SINGLE PIECE
NON-VARIABLE SPEED AIR HANDLERS
ISO 9001
MODELS: AHP AND SHP SERIES Certified Quality
Management System
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 REQUIRED CONTROL SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .9
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 6 UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . . 7 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Filter Access and Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Dimensions & Duct Connection Dimensions . . . . . . . . . . . . . . . . . . . . 4 Blower Speed Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Cooling Models with and without Electric Heat Wiring . . . . . . . . . . . .14
TXV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Two-Stage Heat Pump Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Proper Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LIST OF TABLES
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical Data - (For Single Source Power Supply) -
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Copper Wire 1 - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electrical Data - (For Multi-Source Power Supply) -
Low Fan Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Copper Wire 1 - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Blower Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electrical Data - 3 - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . .13
Heat Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electrical Data - (For Single Source Power Supply) -
Physical and Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Copper Wire 3 - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Electrical Data - Cooling Only (60 Hz) . . . . . . . . . . . . . . . . . . . . . . . . 10 Air Flow Data - 60 Hz Models - 208 Volt . . . . . . . . . . . . . . . . . . . . . . .13
Conversion Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Air Flow Data - 60 Hz Models - 230 Volt . . . . . . . . . . . . . . . . . . . . . . .14
Electrical Data - 1 - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION II: SAFETY This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
This is a safety alert symbol. When you see this symbol on including, but not limited to building, electrical, and mechanical
labels or in manuals, be alert to the potential for personal codes.
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not FIRE OR ELECTRICAL HAZARD
avoided, will result in death or serious injury. Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
WARNING indicates a potentially hazardous situation, which, if not
A fire or electrical hazard may result causing property damage, per-
avoided, could result in death or serious injury. sonal injury or loss of life.
160618-UIM-F-0806
160618-UIM-F-0806
1. Install this air handler only in a location and position as specified in LIMITATIONS
SECTION III of these instructions.
These units must be wired and installed in accordance with all national
2. Always install the air handler to operate within the air handlers and local safety codes.
intended maximum outlet air temperature. Only connect the air
Voltage limits are as follows:
handler to a duct system which has an external static pressure
within the allowable range, as specified on the air handler rating 1
Air Handler Voltage Voltage code Normal Operating
plate. Voltage Range
3. When an air handler is installed so that supply ducts carry air cir- 208/230-1-60 06 187-253
culated by the air handler to areas outside the space containing 220/240-1-50 93 198-264
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating in the space to be 1. Rated in accordance with ARI Standard 110, utilization range A.
cooled/heated. Airflow must be within the minimum and maximum limits approved for
4. The air handler is not to be used for temporary heating of buildings electric heat, evaporator coils and outdoor units.
or structures under construction.
Entering Air Temperature Limits
5. The size of the unit should be based on an acceptable heat loss or
Wet Bulb Temp.F Dry Bulb Temp. F
gain calculation for the structure. ACCA, Manual J or other
approved methods may be used. Min. Max. Min. Max.
57 72 65 95
SAFETY REQUIREMENTS
1. This air handler should be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
SECTION III: UNIT INSTALLATION
or wastewater codes, and other applicable codes. CLEARANCES
2. Refer to the unit rating plate for the air handler model number, and Clearances must be taken into consideration, and provided for as fol-
then see the dimensions page of this instruction for supply air ple- lows:
num dimensions in Figure 3. The plenum must be installed accord-
1. Refrigerant piping and connections - minimum 12 recommended.
ing to the instructions.
2. Maintenance and servicing access - minimum 36 from front of unit
3. Provide clearances from combustible materials as listed under recommended for blower motor / coil replacement.
Clearances.
3. Condensate drain lines routed to clear filter and panel access.
4. Provide clearances for servicing ensuring that service access is
4. Filter removal - minimum 36 recommended.
allowed for electric heaters and blower.
5. The ductwork and plenum connected to this unit are designed for
5. Failure to carefully read and follow all instructions in this manual zero clearance to combustible materials.
can result in air handler malfunction, death, personal injury and/or
property damage. 6. A combustible floor base accessory is available for downflow
applications of this unit, if required by local code.
