Replacing the Regenerative Discharge Unit

Condition  The controller is turned off and locked out.


Step 1 Use FANUC part number A05B-2312-C100 for the M-500, and part
number A05B-2313-C100 for the S-900, for replacement of the
regenerative discharge unit.
2 Disconnect the cable connected to the regenerative discharge unit.
3 Remove the four M5 screws fastening the discharge unit. Then
replace the unit.

Figure 1019. Replacing the Regenerative Discharge Unit

Four M5 fastening screws


9. REPLACING COMPONENTS
MARMMTRBL02303E
926

9.13 Use Procedure 914 to replace the optional warning light.


REPLACING THE
OPTIONAL WARNING
LIGHT

Procedure 914 Replacing the Optional Warning Light

Condition  The controller is turned off and locked out.


Step 1 Use FANUC part number LAMPXVAL74C024X to replace the
warning light.
2 Remove the existing light assembly from the robot and replace with
the new light assembly.
3 Reconnect the replacement light assembly.
9. REPLACING COMPONENTS

MARMMTRBL02303E 927

9.14 Use Procedure 915 to replace a serial pulse coder.


REPLACING A SERIAL
PULSE CODER

Procedure 915 Replacing a Serial Pulse Coder

NOTE The robot will have to be remastered after this procedure.

Condition  The controller is turned off and locked out.


Step 1 Remove the cables from the pulse coder. Refer to Figure 1020.
2 Remove the screws holding the pulse coder cable connector to the
pulse coder housing.
3 Retract the rubber boot on the inside of the pulse coder cable
connector.
4 Remove the snap ring on the inside of the pulse coder cable connector.
5 Detach the pulse coder cable from the pulse coder housing.

CAUTION
In the next step, be sure to remove the correct bolts, as shown
in Figure 1020. Removing the wrong bolts can destroy the
pulse coder.

6 Remove the four M4 bolts attaching the pulse coder to the motor.
7 Position the new pulse coder on the motor so that the Oldham
coupling engages. If there are witness marks on the pulse coder case
and the motor case, make sure that they line up.
8 Install the four M4 bolts.
9 Attach the pulse coder cable to the pulse coder housing.
10 Install the snap ring on the inside of the pulse coder cable connector.
11 Reposition the rubber boot on the inside of the pulse coder cable
connector.
12 Replace the screws holding the pulse coder cable connector to the
pulse coder housing.
13 Install the screws holding the pulse coder housing to the motor.
14 Attach the cables to the pulse coder housing.
9. REPLACING COMPONENTS
MARMMTRBL02303E
928

Figure 1020. Removing the Pulse Coder


Caution: Do not remove the screws from these four ribbed holes.
The serial pulse coder will seperate and be destroyed

M4 Mounting Bolt Holes


10
MARMMTRBL02303E
BOARD ADJUSTMENTS

This chapter contains information about components located on some


101

printed circuit boards that require adjustment. These components include


jumpers and potentiometers.

10.1 You can set jumpers on the axis control board. Figure 111 shows an
illustration of the axis control board. Table 101 lists the standard
AXIS CONTROL
settings for the jumpers found on the axis control board.
BOARD JUMPERS
Figure 111. Axis Control Board Jumpers

A COM B B HBK A
JUMPER JUMPER

Table 101. Axis Control Board Jumpers

Name Standard setting Description


COM Side A Side A: The RI lines use 0V for the
common reference
Side B:The RI lines use +24 for the
common reference
HBK Side B Side A: The hand breakage detect feature
is not used.
Side B: The hand breakage detect feature
is used.
10. BOARD ADJUSTMENTS
MARMMTRBL02303E
102

10.2 The process I/O board has jumpers, potentiometers you can adjust, and
output drivers you can replace. The process I/O boards are shown in
PROCESS I/O BOARD
Figures 102 through Figure 108.

Figure 112. Process I/O Board AA

Figure 113. Process I/O Board AB


10. BOARD ADJUSTMENTS

MARMMTRBL02303E 103

Figure 114. Process I/O Board BA

Figure 115. Process I/O Board BB


10. BOARD ADJUSTMENTS
MARMMTRBL02303E
104

Figure 116. Process I/O Board CA

Figure 117. Process I/O Board CB


10. BOARD ADJUSTMENTS

MARMMTRBL02303E 105

Figure 118. Process I/O Board DA

10.2.1 Table 102 lists the standard settings for the jumpers located on the
Jumpers process I/O board.

Table 102. Process I/O Board Jumpers

Name Standard Description


setting
UDI1 to UDI20
ICOM1 The common voltage is adjusted to
(Connector CRM2A)
Side A: 0 V common
UDI21 to UDI40 Side B: +24 V common
ICOM2
(Connector CRM2B) Side A
WI01 to WI08
ICOM3 (Connector CRW1) NOTE: Set ICOM3 to B side to use
See Note WDI2 as weld detect input.

SP1 Channel 1 The polarity of the output voltage is


switched to
Open
Channel 2 Strapped: Negative ()
SP2 Open: Positive (+)
10. BOARD ADJUSTMENTS
MARMMTRBL02303E
106

10.2.2 Table 103 lists the process I/O board potentiometers and the adjustments
Potentiometers you can make to them.

Table 103. Process I/O Board Potentiometer Adjustments

Potentiometer Description Adjustment


Adjusts the gain of Execute a robot program and set AO[1] to
channel 1 4095 on the teach pendant. Connect a
digital voltmeter to test pin AO1 and rotate
VR1
VR1 until the meter reads 12.0 V. Connect
the negative () lead of the digital voltmeter
to test pin 0VF.
Adjusts the gain of Execute a robot program and set AO[2] to
channel 2 4095 on the teach pendant. Connect the
digital voltmeter to test pin AO2 and rotate
VR2 VR2 until the meter reads 12.0 V. Connect
the negative () lead of the digital voltmeter
to test pin 0VF. (The 0VF test pin is
different from the common 0V test pin.)
Adjusts the Connect the digital voltmeter to test pin
reference supply P10V and rotate VR3 until the meter reads
VR3 voltage of the 10.00  0.1 V.
digital/analog
converter
10. BOARD ADJUSTMENTS

MARMMTRBL02303E 107

10.2.3 Table 104 lists the output drivers for each process I/O board.
Output Drivers
Table 104. Output Drivers
DO Signal
Driver
AA AB BA BB CA CB DA
DV1 CMDENBL, SYSRDY, PROGRUN, PAUSED
DV2 HELD, FAULT, ATPERCH, TPENBL
DV3 BATALM, BUSY, ACK1/SNO1, ACK2/SNO2
DV4 ACK3/SNO3, ACK4/SNO4, ACK5/SNO5, ACK6/SNO6
DV5 ACK7/SNO7, ACK8/SNO8, SNACK, RESERVED
DV6 SO01, SO02, SO03, SO04
DV7 SO05, SO06, SO07, SO08
DV8 SO09, SO10, SO11, SO12
DV9 SO13, SO14, SO15, SO16
DV10 SO17, SO18, SO19, SO20
DV11 WO01, WO02, WO01, WO02, SO21, SO22,
WO03, WO04 WO03, WO04 SO23, SO24
DV12 WO05, WO06, WO05, WO06, SO25, SO26,
WO07, WO08 WO07, WO08 SO27, SO28
DV13 SO29, SO30,
SO31, SO32,
DV14 SO33, SO34,
SO35, SO36
DV15 SO37, SO38,
SO39, SO40
DV16 SO41, SO42,
SO43, SO44
DV17 SO45, SO46,
SO47, SO48
DV18 SO49, SO50,
SO51, SO52
DV19 SO53, SO54,
SO55, SO56
DV20 SO57, SO58,
SO59, SO60
DV21 SO61, SO62,
SO63, SO64
DV22 SO65, SO66,
SO67, SO68
DV23 SO69, SO70,
SO71, SO72
DV24 SO73, SO74,
SO75, SO76
RESERVED To be used for To be used for To be used for
replacement replacement replacement
10. BOARD ADJUSTMENTS
MARMMTRBL02303E
108

10.3 This section contains information about adjusting the built-in CRT/KB
unit.
BUILTIN CRT/KB UNIT

CRT Display Unit The following can be adjusted at the CRT Display Unit:
20 CRT/KB  Brightness (BRIGHT)
A05B-2051-J101  Contrast (CONT)
 Focus
40 CRT/KB  Horizontal size (H-SIZE)
A05B-2301-J130  Vertical size (V-SIZE)
 Horizontal Hold (H-HOLD)
 Vertical Hold(V-HOLD)
 Vertical linearity (V-LIN)

CAUTION
Keep fingers and tools away from the CRT display unit when
first turning the power on. Use caution at the display unit
anytime when power is on because 10-11 KV is present.

Brightness Turn to the brightest level possible before roster (scanning lines) appear on
the screen.

Contrast Adjust the CONT variable resistor until display characters achieve an
easy to read brightness level. Too much contrast can distort the characters.

Focus Adjust FOCUS variable resistor to sharpen characters.

Horizontal Size (Width) Adjust the HSIZE coil if picture width appears too small or distorted
on the sides.

Vertical Size (Height) Adjust the VSIZE variable resistor if the picture height appears too
small or distorted at the top.

Horizontal Hold Adjust the HHOLD variable resistor if the picture rolls or shifts
horizontally (or diagonally).

Vertical Hold (V-HOLD) Adjust the VHOLD variable resistor if the picture rolls vertically.

Vertical Linearity (V-LIN) Adjust the VLIN variable resistor to obtain equal character size
vertically in the upper and lower parts of the screen.
10. BOARD ADJUSTMENTS

MARMMTRBL02303E 109

The following can be adjusted at the CRT/KB Control Board:

 + 5VDC power supply


Refer to Figure 119 and adjust as follows:
+5VDC supply: Monitor the +5 VDC test point and adjust variable
resistor VR1 until + 5VDC  0.1V is obtained.

 Jumper ST1
Refer to Figure 1110 for jumper setting.

Figure 119. Front View Control Board

VR1

Test point +5V

ST1

Figure 1110. Jumper Setting CRT/KB

Jumper Standard SIDE A = KANA +


setting ALPHA NUMERIC

ST1
SIDE B = ALPHA


NUMERIC
A B
10. BOARD ADJUSTMENTS
MARMMTRBL02303E
1010

10.4 The EMG board contains a jumper which controls the sensitivity of the
brake alarm circuit. Refer to SRVO_ALARM 008.
EMG BOARD
Figure 1111. EMG board

EMG
PCB

Table 105. SBK Jumper Settings


Standard Setting
NAME S-5, S-10, Arc Mate, Arc S-500, S-700, S-800, S-420, S-420D Description
Mate 100/S-6, Arc Mate M-400
Sr., A-510, L-1000,
S-900, M-500
SBK1 Open Side 2 The sensitivity of a brake is adjusted
(for a swiveling axis).
SBK2 Open
SBK3
SBK4
SBK5
SBK6
SET Side 2 Side 1 The sensitivity for the fuse alarm of a
brake is adjusted to :
Side 1: Special setting
Side 2: Standard setting
MARMMTRBL02303E 11 CONNECTIONS

This chapter describes the electrical interface connections in the R-J


111

controller. Figure 121 is a block diagram of electrical interface


connections with the R-J controller.

Figure 121. Block Diagram of Electrical Interface Connection

Pneumatic pressure
Purge Source

ISB Teach Pendant (ISTP)


Unit

ABKR I/O
GEF I/O

Modular I/O

Disk Drive

*1: A remote display is connected.


*2: Optional RS-232-C or RS-422/485 interface.
11. CONNECTIONS
MARMMTRBL02303E
112

11.1 Figure 122 through Figure 1212 show connection diagrams to the
mechanical units.
MECHANICAL
CONNECTIONS Figure 122. Mechanical Connection Diagram for S-420, S-500, S-700, S-800, and
M-400

*1: This cable is not included. It must be supplied by the customer.


*2: Can be connected when the robot is S-500 or S-700.

Figure 123. Mechanical Connection Diagram for ARC Mate, ARC Mate 100/S-6,
ARC Mate Sr., A-510, and L-1000

*1: This cable is not included. It must be supplied by the customer.


