Cable sizing for Ventilation fans (Excluding Chiller room supply and exhaust fans)

List of Nomenclature
Iz - current carrying capacity of the cable in the situation where it is installed
It - tabulated current for a single circuit at an ambient temperature of 30C
Ib - design current, the actual current to be carried by the cable
In - rating of the protecting fuse or circuit breaker
I2 - operating current for the fuse or circuit breaker (the current at which the fuse blows or the circuit breaker opens)
Ca - correction factor for ambient temperature
Cg - correction factor for grouping
Ci - correction factor for thermal insulation.
Ta - Ambient temperature

3Ph voltage 400 V


1Ph voltage 230 V
Power Factor 0.8

In/(Ca*Cg*Ci)

Voltage drop

Voltage drop
Input Power

Adjustment

Earth cable
Earth cable
I2=In*1.45
Intallation

Selected
Voltage drop <
factors

Length

length
Phase

Cable
Equipment

Qty
Cable type
4%*400V
I2<1.45Iz
In
Ib

Iz
Qty

kW A A condition method Ca Cg Ci A A A m mV/A/m % mm2 mm2 m Nos

Vintilation fans
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
In/(Ca*Cg*Ci)

Voltage drop

Voltage drop
Input Power

Adjustment

Earth cable
Earth cable
I2=In*1.45
Intallation

Selected
Voltage drop <
factors

Length

length
Phase

Cable
Equipment

Qty
Cable type
4%*400V
I2<1.45Iz
In
Ib

Iz
Qty

kW A A condition method Ca Cg Ci A A A m mV/A/m % mm2 mm2 m Nos

two core with


Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.04 0.16 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.04 0.16 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.04 0.16 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.04 0.16 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.25 1.09 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.04 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
In/(Ca*Cg*Ci)

Voltage drop

Voltage drop
Input Power

Adjustment

Earth cable
Earth cable
I2=In*1.45
Intallation

Selected
Voltage drop <
factors

Length

length
Phase

Cable
Equipment

Qty
Cable type
4%*400V
I2<1.45Iz
In
Ib

Iz
Qty

kW A A condition method Ca Cg Ci A A A m mV/A/m % mm2 mm2 m Nos

two core with


Ta=35C,
1 1 0.25 1.09 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.04 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.22 0.94 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.03 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.03 0.14 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
two core with
Ta=35C,
1 1 0.04 0.16 10 B 1 1 1 10.00 22 15 OK 5 29.00 0.01 OK 1.5 earth 1.5 5 1
2 core
Unarmoured
Ta=35C, 3 core
1 3 1.5 2.71 6 B 1 1 1 6.00 19.5 8.7 OK 37 27.00 0.68 OK 1.5 1.5 37 1
multicore Unarmoured
Ta=35C, 3 core
1 3 3 5.41 10 D 1 1 1 10.00 19.5 15 OK 16 27.00 0.58 OK 1.5 1.5 16 1
multicore Unarmoured

Ta=35C, 3 core
1 3 1.1 1.98 6 B 1 1 1 6.00 19.5 8.7 OK 16 27.00 0.21 OK 1.5 1.5 16 1
multicore Unarmoured

Ta=35C, 3 core
1 3 5.5 9.92 16 B 1 1 1 16.00 26 23 OK 30 16.00 1.19 OK 2.5 2.5 30 1
multicore Unarmoured
Ta=35C, 3 core
1 3 7.5 13.53 20 B 1 1 1 20.00 35 29 OK 26 10.00 0.88 OK 4 4 26 1
multicore Unarmoured
Ta=35C, 3 core
1 3 4 7.22 16 B 1 1 1 16.00 26 23 OK 40 16.00 1.15 OK 2.5 2.5 40 1
multicore Unarmoured
Ta=35C, 3 core
1 3 4 7.22 16 B 1 1 1 16.00 26 23 OK 26 16.00 0.75 OK 2.5 2.5 26 1
multicore Unarmoured
In/(Ca*Cg*Ci)

Voltage drop

Voltage drop
Input Power

Adjustment

Earth cable
Earth cable
I2=In*1.45
Intallation

Selected
Voltage drop <
factors

Length

length
Phase

Cable
Equipment

Qty
Cable type
4%*400V
I2<1.45Iz
In
Ib

Iz
Qty

kW A A condition method Ca Cg Ci A A A m mV/A/m % mm2 mm2 m Nos

Ta=35C, 3 core
1 1 0.03 0.14 6 B 1 1 1 6.00 22 8.7 OK 5 27.00 0.00 OK 1.5 1.5 5 1
3 core Unarmoured
Ta=35C, 3 core
1 3 15 27.06 60 B 1 1 1 60.00 100 87 OK 21 2.50 0.36 OK 16 16 21 1
multicore Unarmoured

3 core
Ta=35C,
1 3 30 54.13 100 B 1 1 1 100.00 127 145 OK 16 1.65 0.36 OK 25 Unarmoured, 16 16 1
multicore
fire resistant

3 core
Ta=35C,
1 3 18.5 33.38 63 B 1 1 1 63.00 100 91 OK 20 2.50 0.42 OK 16 Unarmoured, 16 20 1
multicore
fire resistant

3 core
Ta=35C,
1 3 11 19.85 32 B 1 1 1 32.00 54 46 OK 23 6.80 0.78 OK 6 Unarmoured, 6 23 1
multicore
fire resistant