Вы находитесь на странице: 1из 13

2330 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO.

6, NOVEMBER/DECEMBER 2011

A Novel Method of Measuring Inherent Power


System Charging Current
Dev Paul, Senior Member, IEEE, Peter E. Sutherland, Fellow, IEEE, and
Sergio A. R. Panetta, Senior Member, IEEE

AbstractHigh-resistance grounded (HRG) power systems damage. Before recent concerns of arc hazards in the indus-
have been used in many industries to minimize equipment damage, try, HRG power systems have been used in many industries,
including but not limited to mining, petrochemicals, shore-to-ship including but not limited to mining, petrochemicals, and shore-
power supplies, and many others. The system charging current
value should be known for designing an HRG power system. One to-ship power supplies, to minimize equipment damage. Upon
method of determining the system charging current is to perform detection of a ground fault on the HRG low-voltage (LV) power
engineering calculations involving the inherent capacitance to systems, with relatively low system charging currents, an alarm
ground for each of the power system components. However, this or an orderly shutdown of the power system is commonly used.
method may not provide accurate data as the sneak capacitance This paper provides a discussion of the lineground arcing fault
to ground for power system components cannot be determined
due to their installation configuration. Therefore, it is essential to and associated damage and supports the conclusion that, for
have a reliable method of measuring the system charging current. a medium-voltage (MV) HRG power system, the fault should
Before describing the proposed method of measuring the sys- be cleared immediately upon occurrence of a line-to-ground
tem charging current, fundamental concepts of system charging fault, particularly when the system charging current is 5.5 A
current and its mathematical analysis are provided. In addition, for system voltages of 4.16 kV and above [2]. Higher system
power system arcing faults and the associated damage when a
fault remains lineground faulted, particularly in the case of a charging current may be due to an extended power system or
medium-voltage power system, are included. Finally, a novel and a relatively longer parallel feeder cable system, which may
suitable method of measuring the inherent power system charging result in additional damage if not tripped immediately upon
current is presented. sensing the line-to-ground fault. A combination of modern mi-
Index TermsArc hazard, capacitance to ground, charging croprocess relays with appropriate current transformers (CTs)
current, current transformer (CT), grounded power system, high- can provide adequate ground fault protection for an HRG power
resistance grounded (HRG), ungrounded power system. system.
For designing an HRG power system, the system charging
I. I NTRODUCTION current that affects the neutral resistor rating should be known.
This paper suggests using a neutral resistor sized based upon
E LECTRICAL arc hazards and their associated effects on
equipment damage are unpredictable. An arc may occur
when equipment insulation between phase to phase and/or
the calculated system charging current [9] and then suggests
performing measurements so that the sneak (unknown) capaci-
phase to ground fails. The intensity of the arc damage is related tance to ground is included in the measurements. In the case of
to the fault current magnitude at insulation failure location. cold-ironing projects [4][6], ship capacitance may be defined
Power system fault statistics indicate that close to 75% of all as sneak capacitance as the ship authority will not provide such
faults involve ground [1], [2]. Therefore, making the ground data needed for designing an HRG system at MV.
fault current low by using the high-resistance grounded (HRG) First, this paper provides a discussion of system charging
power system can minimize the damage at the fault location as current for an ungrounded and an HRG system. Then, an
long as the fault is cleared by appropriate protection devices analysis of arcing fault damage for an HRG system is included.
before it becomes a three-phase fault, which may cause more Last, this paper provides various methods of measuring system
charging current for both types of systems: 1) systems where a
neutral point is available, such as a wye-connected system, and
2) systems where a neutral point is not available, such as delta-
connected systems, where the neutral point is created by use of
Manuscript received January 28, 2011; revised May 19, 2011; accepted
June 26, 2011. Date of publication September 19, 2011; date of current the grounding equipment [2], [3].
version November 18, 2011. Paper 2010-PSEC-552.R1, presented at the 2011
IEEE/IAS Industrial and Commercial Power Systems Technical Conference,
Newport Beach, CA, May 15, and approved for publication in the IEEE II. U NGROUNDED P OWER S YSTEM
TRANSACTIONS ON INDUSTRY APPLICATIONS by the Power System Engi-
neering Committee of the IEEE Industry Applications Society. In an ungrounded power system, either there is no intentional
D. Paul is with AECOM, Oakland, CA 94612 USA (e-mail: dev.paul@
aecom.com). connection of neutral to ground or the neutral point is not avail-
P. E. Sutherland is with GE Energy Services, Schenectady, NY 12306 USA able for grounding purposes. Such a power system is coupled
(e-mail: peter.sutherland@ge.com). to ground by the uniformly distributed inherent capacitance
S. A. R. Panetta is with I-GARD Corporation, Mississauga, ON L5S 1A8
Canada (e-mail: spanetta@i-gard.com). of each phase to ground. In general, this distributed inherent
Digital Object Identifier 10.1109/TIA.2011.2168510 capacitance (C) of each phase to ground is equal in magnitude,

0093-9994/$26.00 2011 IEEE


PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2331

where ICO is shown in (1) and can be written as follows:

ICO = ELN /XCO . (3)

A bolted line-to-ground fault current equal to the total system


charging current discussed here does not seem to pose any
damage to the system; however, such bolted lineground faults
on an ungrounded power system are susceptible to turn into
intermittent low-current arcing faults which have been proven
to be damaging to a power system as a result of transient over-
voltage ranging from 5 to 6 per unit (p.u.) of the system voltage
in short time. See [2, Fig. 317]. These transient overvoltages
are dangerous to equipment insulation, and for this reason,
ungrounded power systems are not used in industrial power
systems [18].

