Вы находитесь на странице: 1из 6

Adaptive Protection Scheme for Smart Grids

S Voima*, H Laaksonen, K Kauhaniemi*

*University of Vaasa, P.O. Box 700 FI-65101 Vaasa, Finland, e-mail: sampo.voima@uva.fi; kimmo.kauhaniemi@uva.fi

ABB Oy Medium Voltage Products, P.O. Box 699 FI-65101 Vaasa, Finland, e-mail: hannu.laaksonen@fi.abb.com

zones are the number of connections to other zones as well as


Keywords: Distance protection, microgrid, Smart Grid, the inclusion of the DG within the zone. A simulation study
adaptive protection. on a sample network is carried out using PSCAD to compare
the performance of some of the chosen protection methods.
Abstract The focus is on the distribution systems and especially in the
MV level where relay protection is applied. In addition, the
The amount of distributed generation (DG) connected to protection is also analysed in controlled island operation
distribution networks is increasing. This can cause challenges (microgrid) with PSCAD simulations.
for traditional protection of distribution networks due to bi- As a result of the analysis a novel adaptive protection scheme
directional power flows, fault current contribution of DG is proposed, which defines the protection system
units and grid code fault-ride-through (FRT) requirements. configuration and settings based on information from the
During the normal, parallel with utility grid, operation, the system state.
protection coordination may be compromised and nuisance or
delayed tripping may be experienced. After possible transition 2 Adaptive protection
to intended island operation the situation becomes even more
demanding from protection point of view due to low short- The adaptive protection was developed in the 1980s. The
circuit currents fed by DG units and sensitive dynamics. development was enabled by the increase of computer based
Therefore, protection adaptation to different topology changes relaying which allowed the possibility to change relay
will be more and more often required in the future distribution characteristics [1]. The evolving networks create the need for
networks. This paper evaluates the performance of different adaptive protection as existing relay settings and protection
protection methods in grid connected and in controlled island methods may become inappropriate. This requires adaptive
operation modes of a part of medium voltage network. The characteristics in protection and creates the need for relays
evaluation is done with PSCAD simulation software for an whose settings can be controlled in response to external
example network. Finally, an adaptive protection scheme for conditions [1].
smart grids is proposed. Moving towards Smart Grids means active management of
the power system in all levels. This is accomplished by
1 Introduction controlling various active elements. Since the configuration
of the network and the state of the active elements is
Todays medium voltage (MV) distribution networks are in constantly changing an adaptive protection concept will be
transition towards future Smart Grids. The amount of needed for Smart Grids. In addition, one more characteristic
distributed generation (DG) connected to MV networks is of future Smart Grids is the controlled island operation for
expected to increase steadily. The addition of active part of the distribution network, which can also be viewed as
distributed energy resources (DER), which include not only self-healing feature for Smart Grids as introduced in [2].
DG but also energy storages and demand response, brings up Having the possibility to transit into island operation can
new requirements for protection that needs to adapt to potentially improve stability and reliability of the network. In
changes in the network topology and configuration. As a microgrids to achieve controlled island operation, power
result of changes in the direction of power flow and short balance within the system must be achieved and maintained
circuit levels due to the increasing number of DG units in MV through local generation [3]. In addition, the protection
networks, the requirements for protection of distribution system needs to be quickly adapted to the new operating state
networks and DG are getting more complicated. The after the islanding. Normally microgrids are used in low
traditional, non-directional overcurrent based, protection voltage network, but they could also be used for part of the
system is not anymore adequate. During intentional island MV system as an ad hoc island in a fault situation. By
operation due to lack of short-circuit current and inertia, the monitoring the system state, both loads and generation,
situation from protection sensitivity, selectivity and operation suitable MV feeder sections can be defined in advance.
speed perspective will become even more challenging. Depending on the load/generation balances the size of
Therefore, new adaptive protection solutions are needed. suitable islands to be used in fault cases may be different at
In this paper different protection methods and situations are different times [3].
analysed with a scheme that is based on a limited set of The protection system must be able to protect the network in
different types of protection zones. The main features of the both possible connection states. In normal operation the