6. Check the rating plate and power supply to be sure that the electri-
cal characteristics match. LOCATION
7. Air handler shall be installed so the electrical components are pro- Location is usually predetermined. Check with owners or dealers
tected from water. installation plans. If location has not been decided, consider the follow-
8. Installing and servicing heating/cooling equipment can be hazard- ing in choosing a suitable location:
ous due to the electrical components. Only trained and qualified 1. Select a location with adequate structural support, space for ser-
personnel should install, repair, or service heating/cooling equip- vice access, clearance for air return and supply duct connections.
ment. Untrained service personnel can perform basic maintenance 2. Use hanging brackets to wall mount this single piece air handler
functions such as cleaning and replacing the air filters. When unit, is not recommended.
working on heating/cooling equipment, observe precautions in the
3. Normal operating sound levels may be objectionable if the air han-
manuals and on the labels attached to the unit and other safety
dler is placed directly over some rooms such as bedrooms, study,
precautions that may apply.
etc.
9. These instructions cover minimum requirements and conform to
4. Select a location that will permit installation of condensate line to
existing national standards and safety codes. In some instances
an open drain or outdoors allowing condensate to drain away from
these instructions exceed certain local codes and ordinances,
structure.
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These NOTE: The primary and secondary drain line must be trapped to allow
instructions are required as a minimum for a safe installation. proper drainage of condensate water. If the secondary drain line is not
used, it must be capped.
INSPECTION The coil is provided with a secondary drain. It should be piped to a loca-
As soon as a unit is received, it should be inspected for possible dam- tion that will give the occupant a visual warning that the primary drain is
age during transit. If damage is evident, the extent of the damage clogged. If the secondary drain is not used it must be capped.
should be noted on the carriers freight bill. A separate request for 5. When an evaporator coil is installed in an attic or above a finished
inspection by the carriers agent should be made in writing. Also, before ceiling, an auxiliary drain pan should be provided under the air
installation the unit should be checked for screws or bolts, which may handler as is specified by most local building codes.
have loosened in transit. There are no shipping or spacer brackets
6. Proper electrical supply must be available.
which need to be removed.
NOTE: In severe high humidity, high temperature indoor unit environ-
Also check to be sure all accessories such as heater kits, suspension ments, an accessory insulation blanket is available to supplement the
kits, and coils are available. Installation of these accessories or field standard cabinet insulation. Insulate with UPG Kit: 1VJ0117 for B cabi-
conversion of the unit should be accomplished before setting the unit in nets, 1VJ0121 for C cabinets or 1VJ0124 on 57 height or 1VJ0224 on
place or connecting any wiring, electric heat, ducts or piping. 52 height D cabinets or seal completely with adequate fiberglass insu-
lation using vapor barrier on the outside.
HORIZONTAL RIGHT
DOWNFLOW AND HORIZONTAL CONVERSION 3. Remove front drain pan, hold down bracket.
(AHP ONLY) 4. Slide coil assembly out of air handler.
These air handler units are supplied ready to be installed in a upflow 5. Rotate cabinet 180 so blower outlet is facing down.
and right hand horizontal position. If unit requires left hand positioning, 6. Re-install coil assembly on downflow bracket.
the unit must have the coil assembly repositioned.
7. Re-attach front drain pan, hold down bracket.
NOTE: The SHP models are for upflow installation only, and should not
be installed in downflow/horizontal applications. 8. Re-attach tubing connection panel.
1. Remove blower, coil, and filter access panels. 9. For horizontal applications, rotate air handler 90 into desired ori-
entation.
NOTE: Conversion must be made before brazing the refrigerant con-
nections to the coil. 10. Re-position drain plugs as necessary based on air handler orienta-
tion.
For downflow and horizontal left installations, follow steps 2 - 8.
