PRESCIENT WALL PANEL

BATT INSULATION (OPTIONAL)

1/2" RC DELUXE, 24" OC


Sim
1
PRESCIENT WALL PANEL (1) LAYER 5/8" GYP. WALLBOARD SP.4

PRESCIENT POST
(1) LAYER 5/8" GYP. (1) LAYER 5/8" GYP.
WALLBOARD WALLBOARD

1/2" RC DELUXE, 24" OC

BATT INSULATION (OPTIONAL) Sim


2
SP.4

(1) LAYER 5/8" GYP. WALLBOARD


NOTE: NOTE:
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS WALLBOARD REQUIREMENTS
HEADER JAMBS NOTE:
Prescient Wall w/ Rated Door Frame - 1HR ICC-ES ESR-3745 Prescient Wall w/ Rated Door Frame - 1HR ICC-ES ESR-3745 Prescient Wall w/ Rated Door Frame - 1HR REFER TO UL REPORTS FOR GYP.
(TYP) UL W428 (TYP) UL W428 (TYP) WALLBOARD REQUIREMENTS
1 2 3
6" = 1'-0" 6" = 1'-0" 3/4" = 1'-0"

PRESCIENT WALL PANEL

BATT INSULATION (OPTIONAL)

Sim
PRESCIENT WALL PANEL 4
(1) LAYER 5/8" GYP. WALLBOARD, SP.4
BOTH SIDES

(1) LAYER 5/8" GYP. WALLBOARD


AROUND OPENING TO MAINTAIN RATING;
BATT INSULATION (OPTIONAL)
TAPED AT JOINTS

(1) LAYER 5/8" GYP.


WALLBOARD, BOTH SIDES

Sim
5
SP.4
(1) LAYER 5/8" GYP.
WALLBOARD AROUND
No. Description Date
OPENING TO MAINTAIN RATING;
TAPED AT JOINTS

NOTE: NOTE:
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS WALLBOARD REQUIREMENTS
HEADER JAMB 5/8" GYP. WALLBOARD NOTE:
Prescient Wall w/ Non Rated Door Frame ICC-ES ESR-3745 Prescient Wall w/ Non Rated Door Frame ICC-ES ESR-3745 Prescient Wall w/ Non Rated Door Frame OPENING WRAP REFER TO UL REPORTS FOR GYP.
(TYP) UL W428 (TYP) UL W428 (TYP) WALLBOARD REQUIREMENTS
4 5 6
6" = 1'-0" 6" = 1'-0" 3/4" = 1'-0"

INFILL WALL PER ARCH


Sim
7
SP.4

INFILL WALL PER ARCH

Prescient Assembly
Details
8
Sim
6" System
SP.4

Opening Assemblies
Project Number N505
Date 06/23/2016
Drawn By JDS
Checked By EPH

6/23/2016 3:14:48 PM
NOTE: NOTE:

SP.4
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS WALLBOARD REQUIREMENTS
HEADER JAMB NOTE:
Non Rated Wall w/ Non Rated Door Frame ICC-ES ESR-3745 Non Rated Wall w/ Non Rated Door Frame ICC-ES ESR-3745 Non Rated Wall w/ Non Rated Door Frame REFER TO UL REPORTS FOR GYP.
(TYP) (TYP) (TYP) WALLBOARD REQUIREMENTS Scale
7
6" = 1'-0"
8
6" = 1'-0"
9
3/4" = 1'-0" As indicated
PRESCIENT INTEGRATED PRESCIENT INTEGRATED
PANEL TRUSS (1) LAYER 5/8" GYP. WALLBOARD (2) LAYERS 5/8" GYP.
PANEL TRUSS
WALLBOARD, BOTH SIDES
(1) LAYER 5/8"
GYP. WALLBOARD BATT INSULATION (OPTIONAL)
BATT INSULATION (OPTIONAL)

BATT INSULATION (OPTIONAL) 1/2" RC DELUXE, 24" OC BATT INSULATION (OPTIONAL) 1/2" RC DELUXE, 24" OC
PRESCIENT POST PRESCIENT WALL PANEL PRESCIENT POST
PRESCIENT WALL PANEL