1
network sections capable to operate in an island mode will be IED or the settings of protection functions according to the
operated in parallel with the utility grid, and transition to changes in the primary system.
island operation is made when necessary. Nevertheless, island In the simulations done in the following chapter only three
operation produces challenges for protection as also indicated phase faults are examined. Fault locations are the same for
in [4]. islanded and grid connected modes, with the addition of one
Many of the DG technologies are based on a DC/AC HV/MV substation busbar fault in grid connected mode.
converter at the grid interface [3]. During network faults the The analysed and simulated protection methods are
short circuit current producing capability of these converters directional overcurrent and distance protection.
is usually limited to only 2-3 times their rated current [5], [6]
or even less than that. Traditional overcurrent protection 3.1 Directional overcurrent protection
scheme becomes infeasible with lack of short circuit current.
The main problems related to the DG protection are Directional overcurrent relays can be used when fault current
identified, for example, in [7]. Very much the same issues are can flow in both directions through the relay location. In
valid for the Smart Grid protection [3]. order to have the ability to distinguish current direction,
voltage measurement is required in addition to the current
measurement.
3 Adaptive network protection schemes The changes in short circuit current levels in microgrid pose
Adaptive protection schemes have various requirements, challenges for current based protection. The short circuit
proposed solutions and methods. Buigues et al. [8] have current might be too low to differentiate between maximum
extensively gone through publications of microgrid protection load current and the lowest short circuit currents. As with
methods. They have made several conclusions based on their non-directional overcurrent protection the selectivity is in
review [8]: some cases achieved by time grading.
x Whatever the microgrid protection methods, it is
likely that some kind of communication will be 3.2 Distance protection
necessary.
Distance protection is virtually independent on variations in
x Combined action of different protection techniques source impedance making it an interesting option when
might be necessary in order to get an optimal researching the protection of microgrids, where the short
protection system for microgrids. circuit current fed from the supporting network is lost. This
x It might be necessary to use different settings and can be viewed as a key advantage of distance protection [9].
even different methodologies for each fault However, in [10] it is observed that load flow changes could
direction. adversely affect the performance of the distance protection by
x Many solutions are based on dividing the network altering the measured impedance from actual positive
into smaller zones. sequence impedance. DG unit between the distance relays
This paper does a comparative study on selected protection measurement point and the fault location could have negative
methods, with a scheme that is based on a limited set of impact on the protection. As a result a DG unit appears as
different types of protection zones. The scheme is analysed in intermediate in-feed to some protection relays. The same
grid connected and in island modes of operation. In grid problems arise in grid connected mode as well [11].
connected mode the protection methods are compared with Impedance of a line is proportional to its length and by
and without DG connection. The number of connection of measuring the impedance an indication of possible fault
each zone as well as the number of DG units within a zone is situations is given. Distance protection uses current and
analysed. The effects of different grid code requirements are voltage to calculate fault impedance as is shown in equation
also examined. (1).
Based on the analysis a protection method is proposed, and
the benefits of the proposed adaptive protection scheme are U
Z (1)
illustrated. Novel adaptive protection scheme can in practice I
be achieved by applying either centralized or de-centralized
intelligent protection management system relying on where Z is impedance, U is measured voltage and I is
extensive communication network, which assigns new measured current [11]. Measured impedance is compared
protection settings to Intelligent Electronic Devices (IED). with predefined relay characteristics, and if the measured
Not all protection methods are suitable for every situation or impedance falls within these characteristics the situation is
network topology encountered. Unnecessary tripping of DER detected as an internal fault. The impedance setting in the
units or feeders can occur due to faults in adjacent feeders and relay determines the reach of the protection.
fault current contribution from DER. Enabling the use of
different protection methods for different network 3.3 Grid codes and FRT requirements
configurations and even the use of different methods in
different parts of the network may be necessary in order to Fault ride-through (FRT) or Low Voltage Ride-through
have acceptable protection speed and selectivity. This could (LVRT) requirements for DG have been developed in order
be done by changing the active protection function in each to secure power system stability during fault conditions. This
obliges the DG units to support the grid during fault and