11. Re-position and replace access panels.
2. Remove tubing connection panel.
FRONT VIEW
BLOWER
COMPARTMENT
COIL COMPARTMENT
(Access panel removed)
VERTICAL
DRAIN PAN HORIZONTAL
DRAIN PAN
REFRIGERANT
LINE CONNECTIONS
SIDE VIEW
HORIZONTAL
PRIMARY DRAIN
HORIZONTAL
PRIMARY DRAIN
SECONDARY DRAIN
UPFLOW 3/4
THREADED ALTERNATE
DRAIN CONNECTIONS
DUCT WORK MAY UPFLOW/DOWNFLOW
BE FASTENED FILTER DOOR
CAUTIOUSLY WITH
SCREWS TO THE SECONDARY DRAIN RETURN AIR
SIDES AND REAR OF UNIT UPFLOW 3/4 THREADED DUCT
F
10-3/8
BLOWER
COMPARTMENT
TOP OUTLET
A CIRCUIT BREAKER DIMENSIONS
PANEL
7-11/32
18-9/32 E
1-1/2
C
B
BOTTOM INLET
FILTER DIMENSIONS
ACCESS DRAIN PAN CONNECTIONS
FOR HORIZONTAL APPLICATIONS
DUCT CONNECTIONS Where return air duct is short, or where sound may be a problem,
sound absorbing glass fiber should be used inside the duct. Insulation
of duct work is a must where it runs through an unheated space during
the heating season or through an uncooled space during the cooling
Use 1/2" screws to connect ductwork to bottom of unit. Longer season. The use of a vapor barrier is recommended to prevent absorp-
screws will pierce the drain pan and cause leakage. If pilot holes tion of moisture from the surrounding air into the insulation.
are drilled, drill only though field duct and unit bottom flange. The supply air duct should be properly sized by use of a transition to
match unit opening. All ducts should be suspended using flexible hang-
Air supply and return may be handled in one of several ways best ers and never fastened directly to the structure. This unit is not
suited to the installation. See Figure 3 for dimensions for duct inlet and designed for non-ducted (freeblow) applications. Size outlet plenum or
outlet connections. transition to discharge opening sizes shown in Figure 3.
The vast majority of problems encountered with combination heating Duct work should be fabricated and installed in accordance with local
and cooling systems can be linked to improperly designed or installed and/or national codes. This includes the standards of the National Fire
duct systems. It is therefore highly important to the success of an instal- Protection Association for Installation of Air-Conditioning and Ventilat-
lation that the duct system be properly designed and installed. ing Systems, NFPA No. 90B.
Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space. If electric heat is used, non-flammable AIR FILTERS
material must be used. Air filters must be field supplied. A 1" filter access rack has been built
into the unit. See Figure 3. Remove filter access cover shown. Install
proper size filter. Standard 1" size permanent or throw away filter may
be used, or, permanent washable filters are available using model num-
bers: 1PF0601, 602, 603BK. See Table 7 for filter size.
.
Please refer to Outdoor Unit Tech Guide to verify which TXV is installed
in this coil and that this is a valid system match for the AC or HP unit
installed.
Equipment should never be operated without filters. The temperature sensing bulb is attached to the coil suction header
line.
HORIZONTAL SUSPENSION (AHP ONLY) NOTE: For models that have factory installed TXVs, take caution not to
For suspension of these units in horizontal applications, it is recom- apply high temperatures to the TXV assembly or equalizer line while
mended to use angle steel support brackets with threaded rods, sup- brazing.
porting the units from the bottom, at the locations shown in Figure 4.
When an evaporator coil is installed in an attic or above a finished ceil- SCREW
ing, an auxiliary drain pan should be provided under the air handler as
is specified by most local building codes. TXV BULB
(Cover completely
NOTE: SHP models may not be installed in downflow/horizontal appli- with insulation)
cations.
NUT
MIN. 3/8 CLAMP SUCTION LINE
THREADED ROD
FIGURE 6: Proper Bulb Location
MIN. 1-1/2 x 1-1/2 Angle
Recommended length
26 minimum
with 2 clearance on
both sides of Air Handler COIL UNDER PRESSURE.
Relieve pressure by removing plug from piping connection. Coil
may have factory installed TXV or may require TXV to be added.
See outdoor unit documentation for correct TXV to be used. Refer
2 1-1/2 to coil nameplate for TXV identification for this unit.
WW
NOTE: The coil should be open to the air for no more than 2 minutes to
XX
keep moisture and contaminates from entering the system. If the coil
Units Dimension cannot be brazed into the refrigeration system in that time, the ends
(Nominal Tons) WW XX should be temporarily closed or plugged. For a short term delay, use
masking tape over the ends of the copper tubing to close the tube to the
018, 024, 030, 20 46
air. For a longer term delay, use plugs or caps. There is no need to
036, 042 24 52 purge the coil if this procedure is followed.
