Академический Документы
Профессиональный Документы
Культура Документы
Short-Circuit Current
Insu Kim Ronald G. Harley
Electrical Engineering Electrical and Computer Engineering
Alabama A&M University Georgia Institute of Technology, Atlanta, GA, USA
Normal, AL, 35711, USA Professor Emeritus at the University of KwaZulu-Natal in
insu.kim@aamu.edu South Africa, rharley@ece.gatech.edu
Abstract-In short-circuit studies, phase shifts in transformers and insisted that transformers connected in different ways
(e.g., connected in wye-delta or vice versa) make difficult to have a significant impact on fault current [11]. Another recent
calculate fault current flowing in sequence-component networks.
study discussed the accuracy of transformer models presented
Therefore, they are often ignored because the magnitude of fault
from the Alternative Transients Program that shift phases in
current is much more of interest than phase angles from the
protection point of view (e.g., overcurrent relays). As high positive- and negative-sequence networks [12]. However,
capacity distributed generation (DG) resources are being these studies have not analyzed distribution networks not only
deployed into distribution networks, they may change the heavily or weakly meshed but also enhanced by DG resources
direction and the phase angle of fault current and cause with relatively high capacity (e.g., 30 and 50 percent). Thus,
abnormal operations of directional or distance relays. Thus, the
the objective of this study is (a) to present an accurate short
objective of this paper is to develop a short-circuit analysis
circuit analysis algorithm able to calculate the magnitude and
algorithm able to (a) calculate changes in phase shifts caused by
transformers in sequence networks with high-capacity DG the phase angle of fault current in meshed or radial networks,
sources and (b) analyze the effect of not only various capacities including phase shifts through transformers, and (b) to analyze
(e.g., 10, 30, and 50 percent) of DG resources but also various the effect of not only various capacities (e.g., 10, 30, and 50
locations of faults on current that flows during a short circuit. percent) of DG resources but also various locations of faults
To verify the developed algorithm, using MATLAB, case studies
on current that flows during the short circuit.
that generate a single line-to-ground fault on (a) the high- and
low-voltage sides and (b) a weakly meshed network are This paper is organized as follows: Section 2 describes a
presented.
problem statement, and Section 3 presents the short-circuit
theory for analyzing phase shifts of transformers and meshed
Index Terms-Distributed generation (DG), phase shift,
sequence network, short circuit, and single line-to-ground fault.
networks. Section 4 provides a flowchart of the implemented
short-circuit analysis algorithm. Section 5 introduces case
I. INTRODUCTION
studies for calculating short-circuit current using the proposed
algorithm. Section 6 summarizes major conclusions of this
As high-capacity distributed generation (DG) resources
study.
such as small-scale synchronous generators, solar, and wind
farms are being deployed into distribution networks, they may II. PROBLEM STATEMENT
change current that flows during a short circuit or an electrical
If a fault occurs on an external line of a distribution system
fault. Thus, many studies have presented various methods for
with high-capacity DG resources, fault current flowing from
short circuit studies, which can be classified by the following
DG resources will flow to the faulted line, which is a reverse
three methods:
direction when compared to the case without DG resources.
(1) solving sequence networks using symmetrical components
Furthermore, since phase angle changes in fault current caused
[1-3],
by DG resources may affect the protection coordination of
(2) iterative compensation methods using bus admittance
directional or distance relays, they should not be ignored.
matrices [4, 5],
Thus, this study is to develop a short-circuit analysis algorithm
(3) iterative compensation methods using bus impedance
able to calculate a phase angle of fault current, including phase
matrices [6-9].
shifts through transformers. For this purpose, it applies a
However, these study ignored phase shifts through
phase-shifting method to positive- and negative-sequence
transformers since the magnitude of fault current is much
networks. In addition, this study changes the capacity of DG
more of interest than phase angles from the protection point of
resources and fault locations in a case study in order to
view (e.g., overcurrent relays). To examine phase shifts of
examine their effect on the magnitude of fault current.