*2: Can be connected when the robot is ARC Mate or ARC Mate Sr.
11. CONNECTIONS

MARMMTRBL02303E 113

Figure 124. Mechanical Connection Diagram for Six-Axis Pedestal Mount System
with Battery in Controller

RJ ROBOT

M1
SERVO AMP C1M1
TERMINAL/FRAME
AXIS 1 & 2

M3
SERVO AMP C1M3
TERMINAL/FRAME
AXIS 3

M2
SERVO AMP C1M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1
PCB CRF1 C1P1
(PULSE CODER
SIGNAL)

CRR5 EMG PCB C1M5


P & M BRAKE
SIGNALS

D1
CONTACT SIGNAL C1D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+6V & 0V C1B1 (INTRINSIC)


BATT

+24PG & 0V DCDC


C1P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE
11. CONNECTIONS
MARMMTRBL02303E
114

Figure 125. Mechanical Connection Diagram for Six-Axis Pedestal Mount System
with Battery in Robot

RJ ROBOT

M1
SERVO AMP C1M1
TERMINAL/FRAME
AXIS 1 & 2

M3
SERVO AMP C1M3
TERMINAL/FRAME
AXIS 3

M2
SERVO AMP C1M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1
PCB CRF1 C1P1
(PULSE CODER
SIGNAL)

CRR5 EMG PCB C1M5


P & M BRAKE
SIGNALS

D1
CONTACT SIGNAL C1D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+24PG & 0V DCDC


C1P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE
11. CONNECTIONS

MARMMTRBL02303E 115

Figure 126. Mechanical Connection Diagram for Catrac Robot Clean-Wall Rail
System with Battery in Controller

RJ JUNCTION BOX ROBOT

M1 M1
SERVO AMP C1M1 C2M1
TERMINAL/FRAME
AXIS 1 & 2
M3 M3
SERVO AMP C1M3 C2M3
TERMINAL/FRAME
AXIS 3 & 7
M2 M2
SERVO AMP C1M2 C2M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1 P1
PCB CRF1 C1P1 C2P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5 C2M5


P & M BRAKE
SIGNALS

D1 D1
CONTACT SIGNAL C1D1 (INTRINSIC) C2D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+6V & 0V C1B1 (INTRINSIC) C2B1 (INTRINSIC)


BATT

P2
+24PG & 0V DCDC
C1P2 C2P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE GROUND CABLE


11. CONNECTIONS
MARMMTRBL02303E
116

Figure 127. Mechanical Connection Diagram for Catrac Robot Clean-Wall Rail
System with Battery in Robot

RJ JUNCTION BOX ROBOT

M1 M1
SERVO AMP C1M1 C2M1
TERMINAL/FRAME
AXIS 1 & 2
M3 M3
SERVO AMP C1M3 C2M3
TERMINAL/FRAME
AXIS 3 & 7
M2 M2
SERVO AMP C1M2 C2M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1 P1
PCB CRF1 C1P1 C2P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5 C2M5


P & M BRAKE
SIGNALS

D1 D1
CONTACT SIGNAL C1D1 (INTRINSIC) C2D1 (INTRINSIC)
TRANSDUCER
(IBRC)

P2
+24PG & 0V DCDC
C1P2 C2P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE GROUND CABLE


11. CONNECTIONS

MARMMTRBL02303E 117

Figure 128. Mechanical Connection Diagram for SevenAxis Universal Rail


System with Battery in Controller

RJ ROBOT

M1
SERVO AMP C1M1
TERMINAL/FRAME
AXIS 1 & 2
M3
SERVO AMP C1M3
TERMINAL/FRAME
AXIS 3 & 7
M2
SERVO AMP C1M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1
PCB CRF1 C1P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5


P & M BRAKE
SIGNALS

D1
CONTACT SIGNAL C1D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+6V & 0V C1B1 (INTRINSIC)


BATT

+24PG & 0V DCDC


C1P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE
11. CONNECTIONS
MARMMTRBL02303E
118

Figure 129. Mechanical Connection Diagram for Seven-Axis Universal Rail


System with Battery inRobot

RJ ROBOT

M1
SERVO AMP C1M1
TERMINAL/FRAME
AXIS 1 & 2
M3
SERVO AMP C1M3
TERMINAL/FRAME
AXIS 3 & 7
M2
SERVO AMP C1M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1
PCB CRF1 C1P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5


P & M BRAKE
SIGNALS

D1
CONTACT SIGNAL C1D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+24PG & 0V DCDC


C1P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE
11. CONNECTIONS

MARMMTRBL02303E 119

Figure 1210. Mechanical Connection Diagram for Seven-Axis Universal Rail


System with Battery in Controller and Junction Box

RJ JUNCTION BOX ROBOT

M1 M1
SERVO AMP C1M1 C2M1
TERMINAL/FRAME
AXIS 1 & 2
M3 M3
SERVO AMP C1M3 C2M3
TERMINAL/FRAME
AXIS 3 & 7
M2 M2
SERVO AMP C1M2 C2M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1 P1
PCB CRF1 C1P1 C2P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5 C2M5


P & M BRAKE
SIGNALS

D1 D1
CONTACT SIGNAL C1D1 (INTRINSIC) C2D1 (INTRINSIC)
TRANSDUCER
(IBRC)

+6V & 0V C1B1 (INTRINSIC) C2B1 (INTRINSIC)


BATT

P2
+24PG & 0V DCDC
C1P2 C2P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE GROUND CABLE


11. CONNECTIONS
MARMMTRBL02303E
1110

Figure 1211. Mechanical Connection Diagram for Seven-Axis Universal Rail


System with Battery in Robot and Junction Box

RJ JUNCTION BOX ROBOT

M1 M1
SERVO AMP C1M1 C2M1
TERMINAL/FRAME
AXIS 1 & 2
M3 M3
SERVO AMP C1M3 C2M3
TERMINAL/FRAME
AXIS 3 & 7
M2 M2
SERVO AMP C1M2 C2M2
TERMINAL/FRAME
AXIS 4,5, & 6

AXIS CONTROL P1 P1
PCB CRF1 C1P1 C2P1
(PULSE CODER
SIGNAL)

AXIS CONTROL
PCB JF7
(PULSE CODER
SIGNALAXIS7)

CRR5 EMG PCB C1M5 C2M5


P & M BRAKE
SIGNALS

D1 D1
CONTACT SIGNAL C1D1 (INTRINSIC) C2D1 (INTRINSIC)
TRANSDUCER
(IBRC)

P2
+24PG & 0V DCDC
C1P2 C2P2
PURGE CONTROL 24V
PCB 5V

GROUND CABLE GROUND CABLE


11. CONNECTIONS

MARMMTRBL02303E 1111

Figure 1212. Mechanical Connection Diagram, Common Part

(*2)

(*2)
or Floppy Disk Drive

(*3)

(*3)

(*3)

Auto breaker

(*3)

(*3)

*1: K41 is optional. K40 is not required if K41 is specified.


*2: This cable is provided with the FANUC Handy File or the floppy disk drive.
*3: Not included. Must be supplied by the customer.
11. CONNECTIONS
MARMMTRBL02303E
1112

11.1.1 For the S-420, cables K70, K71, and K72 are connected as shown in
Robot Connection Figure 1215.
Cables
11. CONNECTIONS

MARMMTRBL02303E 1113

11.1.2 For the P-155, cables C1M1, C1M2, C1M3, C1M5 and C1P1 are
Robot Connection connected as shown in Figure 1213 through Figure 1223.
Cables Figure 1213. Six-Axis Pedestal

AXIS EMG
AMP 1 AMP 2 AMP 3 CONTROL CONTROL
PCB PCB
CRF1
9 9 9

20 20 20
10 10 10

21 21 21 CRR5
11 11 11
22 22 22
12 12 12
23 23 23

C1P1

<AXIS1 <AXIS2 <AXIS3

C1M5

C1M3

C1M1
ROBOT

<AXIS4 <AXIS5 <AXIS6 M1


C1M2 C1M1

M3
C1M3

M2
C1M2

P1
C1P1

C1M5
11. CONNECTIONS
MARMMTRBL02303E
1114

Figure 1214. Seven-Axis Catrac Robot Clean-Wall Rail


AXIS EMG
AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 CONTROL CONTROL
PCB PCB
CRF1
9 9 9 9
20 20 20
10 10 10 10
21 21 21 JF7 CRR5
11 11 11 11
22 22 22
12 12 12 12
23 23 23

C1M5

C1P1

<AXIS1 <AXIS2 <AXIS3 <AXIS7


(EXTENDED)

C1M3

C1M1

<AXIS4 <AXIS5 <AXIS6


C1M2

JUNCTION BOX ROBOT

M1 M1
C1M1 C2M1

M3 M3
C1M3 C2M3

M2 M2
C1M2 C2M2

P1 P1
C1P1 C2P1

C1M5 C2M5
11. CONNECTIONS

MARMMTRBL02303E 1115

Figure 1215. Connection to Servo Amplifiers and Mechanical Unit for S-420

AXIS
CONTROL
PCB

CRM1

CRF1

K71
K72
K70

For the S-420 with three dual-axis servo amplifiers, ARC Mate, S-5, ARC
Mate Sr., and S-10, cables K70 and K71 are connected as shown in
Figure 1216.
Figure 1216. Connection to Servo Amplifiers and Mechanical Unit for S-420,
S-420D, ARC Mate, S-5, ARC Mate 100/S-6, ARC Mate Sr., S-10

AXIS
CONTROL
PCB

CRM1

CRF1
S-420,
S-420D
ARC Mate
ARCMate100/
S-6,
ARC Mate Sr.
S-10
S-5
K71

K70
11. CONNECTIONS
MARMMTRBL02303E
1116

For the S-500, cables K70, K71, and K72 are connected as shown in
Figure 1217.

Figure 1217. Connection to Servo Amplifiers and Mechanical Unit for S-500

AXIS
CONTROL
PCB

CRM1

CRF1
S-500

K71

K72
K70

For the S-700, cables K70, K71, and K72 are connected as shown in
Figure 1218.

Figure 1218. Connection to Servo Amplifiers and Mechanical Unit for S-700

AXIS
CONTROL
PCB

CRM1

CRF1
S-700

K71

K72
K70
11. CONNECTIONS

MARMMTRBL02303E 1117

For the S-800, cables K70, K71, and K72 are connected as shown in
Figure 1219

Figure 1219. Connection to Servo Amplifiers and Mechanical Unit for S-800

AXIS
CONTROL
PCB

CRM1

CRF1
S-800

K71

K72
K70

For the A-510, cables K70 and K71 are connected as shown in
Figure 1220

Figure 1220. Connection to Servo Amplifiers and Mechanical Unit for A-510

AXIS
CONTROL
PCB

CRM1

Not used CRF1


A-510

K71

K70
11. CONNECTIONS
MARMMTRBL02303E
1118

For the M-400 and M-500, cables K70, K71, and K72 are connected as
shown in Figure 1221.

Figure 1221. Connection to Servo Amplifiers and Mechanical Unit for M-400 and
M-500

AXIS
CONTROL
PCB

CRM1

CRF1
M-400
M-500

K71

K72
K70

For the L-1000, cables K70 and K71 are connected as shown in
Figure 1222.

Figure 1222. Connection to Servo Amplifiers and Mechanical Unit for L-1000

AXIS
CONTROL
PCB

CRM1

CRF1
L-1000

K71

K70
11. CONNECTIONS

MARMMTRBL02303E 1119

Figure 1223. Seven-Axis Universal Rail


AXIS EMG
AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 CONTROL CONTROL
PCB PCB
CRF1
9 9 9 9
20 20 20
10 10 10 10
21 21 21 JF7 CRR5
11 11 11 11
22 22 22
12 12 12 12
23 23 23

C1M5

C1P1

<AXIS1 <AXIS2 <AXIS3 <AXIS7


(EXTENDED)

C1M3

C1M1

<AXIS4 <AXIS5 <AXIS6


C1M2

JUNCTION BOX ROBOT

M1 M1
C1M1 C2M1

M3 M3
C1M3 C2M3

M2 M2
C1M2 C2M2

P1 P1
C1P1 C2P1

C1M5 C2M5
11. CONNECTIONS
MARMMTRBL02303E
1120

11.1.3 Use the following guidelines when connecting the input power supply:
Connecting the Input  Adjust the input transformer taps depending on the plant input voltage
Power Supply before supplying power to the robot. Refer to Section 1.9 for the
correct tap setting information.

 Consider the robot power capacity and the circuit breaker capacity.
Use the correct gauge wire to withstand the maximum current used.

 Connect the power supply to the terminals located above the circuit
breaker or on the top of the disconnect.

 Use a ground of class 3 or better.

 Be sure to ground the work table or fixture used by an arc welding


robot so that it can handle the large current.
The motor is driven by the PWM inverter system using the power
transistor bridge. If the servo amplifier is used without a transformer, a
high-frequency leakage current flows through the stray capacitance
between the ground and the motor coils, power cable, and amplifier. This
might cause the leakage-current circuit breaker or leakage-protection relay
installed in the path of the power supply to cut out.
If connecting power directly to the servo amplifiers, use the leakage
current circuit breaker listed in Table 111 to prevent incorrect operation.
Table 111. Example of Leakage Current Circuit Breaker for Inverters
Manufacture Type
EG A series
Fuji Electric Co
Co., Ltd
Ltd.
SG A series
ES100C type
Hitachi Ltd.
Hitachi, Ltd
ES225C type
Leakage current circuit breaker, C type
Matsushita Electric Works,
Works Ltd.
Ltd
Leakage current circuit breaker, KC type

Figure 1224 shows the cable connection for a circuit


breaker.Figure 1225 shows the cable connection for a fused flange
disconnect.
Figure 1225 shows the cable connection for a fused flange disconnect.
11. CONNECTIONS

MARMMTRBL02303E 1121

Figure 1224. Input Power Supply Connection, Circuit Breaker

Figure 1225. Input Power Supply Connection, Fused Flange Disconnect

K01

Main
Disconnect

FL1 FL2 FL3

Fuse Block
11. CONNECTIONS
MARMMTRBL02303E
1122

11.1.4 The external power on/off signal turns on and off the power supply from
Connecting the outside of the control unit, and is connected as shown in Figure 1227.
External Power Supply
ON/OFF Switch
Figure 1226. External Power Supply ON/OFF Switch Connection

19

24

20 EXON
1
62
33 34

48

EXOFF
31 32

49

25

External power supply ON/OFF switch


Use a contact conforming to the following: Voltage rating: 50 VDC, current: 100 mA or more.

The power supply on/off timing chart is as follows:


11. CONNECTIONS

MARMMTRBL02303E 1123

Figure 1227. External Power Supply ON/OFF Switch Connection

EMG
PCB

Power on Power off

External power supply ON/OFF switch


Use a contact conforming to the following: Voltage rating: 50 VDC, current: 100 mA or more.

