Вы находитесь на странице: 1из 9

Gaoyuan, LIANG Year 2010

Grounding Design of Electric Power Plants and Transformer


Substations in High Soil Resistivity Area
Gaoyuan Liang
Inner Mongolia Electric Power Research Institute Network Centre

Abstract: This paper discusses current grounding standards still maintain 2000V earth potential
design issues of present electric power plants, regulation value unchanged even though the system
transformer substations in high soil resistivity area, short circuit capacity is growing, therefore, it is much
by incorporating the actual engineering data of a strict on the permissible value of grounding grid
220KV substation, analyzes the impact degree of contact potential and step potential. According to the
grounding design parameters to earth potential, recent situation analysis of engineering design, it is
contact potential, and step potential. It also can be very difficult to drop ground resistance below
used as a reference point for peers to discuss in DL/T621-1997 industrial standards. The following
engineering design. article will emphasis on exploring current grounding
design issues and solutions of present electric power
Key Words:High Resistivity, Electric Power plants, transformer substation in high soil resistivity
Plants, Transformer Substation, Grounding, area, by incorporating the actual engineering data of a
Design 220KV substation.

The main object of grounding design for electric


1. Overview power plants and transformer substation is that
Along with the rapid demand growth of urban designing a desirable grounding grid to meet power
residential electric load, there are increasing number system operational requirements, ensure the safety of
of 220KV transformer substation are seat in city as personnel and devices. A low resistance grounding
distribution substations in order to meet the electrical grid obviously benefits the safe running of the
load distribution requirements. The major features of equipment and personnel against harmful shock.
those transformer substations are: small-scale sites, However, there are many factors contribute to the
using GIS on 220KV and 110KV high-voltage safety grounding of electric power plants and
electrical equipment, occupying less area. transformer substations. Considering the expanding of
current electrical network capacity, there is no safety
The increasing power system capacity has cased high guarantee of equipment and personnel even though
earth fault currents in those substations. Therefore, the the grounding grid can be maintained at a low
outstanding issues in transformer substation resistance level. There is no direct connection between
grounding design are: small grounding area the resistance of overall grounding system and a
2
(5,000~10,000 m ), high soil resistivity (typically harmful shock to persons. Electric power plants and
500~1200m or higher), lack of condition to lay the transformer substations with relatively low grounding
external grounding. Although electric power plants resistance can be very dangerous. On the contrast, by
occupy larger area than transformer substations, it is careful designing the grounding grid, those with
still a tough challenge in designing ground grid when higher grounding resistance will become more secure
the soil resistivity is higher and earth current is (1). The following paragraph will discuss the factors
escalating. In addition, DL/T621-1997 industrial and the solutions when designing safety grounding for

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 1
Gaoyuan, LIANG Year 2010

Electric Power Plants, Transformer Substation in high Step potential difference is the ground surface voltage
soil resistivity areas. when the distance between the feet of a person is 0.8m.
Because the voltage decreased in soil when earth fault
currents or lighting currents flow into ground, where
2. The safety grounding design factors the soil resistivity contributes voltage difference the
andsolutions most. In the uniform soil, the step potential difference
The aim of sound safety grounding grids design is that is small due to the lower soil resistivity. Likewise, the
to provide a lower enough secure access point on step potential difference increased due to the high soil
earth potential, contact potential, and step potential for resistivity. However, it is far more complicated in the
electric power plants and transformer substations. non-uniform soil condition. The soil resistivity is still
the main drive of step potential difference on human
Contact potential is formed when earth-fault current elements, see formula below (3),
flow through equipments and generates distribution Step potential difference (Allowable Value) Us(V)
potential on the ground surface, the voltage exists
Us(V)= Ut(v)=(174+0.17f)/ (3)
where the distance from ground surface to equipments
is 0.8m horizontal and 1.8m vertically. As a matter of
Maximum Grounding Step potential difference
fact, the existing mesh of grounding grid generates
voltage between every point on the mesh to grounding. Usmax(V)

The maximum contact potential difference is the


Usmax(V)= Ksmax Ug (4)
voltage (maximum value) from the centre of mesh to
the earth electrode of grounding grid. When operators Usmax - Maximum Step Potential Difference;

working with charged equipment shell have grounding


Ksmax - Coefficient of Maximum Step
access, it is crucial to avoid potential electric shock
hazard by limiting contact potential difference within Potential Difference

a security level. Earth potential rise is cause by a grounding fault, the


voltage rise in ground grid when earth current flows
The formulas to calculate allowable contact potential through electrode. The shift of potential caused by
difference value (Ut(v))and grounding grid maximum increasing earth potential is not only threat the
contact potential difference (Utmax(v)) are showing as equipments and operators, but also creates potential
below: counterattack voltage hazards to local equipments.