2
abnormal network conditions and to prevent unnecessary The system comprises of one 20 kV overhead line feeder with
disconnection of DG units due to faults. Therefore, to prevent a total length of 40 km. The 40 km segment is also separated
unnecessary tripping, faulty lines should be disconnected first as a microgrid. The feeder is divided into three protection
by the protection system and only after that the DG units are zones with respective lengths of 10 km, 15 km and 15 km.
disconnect according to their FRT/LVRT profile. Fast Circuit breakers have been connected between the zones.
operation of protection is required, and emphasised if there Voltage and current are measured from those locations and
are several protection zones. To achieve this communication those measurements are used in the directional overcurrent
based protection methods and schemes are often required to and distance protection. IEDs are connected to the network
ensure selective operation. and referred to by numbers as shown in figure 1. There are
five possible fault locations which are marked from as F1 to
3.4 Communication requirements F5 in figure 1. A fault marked as F1 is in the low voltage
network connected via 20/0.4 kV Dy-connected transformer.
Communication requirements are different depending on Faults from F2 through F4 are in the MV network, as well as
whether the communication is used directly for protection the fault F5 which is in the MV busbar outside the islanded
(such as differential protection) or only used for transferring part and thus not considered in island mode.
network state information. In the proposed adaptive scheme 110 kV

the relays communicate with each other to get crucial


information on changes in network conditions. In this way the 110 / 20 kV
information needed to adjust protection settings for example
when transition to island operation has occurred is available.
Communication is also needed for managing the adaptive MV bus
F5

protection system [3]. 20 kV


Outgoing
MV feeders IED 1

4 Simulations
Pigeon Pigeon
10 km 10 km
In this chapter the simulations with an example network are F1&F2
carried out with PSCAD transient simulation software. In the
simulations a three phase fault is simulated in different
F4
locations. The simulation model is depicted in the following IED 2
chapter, followed by the different simulations done, and G
IED 3
finally the results of the simulations. DG unit 1
Pigeon
15 km
(converter based,
1.5 MVA)
4.1 Simulation model
F3
Pigeon
The example network is presented in figure 1. The examined 15 km
IED 4 IED 5
system consists of two generators and a network with
overhead line. A part of the network is possible to be used as DG unit 2
(converter based,
a microgrid. The coloured area in figure 1 shows the part that G 1.5 MVA)

can be disconnected as a microgrid.


Figure 1: Simulated network.
The two generators connected are identical in their rated
power (1.5 MVA), and their maximum current output has
4.2 Simulations
been limited to 1.2 p.u. They represent typical converter
interfaced DG units. They are modelled as controlled voltage Simulation runs are done for the above mentioned network in
sources. In grid connected mode both operate in current both grid connected and in island modes. In each run the
control mode to output a desired power (constant P and Q). In faults are applied in the defined locations with a predefined
island operation one is set as a master unit operating with sequence so that the results for all fault locations are obtained
constant frequency and keeping the voltage the nominal with one simulation run. The network is first simulated in grid
value, while the other unit continues to operate in PQ control connected mode for the five fault situations followed by
mode. The DG units are connected to the network in locations simulations where the feeder is disconnected from the
shown in figure 1, one 10 km from the start of the feeder and supporting network and simulated as a microgrid in four fault
the other 15 km further. situations.
Load consists of mainly constant impedance based passive Table 1 below depicts fault starting times and fault locations
loads connected evenly throughout the network, small part of for both grid connected and islanded simulations. In all fault
the load is constant power load connected to a single phase. cases the fault duration is 100 ms. In microgrid case the fault
Also few diode loads have been included. A total load of 0.82 F5 is not simulated and simulation ends at 3.0 s time.
MW and 0.22 MVAr has been connected to the microgrid
part of the network. The system earthing method is chosen to
be isolated, and thus the disconnection of the microgrid from
the secondary side does not affect the earthing method.