The power supply on/off timing chart is as follows:


11. CONNECTIONS
MARMMTRBL02303E
1124

11.1.5 The external emergency stop connection is shown in Figure 1229 and
External Emergency Figure 1231 and described in Table 112 and Table 113.
Stop Connection Figure 1228. External Emergency Stop Output Connection

19

24

3
EMG OUT1
EMG OUT C

2
1
EMG OUT 2
20
1
62

48

EMG B1

27 28
49 EMGB2

25
Emergency Stop
Control PCB
11. CONNECTIONS

MARMMTRBL02303E 1125

Figure 1229. External Emergency Stop Output Connection

EMG
PCB

CRR3

CRR4

Emergency stop
control board

Table 112. External Emergency Stop Output Signals


Description Current,
Signal
Voltage
Emergency stop output signals
EMGOUT1 The contact is open if an emergency stop
occurs or the power is turned off.
EMGOUTC The contact is closed during normal Rated contact:
operation. 250 VAC, 5 5-A
A
Emergency stop output signals. resistor load
EMGOUT2
The contact is open during normal operation.
The contact is closed if an emergency stop
EMGOUTC
occurs or the power is turned off.
Emergency stop output signals of the teach
pendant
EMGB1 Rated contact:
The contact is open if the emergency stop
24 VDC, 0.1-A
button on the teach pendant is pressed.
EMGB2 resistor load
The contact is closed during normal
operation.
11. CONNECTIONS
MARMMTRBL02303E
1126

Figure 1230. External Emergency Stop Input Connection

19

24
*E1N1

45 46
20 *E1NC
External EStops
1
62 *E1NC

43 44
48 *E1N2

49
*FENCE 1
35 36

25 *FENCE 2

* Jumper across switches when not in use.


11. CONNECTIONS

MARMMTRBL02303E 1127

Figure 1231. External Emergency Stop Input Connection

External Emergency stop switch

Connected at
shipment
(Note)

Connect to IMSTP
on the UOP

Printed circuit board


for emergency control

Door switch on safety fence


Connected at
shipment

Note: Connect to EMGIN1 or EMGIN2.

To connect to the external emergency stop input, connect a double-pole


emergency stop switch to both the Emergency Stop printed circuit board
and the peripheral device interface.

Use a contact rated at 250 V, 10 A or more on the Emergency Stop printed


circuit board.
Table 113. External Emergency Stop Input Signals
Description Current,
Signal
Voltage
Connect one of the external emergency stop
EMGIN1 switch circuits to the terminals.
If the external emergency stop switch is 100 VAC, 5 A,
EMGINC pressed, the 100 VAC power for the motor is open/close
cut directly. To affect EMGOUT1 or EMGOUT2,
connect to EMGIN1 and EMGINC. To not
EMGIN
EMGIN2 affect EMGOUT1 or EMGOUT2, connect to
EMGIN2 and EMGINC.
EMGINC If these signals are not used, short all external
emergency stop terminals together.
These signals are used to stop the robot when
the door on the safety fence is open. 24 VDC, 0.1 A,
FENCE1 While the DEADMAN switch on the teach open/close
pendant is pressed and the teach pendant
enable switch is ON, these signals are ignored
FENCE2 and an emergency stop does not occur.
If these signals are not used, short these
terminals.

M3 screws are provided on the terminal. Use crimp terminals 7 mm wide


or less.
11. CONNECTIONS
MARMMTRBL02303E
1128

11.2 The R-J I/O peripheral device interfaces include process I/O printed circuit
boards and/or a modular I/O unit selected according to the applications.
PERIPHERAL DEVICE
Table 114 lists the printed circuit boards and unit. Figure 1234 shows
AND END EFFECTOR the locations.
INTERFACES

11.3 The R-J I/O peripheral device interfaces include process I/O printed circuit
boards and/or a modular I/O unit selected according to the applications.
PERIPHERAL DEVICE, Table 114 lists the printed circuit boards and unit. Figure 1232 and
ARC WELDING, AND Figure 1233 show their locations.
END EFFECTOR
INTERFACES
Table 114. Peripheral Device Interface Types
Number of I/O
No. Name Part Number Points Remarks
DI DO D/A A/D
1 Process I/O printed circuit board AA A16B-2200-0780 40 40 2 6 Standard (with welding interface)
2 Process I/O printed circuit board AB A16B-2200-0782 40 40 Standard (without welding interface)
3 Process I/O printed circuit board BA A16B-2201-0510 32 32 2 4 Source type DO (with welding
(weld interface) interface)
A20B-2000-0540
4 Process I/O printed circuit board BB A16B-2201-0510 32 32 Source type DO (without welding
interface)
5 Process I/O printed circuit board CA A16B-2201-0470 40 40 2 4 Backplane installation type (with
welding interface)
6 Process I/O printed circuit board CB A16B-2201-0472 40 40 Backplane installation type (without
welding interface)
7 Process I/O printed circuit board DA A16B-2201-0480 96 96 Backplane installation type (without
welding interface)
8 I/O unit model A03B-0807-C002 Depending on a Up to 5 slots
A03B-0807-C001 selected I/O module Up to 10 slots
11. CONNECTIONS

MARMMTRBL02303E 1129

Figure 1232. Locations of Peripheral Device Interfaces, B-Size Controller

Main CPU printed circuit board

Printed circuit board for


emergency stop control

Process I/O printed circuit board


CA/CB/DA

Modular I/O unit or


Process I/O printed circuit board
AA/AB/BA/BB or I/O unit model A
11. CONNECTIONS
MARMMTRBL02303E
1130

Figure 1233. Locations of Peripheral Devices, C-Size Controller




Operator panel



Extended
Back plane
Modular I/O rack or

Process I/O rack




Power disconnect

Servo Amplifiers #1 Main CPU


Fuses FL13
Servo Amplifiers #2
Axis control board
Servo Amplifiers #3
Power supply unit

Servo Amplifiers #4 and #5 Emergency stop


control board
Servo Amplifiers #6 Option 1 and 2 slots

Multitap transformer

User transformer
11. CONNECTIONS

MARMMTRBL02303E 1131

Figure 1234. Locations of Peripheral Devices, C-Size Controller



Operator panel






STAHL Extended
Servo Amplifiers ISBs Back plane STBI Term Strip
Purge 24V DC
Power Supply

Power disconnect

Main CPU
Fuses FL13
Transit Board Axis control board
Power supply unit

Emergency stop
control board
Option 1 and 2 slots

BDX
ISB Unit
ALC
relay

Multitap transformer

User transformer
11. CONNECTIONS
MARMMTRBL02303E
1132

11.3.1 Process I/O printed circuit board AA, AB, BA, BB, CA, CB, and DA and
Peripheral Device an I/O unit can be combined. Figure 1235 shows the combinations.
Interface Combination
Figure 1235. Peripheral Device Interface Combination

1 Board

2-Board Combination

3-Board Combination
11. CONNECTIONS

MARMMTRBL02303E 1133

11.3.2
Process I/O Printed
Circuit Board AA or AB
Figure 1236. Process I/O Printed Circuit Board AA or AB

(Additional analog
signal input)

CRW1 and CRW2 are not provided for process I/O printed circuit board BB.

Table 115. Process I/O Printed Circuit Board AA or AB


Cable
Name Drawing Number Remarks
Number
K10 Process I/O connection cable A05B2300J013 R-J control unit internal cable
A05B2302J110 Connected length: 7 m
Honda Tsushin, 50 pins: one-to-one
K50A Peripheral device connection cable A05B2302J11 Connected length: 14 m
K50B Honda Tsushin, 50 pins: one-to-one
A05B2302J112 Connected length: 30 m
Honda Tsushin, 50 pins: one-to-one
A05B2302J270 Connected length: 3 m
K45 Welder connection cable A05B2302J271 Connected length: 6 m
A05B2302J272 Connected length: 13 m
Cannot be used for TIG welding
K46 Peripheral device connection cable Not included. Must be supplied by customer.
11. CONNECTIONS
MARMMTRBL02303E
1134

11.3.3
Process I/O Printed
Circuit Board BA or BB
Figure 1237. Process I/O Printed Circuit Board BA or BB

(Additional analog
signal input)

CRW1 and CRW2 are not provided for process I/O printed circuit board BB.

Table 116. Process I/O Printed Circuit Board BA or BB


Cable
Name Drawing Number Remarks
Number
K10 Process I/O connection cable A05B2300J013 R-J control unit internal cable
K52 Peripheral device connection cable Not included. Must be supplied by the customer.
K53 Peripheral device connection cable Not included. Must be supplied by the customer.
A05B2302J270 Connected length: 3 m
K45 Welder connection cable A05B2302J271 Connected length: 6 m
A05B2302J272 Connected length: 13 m
Cannot be used for TIG welding
K46 Peripheral device connection cable Not included. Must be supplied by customer.
11. CONNECTIONS

MARMMTRBL02303E 1135

11.3.4
Process I/O Printed
Circuit Board CA or CB
Figure 1238. Process I/O Printed Circuit Board CA or CB

(Additional analog
signal input)

CRW1 and CRW2 are not provided for process I/O printed circuit board BB.

Table 117. Process I/O Printed Circuit Board CA or CB


Cable
Name Drawing Number Remarks
Number
K10 Process I/O connection cable A05B2300J013 R-J control unit internal cable
K11 Peripheral device connection cable A05B2300J014 R-J control unit internal cable (for connecting
additional printed circuit boards)
K50A, A05B2302J113 Connected length: 7 m
K50B Honda Tsushin, 50 pins: one-to-one
K50C Peripheral device connection cable A05B2302J114 Connected length: 14 m
K50D Honda Tsushin, 50 pins: one-to-one
A05B2302J115 Connected length: 30 m
Honda Tsushin, 50 pins: one-to-one
A05B2302J273 Connected length: 3 m
K45 Welder connection cable A05B2302J274 Connected length: 6 m
A05B2302J275 Connected length: 13 m
Cannot be used for TIG welding
K46 Peripheral device connection cable Not included. Must be supplied by customer.
11. CONNECTIONS
MARMMTRBL02303E
1136

11.3.5 Up to two boards can be installed in one cabinet.


Process I/O Printed
Circuit Board DA Figure 1239. Process I/O Printed Circuit Board DA

Table 118. Process I/O Printed Circuit Board DA


Cable
Name Drawing Number Remarks
Number
K10 Process I/O connection cable A05B2300J013 R-J control unit internal cable
K11 Peripheral device connection cable A05B2300J014 R-J control unit internal cable (for connecting
additional printed circuit boards)
A05B2302J113 Connected length: 7 m
Honda Tsushin, 50 pins: one-to-one
K50 Peripheral device connection cable A05B2302J114 Connected length: 14 m
A-H Honda Tsushin, 50 pins: one-to-one
A05B2302J115 Connected length: 30 m
Honda Tsushin, 50 pins: one-to-one
A05B2302J120 Connected length: 7 m
Honda Tsushin, 20 pins: one-to-one
K51 Welder connection cable A05B2302J121 Connected length: 14 m
A-D Honda Tsushin, 20 pins: one-to-one
A05B2302J122 Connected length: 30 m
Honda Tsushin, 20 pins: one-to-one
11. CONNECTIONS

MARMMTRBL02303E 1137

11.3.6
Process I/O Printed
Circuit Board with the
Modular I/O Unit
Figure 1240. Process I/O Printed Circuit Board with Modular I/O

Table 119. Process I/O Printed Circuit Board DA


Cable
Name Drawing Number Remarks
Number
K15 I/O unit connection cable R-J control unit internal cable. Attached to the I/O
unit mainframe.
K16 I/O unit power connection cable R-J control unit internal cable. Attached to the I/O
unit mainframe.
K54 Peripheral device connection cable Not included. Must be supplied by the customer.
11. CONNECTIONS
MARMMTRBL02303E
1138

11.3.7 Figure 1241 shows the connection when two or more process I/O printed
Two or More Process circuit boards and the modular I/O unit are used. Up to two process I/O
CA/CB/DAs and 1 process I/O AA/AB/BA/BB or I/O unit model A can
I/O Boards with the be installed in one cabinet.
Modular I/O Unit
Figure 1241. Two or More Process I/O Boards and the I/O Unit (Model A)

Table 1110. Two or More Process I/O Boards and the I/O Unit (Model A)
Cable
Name Drawing Number Remarks
Number
K10 Process I/O connection cable A05B2300J013 R-J control unit internal cable
K11 Peripheral device connection cable A05B2300J014 R-J control unit internal cable (for connecting
additional printed circuit boards)
K12 Process I/O connection cable A05B-2300-J017 R-J control unit internal cable for connecting
additional printed circuit boards.
K15 I/O unit connection cable R-J control unit internal cable. Attached to the I/O
unit mainframe.
K16 I/O unit power connection cable R-J control unit internal cable. Attached to the I/O
unit mainframe.
11. CONNECTIONS

MARMMTRBL02303E 1139

11.3.8 There are 18 exclusive data inputs (DI) and 20 exclusive data outputs (DO)
Peripheral Device and for a process I/O printed circuit board. These signals are allocated to the
process IO printed circuit board connected first when two or more printed
Control Unit boards are combined. General signals SI/SO are allocated to the second
Connection and the following process I/O printed circuit boards.