III. R ESISTANCE G ROUNDED P OWER S YSTEM


A zero-sequence equivalent circuit of a resistance grounded
power system with a neutral resistor RN is shown in Fig. 3. This
Fig. 1. (a) Ungrounded power system voltage and inherent capacitive current
vector diagramPower system phase sequence clockwise. (b) Power system
is based upon the assumption that all other impedance values
inherent capacitive current vector diagram. of the power system components are small compared to XCO ,
which is a valid assumption for industrial and commercial
power systems, particularly for a resistance grounded power
and the corresponding reactance is generally represented as system.
XCO . Thus, for a 60-Hz power system, the value of XCO in From Fig. 3, zero-sequence current (IO ) is represented as
ohms will be (1/j260C), where C is in farads.
The system charging current of an ungrounded power system I0 = ELN / [1/ {(3RN XCO )/(3RN + XCO )}] .
without any ground fault is shown in Fig. 1(a). This system
charging current can be detected by a zero-sequence CT on Lineground bolted fault (IF ) is 3IO as represented in the
the main circuit breaker at the time of closing the breaker. This following:
CT should be a high-accuracy class or digital clamp on type CT
with a digital recorder. Once the system is energized, this CT 3I0 = 3ELN [(1/XCO +1/3RN )] = 3(ICO +IRO ) = IC +IR .
will not be able to measure the system charging current even if
a lineground fault occurs. Therefore, zero-sequence resistance of the system (RO ) can
Under the normal power system condition, the system charg- be considered as 3RN . Vector addition of two fault current
ing current from each phase to ground represented by (1) components IR and IC at 90 phase angle will have ground
is shown in Fig. 1(a), and their vector addition is shown in fault IF from faulted phase to ground represented by the
Fig. 1(b). See [2, Fig. 3.5] for additional clarifications expression
 2 2

IF = IC + IR .
IAC = IBC = ICC = ICO = j wCELN (in amperes) (1)
Current IR will flow from faulted phase to ground and then to
where system via (RN ), whereas current (IC ) will flow from the two
ELN lineneutral system voltage, in volts; unfaulted phase capacitances to ground and then from ground
C line-to-ground capacitance of each phase, in farads; to system via faulted phase.
w 377 (2f ) in the case of 60-Hz frequency. A line-to-ground fault on an ungrounded power system
For a bolted line-to-ground fault on phase A, the vector shown in Fig. 2 can be considered a special case of the resis-
diagram of the power system phase voltages and currents is tance grounded power system shown in Fig. 3 where resistor
shown in Fig. 2. A ground fault current equal to the total system RN will be of infinite value. The fault current for ungrounded
charging current will flow from the unfaulted phases to ground, power system will then simply be the total system charging
as their voltages with
respect to ground will become line-to-line current IC (3ICO ) which matches the results indicated in (2)
voltage, which is 3 times the normal line-to-neutral voltage, from a vector diagram.
and will return to the system by the faulted phase. It is not the bolted lineground fault that is damaging but
From Fig. 2, the total system charging current (IC ) flowing a low-level intermittent arcing ground fault with variable arc
through the faulted phase A back to the system can be repre- fault impedance which is difficult to detect but dangerous and
sented by (2). See [2, Fig. 3.6] for additional clarifications damaging in both LV and MV systems. We will discuss a
lineground arcing fault with fault impedance in the following
IC = 2 3j w C ELN cos(30) = 3 ICO (2) section.
2332 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

Fig. 2. Ungrounded power system voltages and currents during phase A to ground bolted fault.

Fig. 3. Zero-sequence circuit diagram for a bolted phase-to-ground fault on a


resistance grounded power system.

Fig. 4. HRG power systemBolted ground fault on phase A.


Fig. 5. Voltage vector diagram for arcing faults on phase A.
A. HRG Power System
fault condition, the current flowing through the resistor IR can
Depending upon the value of RN which controls the resistive be made equal to IC by sizing resistor RN based upon the
component of the line-to-ground fault current, the system will estimated value of IC . The current (IR ) will be in phase with
be considered an HRG power system when IR IC (the ratio neutral-to-ground voltage, which will be at 90 to the current
of IR /IC is between 1 and 1.25) or a low-resistance grounded IC that flows from the power system through the healthy phase
(LRG) power system where IR is much higher than IC and capacitances to ground. Thus, these two currents,
equal in mag-
there is very little effect of system charging current on the nitude and 90 apart, will have the vector sum of 2 times IC .
line-to-ground fault current. For example, for a 400-A LRG
power system with a system charging current of 7 A, a bolted
B. HRG Power System20% Arcing Fault on Phase A
lineground fault will be 400.06 A.
The lineground fault current (IF ) shown in Fig. 4 will have Fig. 5 shows the phase voltage vector diagram for the 20%
two components: the resistive current (IR ) and capacitive cur- and 80% arcing faults on phase A on an HRG power system. It
rent (IC ) as the system neutral is connected to ground through is assumed that a 20% arcing fault on A phase shifts point A
a resistor. For an HRG system, under a bolted phaseground away from the ground at point Y. During such an arcing fault,
PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2333