3
Time (s) Event 800
1.0 Fault F1 in LV network IED2 Island

1.5 Fault F2 in MV network 600 IED2 NODG

Current / A
2.0 Fault F3 in MV network IED2 DG
400
2.5 Fault F4 in MV network
3.0 Fault F5 in MV busbar 200
3.5 End of simulation
Table 1: Simulation sequence. 0
1 1.5 2 2.5 3 3.5
Time / s
4.3 Simulation results Figure 3: Fault current magnitudes in both operating modes as
measured from IED 2.
In this chapter the most interesting simulation results are
shown and discussed. The results from directional overcurrent The figure 4 represents impedance measured from IED 2
protection simulations are presented first, followed by results during fault F2 in island operation. The distance relay
from distance protection simulations. characteristics have been drawn to equal 85 % of the line
The following figure (figure 2) shows current measurement of length (green line). It can be observed that fault F2 is within
three relays (IED 2, IED 3 and IED 4) for faults in microgrid. the reach settings and the relay detects the fault accurately.
The fault starting times and their type can be seen from table The fault in the LV network, F1 was also simulated and not
1, and fault locations from the figure 1. For fault F1, in the detected by the IED 2. The measured resistance varied from
LV network, all the relays measure very similar currents and
60: to 86:, and reactance varied from 105: to 135:,
distinguishing where the fault is becomes a challenging task.
therefore the measured impedance is clearly outside the relay
During fault F2, IED 2 measures slightly bigger current than
characteristics. Faults F1 and F2 are both located 4km from
for fault F1, but in practice the difference is far too low for
DG1 and IED 2.
current based grading. For IEDs 2 and 3 the current
magnitude measurement is similar for three phase faults in 3

MV network than it is for three phase faults in LV network. 2


Reactance / :

Therefore, it is impossible to distinguish whether the fault is


in LV or in MV network. For fault F1 the directional ability 1

does not give value for IED 4 as it sees the fault in the same 0
direction as IED 2. Directional ability is, nonetheless, needed Impedance
for IED 3 to be able to not to operate for faults F1 and F2. -1
Relay characteristics
Furthermore, fuse to relay coordination between MV feeder 0 1 2 3 4 5 6 7 8
protection and LV system protection becomes even more Resistance / :
important, which possibly increases the operation time of the Figure 4: Impedance characteristics of IED 2 and F2.
MV network protection.
120 Figure 5 has impedance measurement from IED 3 during fault
IED2 Current
100 IED3 Current
F3 in both grid connected mode with DG units and in
80
IED4 Current microgrid. As can be seen from the figure 5, both impedance
measurements are outside of the drawn relay characteristics,
Current / A

60
85 % of line length, and are accurately measured because the
40 fault is located at the end of the feeder. IED 4 trips to this
20 fault in the 1st time grading zone while IED 3 trips in the 2 nd
time grading zone, and therefore fault clearing for faults near
0
1 1.5 2 2.5 3 the end of the feeders is time delayed. This clearly illustrates
Time / s
how the distance protection is immune to the source
Figure 2: Fault current magnitudes in island mode.
impedance size and type.
In the figure 3 it can be seen that the fault currents are very 6
similar in grid connected mode, regardless of DG connection.
Reactance / :

Overcurrent based protection can be used in grid connected 4

mode. The current magnitudes during island operation,


2
however, are much smaller. As seen from the figure 3 the
Impedance microgrid
fault current measured for fault F2 during island operation is 0 Impedance grid connected
only marginally greater than the current flowing through the Relay characteristics
feeder during normal operation in grid connected mode with 0 1 2 3 4 5 6 7 8 9
DG units connected. As a result fault detection with current Resistance / :
based protection in islanded mode is not possible without a Figure 5: Impedance characteristics of IED 3 and F3.
complete change in protection settings.
Similar results were observed from the simulation for other
fault situations and other IEDs also. Table 2 shows the results