The common voltage of the DI signals input to pins 1 to 4 of connector


CRM2A is clamped +24V (common) in each process I/O printed circuit
board. This is also true when multiple boards are combined.
Table 1111 shows signals of a process I/O printed circuit board
Table 1111. Process I/O Printed Circuit Board Signals, DI Signals
Connector Number Signal Name Description Remarks
CRM2A-1 *IMSTP Immediate stop Clamped at +24V common
CRM2A-2 *HOLD Temporary stop Clamped at +24V common
CRM2A-3 *SFSD Safe speed Clamped at +24V common
CRM2A-4 CSTOPI Cycle stop Clamped at +24V common
CRM2A-5 FAULT RESET External reset
CMR2A-6 START Start
CRM2A-7 HOME Return to home position
CRM2A-8 ENBL Operation enabled
CRM2A-9 RSR1 Robot service request
PNS1 Program number selection Option
CRM2A-10 RSR2 Robot service request
PNS2 Program number selection Option
CRM2A-11 RSR3 Robot service request
PNS3 Program number selection Option
CRM2A-12 RSR4 Robot service request
PNS4 Program number selection Option
CRM2A-13 RSR5 Robot service request
PNS5 Program number selection Option
CRM2A-14 RSR6 Robot service request
PNS6 Program number selection Option
CRM2A-15 RSR7 Robot service request
PNS7 Program number selection Option
CRM2A-16 RSR8 Robot service request
PNS8 Program number selection Option
CRM2A-29 PNSTROBE PNS strobe
CMR2A-30 PROD START Start of automatic operation
11. CONNECTIONS
MARMMTRBL02303E
1140

Table 1111. (Contd) Process I/O Printed Circuit Board Signals, DI Signals
Connector Number Signal Name Description Remarks
CRM2A-31 SI01 Peripheral device status General signal
CRM2A-32 SI02
CRM2B-1 SI03
CRM2B-2 SI04
CRM2B-3 SI05
CRM2B-4 SI06
CRM2B-5 SI07
CRM2B-6 SI08
CRM2B-7 SI09
CRM2B-8 SI10
CRM2B-9 SI11
CRM2B-10 SI12
CRM2B-11 SI13
CRM2B-12 SI14
CRM2B-13 SI15
CRM2B-14 SI16
CRM2B-15 SI17
CRM2B-16 SI18
CRM2B-29 SI19
CRM2B-30 SI20
CRM2B-31 SI21
CRM2B-32 SI22

Table 1112. Process I/O Printed Circuit Board Signals, DO Signals


Connector Number Signal Name Description Remarks
CRM2A-33 CMDENBL During automatic operation
CRM2A-34 SYSRDY Preparation completed
CRM2A-35 PROGRUN During regeneration
CRM2A-36 PAUSED Program being interrupted
CRM2A-38 HELD During temporary stop
CRM2A-39 FAULT Alarm
CRM2A-40 ATPERCH Home position
CRM2A-41 TPENBL Teach pendant enabled
CRM2A-43 BATALM Battery voltage drop
CRM2A-44 BUSY During operation
CRM2A-45 ACK1 Robot service request acceptance
SNO1 Selected program number Option
CRM2A-46 ACK2 Robot service request acceptance
SNO2 Selected program number Option
CRM2A-19 ACK3 Robot service request acceptance
SNO3 Selected program number Option
11. CONNECTIONS

MARMMTRBL02303E 1141

Table 1112. (Contd) Process I/O Printed Circuit Board Signals, DO Signals
Connector Number Signal Name Description Remarks
CRM2A-20 ACK4 Robot service request acceptance
SNO4 Selected program number Option
CRM2A-21 ACK5 Robot service request acceptance
SNO5 Selected program number Option
CRM2A-22 ACK6 Robot service request acceptance
SNO6 Selected program number Option
CRM2A-24 ACK7 Robot service request acceptance
SNO7 Selected program number Option
CRM2A-25 ACK8 Robot service request acceptance
SNO8 Selected program number Option
CRM2A-26 SNACK
CRM2A-27 RESERVED
CRM2B-33 SO01 Peripheral device control signal General signal
CRM2B-34 SO02
CRM2B-35 SO03
CRM2B-36 SO04
CRM2B-38 SO05
CRM2B-39 SO06
CRM2B-40 SO07
CRM2B-41 SO08
CRM2B-43 SO09
CRM2B-44 SO10
CRM2B-45 SO11
CRM2B-46 SO12
CRM2B-19 SO13
CRM2B-20 SO14
CRM2B-21 SO15
CRM2B-22 SO16
CRM2B-24 SO17
CRM2B-25 SO18
CRM2B-26 SO19
CRM2B-27 SO20
11. CONNECTIONS
MARMMTRBL02303E
1142

Figure 1242. Peripheral Device and Control Unit Connection -A1/A2

Note 1: The peripheral device connection cables


are optional.
Note 2: All of COM** are connected 0 V.

Table 1113. Applicable Process I/O Printed Circuit Board - A1/A2


Type Specifications CRM2A CRM2B
AA A05B-2300-J001  
AB A05B-2300-J002  
BA A05B-2300-J020  
BB A05B-2300-J021  
CA A05B-2300-J030  
CB A05B-2300-J031  
DA A05B-2300-J035  
 = applicable  = not applicable
11. CONNECTIONS

MARMMTRBL02303E 1143

Figure 1243. Peripheral Device and Control Unit Connection -A3/A4

Note 1: The peripheral device connection cables


are optional.
Note 2: All of COM** are connected 0 V.

Table 1114. Applicable Process I/O Printed Circuit Board - A3/A4


Type Specifications CRM2C CRM2D
AA A05B-2300-J001  
AB A05B-2300-J002  
BA A05B-2300-J020  
BB A05B-2300-J021  
CA A05B-2300-J030  
CB A05B-2300-J031  
DA A05B-2300-J035  

 = applicable
 = not applicable
11. CONNECTIONS
MARMMTRBL02303E
1144

Figure 1244. Peripheral Device and Control Unit Connection - B1/B2

Note 1: The peripheral device connection


cables are optional.
Note 2: All of COM** are connected 0 V.

Table 1115. Applicable Process I/O Printed Circuit Board - B1/B2


Type Specifications CRM4A CRM4B
AA A05B-2300-J001  
AB A05B-2300-J002  
BA A05B-2300-J020  
BB A05B-2300-J021  
CA A05B-2300-J030  
CB A05B-2300-J031  
DA A05B-2300-J035  

 = applicable
 = not applicable
11. CONNECTIONS

MARMMTRBL02303E 1145

Figure 1245. Peripheral Device and Control Unit Connection -C1

Note 1: The peripheral device connection cable is not


supplied by FANUC. It must be supplied by the
customer.

Table 1116. Applicable Process I/O Printed Circuit Board - C1


Type Specifications TBI1 TB01
AA A05B-2300-J001  
AB A05B-2300-J002  
BA A05B-2300-J020  
BB A05B-2300-J021  
CA A05B-2300-J030  
CB A05B-2300-J031  
DA A05B-2300-J035  
 = applicable
 = not applicable
11. CONNECTIONS
MARMMTRBL02303E
1146

Figure 1246. Peripheral Device Interface Control for A1, A2, A3, and A4

Control Unit Connector pin No. Peripheral device


+24E CRM2A(49,50)
A4 A3 A2 A1
CRM2x (1)
SI43 SI23 SI03 *IMSTP RV

CRM2x (2)
SI44 SI24 SI04 *HOLD RV

CRM2x (3)
SI45 SI25 SI05 *SFSPD RV

CRM2x (4)
SI46 SI26 SI06 *CSTOPI RV

CRM2x (5)
SI47 SI27 SI07 FAULT RESET RV

CRM2x (6)
SI48 SI28 SI08 START RV

CRM2x (7)
SI49 SI29 SI09 HOME RV

CRM2x (8)
SI50 SI30 SI10 ENBL RV

CRM2x (9)
SI31 SI11 RSR1/PNS1 RV
SI51

CRM2x (10)
SI52 SI32 SI12 RSR2/PNS2 RV

CRM2x (11)
SI53 SI33 SI13 RSR3/PNS3 RV

CRM2x (12)
SI54 SI34 SI14 RSR4/PNS4 RV

CRM2x (13)
SI55 SI35 SI15 RSR5/PNS5 RV

CRM2x (14)
SI56 SI36 SI16 RSR6/PNS6 RV

CRM2x (15)
SI57 SI37 SI17 RSR7/PNS7 RV

CRM2x (16)
SI58 SI38 SI18 RSR8/PNS8 RV

CRM2x (29)
SI59 SI39 SI19 PNSTROBE RV

CRM2x (30)
SI60 SI40 SI20 PROD START RV

CRM2x (31)
SI61 SI41 SI21 SI01 RV

CRM2x (32)
SI62 SI42 SI22 SI02 RV
Note: For A1, CRM2x = CRM2A and ICOMn = ICOM1 +24E
For A2, CRM2x = CRM2B and ICOMn = ICOM2 B A
For A3, CRM2x = CRM2C and ICOMn = ICOM3 Common switching
For A4, CRM2x = CRM2D and ICOMn = ICOM4 set pin (ICOMn)
11. CONNECTIONS

MARMMTRBL02303E 1147

Figure 1247. Peripheral Device Interface for A1, A2, A3, and A4

Control Unit Connector Pin No. Peripheral Device

A4 A3 A2 A1 LOAD
DV CRM2x(33)
SO41 SO21 SO01 CMDENBL RELAY

CRM2x(34)
SO42 SO22 SO02 SYSRDY DV LOAD
CRM2x(35)
SO43 SO23 SO03 PROGRUN DV LOAD
CRM2x(36)
SO44 SO24 SO04 PAUSED DV LOAD
CRM2x(38)
SO45 SO25 SO05 HELD DV LOAD
CRM2x(39)
SO46 SO26 SO06 FAULT DV LOAD
CRM2x(40)
SO47 SO27 SO07 ATPERCH DV LOAD
CRM2x(41)
SO48 SO28 SO08 TPENBL DV LOAD
CRM2x(43)
SO49 SO29 SO09 BATALM DV LOAD
CRM2x(44)
SO50 SO30 SO10 BUSY DV LOAD
CRM2x(45)
SO51 SO31 SO11 ACK1/SNO1 DV LOAD
CRM2x(46)
SO52 SO32 SO12 ACK2/SNO2 DV LOAD
CRM2x(19)
SO53 SO33 SO13 ACK3/SNO3 DV LOAD
CRM2x(20)
SO54 SO34 SO14 ACK4/SNO4 DV LOAD
CRM2x(21)
SO55 SO35 SO15 ACK5/SNO5 DV LOAD
CRM2x(22)
SO56 SO36 SO16 ACK6/SNO6 DV LOAD
CRM2x(24)
SO57 SO37 SO17 ACK7/SNO7 DV LOAD
CRM2x(25)
SO58 SO38 SO18 ACK8/SNO8 DV LOAD
CRM2x(26)
SO59 SO39 SO19 SNACK DV LOAD
CRM2x(27)
SO60 SO40 SO20 RESERVED DV LOAD

CRM2x(23,28,37,42,47)
Note: For A1, CRM2x = CRM2A 0V +24V
+24V regulated
For A2, CRM2x = CRM2B power supply

For A3, CRM2x = CRM2C


For A4, CRM2x = CRM2D
11. CONNECTIONS
MARMMTRBL02303E
1148

Figure 1248. Peripheral Device Control Interface B1

Connector pin No. Peripheral device


+24E CRM4A(49,50)

CRM4A(1)
SI63 RV

CRM4A(2)
SI64 RV

CRM4A(3)
SI65 RV

CRM4A(4)
SI66 RV

CRM4A(5)
SI67 RV

CRM4A(6)
SI68 RV

CRM4A(7)
SI69 RV

CRM4A(13)
SI70 RV

+24V B A

Common Switching
Set Pin
(Icom5)

Connector Pin No.

LOAD
DV CRM4A(14)
SO61 RELAY

CRM4A(15)
SO62 DV LOAD
CRM4A(16)
SO63 DV LOAD
CRM4A(17)
SO64 DV LOAD
CRM4A(8)
SO65 DV LOAD
CRM4A(9)
SO66 DV LOAD
CRM4A(10)
SO67 DV LOAD
CRM4A(11)
SO68 DV LOAD

CRM4A(20)
0V +24V
+24V regulated
power supply
11. CONNECTIONS

MARMMTRBL02303E 1149

Figure 1249. Peripheral Device Control Interface B2

Connector pin No. Peripheral device


+24E CRM4B(49,50)

CRM4B(1)
SI71 RV

CRM4B(2)
SI72 RV

CRM4B(3)
SI73 RV

CRM4B(4)
SI74 RV

CRM4B(5)
SI75 RV

CRM4B(6)
SI76 RV

CRM4B(7)
SI77 RV

CRM4B(13)
SI78 RV

+24V B A

Common Switching
Set Pin
(Icom5)

Connector Pin No.