Fig. 6. (a) Power system voltages during 20% resistive arcing fault. (b) Three-phase capacitive currents during 20% resistive arcing fault. (c) Fault current during
20% resistive arcing fault.

the voltage of phase A with respect to ground may change from Next, to determine the IR and IC components of the fault
zero (bolted fault) to 20% of the line-to-neutral voltage, i.e., current IF during arcing faults, Fig. 6(b) and (c) is included.
point A may jump between point Y and point G, as shown Fig. 6(b) shows all three-phase capacitive currents and resistive
in Fig. 5. Fig. 6(a) further clarifies the power system voltage currents, whereas Fig. 6(c) shows both the resistive and total
configuration changes during such an arcing fault. capacitive components of the fault current, including the total
2334 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

fault current. This analysis is based upon the assumption that prudent to set design criterion that fault current component
this 20% resistive arcing fault is stationary and will not develop IR , which may be as high as 67%, is higher than IC during
dangerous transient overvoltage, considering that the condition bolted line-to-ground fault. Using this criterion, then during the
that IR is greater than or equal to IC is maintained. This 80% arcing fault, IR will become equal to ICO . This can be
relationship of IR equal to IC is represented by (4) and (5) and illustrated by modifying (6) into (8) as follows:
shown in Fig. 6(c).
This 20% arcing fault condition illustrates that the HRG IR = 0.2 p.u. = 1.67 0.6 ICO = 1.002 ICO . (8)
system criterion is maintained, i.e., IR IC , if we select the
resistor for a bolted fault condition with IR slightly higher than IV. HRG P OWER S YSTEM DAMAGE AT FAULT L OCATION
IC . It is the authors opinion that many engineers have been
designing a neutral resistor for HRG power systems by using It has been proven that, if the HRG power system is grounded
IR to be 1.25IC as a rule of thumb to avoid dangerous over- through a resistor such that, during bolted line-to-ground fault,
voltage during arcing faults. Equations (4) and (5) are derived IR IC , then a 60-Hz transient overvoltage on the power
using vector diagrams shown in Figs. 5 and 6(a). From these system will not exceed more than 2.6 p.u.of the system voltage,
equations, it is concluded that the displacement of A and G with where the p.u. peak system voltage is 2/3 ELL ; see [15,
respect to neutral for a 20% arcing fault will keep IR > IC and Fig. 2]. It should be noted that, during lineground fault tests
thus will not lead to dangerous transient overvoltage conditions on an HRG generator rated at 27 kV, transient current up to
2.31 kA at 8.7 kHz was observed, indicating peaks of high
IR = 0.8 p.u. = 0.8 3 ICO = 2.4 ICO (4) frequency transient currents at the fault location; however, p.u.
voltage on the healthy phases was close to 2.37 p.u. [16]. Many
where p.u. is the p.u. value 1 for IR under a bolted HRG generators use a distribution transformer with a secondary
lineground fault condition, which is 3ICO if the HRG system resistor or resonant grounded system instead of a resistance
is designed based upon the criterion of IR equal to IC . Using grounded system [17]. A detailed discussion of such HRG
the data shown in Fig. 6(a), the reduced value of IC in the case generator systems is beyond the scope of this paper [15][18].
of 20% arcing fault is as follows: It should be stated that, for an HRG power system, the damage
at the fault location is described by (9), which is used for the
tan() = 0.866/(0.5 + 0.8) = 0.866/1.3 = 0.666
heat produced by the flow of current through a resistor
Length Y B = 0.8662 + 1.32 = 1.562 
= tan (0.666) = 33.67 Damage = IF2 (t)RF dt (in watt seconds or joules) (9)
IC = [2 cos() 1.562 0.2] ICO = 2.4 ICO . (5)

In this 20% arcing fault, the fault current component IR where the current (IF ), fault resistance (RF ), and fault clearing
becomes 80% of the IR value for a bolted ground fault, and time (t) are in amperes, ohms, and seconds, respectively.
the total capacitive component IC is also reduced to 80% of To avoid performing integration which has been used to
the total system charging current during the bolted ground fault represent higher current at the instant of fault (t+) and then
condition. decreasing magnitude over time t, we can rewrite (9) as follows:

Damage = IF2 RF t (in watt seconds or joules) (10)