AHP048, AHP060 28 57
REFRIGERANT LINE CONNECTION
SHP48, SHP60 24 52
FIGURE 4: Typical Horizontal Installation
4. Remove grommets where tubes exit the cabinet to prevent burning Suggested pitch should not exceed 1/4 inch per foot of coil.
them during brazing. The coil is provided with a secondary drain that should be trapped and
5. Purge refrigerant lines with dry nitrogen. piped to a location that will give the occupant a visual warning that the
6. Braze the suction and liquid lines. primary drain is clogged. If the secondary drain is not used it must be
7. Remove the heat shield. capped.
8. Re-attach the grommets to the lines carefully to prevent air leak- The drain pan connections are designed to ASTM Standard D 2466
age. Schedule 40. Use 3/4" PVC or steel threaded pipe. Since the drains are
9. Attach the coil access panel to the cabinet. not subject to any pressure it is not necessary to use Schedule 40 pipe
for drain lines.
Refer to Outdoor unit Installation Manual for evacuation, leak check and
charging instructions. It is recommended that all drain connections be sealed with teflon tape
or equivalent.
Lines should be sound isolated by using appropriate hangers or strap-
ping.
All evaporator coil connections are copper-to-copper and should be SECTION IV: ELECTRIC HEATER
brazed with a phosphorous-copper alloy material such as Silfos-5 or INSTALLATION
equivalent. DO NOT use soft solder. If the air handler requires electric heat, install the electric heat kit
according to the installation instructions included with the kit. After
DRAIN CONNECTIONS installing the kit, mark the air handler nameplate to designate the heater
All drain lines should be trapped a minimum of three inches, should be kit that was installed. If no heater is installed, mark the name plate
pitched away from unit drain pan and should be no smaller than the coil appropriately to indicate that no heat kit is installed.
drain connection. The HEAT ENABLE jumper (See Figure 7) must be moved to the HEAT
position to enable operation of the heater.
Use only 4HK heater kits, as listed on Air Handler name plate and in
these instructions. Use data from Tables 10 through 19 for information
Threaded drain connection should be hand-tightened, plus no more on required minimum motor speed tap to be used for heating operation,
than 1/16 turn. maximum over-current protection device required and minimum electri-
cal supply wiring size required for listed combination of Air Handler
Route the drain line so that it does not interfere with accessibility to the and Heater Kit.
coil, air handling system or filter and will not be exposed to freezing
For upflow, downflow and horizontal right hand applications the kits can
temperatures. See Figures 2 and 3 for drain connection locations.
be installed without modification.
NOTE: When the coil is installed in an attic or above a finished ceiling,
Field modification is required for horizontal left hand airflow application
an auxiliary drain pan should be provided under the coil if specified by
only. Follow instructions with heater for modification.
local building codes.
Coils should be installed level or pitched slightly toward the drain end.
LOW FAN
RELAY OUTPUT
MODE JUMPER
FUSE
SPARE JUMPER
SECTION VII: LINE POWER the disconnect. The power lead conduit should be terminated at the
CONNECTIONS electrical control box. Refer to Tables 11, 12, 14, 16, 17 and 19 to deter-
mine proper wire sizing. Also see Figure 3. To minimize air leakage,
Power may be brought into the unit through the supply air end of the seal the wiring entry point at the outside of the unit.
unit (top when unit is vertical) or the left side panel. Use the hole appro-
priate to the units orientation in each installation to bring conduit from
TYPICAL WIRING WITHOUT ELECTRIC HEAT ELECTRIC HEAT 1 PHASE ELECTRIC HEAT
GND. LUG GND. WITHOUT CIRCUIT BREAKER WITH CIRCUIT BREAKER
LUG 3 PHASE (10 - 15 KW) AS SHIPPED FROM FACTORY
SINGLE SOURCE
GND. LUG GND.
LUG (2.5 - 25 KW) - 25 KW SHOWN
POWER
SUPPLY
GND. LUG GND.