LOAD
DV CRM4B(14)
SO69 RELAY

CRM4B(15)
SO70 DV LOAD
CRM4B(16)
SO71 DV LOAD
CRM4B(17)
SO72 DV LOAD
CRM4B(8)
SO73 DV LOAD
CRM4B(9)
SO74 DV LOAD
CRM4B(10)
SO75 DV LOAD
CRM4B(11)
SO76 DV LOAD

CRM4B(20)
0V +24V
+24V regulated
power supply
11. CONNECTIONS
MARMMTRBL02303E
1150

Figure 1250. Peripheral Device Control Interface C1

Peripheral device
Receiver Circuit
TBI(1)
*IMSTP RV

TBI(2)
*HOLD RV

TBI(3)
*SFSPD RV

TBI(4)
CSTOPI RV

TBI(5)
FAULT RESET RV

TBI(6)
START RV

TBI(7)
HOME
RV

TBI(8)
ENBL
RV

COM1 TBI(9) COM


(+24V or 0V)
0V TBI(10)
0V +24V
+24V regulated
power supply

Receiver Circuit
TBI(11)
RSR1/PNS1 RV

TBI(12)
RSR2/PNS2 RV

TBI(13)
RSR3/PNS3 RV

TBI(14)
RSR4/PNS4 RV

TBI(15)
RSR5/PNS5 RV

TBI(16)
RSR6/PNS6 RV

TBI(17)
RSR7/PNS7 RV

TBI(18)
RSR8/PNS8 RV

COM2 TBI(19) COM


(+24V or 0V)
0V TBI(20)
11. CONNECTIONS

MARMMTRBL02303E 1151

Figure 1251. Peripheral Device Control Interface C1

Peripheral device
Receiver Circuit
TBI(21)
PNSTROBE RV

TBI(22)
PROD START RV

TBI(23)
SI01 RV

TBI(24)
SI02 RV

TBI(25)
SI03 RV

TBI(26)
SI04 RV

TBI(27)
SI05 RV

TBI(28)
SI06 RV

COM1 TBI(29) COM


(+24V or 0V)
0V TBI(30)

Receiver Circuit
TBI(31)
SI07 RV

TBI(32)
SI08 RV

TBI(33)
SI09 RV

TBI(34)
SI10 RV

TBI(35)
SI11 RV

TBI(36)
SI12 RV

TBI(37)
SI13 RV

TBI(38)
SI14 RV

COM1 TBI(39) COM


(+24V or 0V)
0V TBI(40)
11. CONNECTIONS
MARMMTRBL02303E
1152

Figure 1252. Peripheral Device Control Interface C1

Control unit Peripheral device


(peripheral device control interface C1)

+ 24 V regulated
power supply

Internal
circuit

+ 24 V regulated
power supply

Internal
circuit
11. CONNECTIONS

MARMMTRBL02303E 1153

Figure 1253. Peripheral Device Control Interface C1

Control unit Peripheral device


(peripheral device control interface C1)
+ 24 V regulated
power supply

Internal
circuit

+ 24 V regulated
power supply

Internal
circuit
11. CONNECTIONS
MARMMTRBL02303E
1154

Figure 1254. Peripheral Device Control Interface C1

Control unit Peripheral device


(peripheral device control interface C1)

+ 24 V regulated
power supply

Internal
circuit

+ 24 V regulated
power supply

Internal
circuit
11. CONNECTIONS

MARMMTRBL02303E 1155

Figure 1255. Peripheral Device Control Interface C1

Control unit Peripheral device


(peripheral device control interface C1)

+ 24 V regulated
power supply

Internal
circuit

+ 24 V regulated
power supply

Internal
circuit
11. CONNECTIONS
MARMMTRBL02303E
1156

11.3.9
Mechanical Unit and
End Effector
Connection Figure 1256. Mechanical Unit and End Effector

Mechanical unit

Refer to Figure 11-42 to 1145 for pin


configuration for your specific robot. End Effector

+24V B A
Common switching
set pin
11. CONNECTIONS

MARMMTRBL02303E 1157

Figure 1257. End Effector Pin Configuration Arc Mate/S-5, Arc Mate Sr/S-10,
S-420, S-500, S-700, S-800, S-900, M-400 and M-500

End Effector

Figure 1258. End Effector Pin Configuration Arc Mate 100/S-6

End Effector

OR

1 2 3
RDO1 *HBK 0V
4 5
RDI1 +24E
11. CONNECTIONS
MARMMTRBL02303E
1158

Figure 1259. End Effector Pin Configuration A-510

End Effector

Figure 1260. End Effector Pin Configuration L-1000

End Effector
11. CONNECTIONS

MARMMTRBL02303E 1159

11.3.10
Control Unit and
Welder Connection
Figure 1261. Control Unit and Welder Connection - CRW1/CRW2

Note: The welder and peripheral device


connection cable are optional.

Table 1117. Applicable Process I/O Printed Circuit Board


Type Specifications CRW1 CRW2
AA A05B-2300-J001  
AB A05B-2300-J002  
BA A05B-2300-J020  
BB A05B-2300-J021  
CA A05B-2300-J030  
CB A05B-2300-J031  
DA A05B-2300-J035  

 = applicable
 = not applicable
11. CONNECTIONS
MARMMTRBL02303E
1160

Figure 1262. Control Unit and Welder Connection - CRW1 Analog Signal
Assignment
11. CONNECTIONS

MARMMTRBL02303E 1161

Figure 1263. Control Unit and Welder Connection - CRW1 Digital Signal
Assignment
11. CONNECTIONS
MARMMTRBL02303E
1162

Figure 1264. Control Unit and Welder Connection - CRW2 Analog Signal
Assignment
11. CONNECTIONS

MARMMTRBL02303E 1163

11.3.11 Table 1118 contains the specifications of the peripheral device interface.
Peripheral Device
Interface
Table 1118. Peripheral Device Interface Specifications
Type Example of Connection Signal Standards
Output signals Electrical Specifications
in peripheral Rated voltage: 24 VDC
device interface Maximum applied voltage: 30 VDC
A and B Maximum load current: 0.2 A
Transistor type: Open collector NPN
Saturation voltage at connection: 1.0 V (approx.)
Spark Killer Diode
Rated peak reverse voltage: 100 V or more
Rated effective forward current: 1 A or more
Note on Use
Do not use the +24V power supply of the robot.
When loading a relay, solenoid, and so on directly,
connect them in parallel with diodes for preventing
back electromotive force. If a load is connected
causing a surge current when a lamp is turned on,
use a protective resistance.
Applicable Signals
Output signals of process I/O printed circuit board CRM2
and CRM4; CMDENBL, SYSRDY, PROGRUN, PAUSED,
HELD, FAULT, ATPERCH, TPENBL, BATALM, BUSY,
ACK1 to ACK8, SNO1 to SNO8, SNACK, SO1 to SO20

Input signals in
peripheral
device interface Electrical Specifications of the Receiver
A and B Type: Grounded voltage receiver
Rated input voltage: Contact closed: +20V to +28V
Contact open: 0V to +4V
Maximum applied
input voltage: +28 VDC
Input impedance: 3.3 k (approx.)
Response time: 5 ms to 20 ms
Specifications of the Peripheral Decive Contact
Rated contact capacity: 30 VDC, 50 mA or more
Input signal width: 200 ms or more (on/off)
Chattering time: 5 ms or less
Closed circuit resistance: 100  or less
Peripheral
Opened circuit resistance: 100 k or more
device
contact Note on Use
signal Apply the +24V power at the robot to the receiver.
However, the above signal specifications must be
satisfied at the robot receiver.
Robot
receiver Applicable Signals
signal
Input signals of process I/O printed circuit board CRM2
and CRM4; *IMSTP, *HOLD, *SFSD, CSTOPI, FAULT
RESET, START, HOME, ENBL, RSR1 to RSR8, PNS1 to
TB: Chattering 5 ms or less PNS8, PNSTROBE, PROD STASRT, SI1 to SI22
TC: 5 to 20 ms
11. CONNECTIONS
MARMMTRBL02303E
1164

Table 1118. (Contd) Peripheral Device Interface Specifications


Type Example of Connection Signal Standards
Output signals Electrical Specifications
in peripheral Rated voltage: 24 VDC
device interface Maximum applied voltage: 30 VDC
C Maximum load current: 1.6 A (*1)
*1: This value is the maximum load current at one point.
When four points on the same common are turned on at
the same time, the maximum load current at one common
is 5.0 A.
Spark Killer Diode
Rated peak reverse voltage: 100 V or more
Rated effective forward current: 1 A or more
Note on Use
Do not use the +24 V power supply of the robot. When
loading a relay, solenoid, and so on directly, connect them
in parallel with diodes for preventing back electromotive
force. If a load is connected causing a surge current
when a lamp is turned on, use a protective resistance.
Applicable Signals
Output signals of process I/O printed circuit board BA/BB
TBO1; CMDENBL, SYSRDY, PROGRUN, PAUSED,
HELD, FAULT, ATPERCH, TPENBL, BATALM, BUSY,
ACK1 to ACK8, SNO1 to SNO8, SNACK, SO1 to SO12.
Input signals in
peripheral Electrical Specifications of the Receiver
Type: Grounded voltage receiver
device interface
Rated input voltage: Contact closed: +20V to +28V
C Contact open: 0V to +4V
Maximum applied
input voltage: +28 VDC
Input impedance: 3.3 k (approx.)
Response time: 5 ms to 20 ms
Specifications of the Peripheral Device Contact
Rated contact capacity: 30 VDC, 50 mA or more
Input signal width: 200 ms or more (on/off)
Chattering time: 5 ms or less
Closed circuit resistance: 100  or less
Opened circuit resistance: 100 k or more

Note on Use
Apply the +24V power at the robot to the receiver.
However, the above signal specifications must be
satisfied at the robot receiver.

Applicable Signals
Input signals of process I/O printed circuit board BA/BB
TBI1; *IMSTP, *HOLD, *SFSD, CSTOPI, FAULT RESET,
START, HOME, ENBL, RSR1 to RSR8, PNS1 to PNS8,
PNSTROBE, PROD STASRT, SI1 to SI24

Peripheral
device
contact
signal

Robot
receiver
signal

TB: Chattering 5 ms or less TC: 5 to 20 ms


11. CONNECTIONS

MARMMTRBL02303E 1165

11.3.12 Table 1119 contains the specifications of the end effector control
End Effector Control interface.
Interface
Table 1119. End Effector Control Interface Signals
Type Example of Connection Signal Standards
Output signals Electrical Specifications
Rated voltage: 24 VDC
Maximum applied voltage: 30 VDC
Maximum load current: 0.2 A
Transistor type: Open collector NPN
Saturation voltage at connection: 1.0 V (approx.)
Spark Killer Diode
Rated peak reverse voltage: 100 V or more
Rated effective forward current: 1 A or more
Note on Use
The +24 V power supply at the robot can be used when
the total current of the welding interface and end effector
interface is 0.7 A or less. When loading a relay, solenoid,
and so on directly, connect them in parallel with diodes for
preventing back electromotive force. If a load is
connected causing a surge current when a lamp is turned
on, use a protective resistance.
Applicable Signals
Output signals of the end effector control interface
RO1 to RO8

Input signal
Electrical Specifications of the Receiver
Type: Grounded voltage receiver
Rated input voltage: Contact closed: +20V to +28V
Contact open: 0V to +4V
Maximum applied
input voltage: +28 VDC
Input impedance: 3.3 k (approx.)
Response time: 5 ms to 20 ms
Specifications of the Peripheral Device Contact
Rated contact capacity: 30 VDC, 50 mA or more
Input signal width: 200 ms or more (on/off)
Chattering time: 5 ms or less
Closed circuit resistance: 100  or less
Opened circuit resistance: 100 k or more
Peripheral
device Note on Use
contact
signal Apply the +24V power at the robot to the receiver.
However, the above signal specifications must be
satisfied at the robot receiver.
Robot Applicable Signals
receiver
signal Input signals of the end effector control interface
RI1 toRI 8, *HBK, *PPABN

TB: Chattering 5 ms or less TC: 5 to 20 ms


11. CONNECTIONS
MARMMTRBL02303E
1166

11.3.13 Table 1120 contains the specifications of the arc welding interface.
Arc Welding Interface
Process I/O AA
Table 1120. Arc Welding Interface Signals
Type Example of Connection Signal Standards
Digital output Electrical Specifications
signals Rated voltage: 24 VDC
Maximum applied voltage: 30 VDC
Maximum load current: 0.2 A
Transistor type: Open collector NPN
Saturation voltage at connection: 1.0 V (approx.)
Spark Killer Diode
Rated peak reverse voltage: 100 V or more
Rated effective forward current: 1 A or more
Note on Use
The +24 V power supply at the robot can be used when
the total current of the welding interface and end effector
interface is 0.7 A or less. When loading a relay, solenoid,
and so on directly, connect them in parallel with diodes for
preventing back electromotive force. If a load is
connected causing a surge current when a lamp is turned
on, use a protective resistance.
Applicable Signals
Output signals of the end effector control interface
WO1 to WO8
Digital input
Electrical Specifications of the Receiver
signals
Type: Grounded voltage receiver
Rated input voltage: Contact closed: +20V to +28V
Contact open: 0V to +4V
Maximum applied
input voltage: +28 VDC
Input impedance: 3.3 k (approx.)
Response time: 5 ms to 20 ms
Specifications of the Peripheral Device Contact
Rated contact capacity: 30 VDC, 50 mA or more
Input signal width: 200 ms or more (on/off)
Chattering time: 5 ms or less
Closed circuit resistance: 100  or less
Opened circuit resistance: 100 k or more

Note on Use
Apply the +24V power at the robot to the receiver.
Peripheral However, the above signal specifications must be
device satisfied at the robot receiver.
contact
signal
Applicable Signals
Input signals of the arc welding interface
WI1 to WI8
Robot
receiver
signal

TB: Chattering 5 ms or less TC: 5 to 20 ms


11. CONNECTIONS

MARMMTRBL02303E 1167

Table 1120. (Contd) Arc Welding Interface Signals


Type Example of Connection Signal Standards
Analog output Arc Welding Interface Note on Use
signals: welding Input impedance: 3.3 k or more
voltage Install a high-frequency filter.
command, wire
feed speed
command

Analog input Note on Use


Arc Welding Interface
signals: welding Output signals without ripples.
voltage
detection,
welding current
detection

Analog input
Arc Welding Interface Note on Use
signal: wire The resistance between the positive and negative
stick detect terminals on the welder must be 100  or more. The
WDI+, WDI maximum voltage of this circuit is 80 V. For TIG welding,
connected the wirestick detection signal line, insulating it
from a welding circuit (high frequency).
11. CONNECTIONS
MARMMTRBL02303E
1168

11.3.14 This section describes the connections and specifications for modular I/O
Modular I/O Inputs units.

Table 1121. Input Modules AID32A and AID32B, Nonisolated


Item AID32A AID32B
Points/module 32 points 32 points
Points/common 16 points/common 16 points/common
Sink/source cur- Both directions Both directions
rent
Input voltage 24VDC +10% 20% 24 VDC +10% 20%
Input current 7.5mA (average) 7.5mA (average)
ON voltage cur- Min. 18VDC min. 6 mA Min. 18 VDC min. 6 mA
rent
OFF voltage cur- Max. 6VDC max. 1.5 mA Max. 6VDC max. 1.5 mA
rent
Respo Max. 20 This is the value from input to output This is the value from input to output
nse OFF  ON in the module. The actual value is Max. 2 ms in the module. The actual value is
ms
Time determined by adding it to the determined by adding it to the
Max. 20 scanning time depending on each scanning time depending on each
ON  OFF Max. 2 ms
ms system. system.
Input display Not provided Not provided
External connec- Connector (HONDA TSUSIN MR-50RMA) Connector (HONDA TSUSIN MR-50RMA)
tion
Terminal : input circuit CM
connection and Internal
circuitry Circuit
29,45 21,36
CMA 49,50 CMC 40,41
A0 16 C0 07
A1 32 C1 24
A2 48 C2 39
A3 15 C3 06
A4 31 C4 23
A5 47 C5 38
A6 30 C6 22
A7 46 D7 37
B0 12 D0 03
B1 28 D1 20
B2 44 D2 35
B3 11 D3 02
B4 27 D4 19
B5 43 D5 34
B6 10 D6 01
B7 42 D7 33
13,17 +24V 04,08 +24V
14,18 GND 05,09 GND

+24V or GND can be selected for input common as above figure.