Contact Potential Difference (Allowable Value) Ut(v) The index of earth current and grounding resistivity
are earth potential.
Ut(v)=(174+0.17f)/ (2) Earth potential Ug(v)

Grounding Grid Maximum Contact Potential Ug (v)=IR

Difference Utmax(v) I - Ground short circuit current, A

Utmax=KmaxUg R Earth resistance of grounding devices

Utmax - Maximum Contact Potential There are many factors contribute to above three
elements, somehow, the most influential ones are
Difference; earth fault current (I), duration time (t), shunt

Ktmax Coefficient of Maximum Contact coefficient of overhead ground wire (K), soil
-
resistivity (), ground surface resistivity (f),
Potential Difference uniformity of soil resistivity etc.

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 2
Gaoyuan, LIANG Year 2010

The following paragraphs will also analyze the considering double-layer soil (f =2500m), the
requirements, influential factors and solutions to new contact and step potentials are 773V, 2483V. As
above three security elements in grounding grid the ground resistance is 2.5, the earth potential value
design. An existing GW substation design data will be is as high as 28170V, far more great than standard
used to demonstrate influential factors and degrees in 2000V. In order to reach the requirements, the ground
grounding grid design elements. resistance should below 0.1 and it is 4% of the
The original parameters of a substation grounding original value, which also suggested minimizing soil
design are listed as below: resistivity down to 34.8m.

Duration time of ground short circuit (fault) The argument is focused on how to maintain the
safety of GW substation grounding grid while the
current, t:0.6s ground resistance cannot be reduced.

Maximum current of earth fault (maximum


2.1 The impact of earth fault duration time
shunt coefficient), I:1.5kA to grounding design parameters
As shown on Chart 1, the variation curves of contact
Uniform soil resistivity value (including the
potential and step potential move with earth fault

seasonal coefficient), 500m duration time. It is quite obvious that the fault
duration time has a great impact on safety issues.
Available grounding grid area (109*92m), S: Therefore, fast fault clearing will guard substation
operating much safer. For instance, when fault cleared
10028m2
in 0.1s, contact and step potentials are 819V, 1657V.
Surface resistivity of cushion macadam (moist), When it is in 0.6s, the contact and step potentials are
334V and 676V, the allowable voltage are all
f: 2500m
decreased to 40% of its value in 0.1s. The fault
According to DL/T621-1997, electric devices duration time has a greater influence to contact
grounding at Electric Power Plants, Transformer potentials and step potentials, especially between
Substation should dominate horizontal manual 0.1~0.9s. In reality, the switch breaking time and
grounding grids. GW substation proposed to adopt protection operating time of circuit breaker units that
compound grounding grids which combined are mostly relied on the type of equipments and
horizontal and vertical grounding electrodes. By manufacture which normally cannot be changed. Also
engineering calculation, the allowable contact and it would be too expensive and unrealistic if the
step potentials are 334V, 676V respectively. If changes have to be made.

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 3
Gaoyuan, LIANG Year 2010

2.2 The impact of ground surface resistivity surface. For instance, GW substation sets pebble
to grounding design parameters isolation layer with 2500 m, the number flat steel
required for horizontal ground are 600m (weight
Chart 2 demonstrates the impact of ground surface 2.226t), and it meets step potential requirement by
resistivity to contact potentials and step potentials. It setting up a 20m mesh distance. Otherwise, the
shows that ground surface resistivity has a greater number flat steel required for horizontal ground would
impact to the allowable vale of step potentials than be 20000m (weight 75.4t), and the mesh spacing is
contact potentials. Therefore, it is more effective to 1m which is more than 33 times more than setting
adopt quarantine measures when improving step pebble isolation layer.
potential hazard. In engineering design, contact Hence, adopting isolation layer method is more
potentials can be limited by using high soil resistivity economical wise for substations occupy small area.
material on operating platform. But rain is a critical element where using pebble
Considering the surface soil resistivity has greater isolation layer, the resistivity sharply drops when the
impact on the allowable value of contact and step ground surface is wet or rain. Therefore, it is quite
potentials, ground electrode material usage can be important to wear insulating shoes when entering
reduced by paving high resistivity material on the operating areas in raining days or wet seasons.