C. HRG Power System80% Arcing Fault on Phase A
where IF is now steady rms current in amperes instead of a
The phase voltage and current vector diagrams for an 80%
time-varying current.
arcing fault to ground on phase A are shown in Fig. 7(a)(c).
Arc voltage drop (EARC ) will be IF RF . This is one concept
The IR and IC components of the fault current for 80% arcing
of understanding that the arc voltage has a linear relationship
fault condition are represented by (6) and (7). Both (6) and (7)
between the arc current and arc resistance. Much research is un-
are derived using Figs. 5 and 7(a)
derway to understand the behavior of the arc, arc voltage drop,
IR = 0.2 p.u. = 0.2 3 ICO = 0.6 ICO (6) and arc resistance. The purpose of this paper is to understand
tan() = 0.866/(0.5 + 0.2) = 0.866/0.7 = 1.2371 the heat generated by the arcing fault at the fault location and
not to establish that this is the only way to represent the arcing
Length XB = (0.8662 + 0.72 ) = 1.1136
fault and arc voltage drop. The heat generated at the arc may be
= tan (1.2371) = 51.049
represented by the modification of (10) to (11) using arc voltage
IC = [2 cos() 1.1136 0.8] ICO = 0.599 ICO . drop as follows:
(7)
Damage = EARC IF t (in watt seconds or joules). (11)
From (6) and (7), for an 80% resistive arcing fault condition,
IR is equal to IC but reduced to 20% magnitude which is Therefore, for a theoretical bolted fault condition with a zero
the same as that during bolted lineground fault and will not fault resistance, (9)(11) represent practically zero damage at
develop dangerous transient overvoltage on the system. The fault location (although there may be a trace of discoloring on
aforementioned analysis proves that both IR and IC decrease the enclosure at the fault location). All of the energy of the fault
equally when we consider arcing faults varying from 20% to will dissipate as heat inside the neutral resistor. This conclusion
80% arcing fault conditions. For an HRG power system, it is is based upon the theory that the fault remains a line-to-ground
PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2335

Fig. 7. (a) Power system voltages during 80% resistive arcing fault. (b) Three-phase capacitive current during 80% resistive arcing fault. (c) Fault current during
80% resistive arcing fault.

fault. Under actual fault conditions, however, it is uncertain left grounded by a bolted grounding jumper. This suggests that
whether there are bolted line-to-ground faults. An exception there will be some fault impedance and some damage at the
to this occurs where the system is energized with one phase fault location under an actual bolted line-to-ground fault.
2336 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

TABLE I Using (14), for a bolted fault condition and for a 20% arcing
A RCING FAULT DAMAGE IN p.u. ON AN HRG P OWER S YSTEM D ESIGNED
U SING IR = 1.67IC C RITERION , I NSTEAD OF U SING IR = IC OR fault condition, the total heat will be 23.86 and 19.94 kJ,
IR = 1.25IC C RITERION respectively. The same results can be obtained by applying
a multiplication factor of 14.28975 (0.15 15 11/ 3) to
the p.u. values indicated in column C7 of Table I. The same
multiplication factor can provide results to any of the values in
columns C5 and C6. The damage at the fault location seems
to be the highest for a 50% arcing fault, as seen in Table I,
column C5. These theoretical data need validation by actual
test data.
The fault energy versus the fault damage at the fault location
in terms of such effects as spit marks, smoke marks, puncture
For analysis purposes on MV arcing lineground faults with insulation, etc., is described in [14] and may be used with actual
resistive arc, we will consider arc voltage drop from 20% to calculated energy at the fault locations using Table I. It should
80% of the system voltage [12], [13]. The resistive arcing faults be stated that the results in Table I are based upon the stationary
at both of these extremes, i.e., 20% and 80%, were discussed faults (i.e., persistent arc fault current at the system frequency).
at length earlier. It is uncertain whether only the resistive arc Some new insights on test results on intermittent line-to-
is the actual arcing fault condition or if, instead, it may just ground fault current in the generator stator windings seem to
be one specific arcing fault condition. We discussed the HRG contain some high frequency current [16]. Practical knowledge
power system to reduce line-to-ground fault current but are still of such intermittent arcing fault energy in the case of HRG
uncertain about the transient overvoltage due to power system system requires further research and is beyond the scope of
dynamics as well as the system charging current interacting this paper.
with certain system inductance during arcing ground faults. The following questions will aid in selecting the proper RN
For every ground fault condition, if we trip the power system value and setting the ground fault relay pickup in the case of an
without any intentional time delay, then the risk of damage HRG power system.
due to arcing ground faults and faults involving other phases
1) For the selected value of RN based upon the system
is reduced.
charging current IC , do we expect transient overvoltage
For an HRG power system, under the arcing fault conditions
condition during the arcing ground fault condition? The
discussed, we noticed reduction in both components IR and IC
answer is no, if we select RN based upon the criterion
and the fault current IF . The total fault energy (damage at fault
of designing HRG system where IR IC for a bolted
location) may be estimated by any of (9)(11). Similarly, the
lineground fault condition.
heat generated inside the neutral resistor can be estimated by
2) For an HRG power system designed based upon the
(9) or (10).
criterion of IR = IC during bolted lineground fault and
Using the criterion of IR equal to 1.67 IC during bolted line-
having IC of 10 A, it is noted that the fault current may
to-ground fault condition, the resistor RN value can be derived
vary anywhere from 14.2 to 2.84 A, whereas the neutral
as follows:
ground relay will see the change of current from 10 A in
IR = 1.67 IC = ELN /RN (12) the case of a bolted fault to 2.0 A in the case of an 80%
RN = ELN /1.67 IC . (13) arcing fault. This example indicates that the ground fault
relay should be sensitive and its pickup should be set at
Using RN derived by (13), Table I provides fault damage and 20% of the maximum expected bolted phase-to-ground
heat developed inside the neutral resistor in p.u. for varying re- fault current without any time delays for the MV power
sistive arc voltage drop EARC . This EARC is shown in Table I, system.
column C1. The reduced current through RN during arcing
faults will become [(ELN EARC )/ELN ] (IR ), where IR V. P OWER S YSTEM C HARGING
is the current under the bolted line-to-ground fault condition. C URRENT M EASURING M ETHODS
This reduced IR is shown in column C2. The corresponding
reduced IC is shown in column C3, and the fault current is Methods 1 and 2 have been described in the published
shown in column C4. Columns C5 and C6 indicate the heat literature but may not be suitable as discussed hereinafter.
developed at the fault location and inside the RN , respectively. Method 1Use an Isolated Variable 120-V Power Source
The column C7 value is the sum of values indicated in columns at the Power System Transformer Neutral [1]: This method
C5 and C6. is based upon the concept that, under an energized system,
Assuming that we have an 11.0-kV power system with a the system charging current may be obtained if the system
system charging current of 15 A and the ground fault clearing neutral is offset from the ground by injecting LV from an
time is 0.15 s, then the total heat generated may be calculated ungrounded power source, as shown in Fig. 8(a). Fig. 8(b)
using the following: shows an electrical equivalent circuit of the injected variable
voltage at the system neutral to facilitate recording of corre-
T otal Heat = (EARC ) (IF )(t) + (ELN EARC ) (IR )(t). sponding variable current through the parallel capacitances of
(14) the three phases. When a graph, as shown in Fig. 8(c), indicates
PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2337