PRESCIENT WALL PANEL


PRESCIENT WALL PANEL
(1) LAYER 5/8" GYP. WALLBOARD (1) LAYER 5/8" GYP. (2) LAYERS 5/8" GYP.
WALLBOARD 1/4" GAP BETWEEN CEMENTITIOUS WALLBOARD, BOTH SIDES
FLOORING TO PREVENT SOUND 1/2" RC DELUXE, 24" OC
1/4" GAP BETWEEN CEMENTITIOUS 1/2" RC DELUXE, 24" OC TRANSFER; FILL w/ ACOUSTICAL
FLOORING TO PREVENT SOUND FIRE CAULK
TRANSFER; FILL w/ ACOUSTICAL
FIRE CAULK

NOTE: NOTE: NOTE: NOTE:


REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS PLAN WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS PLAN

Demising/Corridor Prescient Wall - 1HR ICC-ES ESR-3745 Demising/Corridor Prescient Wall - 1HR ICC-ES ESR-3745 Demising/Corridor Prescient Wall - 2HR ICC-ES ESR-3745 Demising/Corridor Prescient Wall - 2HR ICC-ES ESR-3745
(TYP) UL W428 (TYP) UL W428 (TYP) UL W428 (TYP) UL W428
1 2 3 4
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"

(1) LAYER 5/8" GYP.


WALLBOARD, BOTH SIDES (2) LAYERS 5/8" GYP.
WALLBOARD, BOTH SIDES
PRESCIENT INTEGRATED PRESCIENT INTEGRATED
PANEL TRUSS PANEL TRUSS
BATT INSULATION (OPTIONAL)
BATT INSULATION (OPTIONAL)

BATT INSULATION (OPTIONAL) PRESCIENT POST


BATT INSULATION (OPTIONAL) PRESCIENT POST
PRESCIENT WALL PANEL PRESCIENT WALL PANEL

PRESCIENT WALL PANEL


PRESCIENT WALL PANEL
(1) LAYER 5/8" GYP. WALLBOARD (1) LAYER 5/8" GYP. (2) LAYERS 5/8" GYP. WALLBOARD (2) LAYERS 5/8" GYP.
WALLBOARD WALLBOARD
No. Description Date

NOTE: NOTE: NOTE: NOTE:


REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS PLAN WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS PLAN
ICC-ES ESR-3745 ICC-ES ESR-3745 ICC-ES ESR-3745 ICC-ES ESR-3745
Internal Prescient Wall - 1HR (TYP) Internal Prescient Wall - 1HR (TYP) UL W428 Internal Prescient Wall - 2HR (TYP) UL W428 Internal Prescient Wall - 2HR (TYP) UL W428
5 6 7 8
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"

TPO OR EPDM MEMBRANE OR


METAL ROOF DECK PANELS

MIN 1 1/2" METAL DECK


CEMENTITIOUS FLOORING

5/8" SHEATHING
PRESCIENT FLOOR
TRUSS MIN 2" FOAMED PLASTIC
ROOF INSULATION
PRESCIENT FLOOR TRUSS CEMENTITIOUS PRESCIENT FLOOR TRUSS CEMENTITIOUS
FLOORING FLOORING

Prescient Assembly
Details
6" System

MIN 3 1/2" BATT INSULATION MIN 3 1/2" BATT INSULATION PRESCIENT TRUSS
Wall & Floor/Roof
MIN 3 1/2" BATT INSULATION 1/2" RC; 12" O.C. AT CEILING
Assemblies
(1) LAYER 5/8" GYP. WALLBOARD 1/2" RC DELUXE; 12" OC (2) LAYERS 5/8" GYP. WALLBOARD 1/2" RC DELUXE; 12"
AT CEILING OC AT CEILING Project Number N505
1/2" RC DELUXE; 12" OC AT CEILING
(1) LAYER 5/8" GYP. WALLBOARD Date 06/23/2016
(1) LAYER 5/8" GYP. WALLBOARD Drawn By JDS
Checked By EPH

6/23/2016 3:14:50 PM
NOTE: NOTE: NOTE: NOTE:
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.

