Example 1
34.5kV
SCC = 1200 MVA
10/12.5 MVA
6%
13.8 kV
13.8 kV
MVA base kV
Zutility = x oldbase
MVA oldbase kVbase
13.8 kV
100 34.5
= x
F
1200 34.5
= 0.0833
Calculate the fault current at F
Example 1
13.8 kV
34.5kV
SCC = 1200 MVA
10/12.5 MVA
6%
5MVA
Xd=0.12
13.8 kV
13.8 kV
ZTpu 0.48
13.8 kV
0.0833
Zutility
2.4
ZGpu 0.456
ZTpu 0.48
Example 2 Addition of a Generator
ZGpu 0.456
ZTpu 0.48
Example 2 Addition of a Generator
34.5kV 34.5kV
SCC = 1200 MVA SCC = 1200 MVA
10/12.5 MVA
6%
5MVA
10/12.5 MVA Xd=0.12
6%
13.8 kV 13.8 kV
F F
34.5kV
SCC = 1200 MVA
13.8 kV
F 3 MVA
5%
2.4 kV
M 2500 HP
Xd=0.17
13.8 kV
F 3 MVA
5%
2.4 kV
M 2500 HP
Xd=0.17
M 2500 HP
Xd=0.17
2.4 kV
M 2500 HP
Xd=0.17
2500 * 0.746
13.8 kV
Motor rating =
pf
1865
= = 2154
F 3 MVA 0.866
5%
MVA base
2.4 kV
Z Mpu = Zm x
MVA oldbase
100
M 2500 HP = 0.17 x = 7.89
Xd=0.17 2.154
M 2500 HP
Xd=0.17
M 2500 HP
Xd=0.17
1.0V 1.0V
0.0833 1.667
Zutility
ZMpu 0.4354
2.4
ZGpu
ZTpu1 0.48
7.89 ZTpu2
Example 3 Presence of transformer & motor
Vpu 1.0
IFpu = = = 2.297 pu
1.0V ZEq 0.4354
Ibase
IFHV = IFpu x
3
0.4354
2898.55
= 2.297 x = 3844 A
3
I
IFLV = FHV x 34.5
13.8
= 9609 A
Symmetrical Fault
34.5kV
34.5kV 34.5kV
SCC = 1200 MVA
SCC = 1200 MVA SCC = 1200 MVA
10/12.5 MVA 5MVA
6% Xd=0.12
10/12.5 MVA 10/12.5 MVA
6% 6%
5MVA 13.8 kV
Xd=0.12
F 3 MVA
5%
13.8 kV 2.4 kV
13.8 kV
M 2500 HP
F F Xd=0.17