Fig. 8. (a) Use isolated variable voltage at the power system neutral. (b) Equivalent electrical circuit of (a). (c) Derivation of (k) which is (XCO /3).

that the ratio k has become constant, then it represents that both the LV and MV as the injected voltage need not be high
the injected voltage has displaced system neutral away from but of sufficient magnitude to reach the level of developing
ground and current flow through the parallel capacitances has a linear relationship between voltage and current. Since the
reached its maximum value to represent the effect of parallel phase angle relationship of this injected voltage to any of the
capacitance to ground. This ratio k then represents the total system phase-to-neutral voltage is not known, thus, to avoid
system capacitance reactance (XCO /3), which is one-third the system overvoltage conditions, the injected voltage should not
line-to-ground capacitance reactance XCO of each phase. This exceed 25% of the lineneutral system voltage, particularly
capacitance reactance value then will be used to derive the in the case of LV systems [2]. This testing can be achieved
system charging current by using (15). by keeping the fused load-interrupter switch in Fig. 8(a) in
This method requires that the entire power system be ener- an open position initially. There should be no voltage in the
gized by closing the secondary breaker and 120 V be injected measuring circuit when the fused load-interrupter switch is
by an ungrounded power source. This method can be used for closed, which can be achieved by keeping the autotransformer
2338 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

Fig. 9. Ungrounded power system, use a variable resistor to ground one phase.

initially at zero secondary voltage. Then, the voltage can be conditions, a loading resistor on potential transformer (PT)
gradually increased by carefully moving the potentiometer and secondary was used [12], [13].
keeping note of the applied voltage and current flow through the Method 2Use a Bolted Connection of One Phase to Ground
circuit until the ratio of voltage to current becomes constant, With a Variable Resistor: This method appears to work in
as shown in the graph in Fig. 8(c). The constant k deter- theory, as shown in Fig. 2 and (2), particularly for LV systems.
mined from this graph then can provide the system charging To simulate this condition, the equipment shown in Fig. 9 is
current by suggested. As the system is ungrounded, this method may pose
danger to both the equipment and the personnel involved in
testing, as the resistor needs to change gradually until there
IC = ELN /k = 3(ELN /XCO ) = 3ICO . (15)
is no resistance in the circuit. Dangerous transient overvoltage
may occur as the power system is ungrounded [3], particularly
This method requires several recordings of both the voltages in the case of MV systems with higher system charging current
and currents to determine the linear relationship between the and higher voltage. Perhaps, to minimize such transient over-
two, which may pose danger to the LV equipment in the voltages, [2, Section 3.52] describes the total resistor rating to
presence of MV system as the system is fully energized. This be 2 (XCO /3) rated at 60 s for a 2.4-kV system. Additional
method has been used in actual measurements [1], [2]; however, analysis is required to assure that testing is safe, particularly
why this test voltage must be less than exactly 25% system when the effect of sequential reduction of resistors on arcing
lineneutral voltage indicated in [2] cannot be explained in during testing is not known. Although, in [10], this method was
this paper. The authors were also able to contact Baldwin used on 2.4 kV, the authors think that such a method should not
Bridger [1] before the paper presentation at the conference. be used without further analysis of the complete power system
Baldy reviewed the paper with great interest and indicated this for higher voltage systems with high system charging cur-
method as a scientific wild guess. rents such as on cold-ironing projects requiring 6.6- or 11-kV
A similar method was used on a 13.8-kV power distribution voltages.
system with the addition of a single-phase transformer to the Method 3Bolted Connection of One Phase to Ground
autotransformer shown in Fig. 8(a) and a neutral grounding With a Fixed Resistor and a Contactor to Short the Resistor
resistor (NGR) to simulate an injected voltage of 8 kV to match Remotely: This method has some improvements over Method
with system lineneutral voltage. Since the NGR was included 2, as the remote operation of the switching device, such as a
in the circuit, the precaution of injected voltage not to exceed contactor rated for the line-to-line system voltage, can short-
25% was not a concern; however, to avoid ferroresonance circuit the resistor quickly to simulate bolted line-to-ground
PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2339