9
WALLBOARD REQUIREMENTS

Prescient Floor/Ceiling Assembly - 1HR


(TYP)
1 1/2" = 1'-0"
SECTION
ICC-ES ESR-3745
UL G592, UL H502
10
WALLBOARD REQUIREMENTS

Truss - 1HR (TYP)


1 1/2" = 1'-0"
SECTION
Prescient Floor/Ceiling Assembly - Parallel to ICC-ES ESR-3745
UL G592, UL H502 11
WALLBOARD REQUIREMENTS

Prescient Floor/Ceiling Assembly - 2HR


(TYP)
1 1/2" = 1'-0"
SECTION
ICC-ES ESR-3745
UL G592, UL H502
12
WALLBOARD REQUIREMENTS

Roof/Ceiling Detail for Rated or Non Rated


Prescient Assembly (TYP)
1 1/2" = 1'-0"
ICC-ES ESR-3745
UL P572
Scale
SP.5
1 1/2" = 1'-0"
CEMENTITIOUS FLOORING
PRESCIENT POST
1/4" GAP BETWEEN CEMENTITIOUS
FLOORING TO PREVENT SOUND PRESCIENT CORRIDOR WALL
CEMENTITIOUS FLOORING
TRANSFER; FILL w/ ACOUSTICAL PRESCIENT FLOOR TRUSS CEMENTITIOUS FLOORING
FIRE CAULK
BATT INSULATION (OPTIONAL)
MIN 3 1/2" BATT INSULATION

PRESCIENT FLOOR
PRESCIENT FLOOR TRUSS TRUSS
1/2" RC DELUXE; 24" OC AT WALL MIN 3 1/2" BATT INSULATION
PRESCIENT INTEGRATED
PANEL TRUSS MIN 3 1/2" BATT INSULATION
(1) LAYER 5/8" TYPE X,
BOTH SIDES

(1) LAYER 5/8" TYPE C MIN 1/4" GAP; 1 1/2" TYPE S SCREWS, 16" OC
PRESCIENT DEMISING WALL BOTH SIDES

(1) LAYER 5/8" GYP. WALLBOARD 1/2" RC DELUXE; 12" OC AT CEILING


1/2" RC DELUXE; 1/2" RC DELUXE, 24" OC
BATT INSULATION (OPTIONAL)
12" OC AT CEILING 1/2" RC DELUXE; 12" OC AT CEILING (1) LAYER 5/8" GYP. WALLBOARD

PRESCIENT WALL PANEL (1) LAYER 5/8" TYPE X PRE-ROCK (1) LAYER 1" GYP. WALLBOARD PRE-ROCK (1) LAYER 5/8"
SHAFT LINER SCREWED TO TOP PLATE GYP. WALLBOARD
1 1/2" TYPE S SCREWS 16" OC METAL TRACK RUNNER
(1) LAYER 5/8" TYPE X
1/2" RC DELUXE, 24" OC
NOTE: NOTE: UNRATED INFILL WALL PER ARCH NOTE:
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. NOTE: REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS WALLBOARD REQUIREMENTS REFER TO UL REPORTS FOR GYP. WALLBOARD REQUIREMENTS
SECTION PLAN WALLBOARD REQUIREMENTS SECTION SECTION
Demising/Corridor Prescient Wall - 1HR ICC-ES ESR-3745 Demising/Corridor Prescient Wall - 1HR ICC-ES ESR-3745 ICC-ES ESR-3745 Infill Wall - Pre-Rock - Unrated - Parallel to ICC-ES ESR-3745
(TYP) UL W428, UL G592, UL H502 (TYP) UL W428 UL G592 UL H502 Truss (TYP)
Infill Wall - Pre-Rock - Unrated (TYP) UL G592, UL H502
1 2 3 4
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"

PLUMBING CAN RUN


HORIZ. THROUGH PANEL
(1) LAYER 5/8" GYP. WALLBOARD
MIN (1) LAYER 5/8" GYP. WALLBOARD
PRESCIENT POST
PLUMBING WALL HOUSES PLUMBING FLOOR MOUNTED
BATT INSULATION
LINES TO AVOID VERTICAL TUB DRAIN BATT INSULATION (OPTIONAL)
(OPTIONAL)
PENETRATION OF PRESCIENT PANEL
MIN 1" PLYCEM MIN 2" CEMENTITIOUS SUBFLOORING
CEMENTITIOUS FLOORING