In the uniform soil environment, there is a negative resistivity. It has a much obviously result to decrease
linear correlation between earth potential and soil contact and step potentials by reducing soil resistivity

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 4
Gaoyuan, LIANG Year 2010

rather than earth potential. And the grounding grids According to the calculate formula, there is a positive
become secure when resistivity drops down to certain linear correlation between earth potential and earth
lower value. In applied engineering, it is difficult and current. It is an effective method to maintain low earth
expensive to reduce resistivity partially, not to potential, maximum contact and step potentials of
mention dropping down to certain lower value. From ground grid by decreasing system earth fault current,
above analysis, in order to meet contact potentials, it increasing ground current distribution, and cutting
is un-realistic and un-achievable to reduce earth down earth current. In practice, system capacity,
resistance from 2.5 to 0.1 , even though by impedance, and operating methods are determining
investing great amount of labour and material. earth fault current. Also fault current in two-phase and
For example, a substation in Shenzhen city, the single-phase grounding can be limited to certain point
measured earth resistivity was 3.08 before applying by system adjustment. However, it is not
any resistance reducing measurements, even though recommended to decrease earth potential by
adopted the methods of connecting earth to trench, restricting system operation. With the system capacity
replacing soil, adding resistance reducing agent, and expending, earth fault current will increasing
burring earth deep, earth resistivity only dropped accordingly. To decrease earth current, the ideal
down to 2.6, however, the investment was increased method is increasing the diversion effect of overhead
7,000,000. Even with the recommended explosion ground wire, but should considering the affect from
grounding technology which could reduce earth wiring tower potential.
resistivity by 20%~50%, only reached to 0.62~1.5.
It still does not meet owner required 0.5. When 2.4 The impact of grounding grid size to
decrease contact potential to 1243.5 ~ 3108.8V, still grounding design parameters
does not meet standard specification of 444.1V. It is For the grounding grid has sufficient area, there is a

quite challenge to maintain earth potential at 2000V as negative linear correlation between earth resistance

well as resistivity reached to 0.1. and square root of ground grid area. With larger

All above, soil resistivity contributes the most to earth ground grid area, earth resistance is relatively smaller.

potential, while ground surface resistivity affects Hence, it is an effective way to decrease earth

contact and step potentials the most. In conclusion, the resistance by increasing ground grid area in the design.

most effective way to solve contact potential and step As shown in chart 3, when doubling the ground grid

potential issues is that paving high resistivity isolation area, earth potential and earth resistance are all

layers on the ground. decreased by 30%. If grounding the lowest resistance


part of soil, the result will be more remarkable. But
2.3 The impact of earth current (or shunt from the practical perspective, on few electric power
coefficient ) to grounding design plants and substations at the seaside could achieve it,
parameters the rest simply lack of land to adopt this method.

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 5
Gaoyuan, LIANG Year 2010

2.5 The impact of grounding material quantity to grounding design parameters


To certain grounding grid, increasing the amount of potential difference from centre of mesh to grounding
grounding material can effectively decline grounding electrode, and step potential. For instance, there are
contact potential, especially to step potential. As show cases, in foreign countries where the operation
in chart 4, it demonstrates the reflection of contact and platform is made from 0.6m * 0.6m (1) metal mesh.
step potential to horizontal grounding material However, it is not economic wise to solve the
quantity. Mainly because of the additional grounding excessive contact and step potential issues by
material, especially by increasing horizontal adopting excessive grounding material. Reasonable
grounding electrode, not only reduced mesh spacing use of grounding material and control project cost are
of ground grid, the ground surface potential must be considered in design.
distribution became more even, but also solved the

is more than 6~7 times (4). Take GW substation for


In summary, by measuring grounding grid of existing instance, its earth potential is 28.7kV, which is 14.3
electric power plants and substation, also including times of standard 2kV. For those electric power
new designed grounding grid, the actual measurement plants and substations located in high soil resistivity
results of earth, contact and step potentials from area, it is also not cost effective and realistic by
majority substations are beyond standard. In some decreasing earth potential to standard. It is a huge
cases, there are few substations are above standard challenge in ground designing to achieve a reasonable
earth potential limit by 10 times, and contact potential safe ground grid when the high potential exists.