Fig. 10. Ungrounded power system with a fixed resistor and a contactor to short the resistor from remote.

fault to make a direct recording of the system charging current, value of these readings will provide the total system charging
as shown in Fig. 10. Problems discussed for Method 2 still current.
apply to this method. The effects of the dynamic nature of the Fig. 12 shows a system charging current recorder consisting
power system and its voltage swings at the instant of performing of a microprocessor unit to be developed based upon the
test are unclear and may pose danger during testing. criteria of (16). This new smart portable unit will consist of
Method 4Use an NGR With Appropriate Taps and Equip- a minimum of two low-pass filters, analog-to-digital converter,
ment for Making a Bolted Ground Fault on a Phase: This programmable logic controller, storage, dc power supplies, dig-
method provides the assurance of not having dangerous tran- ital display, and an ON/OFF feature; see Fig. 13 for schematics
sient overvoltage as measurements are conducted on a grounded of these internal components.
power system. Using high-accuracy current sensors, measure- Method 5Ungrounded Delta-Connected Power System
ments of the fault current IF through the grounded phase and Without a Power System Neutral Requiring HRG Grounding
the fault current IR through the NGR circuit, as shown in Equipment [7]: There are two alternative schemes to provide a
Fig. 11, are needed. The total system charging current IC then derived neutral for grounding purposes [2], [6], [8]. Method 5A
can be obtained by using listed in Table II is to use three single-phase transformers rated
at lineline primary and 120-V secondary with connections
 2 
IC = IF IR
2
. (16) as shown in Fig. 14. The size of resistor R is based upon
an estimation of IC and using the criterion IR IC during
Take three sets of readings by changing the resistor tap: Tap bolted lineground fault. The resistor R should have taps which
1 (IF 1 , IR1 ), Tap 2 (IF 2 , IR2 ), and Tap 3 (IF 3 , IR3 ). For safety will meet the criterion of IR IC for a bolted lineground
reasons, the entire power system should be de-energized, the ca- fault. By using a variable voltage source on the secondary,
ble capacitance should be discharged after taking measurements change the voltage, and when the voltage is close to 200 V
at the first tap, and then the system should be re-energized to (3 times the rated secondary voltage of the single phase trans-
take measurements at different resistor taps. The average of the formers), and the resistor tap is set at IR = IC , then the
three values will provide system charging current. system charging current will be the measured primary current.
The resistor taps should provide IR greater than IC at each Power system dynamic swings at the instant of performing
tap to avoid the concern of transient overvoltage. If a particular measurements and coupling of variable voltage to the system
power system is expected to have unequal system capacitance voltage are a concern. For safety reasons explained in Method 1,
to ground due to its installation configuration, then tests may in Method 5A, an injected voltage should not exceed 25%
be performed on each phase. This will provide a total of of the lineneutral rated voltage of the equipment set that
either three or nine readings depending upon performing either makes driving neutral. Method 5B listed in Table II is to use
one or three measurements on each phase, and the average a zigzag transformer [8], [10] with a suitable tapped resistor
2340 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

Fig. 11. NGR with appropriate taps and a fixed resistor and a contactor to short the resistor from remote.

upon the authors opinion that several readings of voltages and


currents are required to make the time duration of the test
longer, during which time the dynamic nature of the power
system may interfere with the test setup.