PRESCIENT FLOOR TRUSS


(1) LAYER 5/8" GYP. WALLBOARD

PRESCIENT INTEGRATED
PANEL TRUSS
1/2" RC DELUXE; 24" OC

MIN 3 1/2" BATT INSULATION UNRATED INFILL WALL


MIN 3 1/2" BATT INSULATION
PER ARCH
(1) LAYER 5/8" GYP. WALLBOARD 1/2" RC DELUXE; 12" OC AT CEILING No. Description Date
(1) LAYER 5/8" GYP. WALLBOARD 1/2" RC DELUXE;
12" OC AT CEILING
PLUMBING CHASE WALL
(1) LAYER 5/8" GYP.
WALLBOARD
NOTE: REFER TO PRESCIENT & HILTI
THROUGH-PENETRATION UL LISTINGS
PRESCIENT WALL PANEL
PER PENETRATION DIAMETER

1/2" RC DELUXE, 24" OC


NOTE: (ONE SIDE ONLY) NOTE: NOTE:
REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP. REFER TO UL REPORTS FOR GYP.
WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS SECTION WALLBOARD REQUIREMENTS PLAN
ICC-ES ESR-3745 ICC-ES ESR-3745 ICC-ES ESR-3745
Plumbing Wall - 1HR T Rating (TYP) UL W428, UL G592, UL H502 Tub Drain Detail - 1HR T Rating (TYP) UL G592, UL H502, UL F-E-2050 Infill Wall - Pre-Rock - Unrated (TYP) UL W428
5 6 7
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"

ACOUSTICAL SEALANT TOP AND BOTTOM

CEMENTITIOUS FLOORING CEMENTITIOUS FLOORING;


CEMENTITIOUS FLOORING CONTINOUS TO EDGE OF SHAFT

MIN 3 1/2" BATT INSULATION

FIRE CAULK WHERE TRUSS HANGER

PRESCIENT INTEGRATED
PENETRATES (2) LAYERS 5/8" GYP. WALLBOARD Prescient Assembly
PRESCIENT INTEGRATED
PANEL TRUSS
PANEL TRUSS

PRESCIENT FLOOR TRUSS


Details
MIN 3 1/2" BATT INSULATION 6" System
1" x 2 1/2" SERVICE 1" x 2 1/2" SERVICE
HOLE AT 24" O.C. HOLE AT 24" O.C.
CEILING AS SCHEDULED; (1) OR (2) LAYERS
5/8" GYP. WALLBOARD, PER RATING

(1) LAYER 5/8" GYP. WALLBOARD (1) LAYER 5/8" GYP. WALLBOARD
1/2" RC DELUXE; 12" OC AT CEILING Combination
1/2" RC DELUXE; 12" OC AT CEILING 1/2" RC DELUXE; 12" OC AT CEILING
BOTTOM CHORDS OF TRUSS CUT SHORT TO AVOID
PENETRATION OF RATED WALL ASSEMBLY
Assemblies
Project Number N505
BATT INSULATION (OPTIONAL) BATT INSULATION (OPTIONAL) (2) LAYERS 5/8" GYP. WALLBOARD, BOTH SIDES
Date 06/23/2016
PRESCIENT WALL PANEL PRESCIENT WALL PANEL PRESCIENT WALL PANEL
5/8" EXTERIOR SHEATHING Drawn By
5/8" EXTERIOR SHEATHING
JDS
EXTERIOR PRESCIENT WALL; DRYWALL Checked By EPH

6/23/2016 3:14:51 PM
EXTERIOR PRESCIENT WALL; DRYWALL BATT INSULATION (OPTIONAL)
DOES NOT EXTEND TO UNDERSIDE OF DECK DOES NOT EXTEND TO UNDERSIDE OF DECK

SP.6
NOTE: NOTE: (1) LAYER 5/8" GYP. WALLBOARD
REFER TO UL REPORTS FOR GYP. (1) LAYER 5/8" GYP. WALLBOARD REFER TO UL REPORTS FOR GYP. NOTE:
WALLBOARD REQUIREMENTS WALLBOARD REQUIREMENTS REFER TO UL REPORTS FOR GYP.
SECTION WALLBOARD REQUIREMENTS SECTION
SECTION ICC-ES ESR-3745
Prescient Exterior Wall - Perpendicular to ICC-ES ESR-3745 Prescient Exterior Wall - Parallel to Truss ICC-ES ESR-3745
Truss (TYP) UL W428, UL G592, UL H502 (TYP) UL W428, UL G592, UL H502 2HR Shaft Assembly (TYP) UL W428, UL G592, UL H502 Scale 1 1/2" = 1'-0"
8 9 10
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"