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 6
Gaoyuan, LIANG Year 2010

3. Complete ground grid design insulated frames can be applied in real scenarios. If
measurement the ground grid is located within the fences, it is
necessary to set isolation area out side of the fences
By applying essential measurements to reduce and displaying electric danger sign to minimize
resistance, the earth potential still cannot be reduced potential electric hazard to staff. If the ground grid is
to the standard requirement. Grounding grid design beyond fences, the step potential must satisfy the
should be focused on dealing with voltage equalizer safety standard.
and isolation, especially on the particular area on
ground grid. 3.3 Control cable grounding issue
It is important to strengthen the control of cable
grounding to prevent counterattack damage to the
3.1 Voltage equavalent issue on ground grid
cable and secondary equipment. If the cable is not
edge very long, grounding one end of cable jacket can
reduce current outside of the single-conductor cable.
Theoretically, electric power plants and substations
For a long cable, both sides and the skin of the joint
are designed on the basis of uniformed soil resistivity. all should be grounded. To eliminate the EMF, both
ends of shielding control cables should be grounded.
Actually, soil resistivity is not equivalent either
The control cable jacket spacing may be too large at
horizontally or vertically. According to DL/T621-1997 each grounding point, which will cause large current
flows through cable jacket when earth fault potential
standard, it is difficult for the non-equalizing treated
happened. To avoid current damage, the best solution
ground grid to meet contact and step potential is installing a separate ground cable on cable jacket
where between grounding point and parallel to the
requirement even if the earth potential is below 2000V.
control cable.
In the case of GW substation, step potential meets
requirement when soil resistivity dropped down to 3.4 Telecommunication cable grounding issue
34.8, however, the contact potential still needs to be It is important to isolate communication cable to avoid
the shift potential damage.
worked on by potential equalizing treatment. Since the Communication lines need to take into measurement
edge effect of earth current, there is a huge potential in design to ensure the safety of staff and
communication terminal devices. In order for the
gradient on the ground grid edge (1). The design substation communication terminal and remote
should be focused on dealing with the voltage terminal isolation, consider using fiber optic
communications cable, eliminating high potential of
equalize on grid edge. transfer.
To prevent potential difference over the standard, the
main measurements are: 3.5 Low voltage power supply line grounding
a) Increasing the density and depth along issue
It is critical to isolate low voltage neutral lines to
vertical electrode on ground grid edge
avoid the shift potential damage caused to residence
b) Burying two or more horizontal electrode
from high voltage substations. In substations or
around the edge. And the inbuilt electrodes
nearby, neutral lines should be treated as "charged"
should go deeper with the distance far away
conductor, and isolate neutral lines with substation
from substation, which is called the hat
grounding system by using insulator has a high
brim voltage potential area.
potential resistance. Meantime, the neutral wire
c) Changing the distance between horizontal
should be placed in a secure location to prevent staff
electrodes on grid. The density of horizontal
exposed to risks, isolate when necessary.
electrodes should be higher at where close
to the grid edge.
3.6 Metal pipes grounding issue
All kinds of metal pipes should be isolated to prevent
3.2 Metal frame grounding issue shifting potentials.
To prevent the possible earth potential damage caused Pipes and metallic conductors should be connected to
grounding systems to avoid internal hazard with
by metal frame around electric power plants and substations. To prevent the high potential spread out
substations, connecting frame to ground grid or using along metal pipes, isolation zone should be set around