transformers, a study presented a mathematical model and
graph theory (which is referred to as a V-equivalent) of the III. SHORT-CIRCUIT STUDY
delta-wye transformer that shift phases [10]. Another study
modeled the transformer and the load in short circuit analysis A. Current of a Single Line-to-Ground Fault
[ 1j
sequence open-circuit driving-point impedances of faulted bus study applies the Kirchhoffs Current Law (KCL) to the
or line i in bus impedance matrices, respectively, meshed topology. For example, if a fault occurs on bus 3 in
Zr= fault impedance. Fig. 2, currents flowing through the branches is determined by
The fault current If of line i is
the following KCL:
IJ =310 =311 =312, 1 -1 0 0 I I. 3
o 1 0 /21 12
- (4)
0 1 124 IF - 13
(3)
1 0
B. Representation of Transformers in Sequence Networks o 0 -1 1 3
In short-circuit studies, since the main concern of which is where Ii,j = the current that flows from buses ito j,
usually the magnitude of fault current, phase shifts through
Ii = the current incoming to or outgoing from bus i.
transformers are often ignored. In other words, transformers
are replaced by simply zero-, positive-, and negative-sequence Since It, h h h and IF can be determined by solving the
impedances. To examine such phase shifts of transformers, sequence networks, the currents flowing through branches,
Fig. 1 illustrates a method that shifts phases between two (e.g., 12, 1 ) can be found by an inverse transformation of (4).
buses in positive- and negative-sequence networks in the case
of a transformer connected in delta-grounded wye. In the
positive-sequence network of the transformer balanced in
three phases, a phase of +30 will be shifted from buses ito j,
shown in (a). The negative sequence shifts by -30.
V. CASE STUDY
BusR
0,7038 0,6186 1.0000
OLO
0,7496 0,2532 zero-sequence network is only jO. l2 Pu. Therefore, it shows
L-52,23 L-134,18 L90,00 L32.49 LI42,62
0,9117 0,9662 0,2426 0,6210 0,3793
the highest magnitude of fault current in all the cases. In
Feeder 2 OLO
L-I13.44 LI12,04 L-175,34 LO,91 L178,5JD addition, in the all cases, the higher capacity a DG source has,
DG ILO IL-120,00 ILI20,00 OLO ILO OLO
fault current with the higher magnitude flows. Note that in the
case of without DG, the fault location of feeder 2 was moved
TABLE TV LINE CURRENTS AFTER A FAULT ON FEEDER 2 to the secondary side of the grounded wye-delta transformer in
Current in PU
Bus Fig. 4, (to avoid that fault current does not flow in the case of
Phase A Phase B Phase C lo(Zero) l,(posilive) h(Negative)
Generator* 0.4333 0,2167 0,2167
OLO
0,2167 0,2167 a fault on feeder 2 of the test feeder without DG because the
BusS L-79,96 LI00,04 LI00,04 L-79,96 L-79,96
side of the DG source is open in the zero-sequence network).
BusS* 0,3753 0,3753 0,2167 0,2167
OLO OLO
Feeder I L-79,95 LI00,05 L-49,95 L-109,95
Feeder 1* 0,3753 0,3753 0,2167 0,2167
OLO OLO
BusR L-79,95 LI00,05 L-49,95 L-109,95
BusR* 0,3753 0,3753 0,2167 0,2167
OLO OLO
Feeder 2 L-79,95 LI00,05 L-49,95 L-109,95
Feeder 2* 1.2128 0.4043 0.4043 0.4043
OLO OLO
Fault L-85,34 L-85,34 L-85,34 L-85,34
DG* 0,7824 0,2167 0,2167 0.4043 0,1896 0,1896
Feeder 2 L-88,32 L-79,96 L-79,96 L-85,34 L-91.49 L-91.49
of fault current, this study changes not only the capacity of To verify the proposed algorithm that analyzes faults
DG resources in a range of 10 MW (10 percent) to SO MW (SO occurring on the meshed network, this study presents a case
percent) but also fault locations. Fig. 7 shows the trends in the study of the IS-bus meshed distribution system in Fig. 8 and
magnitude of fault currents. In the cases of without DG and 10 generates a SLG fault on bus 13 of the network. TABLE V
percent DG, if a SLG fault occurs close to the substation (e.g., shows the results of fault currents of each branch with an
Bus S), the magnitude of fault current is greater than that impedance of 0, calculated from equation (4). Note that h=
caused by a fault occurred far from the substation (e.g., Feeder h.13 + 115,13 + 113 . In this case study, load current is also
2). However, since the DG source has relatively low ignored.
ground, and three-phase faults. In addition, this study did not
analyze sufficiently large distribution networks. However, the
developed algorithm can be extended for such cases by taking
into account of load current, implementing the other fault
types, and modeling large distribution networks, all of which
are still our future work.
REFERENCES