PROPOSED MEDICAL FACILITIES AT OBSTETRICS & GYNAE DEPARTMENT JPMC,


KARACHI

SUMMARY OF HVAC LOADS ON ROOF

Load Equip. Size Area Load on Slab


S. No. Unit Description No. Slab Location 2
(kg) (lb) (ft x ft) (ft ) (psf)

1 AHU 3 & 4 2 300 661.39 Waffle Slab 6'-6"x6'-0" 39 67.8 *

2 Chillers 1 4500 9920.79 Grid 9-10 & E-F 9'-0"x18'-0" 162.00 122 *

3 Chillers 1 4500 9920.79 Grid 10-11 & E-F 9'-0"x18'-0" 162.00 122 *

4 Pumps 2 500 1102.31 Grid 11-12 & E-F 6'-0"x3'-0" 18 245 *

5 AUH 2 1 250 551.16 Grid X-Y & 10E-10D 6-0"x6'-6" 39 28 *

6 AUH 1 1 250 551.16 Grid X-Y & 10B-10D 6-0"x6'-6" 39 28 *

NOTE: * Loads has been twice to incorpotare dynamic effects of all HVAC equipments