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 7
Gaoyuan, LIANG Year 2010

fences near power plants and substations. Most among metals, therefore personnel hazard
importantly, the isolation zone has to be in great
distance to avoid nearby soil bypass. still obvious even the potential is small on
Isolation area must be able to withstand the potential GIS shell. It is the best solution to reduce
difference between a substation and nearby ground -
earth potential. touch potential and step potential hazard by
grounding multi-point of GIS shell.
4. Key factors of designing ground grid Working together with GIS manufacture to
inhighsoilresistivityarea find out the suitable grounding material size,
a) Metallic fences grounding connecting points and shell potential
In the event of earth fault grounding, there requirement, also the emphasis should be
is a higher potential gradient difference near focused on DC component, switch actions
fences around power plants and substations and maximum potential when earth fault
caused by edge effect of earth current. grounding happened and connect equal
Designers should be alerted that electric potential properly.
shock hazard still exists regardless of d) System capacity development
whether the fences connected to grounding System capacity should be designed by the
grid or not, particularly in high soil life cycle of power plants and substation (1)
resistivity area, it may be worse. rather than standard 5~10 years
b) Focusing on voltage equivalent on main development plan recommended by
building, auxiliary workshop, and coal DL/T621-1997. By studying cases, it has
transmission system in addition to booster been found that the follow-up supplement
station of power plants. and optimize are difficult and expensive.
Above areas are normally considered as e) Note the side effect caused by un-even soil
crucial parts in the design, it has created resistivity
touch and step potential hazard due to large Grounding grid design is based on the
mesh grounding. For example, a LNG condition of equivalent uniformed soil
power plant in Guangdong province, its resistivity. Due to the actual effect, the
earth potential value is 20.8kV, if decreasing designed ground grid is not safe, especially
it down to 20kV, the soil resistivity needs to in high soil resistivity area. Therefore,
drop from 791 m to 76 m . Under this followed by grounding grid construction,
circumstance, step potential could still meet measuring actual ground potential
safety standard even not laying horizontal distribution curve and eliminate unsafe
electrodes to equivalent potentials. However, elements to complete setting of grounding
if not paving high soil resistivity isolation grid.
layer, the required touch potential cannot be
meet even expending mesh distance up to 5. Conclusion
1m. When the earth potential is 20.8kV, it is a) With increasing capacity of the power

required to set a 37m mesh distance on system and decreasing floor area of power

grounding grid to meet step potential plants and transformer substation network, it

requirement. Therefore, isolation is a great challenge to design grounding

measurements should to take into account to grids in high resistivity area and it requires

prevent grounding when staff operation designers to be more careful.


b) The lower earth resistance does not mean a
devices.
safe ground grid, and ground grid resistance
c) GIS grounding is not the direct unsafe cause to personnel
and device. Theoretically, no matter how
As GIS could easily cause touch potential
much ground grid resistance is, a careful

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 8
Gaoyuan, LIANG Year 2010

designed ground grid will be very safe. On 4. Yang Ziyi, 2000, The Comprehensive
the other hand, although the ground network
resistance is low, potential hazard elements Analysis Of Current Substation Grounding
are not considered in design, it is very much Design
insecure with a grounding grid without
eliminate excessively high touch potential, 5. IEEE Guide for Generating Station
step potential, transfer potential. Grounding IEEE Std665-1995.
c) To stop 2~10kv system valve type arrester

actions, methods can be adopted by
decreasing resistance, distribute current and
earth level.
d) Besides decreasing grounding grid
resistance to lower the earth level, it is much
easier to increase shunt coefficient of
overhead arrester wire to decrease
grounding current.
e) To decrease step potential, there are few
methods can be adopted such as increasing
quantity of horizontal electrodes or
designing a suitable mesh size to meet
requirements. Distributing the unequal
layout of mesh can greatly reduce the cost
of ground grid design.
f) In order to limit step potential and not using
excessive horizontal electrode, the
alternative solutions are laying wood
floorboard on operation platform, paving
asphalt and gravel mixture to isolate
platform or using metal ground platform.
g) In power plant ground grids design, it is
important to take full advantage of existing
building foundations, underground water
pipes to connect equal potential and
eliminate dangerous potentials in entire
power plant ground grid.

Bibliography
1. IEEE Guide for Safety in AC Substation
Grounding IEEE Std80-2000
2. DL/T 621-1997 AC Electric Devices
Grounding
3. Electric Engineering Design Manual
(Electrical Transmission Circuit), BeiJing,
1989, Water Resources and Electric Power
Press.

Grounding Design of Electric Power Plants and Transformer Substations in High Soil Resistivity Area 9

Вам также может понравиться