Linear Power Series

SmartVision IEC 61850 Interface


5. May, 2015 / Revision 02

1
IEC 61850 Interface

Control
DTS Temp. DTS Temp.
RTTR Data RTTR Data Data

Load Current
Load Current
DTS Monitoring Database
System

Import of current values to SmartVision


Request

Response
Query of temperature, alarm and ampacity
values from SmartVision
Request
SmartVision Interface
Response
SAS (IEC61850 Server : port 102)
(Client)
IEC61850 Protocol

2
IEC61850 Definition
Input to SmartVision
Load values for all circuits

Output provided by SmartVision


Surface Temperature Values
Surface Temperature Pre-Alarms
Surface Temperature Alarms
System Failure / FiberBreak

Additional Outputs provided by SmartVision with RTTR


Calculated Conductor Temperature Values
Calculated Conductor Pre-Alarms
Calculated Conductor Alarms
Ampacity
Emergency Ratings (Time, Load, Temperature)

3
IEC61850 Definition - Inputs

logicalDeviceName/logicalNode.dataObject.Attribute

4
IEC61850 Definition Outputs (without RTTR)
FeederMonitorAPSmartVision/ZCAB1.MaxTmp.mag.f
= Max Temperature of Circuit #1 as Float
FeederMonitorAPSmartVision/ZCAB2.MaxTmp.mag.f
= Max Temperature of Circuit #2 as Float
FeederMonitorAPSmartVision/ZCAB3.MaxTmp.mag.f
= Max Temperature of Circuit #3 as Float

FeederMonitorAPSmartVision/ZCAB1.TmpWarn.stVal
= Surface Pre-Alarm Circuit #1 as Boolean
FeederMonitorAPSmartVision/ZCAB2.TmpWarn.stVal
= Surface Pre-Alarm Circuit #2 as Boolean
FeederMonitorAPSmartVision/ZCAB3.TmpWarn.stVal
= Surface Pre-Alarm Circuit #3 as Boolean

ZCAB
FeederMonitorAPSmartVision/ZCAB1.TmpAlm.stVal
ZCAB0 is used for global circuit alarm status and circuit independent alarm
= Surface Alarm Circuit #1 as Boolean
status information (i.e. history alarms).
ZCABx is used for circuit specific data and alarm status where x is a circuit FeederMonitorAPSmartVision/ZCAB2.TmpAlm.stVal
index which is can be set in circuit setup (ZCAB1, ZCAB2 etc.). = Surface Alarm Circuit #2 as Boolean
FeederMonitorAPSmartVision/ZCAB3.TmpAlm.stVal
= Surface Alarm Circuit #3 as Boolean

FeederMonitorAPSmartVision/ZCAB0.FltAlm.stVal
= Fault Alarm
FeederMonitorAPSmartVision/ZCAB0.FiberAlm.stVal
= FiberBreak

5
IEC61850 Definition Additional Outputs (with RTTR)
RTTR Calculated Ampacity
RTTR Calculated Conductor Temperatures
FeederMonitorAPSmartVision/ZCAB1.MaxA.mag.f = Ampacity Circuit #1
FeederMonitorAPSmartVision/ZCAB2.MaxA.mag.f = Ampacity Circuit #2
FeederMonitorAPSmartVision/ZCAB1.CondTmp.mag.f
FeederMonitorAPSmartVision/ZCAB3.MaxA.mag.f = Ampacity Circuit #3
= Max Conductor Temperature of Circuit #1 as Float
FeederMonitorAPSmartVision/ZCAB2. CondTmp.mag.f
= Max Conductor Temperature of Circuit #2 as Float
RTTR Calculated Emergency Ratings (Circuit #1)
FeederMonitorAPSmartVision/ZCAB3. CondTmp.mag.f
= Max Conductor Temperature of Circuit #3 as Float
FeederMonitorAPSmartVision/ZCAB1. ER1_A.mag.f
= Emergency Rating #1 Load
RTTR Calculated Conductor Temperatures Alarms
FeederMonitorAPSmartVision/ZCAB1. ER1_Tmp.mag.f
= Emergency Rating #1 Temp
FeederMonitorAPSmartVision/ZCAB1. CondTmpWarn.stVal
FeederMonitorAPSmartVision/ZCAB1. ER1_Tmh.mag.f
= Conductor Pre-Alarm Circuit #1 as Boolean
= Emergency Rating #1 Time
FeederMonitorAPSmartVision/ZCAB2. CondTmpWarn.stVal
= Conductor Pre-Alarm Circuit #2 as Boolean
FeederMonitorAPSmartVision/ZCAB1. ER2_A.mag.f
FeederMonitorAPSmartVision/ZCAB3. CondTmpWarn.stVal
= Emergency Rating #1 Load
= Conductor Pre-Alarm Circuit #3 as Boolean
FeederMonitorAPSmartVision/ZCAB1. ER2_Tmp.mag.f
= Emergency Rating #1 Temp
FeederMonitorAPSmartVision/ZCAB1.CondTmpAlm.stVal
FeederMonitorAPSmartVision/ZCAB1. ER2_Tmh.mag.f
= Conductor Alarm Circuit #1 as Boolean
= Emergency Rating #1 Time
FeederMonitorAPSmartVision/ZCAB2. CondTmpAlm.stVal
= Conductor Alarm Circuit #2 as Boolean
RTTR Calculated Emergency Ratings (Circuit #2, #3,)
FeederMonitorAPSmartVision/ZCAB3. CondTmpAlm.stVal
= Conductor Alarm Circuit #3 as Boolean
Analogue > Replace ZCAB1 by the Circuit number e.g. ZCAB2 for circuit #2.