POWER LUG
SUPPLY
1 PHASE ELECTRIC HEAT TERMINAL
WITH CIRCUIT BREAKER BLOCK
& BREAKER BAR REMOVED ELECTRIC HEAT
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN WITHOUT CIRCUIT BREAKER POWER
GND. LUG GND. SINGLE SOURCE (2.5 - 10 KW) SUPPLY
LUG
GND. LUG GND. (JUMPER BAR)
POWER LUG
MAY BE 1, 2, OR 3
SUPPLY 1
CIRCUIT BREAKERS
POWER
POWER
SUPPLY 2
SUPPLY
POWER TERMINAL POWER WIRING (208/230-1-60)
SUPPLY 3 BLOCK
NOTE: USE ONLY COPPER CONDUCTORS
MAY BE 1, 2, OR 3 CONNECT TRANSFORMER LEADS WITH WIRE NUTS
CIRCUIT BREAKERS (TYPICAL ALL HEAT KITS)
SECTION VIII: BLOWER SPEED Adjust blower motor speed to provide airflow within the minimum and
CONNECTIONS maximum limits approved for evaporator coil, electric heat and outdoor
unit. Speed tap adjustments are made at the motor terminal block, See
All air handlers, except the 5 ton (060 model), contain 3-speed blower
Figure 9. Airflow data is shown in Table 15.
motors. The 5 ton (060 model) has a programmed X-13 motor. Connect motor wires to motor speed tap receptacle for speed desired.
See unit wiring label for motor wiring details.
WHT
TO
CONTROL BOARD
PUR
24 V FACTORY WIRED TO
BLK TRANSFORMER
YEL
CAP
1 C FACTORY WIRED TO
BRN
GRN FAN MOTOR RELAY
2 G TERMINAL ON
PUR
3 L CONTROL BOARD
YEL HIGH
4 N
5 PUR 230 VOLT MED
TO BLOWER MOTOR
208 / 230V GRN LOW
TRANSFORMER
FAN MOTOR BLOWER
230V
5 TON HIGH EFFICIENCY MOTOR 1-1/2 TON TO 4 TON STANDARD MOTOR GND.
TABLE 11: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-1-60
Field Wiring
Heater
Heater
Models
Models*
Amps Min. Circuit Ampacity Max. O.C.P.1 Amps/Type 75C Wire Size - AWG
240V
208V 240V 208V 240V 208V 240V
4HK*6500206 10.4 13.50 15.40 15 20 12 12
18B 4HK*6500506 20.0 23.79 27.38 25 30 10 10
4HK*6500806 31.3 35.98 41.50 40 45 8 8
4HK*6500206 10.4 13.03 14.88 15 15 14 14
4HK*6500506 20.0 23.42 26.88 25 30 10 10
24B
4HK*6500806 31.3 35.60 41.00 40 45 8 8
4HK*6501006 40.0 45.08 51.88 45 60 8 6
4HK*6500506 20.0 24.17 27.75 25 30 10 10
30B 4HK*6500806 31.3 36.35 41.88 40 45 8 8
4HK*6501006 40.0 45.83 52.75 50 60 8 6
4HK*6500506 20.0 25.79 29.50 30 30 10 10
4HK*6500806 31.3 37.98 43.63 40 45 8 8
36C 4HK*6501006 40.0 47.46 54.50 50 60 8 6
4HK16501506 60.0 69.13 79.50 70 90 4 3
4HK16501806 73.3 83.57 96.13 90 100 4 3
4HK*6500506 20.0 25.92 29.75 30 30 8 8
4HK*6500806 31.3 38.10 43.88 40 45 8 8
42C 4HK*6501006 40.0 47.58 54.75 50 60 6 6
4HK16501506 60.0 69.25 79.75 70 90 4 3
4HK16501806 73.3 83.69 96.38 90 100 3 3
4HK*6500506 20.0 25.92 29.75 30 30 10 10
4HK*6500806 31.3 38.10 43.88 40 45 8 8
4HK*6501006 40.0 47.58 54.75 50 60 8 6
48D
4HK16501506 60.0 69.25 79.75 70 90 4 3
4HK16501806 73.3 83.69 96.38 90 100 3 3
4HK16502006 80.0 90.92 104.75 100 110 3 2
4HK*6500506 20.0 31.17 34.50 35 35 8 8
4HK*6500806 31.3 43.35 48.63 45 50 8 8
4HK*6501006 40.0 52.83 59.50 60 60 6 6
60D 4HK16501506 60.0 74.50 84.50 90 90 3 3
4HK16501806 73.3 88.94 101.13 90 110 3 2
4HK16502006 80.0 96.17 109.50 100 125 3 1
4HK16502506 100.0 117.83 134.50 125 150 1 1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
* May be 0 (no breaker) or 1 (with breaker).
