Gefran 400 Temperature

Controller: Quick Start Guide

Tel: +27 11 966 9800 (JHB)


+27 21 762 8995 (CT)
sales@unitemp.com
www.unitemp.com/contact
Quick Start Guide
400-D-R-x Programmable PID Controller Heat & Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additional wiring
Power Controller
Press F once, Ctr appears ENTER 6
Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note number from the list ALARM Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by General Setup
Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C
5 TC R F 35 PTC F - 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V
+ 22
Scale limit HEATER
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit POWER CONTROL
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until CFG appears
24 1 +
Press and hold F until you return to the main process display. This is the display after PAS
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, POWER THERMOCOUPLE
Lo, H i, if no input is connected.
If needed, automatic tuning (Self-Tune) can be enabled
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). with the following steps
Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. With the machine at ambient temperature and
the control setpoint (SV) set..
Press F twice to return to the main display. Press and hold F until CFG appears
Press the button to switch between automatic and manual control modes from the Press F once, S.Tu appears ENTER 2
main display. The deviation LEDs ( ) will flash while in manual mode. Press F once
Cycle power to the controller
Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
48x48 DIN 400-D-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
401-R-R-R-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additional wiring
Power Controller configurations are
Press F once, Ctr appears ENTER 8
Sensor Type Sensor Type
Program for yourapplication 0 TC J C 30 PT100 C available in the Users
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 Manual and General
Note
2 TC K C 32 JPT100 C
Setup Guide
number from the list 3 TC K F 33 JPT100 F COOLING
Change all menu parameters by Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C

using the front panel buttons


5 TC R F 35 PTC F 21 6
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V 22 5
Scale limit
HEATER ALARM
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until Out appears
24 1 +
Press F repeatedly until, r.o.2 appears ENTER1
Press F once, r.o.3 appears ENTER 2 POWER THERMOCOUPLE

Press and hold F until CFG appears If needed, automatic tuning (Self-Tune) can be enabled
Press and hold F until you return to the main process display. This is the display after PAS with the following steps
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, With the machine at ambient temperature and
Lo, H i, if no input is connected. the control setpoint (SV) set..
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). Press and hold F until CFG appears
Press F once, S.Tu appears ENTER 2
Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. Press F once
Press F twice to return to the main display.
Cycle power to the controller
Cycle power to the controllerThe right-most
Press the button to switch between automatic and manual control modes from the decimal point will light during the tuning process
main display. The deviation LEDs ( ) will flash while in manual mode. Self-Tune will automatically save new PID
48x48 DIN 401-R-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
401-D-R-R-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additionalwiring
Additional wiring
Power Controller configurationsare
configurations are
Press F once, Ctr appears ENTER 8
Sensor Type Sensor Type
Program for yourapplication 0 TC J C 30 PT100 C availableininthe
available theUsers
Users
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 Manualand
Manual andGeneral
General
Note
2 TC K C 32 JPT100 C
SetupGuide
Setup Guide
number from the list 3 TC K F 33 JPT100 F COOLING
Change all menu parameters by Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C
5 TC R F 35 PTC F - 21 6
using the front panel buttons
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V
+ 22 5
Scale limit HEATER
POWER CONTROL ALARM
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until Out appears
24 1 +
Press F repeatedly until, r.o.2 appears ENTER1
Press F once, r.o.3 appears ENTER 2 POWER THERMOCOUPLE