Note: Make sure to connect all common (CMA, CMC) pins.
11. CONNECTIONS

MARMMTRBL02303E 1169

Table 1122. Input Modules AID16C and AID16D


Item AID16C AID16D
Points/module 16 points 16 points
Points/common 16 points/common 16 points/common
Sink/source current Source current type Sink current type
Input voltage 24VDC +10% 20% 24 VDC +10% 20%
Input current 7.5 mA (average) 7.5 mA (average)
ON voltage current Min. 15VDC min. 4 mA Min. 15 VDC min. 4 mA
OFF voltage current Max. 5VDC max. 1.5 mA Max. 5VDC max. 1.5 mA
Response This is the value from input to This is the value from input to
Time OFF  ON Max. 20ms output in the module. The Max. 20ms output in the module. The
actual value is determined by actual value is determined by
ON  OFF Max. 20ms adding it to the scanning time Max. 20ms adding it to the scanning time
depending on each system. depending on each system.
Input display LED display LED display
External connection Terminal block connector (20 terminals, M3.5 Terminal block connector (20 terminals, M3.5
screw terminal) screw terminal)
Terminal connection and
circuitry (C) (D)
1
A0 2
A1 3
A2 4
A3 5
A4 6
A5 7
+
A6 8
+ A7 9
B0 10
B1 11
B2 12
B3 13
B4 14
B5 15
B6 16
B7 17
18
19
20

FOR AID16C FOR AID16D


: input circuit : input circuit
LED LED
1 1
11. CONNECTIONS
MARMMTRBL02303E
1170

Table 1123. Input Modules AID32E and AID32F


Item AID32E AID32F
Points/module 32 points 32 points
Points/common 8 points/common 8 points/common
Sink/source current Both directions Both directions
Input voltage 24VDC +10% 20% 24 VDC +10% 20%
Input current 7.5 mA (average) 7.5mA (average)
ON voltage current Min. 15VDC min. 4.5 mA Min. 15VDC min. 4.5 mA
OFF voltage current Max. 6VDC max. 2 mA Max. 6VDC max. 2 mA
Response Max. 20 This is the value from input to This is the value from input to
Time OFF  ON output in the module. The Max. 2 ms output in the module. The
ms
actual value is determined by actual value is determined by
Max. 20 adding it to the scanning time adding it to the scanning time
ON  OFF Max. 2 ms
ms depending on each system. depending on each system.
Input display Not provided Not provided
External connection Connector (HONDA TSUSIN MR-50RMA) Connector (HONDA TSUSIN MR-50RMA)
Terminal connection and
circuitry

: input circuit CM

CMA 49,50 CMC 40,41


A0 16 C0 07
A1 32 C1 24
A2 48 C2 39
A3 15 C3 06
A4 31 C4 23
A5 47 C5 38
A6 30 C6 22
A7 46 C7 37

CMB 29,45 CMD 21,36


B0 12 D0 03
B1 28 D1 20
B2 44 D2 35
B3 11 D3 02
B4 27 D4 19
B5 43 D5 34
B6 10 D6 01
B7 42 D7 33
11. CONNECTIONS

MARMMTRBL02303E 1171

Table 1124. Input Module AIA16G


Item AIA16G
Points/module 16 points
Points/common 16 points/common
Rated load voltage 100 ~ 155VAC  15%
Max. input voltage 132Vrms 50/60Hz
Input current 10.5mArms (120VAC 50Hz)
ON voltage current 74Vrms min. 6mArms
OFF voltage current 20Vrms max. 2.2mArms
Response This is the value from input to
Time OFF  ON Max. 35 ms output in the module. The
actual value is determined by
ON  OFF Max. 35 ms adding it to the scanning time
depending on each system.
Input display LED display
External connection Terminal block connector (20 terminals, M3.5
screw terminal)
Common 16 points/common
Terminal connection and
circuitry
A0 1
A1 2
A2 3
A3 4
A4 5
A5 6
A6 7
A7 8
B0 9
B1 10
B2 11
B3 12
B4 13
B5 14
B6 15
B7 16
17 NC
18 NC
19
20

: input circuit
LED

19
11. CONNECTIONS
MARMMTRBL02303E
1172

11.3.15
Modular I/O Outputs Table 1125. Output Module AOD32A, Non-isolated
Item AOD32A
Points/module 32 points
Points/common 8 points/common
Sink/source current Sink current type
Rated load voltage 5 ~ 24VDC +20% 15%
Maximum load current 0.3A (however 2A/common)
Maximum voltage 0.24V (load current  0.8)
drop when ON
Maximum leak current 0.1 mA
when OFF
Response OFF  ON Max. 1 ms
Time
ON  OFF Max. 1 ms
Output display Not provided
External connection Connector (HONDA TSUSIN MR-50RMA)
Terminal connection
and circuitry
O : output circuit +5~+24

Internal
Circuit

L : load CM
+24A 17 +24C 08
L A0 16 O L C0 07 O
L A1 32 O L C1 24 O
L A2 48 O L C2 39 O
+
L A3 15 O
+ L C3 06 O
L A4 31 O L C4 23 O
L A5 47 O L C5 38 O
L A6 30 O L D6 22 O
L A7 46 O L D7 37 O
CMA 49,50 CMC 40,41

+24B 13 +24D 04
L B0 12 O L D0 03 O
L B1 28 O L D1 20 O
L B2 44 O L D2 35 O
+ L B3 11 O
+ L D3 02 O
L B4 27 O L D4 19 O
L B5 43 O L D5 34 O
L B6 10 O L D6 01 O
L B7 42 O L D7 33 O
CMB 29,45 CMD 21,36
11. CONNECTIONS

MARMMTRBL02303E 1173

Table 1126. Output Modules AOD08C and AOD08D


Item AOD08C AOD08D
Points/module 8 points 8 points
Points/common 8 points/common 8 points/common
Sink/source current Sink current type Source current type
Rated load voltage 12 ~ 24VDC +20% 15% 12 ~ 24VDC +20% 15%
Maximum load current 2A (however 4A/fuse) 2A (however 4A/fuse)
Limit of load Refer to load derating curve
Maximum voltage drop 0.8V (load current  0.4) 1.2V (load current  0.6)
when ON
Maximum leak current 0.1mA 0.1mA
when OFF
Response This is the value from input to This is the value from input to
Time OFF  ON Max. 2 ms output in the module. The Max. 2 ms output in the module. The
actual value is determined by actual value is determined by
ON  OFF Max. 2 ms adding it to the scanning time Max. 2 ms adding it to the scanning time
depending on each system. depending on each system.
Output display LED display LED display
External connection Terminal block connector (20 terminal, M3.5 Terminal block connector (20 terminal, M3.5
screw terminal) screw terminal)
Fuse 5A, 1 piece for each output A0-A3 and A4-A7 5A, 1 piece for each output A0-A3 and A4-A7
Terminal connection Fuses Fuses
and circuitry 1 1
2 2
load 3 load 3
L A0 4 O L A0 4 O
5 5
L A1 6 O L A1 6 O
7 7
L A2 8 O L A2 8 O
9 9
L A3 10 O + L A3 10 O
+ 11 11
L A4 12 O L A4 12 O
13 13
L A5 14 O L A5 14 O
15 15
L A6 16 O L A6 16 O
17 17
L A7 O L A7 O
18 18
19 19

20 20
Fuses

O : output circuit O : output circuit


2 2

Internal Internal
LED Circuit
LED
Circuit

20 20
11. CONNECTIONS
MARMMTRBL02303E
1174

Table 1127. Output Modules AOD16C and AOD16D


Item AOD16C AOD16D
Points/module 16 points 16 points
Points/common 8 points/common 8 points/common
Sink/source current Sink current type Source current type
Rated load voltage 12 ~ 24VDC +20% 15% 12 ~ 24VDC +20% 15%
Maximum load current 0.5A (however 2A/common) 0.5A (however 2A/common)
Maximum voltage drop 0.7V (load current  1.4) 0.7V (load current  1.4)
when ON
Maximum leak current 0.1mA 0.1mA
when OFF
Response This is the value from input to This is the value from input to
Time OFF  ON Max. 2 ms output in the module. The Max. 2 ms output in the module. The
actual value is determined by actual value is determined by
ON  OFF Max. 2 ms adding it to the scanning time Max. 2 ms adding it to the scanning time
depending on each system. depending on each system.
Output display LED display LED display
External connection Terminal block connector (20 terminal, M3.5 Terminal block connector (20 terminal, M3.5
screw terminal) screw terminal)
Terminal connection and L : load L : load
circuitry 1 1
L A0 2 O L A0 2 O
L A1 3 O L A1 3 O
L A2 4 O L A2 4 O
+ +
L A3 5 O L A3 5 O
L A4 6 O L A4 6 O
L A5 7 O L A5 7 O
L A6 8 O L A6 8 O
L A7 9 O L A7 9 O
10 10
11 11
L B0 12 O L B0 12 O
L B1 13 O L B1 13 O
L B2 14 O L B2 14 O
+ L B3 15 O + L B3 15 O
L B4 O L B4 O
16 16
L B5 17 O L B5 17 O
L B6 18
O L B6 18
O
L B7 19 O L B7 19 O
20 20

O : output circuit O : output circuit

1 1

Internal
Circuit
LED Internal LED
Circuit

10 10
11. CONNECTIONS

MARMMTRBL02303E 1175

Table 1128. Output Module AOD32C


Item AOD32C
Points/module 32 points
Points/common 8 points/common
Sink/source current Sink current type
Rated load voltage 12 ~ 24VDC +20% 15%
Maximum load current 0.3A (however 2A/common)
Maximum voltage drop 0.24V (load current  0.8)
when ON
Maximum leak current 0.1mA
when OFF
Response OFF  ON Max. 2 ms This is the value from input to output in the module. The actual value is
Time determined by adding it to the scanning time depending on each system
system.
ON  OFF Max. 2 ms
Output display Not provided
External connection Connector (HONDA TSUSIN MR-50RMA)
Terminal connection and +24
circuitry O : output circuit

Internal
Circuit

CM
L : load

+24A 17 +24C 08
L A0 16 O L C0 07 O
L A1 32 O L C1 24 O
L A2 48 O L C2 39 O
L A3 15 O L C3 06 O
+ +
L A4 31 O L C4 23 O
L A5 47 O L C5 38 O
L A6 30 O L C6 22 O
L A7 46 O L C7 37 O
CMA 49,50 CMC 40,41

+24B 13 +24D 04
L B0 12 O L D0 03 O
L B1 28 O L D1 20 O
L B2 44 O L D2 35 O
+ L B3 11 O L D3 02 O
L B4 27 O L D4 19 O
L B5 43 O L D5 34 O
L B6 10 O L D6 01 O
L B7 42 O L D7 33 O
CMB 29,45 CMD 21,36

Note: For the common (CMA, CMB CMC, CMD) make sure to use both of them.
11. CONNECTIONS
MARMMTRBL02303E
1176

Table 1129. Output Module AOD32D


Item AOD32D
Points/module 32 points
Points/common 8 points/common
Sink/source current Source current type
Rated load voltage 12 ~ 24VDC +20% 15%
Maximum load current 0.3A (however 2A/common)
Maximum voltage drop 0.24V (load current  0.8)
when ON
Maximum leak current 0.1mA
when OFF
Response Max. 2 ms This is the value from input to output in the module. The actual value is
OFF  ON
Time determined by adding it to the scanning time depending on each system.
ON  OFF Max. 2 ms
Output display Not provided
External connection Connector (HONDA TSUSIN MR-50RMA)
Terminal connection and
CM
circuitry O : output circuit Internal
Circuit

0
L : load

CMA 49,50 CMC 40,41


L A0 16 O L C0 07 O
L A1 32 O L C1 24 O
L A2 48 O L C2 39 O
L A3 15 O L C3 06 O
+ +
L A4 31 O L C4 23 O
L A5 47 O L C5 38 O
L A6 30 O L C6 22 O
L A7 46 O L C7 37 O
0A 1B 0C 09

CMB 29,45 CMD 21,36


L B0 12 O L D0 03 O
L B1 28 O L D1 20 O
L B2 44 O L D2 35 O
+ L B3 11 O + L D3 02 O
L B4 27 O L D4 19 O
L B5 43 O L D5 34 O
L B6 10 O L D6 01 O
L B7 42 O L D7 33 O
0B 14 0D 05

Note: For the common (CMA, CMB CMC, CMD) make sure to use both of them.
11. CONNECTIONS