4
of the measured current magnitudes from every IED during transmits the new protection settings forward to protection
fault situations in grid connected mode with DG units devices. In de-centralised decision making for example all
connected and in island mode. The results are given in protection zones are responsible of protecting their own zone
amperes. The results show that for grid connected mode the and independently gather necessary information to make
directional overcurrent protection can be viable, but in island decision on how to change protection settings related to that
operation it becomes inadequate. Simulation results also specific zone.
showed that during island mode it might be possible to use This kind of adaptive scheme has basically relatively low
overcurrent based protection in some situations, but when the requirements for the needed communication system. This
maximum load current is very close to the lowest short circuit considers both the speed of the communication links and their
currents discrimination between fault and heavy load availability. The situation would be different if the
situations becomes challenging. Furthermore, faults in LV communication is used also for protection (for example with
network will be erroneously detected. Distance protection line differential protection). However, in any case the
performed much better in island mode and was able to detect protection system should be designed so that there is valid
all simulated faults. Additionally, distance protection did not backup protection operating in case the communication
detect fault F2 in the LV network. system fails. A challenge for the adaptive protection system is
F1 F2 F3 F4 F5 also the validity of the system data collected. There could be
Grid Island Grid Island Grid Island Grid Island Grid some missing or erroneous data and it should be taken care
IED 1 95 - 1632 - 732 - 496 - 101
that any resulting hazards are avoided. Also the cyber security
issues are vital in this respect.
IED 2 69 70 99 95 732 0 496 0 101
The figure 6 represents an example case where an adaptive
IED 3 25 55 50 55 733 52 507 52 47 scheme can be used to determine the protection method and
IED 4 32 55 50 55 49 53 506 52 47 precalculated settings groups for IEDs. A particular setting
IED 5 13 15 0 0 0 0 513 103 1 group is selected based on, for example, the number of DG
Table 2: Current magnitudes during faults in amperes [A]. connections in the zone. Telecommunication is used to
transfer the status information of the network topology to
The use of distance protection, however, has its limitations. It IEDs. There are different types of protection zones, which are
is usable in situations where the connection is of the above separated by the number connection to other zones and by the
type, that is, the measurements are taken from both sides of a number of DG connection. Their behaviour is different
DG. Distance protection requires a source of fault current whether or not there is DG present in the zone. Moreover, the
flowing through the measurement points. The simulations type of a zone can change when changing the connection
above studied situations where measurements are taken from status of a DG unit, or by changing the status of circuit
both directions of a DG. Overcurrent based protection can be breakers. If a bi-directional power flow is possible in the
more versatile in comparison to distance protection when it zone, the protection needs to be able to differentiate the fault
comes to circuit breaker topology. Therefore, it is not always direction, such as the directional overcurrent or distance
easy to say which protection method is the best for any protection.
situation. When changing to island mode the protection must be
adjusted by either changing the protection method, for
5 Proposed Scheme example from overcurrent to distance protection, or by
changing the relay settings or settings groups. The settings of
As illustrated in the simulations above it is clear that an IEDs may depend on the size of the formed island. IEDs
adaptive protection scheme is needed for Smart Grids. Basing included in the island may have to change to which IEDs they
on the information about the system configuration and the send interlocking signals to according to the size of the island.
statuses of the DG units the protection system needs to be Like the simulations showed (figure 2) overcurrent based
adapted. Assuming that we have a fixed set of IEDs in the protection cannot selectively distinguish between MV and LV
network the adapting means primarily two things: faults. The simulations furthermore showed that distance
x enabling or disabling different protection functions, protection is able to selectively distinguish between faults in
x adjusting the settings of the applied protection the MV and LV networks. In the figure 6 also LV loads are
functions. considered, and protection method should be chosen also
For proper operation an adaptive scheme we need to collect considering LV faults. Further, based on the simulations and
information from the system and then make decision about the analysis, it is safe to say that overcurrent protection
the adjustments needed for the protection system. This can be cannot be used if fault current levels within the island are
accomplished with a suitable protection management system close to the maximum load current. Therefore, distance
consisting various intelligent devices and suitable protection may be suitable to be used in island operation.
communication means. Depending on the connections between the protection zones
The decision making could be based on either centralised or and applied protection methods it is also necessary to make
de-centralised intelligence. In centralised decision making sure the selective operation of the protection of different
one central controller receives information from the network zones. In practice this may be achieved by applying suitable
and according to the input it receives it either selects or time grading or by a telecommunication based interlockings.
calculates new protection settings for the whole network, and The former in some cases may lead quite long time delays