VI. C ONCLUSION AND R ECOMMENDATIONS


The following conclusions and recommendations can be
drawn for this paper.
1) Resistive arcing faults in an HRG power system and the
associated damage are discussed. Analysis indicates that
both IR and IC decrease equally in magnitude and the
Fig. 12. Power system charging current recorder.
design criterion of an HRG method, i.e., IR IC , is
at the neutral meeting the HRG criterion IR IC . Then, the maintained during arcing faults if NGR is selected based
measurements can be performed similar to the one described for upon the criterion of IR IC under a bolted line-to-
Method 4. ground fault condition.
Based upon the merits listed in Table II, Method 4 for the 2) For a quick estimation of fault damage during arcing
wye-connected power systems, including derived neutral sys- faults, this paper includes a table for an HRG power
tems, and Method 5B (using a zigzag transformer) for the delta- system designed using IR = 1.67IC criterion. This table
connected systems are recommended. Methods 2 and 3 may can be modified to suit any criteria such as IR = IC
endanger the power system itself due to transient overvoltages or IR = 1.25IC for estimation of damage during arcing
and possible ferroresonance conditions unless proper analysis fault.
is conducted in determining resistor values needed in the circuit 3) MV HRG power systems [4][6] should use a combina-
[2] to consider this a safe method for MV systems. Methods 1 tion of a sensitive microprocessor ground fault relay and a
and 5A may pose danger due to coupling of injected voltage high-accuracy low-ratio CT with a pickup setting of 20%
with power system voltages unless the injected voltage is kept of IR without any time delay. This may lead to minimum
less than 25% of the lineneutral system voltage. It is based damage at a fault location based upon the assumption that
PAUL et al.: A NOVEL METHOD OF MEASURING INHERENT POWER SYSTEM CHARGING CURRENT 2341

Fig. 13. Internal components of a system charging current recorder.

TABLE II
C OMPARISON OF VARIOUS M ETHODS OF M EASURING
S YSTEM C HARGING C URRENT

the tripping of the power system occurred when the fault


remained line-to-ground fault.
4) From the arcing fault discussion of an HRG power sys-
tem, it is clear that the damage is directly proportional to Fig. 14. Delta-connected power system charging current.
the system voltage (ELN ), the fault current (IF ), and
the fault clearing time (t). For a particular system, both higher system voltage, the fault clearing time should be
ELN and IC are fixed, and the IF also has a maximum as low as practical.
upper limit in the case of a bolted fault. Thus, the only 5) Designing HRG power systems based upon the criterion
parameter to minimize damage is to reduce the fault clear- of IR 1.25IC will accommodate future changes to
ing time (t). Hence, to minimize damage, particularly for a power system which may increase the total system
the MV systems with higher system charging current and charging, and NGR need not be changed. This paper has
2342 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 47, NO. 6, NOVEMBER/DECEMBER 2011