MARMMTRBL02303E 1177

Table 1130. Output Modules AOA05E and AOA08E


Item AOA05E AOA08E
Points/module 5 points 8 points
Points/common 1 point/common 4 points/common
Rated load voltage 100 ~ 230VAC  15%, 47 ~ 63Hz 100 ~ 230VAC  15%, 47 ~ 63Hz
Maximum load current 2A (however 5A/module) 1A (however 2A/common)
Maximum in rush current 25A (1 period) 10A (1 period)
Limit of load Refer to load derating curve
Maximum voltage drop 1.5Vrms 1.5Vrms
when ON
Maximum leak current 3.0mA (115VAC), 6.0mA (230VAC) 3.0mA (115VAC), 6.0mA (230VAC)
when OFF
Response OFF  ON Max. 1 ms This is the value from input to Max. 1 ms This is the value from input to
Time output in the module
module. The output in the module
module. The
Half of the actual value is determined by Half of the actual value is determined by
load load
ON  OFF adding it to the scanning time adding it to the scanning time
frequency depending on each system. frequency depending on each system.
or less or less
Output display LED display LED display
External connection Terminal block connector (20 terminals, M3.5 Terminal block connector (20 terminals, M3.5
screw terminal) screw terminal)
Fuse 3.2A, 1 piece for each output A0 ~ A4 3.2A, 1 piece for each output A0 ~ A3 and
A4~ A7
Terminal connection and 1
1
circuitry L A0 O
2 2
3 O 3
L A0 L A1 O
4 4
5 5
6 L A2 6 O
7 O 7
L A1 L A3 O
8 8
9 9 Fuse
10 10
11 O 11
L A2 12 L A4 12 O
13 13
14 L A5 14 O
15 O 15
L A3 16 L A6 16 O
17 17

18 L A7 18 O
19 O 19
Fuse
L A4 20 20
load load

O : O : output circuit
o
u
2 t-
p
u
t LED LED
c
4 i 10 20
r-
c
u
i
t
11. CONNECTIONS
MARMMTRBL02303E
1178

Table 1131. Output Module AOA12F

Item AOA12F
Points/module 12 points
Points/common 6 points/common
Rated load voltage 100 ~ 115VDC  15% 47 ~ 63Hz
Maximum load current 0.5A/point (however 2A/common)
Maximum in rush current 5A (1 period)
Limit of load Refer to load derating curve
Maximum voltage drop 1.5Vrms
when ON
Maximum leak current 1.5mA (115 VAC)
when OFF
Response This is the value from input to
Time OFF  ON Max. 1 ms output in the module. The
actual value is determined by
ON  OFF Half of the load frequency or less adding it to the scanning time
depending on each system.
Output display LED display
External connection Terminal block connector (20 terminal, M3.5 screw terminal)
Fuse 3.2A, 1 piece for each output A0 ~ A5 and
B0 ~ B5
Terminal connection and L : load
circuitry
L A0 1 O
L A1 2 O
L A2 3 O
L A3 4 O
L A4 5 O
L A5 6 O
7 O
8 O
9
Fuse
10
L B0 11 O
L B1 12 O
L B2 13 O
L B3 14 O
L B4 15 O
L B5 O
16
17 O
O
18 NOTE:
19
Fuse Each output signal group (A0A5 and
20 B0B5) contains six output signals.
O : output circuit However, each group must have an entire
group of eight signals assigned to it.
For example, A0A5 might be occupied
by digital outputs 1 through 6 and B0B5
might be occupied by digital outputs
LED 9 through 14. Digital outputs 7 and 8 and
9 19 digital outputs 15 and 16 are unusuable.
11. CONNECTIONS

MARMMTRBL02303E 1179

Table 1132. Output Modules AOR08G and AOR16G


Item AOR08G AOR16G
Points/module 8 points 8 points
Points/common 1 point/common 4 points/common
Maximum load 30VDC/250VAC, 4A (resistance load) 30VDC/250VAC, 2A (resistance load)
Minimum load 5VDC, 10mA 1A (however 2A/common)
Maximum current 4A/common
Limit of load Refer to load derating curve Refer to load derating curve
Response Time This is the value This is the value
from input to out- from input to out-
OFF  ON Max. 15ms put in the module. Max. 15ms put in the module.
The actual value is The actual value is
determined by determined by
adding it to the adding it to the
ON  OFF Max. 15ms scanning time Max. 15ms scanning time
depending on depending on
each system. each system.
Output display LED display LED display
External connection Terminal block connector (20 terminals, Terminal block connector (20 terminals,
M3.5 screw terminal) M3.5 screw terminal)
Relay life Mechanical Min. 20,000,000 times Min. 20,000,000 times
Electrical Min. 100,000 times (resistance load) Min. 100,000 times (resistance load)

Terminal connection and


circuitry

1 v 1
v 2 L A0 2
L A0 3 L A1 3
v 4 L A2 4
L A1 5 L A3 5
v 6 v 6
L A2 7 L A4 7
v 8 L A5 8
L A3 9 L A6 9
10 L A7 10
11 v 11
v 12 L BO 12
L A4 13 L B1 13
v 14 L B2 14
L A5 15 L B3 15
v 16 v 16
L A6 17 L B4 17
v 18 L B5 18
L A7 19 L B6 19
20 L B7 20

v : Direct current power or alternating : Direct current power or alternating


v
current power current power
11. CONNECTIONS
MARMMTRBL02303E
1180

Table 1133. Output Module ADA02A

Item ADA02A
Number of output 2 channels/module
channels
Digital input 12-bit binary (2s complement representation)
Analog output 10VDC ~ +10VDC (external load resistance: 10K or more) selectable
0mADC ~ + 20mADC (external load resistance: 400 or less) usable
Input/output Digital Input Analog Output
correspondence
+2000 +10V
+1000 +5V or +20mA
0 0V or 0mA
1000 5V
2000 10V
Resolution 5mV or 20 A
Comprehensive accuracy Voltage output  0.5% (for the full scale)
Current output  1% (for the full scale)
Converting time 1ms or less. NOTE: The converting time is the one only inside the module. The actual
response time is added a scan time that is determined by the system.
Isolation Photocopier isolation (between output signal and base). However, non-isolation between
output channels.
External connection At removable terminal block (20 terminals, M3.5 screw terminals)
Number of occupied 82
output points

ADA02A
Load
V0+ Voltage output
2
Channel 0 10K ohms or more
Voltage V0
amp. 4
D/A
converter
Current 6
amp.
10+
8
10
10

V1+
12
Channel 1
Voltage V1
amp. 14
D/A
converter
Current 16 Load
amp. 10+ Current output
18
10 400 ohms or less
20

(Note 1) Use a 2core twisted shielded cable as the connection cable.


(Note 2) Ground the cable shield on the load side
11. CONNECTIONS

MARMMTRBL02303E 1181

Table 1134. Analog Input Module AAD04A

Item AAD04A
Number of input channels 4 channels/module
Analog input 10VDC to +10VDC (input resistance 4.7M)
20mADC to +20mADC (input resistance: 250 selectable
Digital output 12-bit binary (complementary representation of 2)
Input/output Analog Input Digital Output
correspondence
+10V +2000
+5V or +20mA +1000
0V or 0mA 0
5V or 20mA 1000
10V 2000
Resolution 5mV or 20 A
Total precision Voltage input  0.5% (for the full scale)
Current input  1% (for the full scale)
Conversionary time Maximum 2ms. NOTE: Actual response speed is determined by adding the scanning time
depending on each system to this conversion time.
Maximum input 15V 30mA
voltage/current
Insulation Photocopier insulation (between output signal and base). However, non-insulation between
output channels.
External connection At removable terminal block (20 terminals, M3.5 screw terminals)
Number of occupied 82
output points

10+ 1

11+ 2
Voltage input V0+ 3
V1+
Voltage 4
V0
supply
5
V1
6
COM0
7 COM1 MULTI
8 PROCESSOR
FG0
9
FG1 10
12+ 11
13+ 250
12
Current input V2+
13
V3+
Current 14
V2
supply 15
V3
16
COM2
17
COM3
18
FG2
19
FG3
20

(Note 1) Though the example above shows the connection of channels 0 and 2, it is just the
same with the channel 1 (I1+, V1+, V1, COM1 and FG1) and the channel 3 (I3+, V3+,
V3, COM3 and FG3).
(Note 2) Either voltage input or current input can be specified for each channel. When current input is specified,
make sure to shortcircuit in + and Vn+.
(Note 3) Use shielded cables of twisted pair for connecting.
11. CONNECTIONS
MARMMTRBL02303E
1182

11.4 If you manufacture cables, conform to the FANUC standard cables


described in this section. Refer to the description in Peripheral Device
SPECIFICATIONS OF
Interface in this manual for the specifications of the FANUC standard
THE CABLES USED cables.
FOR PERIPHERAL
DEVICES AND
WELDERS

11.4.1 Figure 1265 shows the peripheral device interface A cable, CRM2:
Peripheral Device Honda Tsushin, 50 pins.
Interface A Cable Figure 1265. Peripheral Device Interface A Cable

HONDA TSUSHIN HONDA TSUSHIN

HONDA TSUSHIN
HONDA TSUSHINS
SUPPLIED WITH AN ORDERED CABLE

11.4.2 Figure 1266 shows the peripheral device interface B cable, CRM4:
Peripheral Device Honda Tsushin, 20 pins.
Interface B Cable Figure 1266. Peripheral Device Interface B Cable

HONDA TSUSHIN HONDA TSUSHIN

PERIPHERAL
DEVICE

HONDA TSUSHINS
HONDA TSUSHIN SUPPLIED WITH AN ORDERED CABLE
11. CONNECTIONS

MARMMTRBL02303E 1183

11.4.3 Figure 1267 shows the arc welder connection cable, CRW1: Honda
Arc Welding Interface Tsushin, 34 pins.
Connection Cable Figure 1267. Arc Welder Connection Cable

PERIPHERAL
HONDA TSUSHIN DEVICE

JAPAN AVIATION ELECTRONICS


INDUSTRY, LTD.
JAPAN AVIATION
ELECTRONICS STANDARD POSITION
INDUSTRY, LTD. OF GUIDE KEY

HONDA TSUSHIN

Use a welder connection cable conforming to the FANUC specifications.


11. CONNECTIONS
MARMMTRBL02303E
1184

11.5
CABLE CONNECTION
FOR THE PERIPHERAL
DEVICES, END
EFFECTORS, AND ARC
WELDERS

11.5.1
Peripheral Device
Connection Cable Figure 1268. Peripheral Device Cable Connection

Process I/O printed


circuit board CA/
CB/DA

Process I/O printed


circuit board AA/
AB/BA/BB or I/O
unit model A

Partly cut off the peripheral device


Clamp fixture connection cable to expose the
shield jacket, and fasten the jacket
to the shield plate with a clamp to
Shield jacket protect against noise.

Shield plate
11. CONNECTIONS

MARMMTRBL02303E 1185

11.5.2 Figure 1269 shows the connection of the arc welder cable in the control
Arc Welding Interface unit.
Connection Cable Figure 1269. Arc Welder Cable Connection

Process I/O printed


circuit board CA/
CB/DA

Process I/O printed


circuit board AA/
AB/BA/BB

Partly cut off the peripheral device


connection cable to expose the
shield jacket, and fasten the jacket
to the shield plate with a clamp to
protect against noise.

Clamp fixture

Shield jacket

Shield plate
11. CONNECTIONS
MARMMTRBL02303E
1186

11.5.3 Figure 1270, Figure 1271, and Figure 1272 show the connector for
Peripheral Device peripheral device cables A, B, and C.
Cable Connector Figure 1270. Peripheral Device Cable Connector for A and B(Honda Tsushin
Kogyo)

Table 1135. Peripheral Device Cable Connector for A and B

Connector Applicable Dimensions


Remark
Specifications Interface A (B) C (D)
MR50LMH CRM2 67.9 73.5 44.8 18 Honda Tsushin
Kogyo, 50 pins
MR20LMH CRM4 39.3 44.9 39.8 17 Honda Tsushin
Kogyo, 20 pins

Table 1136. Symbols Used in Figure 1270


Symbol Name
 Connector cover
 Cable clamp screw
Connector clamp spring

Connector clamp screw
Connector 50 pins (male) MR50MH
20 pints (male) MR20MH
11. CONNECTIONS

MARMMTRBL02303E 1187

Figure 1271. Peripheral Device Connector for A and B

Table 1137. Peripheral Device Cable Connector for A and B

Connector Applicable Dimensions


Remark
Specifications Interface A B
MR50RFH CRM2 61.4 56.4 Honda Tsushin Kogyo, 50 pins
MR20RFH CRM4 39.3 44.9 Honda Tsushin Kogyo, 20 pins

Table 1138. Symbols Used in Figure 1271


Symbol Name
 Connector clamp screw
 Screw 2.6 x 8
Connector (MR50RFH)
(MR20RFH)
11. CONNECTIONS
MARMMTRBL02303E
1188

Figure 1272. Peripheral Device Interface Cable C Connector (Phoenix Contact)

Insert the plug vertically toward the


conductor. Insert the cable in the side
of the plug plate key groove.