5
which may not be acceptable, and therefore a fast and secure method explained in figure 6 is intended to go under more
communication links are needed for interlockings. Referring specific studies in future work and papers. The proposed
to the figure 6 below, for example, the faults in the branch adaptive protection scheme was applied for studying the
(upward direction, protected by directional overcurrent relay) suitability of different protection methods to different kinds of
can be detected from the main feeder, depending on reach of protection zones. It enables full integration of the DG to the
the distance relays, leading to danger of both the distance and grid and provides means to utilize the DG also in the
directional overcurrent protection operating in the faults at the controlled island operation of a small part of the network.
branched zone. This problem can be solved so that when
detecting a fault in the branched zone, the directional Acknowledgements
overcurrent relay at the branch sends an interlocking message
to the distance relays at the neighbouring zone. Another This work was carried out in the Smart Grids and Energy
option would be the use of longer time delay for the first zone Markets (SGEM) research program coordinated by CLEEN
of the distance relays, but that might not be possible if there is Ltd. with funding from the Finnish Funding Agency for
DG within the zone as in the figure below. Furthermore, in Technology and Innovation, Tekes.
grid connected mode fast detection and separation of faults is
necessary to prevent nuisance tripping, as the protection of References
DG units disconnect the generation according to their
FRT/LVRT profile. [1] CIGRE. Adaptive Protections and Control Final
The target is to select the most suitable protection method and Report, CIGRE, 1995.
settings according to the current topology, and apply them [2] S. M. Amin, B. F. Wollenberg. Toward a Smart Grid:
every time a change in the network topology happens. For Power Delivery for the 21st Century, IEEE Power
zones with only one connection to other zones the settings can Energy Magazine, 3, pp. 34-41, (2005).
be extended to reach to the end of the zone. Zones with two or [3] K. Kauhaniemi, S. Voima. Functional Requirements of
more zone connections should use time grading depending on Smart Grid Protection, PAC World Conference 2012,
the DG connections. Reach settings can be selected according Budapest Hungary, 28-28 June 2012.
to DG connections and reach that must be covered. When fast [4] A. Oudalov, A. Fidigatti, T. Degner, et al. Novel
communication is used the interlocking commands can be Protection Systems for Microgrid, Final version of
used to block unnecessary tripping instead of time grading. partial report for WP C (TC2: Technical requirements for
Also with communication the fastest reach settings for network protection) on More Microgrids EU-project,
distance relays can be set to reach over the adjacent zone 2009.
border and fault direction information is sent to both [5] S. Chowdury, S. P. Chowdury, P. Crossley. Microgrids
directions by all IEDs enabling the faulted zone to be detected and Active Distribution Networks, The Institution of
in that way and used to selectively operate the correct IED. Engineering and Technology, 2009.
[6] T. Loix, T. Wijnhoven, G. Deconinck. Protection of
Microgrids with a High Penetration of Inverter-Coupled
Energy Sources, CIGRE/IEEE PES Joint Symposium on
Integration of Wide-Scale Renewable Resources Into the
Power Delivery System, Calgary, Canada, July 2009, pp.
1-6.
[7] K. Kauhaniemi, L. Kumpulainen. Impact of Distributed
Generation of the Protection of Distributed Networks,
Figure 6: Example network. Developments in Power System Protection, Amsterdam,
5-8 April, 2004.
[8] G. Buigues, A. Dyko, V. Valverde, I. Zamora, and E.
6 Conclusions Fernndez, Microgrid Protection: Technical challenges
An adaptive protection scheme for Smart Grids has been and existing techniques, International Conference on
demonstrated in this paper. Comparison between directional Renewable Energies and Power Quality (ICREPQ13),
overcurrent and distance protection has been simulated. The Bilbao (Spain), 20-22 March, 2013.
results showed that distance protection can with little to no [9] Areva. Network Protection & Automation Guide,
changes to settings perform well in island operation. The Areva T&D, 2005, ISBN 2-9518589-0-6.
simulations also suggested that adaptation of distance [10] V. P. Mahadanaarachchi, R. Ramakumar. Impacts of
protection would be rather easy. When the scope is expanded Distributed Generation on Distance Protection
to cover also two phase and earth faults the viability of Performance A Review, Power and energy Society
distance protection must be further studied. Directional General Meeting - Conversion and Delivery of Electrical
overcurrent may fail to operate selectively in island operation. Energy in the 21st Century, Pittsburgh, USA, July 2008,
Directional overcurrent protection requires a clear margin pp. 1-7.
with maximum load current and fault currents to have any [11] G. Ziegler. Numerical Distance Protection Principles
consideration. Benefits of the proposed scheme are and Applications. Publicis MCS, Munich and Erlangen,
maintaining selective operation after topology changes. The 1999.

Вам также может понравиться