presented an analysis indicating that the fault damage [14] L. J. Kingrey, R. Painter, and A. S. Locker, Applying high resistance
may not necessarily increase with the slight increase of neutral grounding in medium voltage systems, in Proc. PCIC Conf.,
San Antonio, TX, pp. 3141.
NRG current rating which is higher than system charging [15] IEEE Guide for the Application of Neutral Grounding in Electric Utility
current, as it depends upon fault impedance. Maximum Systems, Part 11Grounding Synchronous Generator Systems, IEEE Std.
fault damage occurs when the fault resistance is such C62.92-1989, 1989.
[16] D. Braun and G. S. Koeppl, Intermittent line-to-ground faults in genera-
that voltage drop across the fault resistance is one-half tor stator windings and consequences on neutral grounding, IEEE Trans.
the system voltage, as shown in Table II. Probability Power Del., vol. 25, no. 2, pp. 876881, Apr. 2010.
[17] P. G. Brown, I. B. Johnson, and J. R. Stevenson, Generator neutral
and sensitivity analysis of NGR rating which is higher grounding: Some aspects of application for distribution transformer with
than the system charging current versus fault damage, secondary resistor and resonant types, IEEE Trans. Power App. Syst.,
taking into consideration the ground fault relay tripping vol. PAS-97, no. 3, pp. 683694, May 1978.
[18] IEEE Recommended Practices for Grounding of Industrial and Commer-
time affected by fault impedance, should be performed to cial Power Systems, IEEE Std. 142-2007, 2007.
optimize NGR current rating.
6) A new novel method of measuring system charging
without using variable voltage source while keeping the Dev Paul (M73SM90) received the M.S. degree
power grounded is considered safer, particularly for MV in electrical engineering from Punjab University,
Chandigarh, India, in 1971.
systems. Direct digital reading is possible with the de- In 1972, he joined Kaiser Engineers which went
velopment of a device based upon the concept shown in through merging with other design engineering com-
Fig. 13. panies, and it is currently AECOM, Oakland, CA. As
a Design Engineer, he worked on a variety of heavy
industrial, Department of Defense, and Department
of Energy facilities and commercial and electrified
ACKNOWLEDGMENT rapid transit projects. He is currently the Senior
Project Director with the Transportation Division,
The authors would like to thank B. Chavdarian with the Port AECOM, where he is responsible for electrical work related to cold-ironing
projects, airport projects, and ac/dc rail transit projects. He is the author of 20
of Long Beach, who requested to review the existing literature technical papers which have been published in American Public Transportation
for measuring the inherent system charging current of medium- Association (APTA) and IEEE conferences proceedings.
voltage power systems, which resulted in this paper. Mr. Paul was a recipient of the Ralph H. Lee Award from the IEEE for
his paper on dc power systems grounding in 2002. He is the Vice-Chair of
Draft IEEE/ISO/IEC Standard P1713 on shore power connections to ships
and the Chairperson of Draft IEEE Standard P1627, Standard for Grounding
R EFERENCES Practices for DC Electrification OCS Including Application of Lightning Surge
Arresters. He is an active member of many IEEE committees responsible for
[1] B. Bridger, High-resistance grounding, IEEE Trans. Ind. Appl., vol. upgrading color book series into mother books. In the past, he served as a Vice-
IA-19, no. 1, pp. 1521, Jan. 1983. Chair for the IEEE Industry Applications Society (IAS) Oakland Chapter.
[2] J. R. Dunki-Jacobs, F. J. Shields, and C. St. Pierre, Industrial Power
System Grounding Design Handbook. Schenectady, NY: Conrad St.
Pierre, 2007.
[3] D. D. Ship and F. J. Angelini, Characteristics of Different Power Systems Peter E. Sutherland (S77M79SM97F07) re-
Neutral Grounding Techniques: Fact & Fiction, in Conf. Rec. IEEE IAS ceived the A.S. degree in electrical engineering tech-
Annu. Meeting, 1988, vol. 2, pp. 15351544. nology and the B.S. degree in electrical engineering
[4] D. Paul and V. Haddadian, Shore-to-ship power supply system for a from The University of Maine, Orono, the M.Sc.E.
cruise ship, in Conf. Rec. IEEE IAS Annu. Meeting, Houston, TX, degree in electrical engineering from the University
Oct. 2009, pp. 17. of New Brunswick, Fredericton, NB, Canada, and
[5] D. Paul, P. R. Ben Chavdarian, and V. Haddadian, Cable-capacitance the Ph.D. degree in electric power engineering from
discharge time with and without the application of grounding device, in Rensselaer Polytechnic Institute, Troy, NY.
Proc. I&CPS Conf., Tallahassee, FL, May 2010, pp. 16. In 1987, he joined General Electric (GE) Com-
[6] D. Paul and B. Ben Chavdarian, Closer look at the grounding of cold pany, Schenectady, NY, where he held a variety of
ironing power system, in Proc. I&CPS Conf., May 2009, pp. 17. positions, such as Senior Engineer in the GE Power
[7] P. Sutherland and A. Mansoor, Conversion of ungrounded system to a Systems Energy Consulting Department. In 2001, he joined Super Power,
high-resistance grounded power system, in Proc. I&CPS Conf., Dear- Inc., Schenectady, where he worked on applications of superconductivity to
born, MI, May 2006, pp. 16. electric power systems. In 2003, he joined EPRI, Schenectady, as a Consulting
[8] E. R. Detjen and K. R. Shah, Grounding transformer applications and Engineer. Since 2005, he has been a Lead Power Systems Engineer with GE
associated protection schemes, IEEE Trans. Ind. Appl., vol. 28, no. 4, Energy Services, Schenectady. He is the author of numerous technical papers.
pp. 788796, Jul./Aug. 1992. Dr. Sutherland is a member of Phi Kappa Phi, Eta Kappa Nu, and Tau Beta
[9] D. S. Baker, Charging current data for guesswork-free design of high- Pi. He is a Registered Professional Engineer in Pennsylvania, New Jersey,
resistance grounded systems, IEEE Trans. Ind. Appl., vol. IA-15, no. 2, Maine, and New York and a Certified Energy Engineer. He is active in the IEEE
pp. 136140, Mar. 1974. Industry Applications Society and in the IEEE Schenectady Section.
[10] E. R. Detjen, Grounding transformer applications and associated pro-
tection schemes, IEEE Trans. Ind. Appl., vol. 24, no. 4, pp. 788796,
Jul./Aug. 1992.
[11] J. A. Demcko, S. K. Younger, R. G. Farmer, and M. W. Schultz, On-line Sergio A. R. Panetta (SM04) received the B.Eng.
measurement of auxiliary system capacitance to ground for grounding and M.Eng. degrees in electrical and electronics en-
resistor sizing, in Proc. Amer. Power Conf., 1991, vol. 53, no. 2, gineering from McMaster University, Hamilton, ON,
pp. 14431447. Canada, in 1983 and 1996, respectively.
[12] F. K. Fox and L. B. McClung, Ground fault tests on high resistance Since graduation, he has been employed in the
grounded 13.8 kV electrical distribution system of modern large chemical power and relay protection field. He is currently with
plant, Part1, IEEE Trans. Ind. Appl., vol. IA-10, no. 5, pp. 581600, I-GARD Corporation, Mississauga, ON.
Sep. 1974. Mr. Panetta is a member of the Association of
[13] L. B. McClung and B. W. Whittington, Ground fault tests on high resis- Professional Engineers of Ontario. He is active in
tance grounded 13.8 kV electrical distribution system of modern large several committees for Under Laborites, compliance
chemical plant, Part11, IEEE Trans. Ind. Appl., vol. IA-10, no. 5, safety appliance, IEEE, and International Electro-
pp. 601617, Sep. 1974. technical Commission (IEC).

Вам также может понравиться