Table 1139. Peripheral Device Interface Cable C Connector


Specifications
Number of
Specifications A mm
Terminals
MVSTBR 2.5/6-ST-5.08 6 25.40
MVSTBR 2.5/10-ST-5.08 10 45.72

Table 1140. Connection Data


Applicable Rated Rated Wire End Processing
Wire Size Current Voltage
Twisted wires AWG12 12A AC250V

Solid wire AWG12 12A AC250V

Wire Jacket
11. CONNECTIONS

MARMMTRBL02303E 1189

11.5.4
End Effector Cable
Connector Figure 1273. Elbow Type Connector S-5, S-10, S-420, S-500, S-700, S-800,
M-400, M-500, ARC Mate, ARC Mate 100/S-6, ARC Mate Sr.
11. CONNECTIONS
MARMMTRBL02303E
1190

Figure 1274. Connector L-1000

A: M22x1
B: 48.82 G: 16.6
C: 30.5
D: 3.0 to 9.0 (Inside diameter)
Manufactured by Daiichi Denshi Kogyo JMCR1610
11. CONNECTIONS

MARMMTRBL02303E 1191

11.5.5
Recommended Cables

Peripheral Device Connect a peripheral device using a completely shielded, heavily protected
Connection Cable cable conforming to the specifications in Table 1141. Allow an extra
1.5m for routing the cable in the control unit. The maximum cable length
is 30 m.
Table 1141. Recommended Cable for Peripheral Device Connection
Number Wire Conductor Sheath Effective Electrical Characteristics
of Wires Specifications Thickness O tside
Outside
Diameter Configuration Conductor Allowable
(FANUC (mm) Diameter
(mm) Resistance Current (A)
Specifications) (mm)
(/km)
50 A66L-0001-0042 1.05 7/0.18 AWG24 1.5 12.5 106 1.6
20 A66L-0001-0041 1.05 7/0.18 AWG24 1.5 10.5 106 1.6

End Effector Connection Connect an end effector using a heavily protected cable with a movable
Cable wire conforming to the specifications in Table 1142. The cable length is
determined so that the cable will not interfere with the end effector and the
wrist can move through its full stroke.
Table 1142. Recommended Cable for End Effector Connection
Number Wire Conductor Sheath Effective Electrical Characteristics
of Wires Specifications Thickness O tside
Outside
Diameter Configuration Conductor Allowable
(FANUC (mm) Diameter
(mm) Resistance Current (A)
Specifications) (mm)
(/km)
6 A66L-0001-0143 1.1 40/0.08 1.0 5.3 91 3.7
AWG24
20 A66L-0001-0144 1.1 40/0.08 1.0 8.6 91 2.3
AWG24
12
MARMMTRBL02303E
COMPLETE WIRING DIAGRAMS

121

Complete wiring for the controller and the robot mechanical unit is shown
in Figure 131 through Figure 1332. The diagrams are valid for all
FANUC Robotics robot models (except where specific robot models are
indicated).
This chapter is useful for verifying the cable connections to all
components within the controller and robot.
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
122

Figure 131. Internal Connection Diagram S-420, S-800

K072

K071

AMP6
&5

K021
K020

K.23
K022
CP2
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 123

Figure 132. Internal Connection Diagram S420 with three Servo Amplifiers,
S420D)
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
124

Figure 133. Internal Connection Diagram ARC Mate, ARC Mate Sr., ARC Mate
100/S-6, S-5, and S-10

K
AXIS4
AXIS1

AXIS5
AXIS2

AXIS6
AXIS3

200VAC
K020

K021
K023

K022
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 125

Figure 134. Internal Connection Diagram S-500

M1
15,16
22, 23
29, 30
36, 37

38

32
39
31

25

19
26
33
18

40
24
17
K72

K71
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
126

Figure 135. Internal Connection Diagram S-700


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 127

Figure 136. Internal Connection Diagram S900


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
128

Figure 137. Internal Connection Diagram A-510


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 129

Figure 138. Internal Connection Diagram M-400 (5-axes)


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1210

Figure 139. Internal Connection Diagram M400 (4 axes)


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1211

Figure 1310. Internal Connection Diagram M500 (5 axes)


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1212

Figure 1311. Internal Connection Diagram M500 (4 axes)


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1213

Figure 1312. Internal Connection Diagram L-1000


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1214

Figure 1313. Internal Connection Diagram Emergency Stop Control PCB

K036
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1215

Figure 1314. Internal Connection Diagram Power Supply Unit

K022
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1216

Figure 1315. Internal Connection Diagram - Main CPU; Axis Control Board

K040

K070
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1217

Figure 1316. Internal Connection Diagram Servo Amplifier Connection S-420,


ARC Mate/S-5, ARC Mate Sr./S-10, ARC Mate 100/S-6, S-500, S-700, and S-800

S-420 with three-servo amplifier configuration


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1218

Figure 1317. Internal Connection Diagram Servo Amplifier Connection A-510,


L-1000, and M-400
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1219

Figure 1318. Internal Connection Diagram Servo Amplifier Connection S-900


and M-500
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1220

Figure 1319. Internal Connection Diagram Modular I/O

K015

K016
EMERGENCY STOP
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1221

Figure 1320. Internal Connection Diagram Teach Pendant

K041
K040

K035

K042

K
K
12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1222

Figure 1321. Internal Connection Diagram Main CPU Interface


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1223

Figure 1322. Internal Connection Diagram Axis Control Board Interface


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1224

Figure 1323. Internal Connection Diagram ARC Mate/S-5, ARC Mate Sr./S-10,
ARC Mate 100/S-6, S-420, S-500 and S-800
12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1225

Figure 1324. Internal Connection Diagram S-700 and A-510


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1226

Figure 1325. Internal Connection Diagram M-400 and L-1000


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1227

Figure 1326. Internal Connection Diagram - M400


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1228

Figure 1327. External Connection Diagram M-500


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1229

Figure 1328. External Connection Diagram S-900


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1230

Figure 1329. External Connection Diagram Process I/O


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1231

Figure 1330. External Connection Diagram Process I/O


12. COMPLETE WIRING DIAGRAMS
MARMMTRBL02303E
1232

Figure 1331. External Connection Diagram Teach Pendant


12. COMPLETE WIRING DIAGRAMS

MARMMTRBL02303E 1233

Figure 1332. Motor Table


13
MARMMTRBL02303E
PRINTS

This chapter includes all electrical prints.


131
13. PRINTS
MARMMTRBL02303E
132

NOTES
13. PRINTS

MARMMTRBL02303E 133

Figure 141. R-J Control Signal and Power Distribution Overview

Rev. 11/12/96 CD
13. PRINTS

134 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 135

Figure 142. Main AC Power Distribution

Rev. 11/12/96 CD
13. PRINTS

136 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 137

Figure 143. AC Power Distribution With Optional 115VAC Secondary

Rev. 11/12/96 CD

F6
45
7.5A F7 115 VAC @ 900VAC
46 TO USER CONNECTION
7.5A

AC POWER DISTRIBUTION WITH


OPTIONAL 115VAC SECONDARY

1A
13. PRINTS

138 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 139

Figure 144. Power Supply Unit (PSU) With Power ON/OFF Circuit

Rev. 11/12/96 CD
13. PRINTS

1310 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1311

Figure 145. EMG Stop & Brake Connection 100 VAC E-Stop Circuit 100 VDC Brake Circuit (1 of 2)

Rev. 11/12/96 CD
13. PRINTS

1312 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1313

Figure 146. EMG Stop and Brake Connection 100 VDC Brake Circuit (2 of 2)

Rev. 11/12/96 CD
13. PRINTS

1314 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1315

Figure 147. EMG Stop and Brake Connection 24 VDC E-Stop Circuit (1 of 2)

Rev. 11/12/96 CD
13. PRINTS

1316 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1317

Figure 148. EMG Stop and Brake Connection 24VDC E-Stop Circuit (2 of 2) Modular I/O Power Distribution

Rev. 11/12/96 CD
13. PRINTS

1318 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1319

Figure 149. Overheat and Cooling

Rev. 11/12/96 CD
13. PRINTS

1320 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1321

Figure 1410. Single Axis Servo Amplifier

Rev. 11/12/96 CD
13. PRINTS

1322 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1323

Figure 1411. Dual Axis Servo Amplifier (With Dynamic Brakes)

Rev. 11/12/96 CD
13. PRINTS

1324 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1325

Figure 1412. Dual Axis Servo Amplifier (Without Dynamic Brakes)

Rev. 11/12/96 CD
13. PRINTS

1326 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1327

Figure 1413. Discharge Resistor and Dynamic Brake Unit (For Amp With No Dynamic Brake)

Rev. 11/12/96 CD
13. PRINTS

1328 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1329

Figure 1414. LSI Module All Servo Amplifiers

Rev. 11/12/96 CD
13. PRINTS

1330 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1331

Figure 1415. DV-M Module Servo Amplifier

Rev. 11/12/96 CD
13. PRINTS

1332 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1333

Figure 1416. ALM-M Module Servo Amplifier

Rev. 11/12/96 CD
13. PRINTS

1334 MARMMTRBL02303E

NOTES
13. PRINTS

MARMMTRBL02303E 1335

Figure 1417. Teach Pendant Power And Data Signal Interconnection

Rev. 11/12/96 CD
13. PRINTS

1336 MARMMTRBL02303E

NOTES
A
TRANSPORTATION AND INSTALLATION

MARMMTRBL02303E A1

This appendix includes information on transporting and installing an R-J


controller.

A.1 The control unit is transported by a crane. Attach a rope to eye bolts at the
top of the control unit, as shown in Figure A1.
TRANSPORTATION
Figure A1. Transportation
A. TRANSPORTATION AND INSTALLATION

A2 MARMMTRBL02303E

A.2
INSTALLATION

A.2.1 When installing the control unit, allow the space for maintenance shown in
Installation Area Figure A2.

Figure A2. Installation Area


A. TRANSPORTATION AND INSTALLATION

MARMMTRBL02303E A3

A.2.2
Assembly During
Installation Figure A3. Assembly During Installation
A. TRANSPORTATION AND INSTALLATION

A4 MARMMTRBL02303E

Figure A4. Assembly During Installation


A. TRANSPORTATION AND INSTALLATION

MARMMTRBL02303E A5

A.2.3
Installation Conditions
Table A1. Installation Conditions
Item Model Specifications/Conditions
Line filter Common to all models 50 Hz; 200 VAC, +10%, 15%
60 Hz; 200 VAC to 220 VAC, +10%, 15%
50/60 Hz  1 Hz, 3-phase
Transformer Common to all models 220, 240, 380, 415, 460, 480, 500, 550, 575 VAC,
+10%, 15%
50/60 Hz  1 Hz, 3-phase
Input power supply capacity ARC Mate, S-5, A-510 2.5 kVA
ARC Mate Sr., S-10, L-1000 3 kVA
S-700 6.5 kVA
S-500, M-400 7 kVA
S-420, S-800 12 kVA
Average power consumption A-510 0.8 kW
ARC Mate, ARC Mate Sr., S-5, S-10 1.0 kW
L-1000 1.2 kW
S-500, S-700, M-400 1.7 kW
S-420 2.5 kW
Ambient temperature range Common to all models 0 to 45 C
Ambient humidity range Common to all models 75% RH max.
No condensation
95% RH maximum for up to 1 month
Atmosphere Common to all models No corrosive gases
Contact FANUC Robotics when operating the unit where
there is a lot of dust or cutting oil.
Vibration Common to all models 0.5 G max.
Contact FANUC Robotics when operating the unit where
vibration frequently occurs.
Weight of control unit Common to all models 180 kg (approx.)

Table A2. Installation Conditions


Item Model Specifications/Conditions
Line filter Common to all models 50 Hz; 200 VAC, +10%, 15%
60 Hz; 200 VAC to 220 VAC, +10%, 15%
50/60 Hz  1 Hz, 3-phase
Transformer Common to all models 220, 240, 380, 415, 460, 480, 500, 550, 575 VAC,
+10%, 15%
50/60 Hz  1 Hz, 3-phase
Input power supply capacity P-155 5 kVA
Average power consumption P-155 2.5 kW
(idle condition)
Ambient temperature range Common to all models 0 to 45 C
A. TRANSPORTATION AND INSTALLATION

A6 MARMMTRBL02303E

Table A2. (Contd) Installation Conditions


Item Model Specifications/Conditions
Ambient humidity range Common to all models 75% RH max.
No condensation
95% RH maximum for up to 1 month
Atmosphere Common to all models No corrosive gases
Contact FANUC Robotics when operating the unit where
there is a lot of dust or cutting oil.
Vibration Common to all models 0.5 G max.
Contact FANUC Robotics when operating the unit where
vibration frequently occurs.
Weight of control unit Common to all models 180 kg (approx.)
A. TRANSPORTATION AND INSTALLATION

MARMMTRBL02303E A7

A.2.4 Adjust the robot according to the procedure in Table A3 at installation.


Adjustment and
Checks at Installation
Table A3. Adjustment and Checks at Installation
Step Description
1 Visually check the inside and outside of the control unit.
2 Check if the screwed terminal is connected properly.
3 Check that the connectors and printed circuit boards are inserted correctly.
4 Check transformer tap setting.
5 Connect control unit and mechanical unit cables.
6 Turn the breaker or disconnect off and connect the input power cable.
7 Check the input power voltage.
8 Press the EMERGENCY STOP button on the operator panel and turn the power on. Check the output voltage.
9 Check the interface signals between the control unit and robot mechanical unit.
10 Check the parameters. If necessary, set them.
11 Release the EMERGENCY STOP button on the operator panel. Turn the power on.
12 Check the movement along each axis in the manual jog mode.
13 Check the end effector interface signals.
14 Check the peripheral device control interface signals.
A. TRANSPORTATION AND INSTALLATION

A8 MARMMTRBL02303E

A.2.5 An overtravel and emergency stop occur when the robot is operated for the
Resetting Overtravel first time after it is installed and the mechanical and control units are
wired. This section describes how to reset the overtravel and emergency
and Emergency Stop at stop.
Installation
Remove the red plate fastening the swiveling axis beforehand. The J2 and
J3 axes are pressed against the hard stops at shipment. Therefore, an
overtravel alarm occurs when the power is turned on after installation.
The robot enters the emergency stop state when the peripheral device
control interface is not connected.

Peripheral Device Interface Take the following actions if signals *IMSTP, *HOLD, *SFSD, and
Processing ENBL are not used.

Figure A5. Peripheral Device Interface Processing

Resetting Overtravel Press the reset switch on the operator panel or the reset key on the teach
pendant. Manually move an axis that has overtraveled into the operating
range while pressing the shift key on the teach pendant.

Вам также может понравиться