Press and hold F until CFG appears If needed, automatic tuning (Self-Tune) can be enabled
Press and hold F until you return to the main process display. This is the display after PAS with the following steps
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, With the machine at ambient temperature and
Lo, H i, if no input is connected. the control setpoint (SV) set..
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). Press and hold F until CFG appears
Press F once, S.Tu appears ENTER 2
Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. Press F once
Press F twice to return to the main display.
Cycle power to the controller
Cycle power to the controllerThe right-most
Press the button to switch between automatic and manual control modes from the decimal point will light during the tuning process
main display. The deviation LEDs ( ) will flash while in manual mode. Self-Tune will automatically save new PID
48x48 DIN 401-D-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
400-R-R-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additional wiring
Power Controller
Press F once, Ctr appears ENTER 8
Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note number from the list COOLING Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by General Setup
Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C
5 TC R F 35 PTC F 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V
22
Scale limit
HEATER
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until Out appears
24 1 +
Press F once, AL.n appears ENTER 0
POWER THERMOCOUPLE
Press F twice, r.o.2 appears ENTER 1
Press and hold F until you return to the main process display. This is the display after PAS If needed, automatic tuning (Self-Tune) can be enabled
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, with the following steps
Lo, H i, if no input is connected. With the machine at ambient temperature and
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). the control setpoint (SV) set..
Press and hold F until CFG appears
Press F twice to return to the main display.
Press F once, S.Tu appears ENTER 2
Press the button to switch between automatic and manual control modes from the Press F once
main display. The deviation LEDs ( ) will flash while in manual mode. Cycle power to the controller
Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
48x48 DIN 400-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
400-R-R-x Programmable PID Controller Heat & Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additional wiring
Power Controller
Press F once, Ctr appears ENTER 6
Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note number from the list ALARM Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by General Setup
Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C
5 TC R F 35 PTC F 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V
22
Scale limit
HEATER
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until CFG appears
24 1 +
Press and hold F until you return to the main process display. This is the display after PAS
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, POWER THERMOCOUPLE
Lo, H i, if no input is connected.
If needed, automatic tuning (Self-Tune) can be enabled
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). with the following steps
Press F twice from the main display, AL.1 appears to adjust the Alarm 1 setpoint. With the machine at ambient temperature and
the control setpoint (SV) set..
Press F twice to return to the main display. Press and hold F until CFG appears
Press the button to switch between automatic and manual control modes from the Press F once, S.Tu appears ENTER 2
main display. The deviation LEDs ( ) will flash while in manual mode. Press F once
Cycle power to the controller
Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
48x48 DIN 400-R-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
400-D-R-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until InP appears Input Sensor 19 Additional wiring
Power Controller
Press F once, Ctr appears ENTER 8
Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, tYP appears ENTER the Input Sensor 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note number from the list Manual and
3 TC K F 33 JPT100 F COOLING
Change all menu parameters by General Setup
Press F repeatedly until Lo.S* appears ENTER the
4 TC R C 34 PTC C
5 TC R F 35 PTC F - 21 Guide
using the front panel buttons
minimum Input Scale limit 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F once, H i.S* appears ENTER the maximum Input 8 TC T C 44 4...20 mA
9 TC T F 46 0...10 V
+ 22
Scale limit HEATER
POWER CONTROL
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
1 Whats Included
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 23 2 -
Press and hold F until Out appears
24 1 +
Press F once, AL.n appears ENTER 0
Press F twice, r.o.2 appears ENTER1 POWER THERMOCOUPLE

Press and hold F until you return to the main process display. This is the display after PAS If needed, automatic tuning (Self-Tune) can be enabled
and will be indicated by the Process Variable if an input sensor is connected, or Sbr, Err, with the following steps
Lo, H i, if no input is connected. With the machine at ambient temperature and
Press F once from the main display,_SP, appears to adjust the control setpoint (SV). the control setpoint (SV) set..
Press and hold F until CFG appears
Press F twice to return to the main display.
Press F once, S.Tu appears ENTER 2
Press the button to switch between automatic and manual control modes from the Press F once
main display. The deviation LEDs ( ) will flash while in manual mode. Cycle power to the controller
Cycle power to the controllerThe right-most
decimal point will light during the tuning process
Self-Tune will automatically save new PID
48x48 DIN 400-D-R-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 400 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY

Powered by TCPDF (www.tcpdf.org)