TABLE 12: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-1-60
Min. Circuit Ampacity Max. O.C.P.1 Amps/Type 75C Wire Size - AWG
Heater Circuit Circuit Circuit
Models
Models 1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240
4HK16501506 47.48 / 54.5 21.68 / 25.00 50 / 60 25 / 25 8/6 10 / 10
36C
4HK16501806 43.88 / 50.31 39.75 / 45.80 45 / 60 40 / 50 8/6 8/8
4HK16501506 47.60 / 54.75 21.68 / 25.00 50 / 60 25 / 25 8/6 10 / 10
42C
4HK16501806 44.00 / 50.56 39.75 / 45.80 45 / 60 40 / 50 8/6 8/8
4HK16501506 47.60 / 54.75 21.68 / 25.00 50 / 60 25 / 25 8/6 10 / 10
48D 4HK16501806 44.00 / 50.56 39.75 / 45.80 45 / 60 40 / 50 8/6 8/8
4HK16502006 47.60 / 54.75 43.35 / 50.00 50 / 60 40 / 50 8/6 8/8
4HK16501506 52.85 / 59.50 21.68 / 25.00 60 / 60 25 / 25 6/6 10 / 10
4HK16501806 49.25 / 55.31 39.75 / 45.81 50 / 60 45 / 60 6/6 8/6
60D
4HK16502006 52.85 / 59.50 43.35 / 50.00 60 / 60 45 / 50 6/6 8/8
4HK16502506 52.85 / 59.50 43.35 / 50.00 21.68 / 25.00 60 / 60 45 / 50 25 / 25 6/6 8/8 10 / 10
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
TABLE 14: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60
Field Wiring
Heater
Heat Kit -
Models
Three Phase
Amps Min. Circuit Ampacity Max. O.C.P.1 Amps/Type 75C Wire Size - AWG
240V
208V 240V 208V 240V 208V 240V
24B 4HK06501025 23.1 27.1 31.3 30 35 10 8
30B 4HK06501025 23.1 26.8 30.8 30 35 10 8
4HK06501025 23.1 27.5 31.6 30 35 10 8
36C
4HK06501525 34.7 40.0 46.1 40 50 8 8
4HK06501025 23.1 29.1 33.4 30 35 10 8
42C 4HK06501525 34.7 41.6 47.9 50 50 8 8
4HK06501825 41.4 48.9 56.3 50 60 8 6
4HK06501025 23.1 29.3 33.6 30 35 10 8
48D 4HK06501525 34.7 41.8 48.1 50 50 8 8
4HK06501825 41.4 49.0 56.5 50 60 8 6
4HK06501025 23.1 34.5 38.4 35 40 8 8
60D
4HK06501525 34.7 47.0 52.9 50 60 8 6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
2. Heaters are 3 Phase.
TABLE 15: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60
Minimum Circuit Ampacity Max. O.C.P.1 Amps/Type 75C Wire Size - AWG
Heater Circuit
Models
Model
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240
60D 4HK16502525 40.8 / 45.6 31.3 / 36.1 -/- 45 / 50 35 / 40 -/- 8/8 8/8 -/-
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
G G G G
Y Y / Y2 Y Y Y / Y2 Y
W1 Y1 Y1
W2 W2 W2 W2
C W1 HUMIDISTAT * W1 W1 HUMIDISTAT *
O C O
HUM HUM
X/L X/L
COM C COM C
FIGURE 10: Cooling Models with and without Electric Heat Wiring
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. Y/Y2 Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
.
R R R
G G
Y2 Y2
Y / Y2 Y2 OUT
Y1 Y1 Y1
W2 W2 OUT
E W1 W1 OUT
W W
O O O
HUM HUMIDISTAT * BS
X/L X/L X/L
C COM C