Академический Документы
Профессиональный Документы
Культура Документы
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
I. INTRODUCTION
This work was supported by National Natural Science Foundation of
China No. 51477184, and National High Technology Research Development
Program of China (863 program) No. 2014AA051901 and Science and
Technology Project of State Grid Corporation of China (52130416000D).
I n China and continental Europe, resonant grounding
systems exist in medium-voltage distribution networks. A
single-phase earth fault does not need to be cleared
Y. Xue, X. Chen and H. Song are with the College of Information and
Control Engineer, China University of Petroleum(East China), Qingdao immediately and can effectively improve the power supply
266580, China (e-mail: xueyd70@126.com, chenxiaoru1990@163.com, availability. However, the fault current is typically weak and
songhuamao814@126.com ).
B. Xu is with the College of Electrical and Electronic Engineering,
difficult to detect. Several new faulty feeder identification
Shandong University of Technology, Zibo 255049, China (e-mail: technologies have been developed in recent years. These
xuby@vip.163.com).1
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
technologies are based on fault transient electrical quantities influenced by the subjective factors. Thus, the algorithm must
and inserting resistance between neutral and the earth and be further improved. In this paper, a novel transient approach
effectively solve the low-impedance fault detection problem. for a resonant grounding system is proposed. The new method
However, because of the natural environment, low uses the projection of transient current with respect to
overhead line and other factors, single-phase high-impedance transient voltage to detect the HIF.
faults (HIFs) frequently occur when conductors break and fall The remainder of this paper is organized as follows. In
to the ground and when conductors touch tree branches [1]. section II, the HIF equivalent circuit in a resonant grounding
HIFs account for 12% of all grounded faults in France [2]. system is established. In section III, the change rule of the
HIF detection in a resonant grounding system is still a zero-sequence current in each feeder and the zero-sequence
considerable challenge because the fault current can decrease voltage of the bus, together with the relationships of their
to less than 2 A and the fault point is unstable. transient components, in the over-damping state are analyzed.
Many novel approaches for the detection of HIF have been Additionally, the variation ranges of the magnitude and the
proposed since the 1970s. In a directly grounded system, the attenuation factor of the transient zero-sequence current are
maximum HIF current is 75 A. When the conductor touches presented. In section IV, the resonance process and
the concrete surface with rebar in a 15 kV system [3], it can distribution of the transient current in the under-damping state
be recognized as a HIF when the fault resistance is larger than are analyzed. Furthermore, the variation ranges of the
115 . Many detection methods have been presented in the frequency, magnitude and attenuation factor of the transient
literature. References [4],[5] describe a apparatus that zero-sequence current are presented. In section V, a novel
monitors and analyzes the load current to obtain an energy method based on comparing the magnitude and polarity of the
value and then compares the energy value with a threshold projection current of each feeder is proposed. In section VI,
value to detect the HIF. Reference [6] monitors the energy the verification results obtained using the Alternative
variance of the second, fourth and sixth harmonics generated Transients Program (ATP), MATLAB simulation and field
by the three-phase unbalanced current to detect the HIF. The data are presented. Finally, conclusions are drawn in section
accuracy of this method is high when the arc fault current is at VII.
least 5 A. Reference [7] uses the wavelet coefficient energy
change of the distortion current to identify the HIF. Other II. HIF EQUIVALENT CIRCUIT
methods use a fast Fourier transform (FFT) [8], Kalman filter Reference [18] establishes a third-order equivalent circuit
[9] or wavelet transform [10]-[13] to extract the components of a single-phase earth fault in a resonant grounding system.
of some special frequency band from the fault currents and The circuit, shown in Fig. 1, precisely simulates both the fault
voltages and then use the nonlinear distortion of the HIF to transient and power frequency electrical parameters.
detect the fault by comparing the magnitude, phase, or energy L R
of the special frequency band components. In a directly i0C0 i0 Lp
i0 f
grounded system, the HIF detection technologies have +
satisfactory simulation results, and some have good practical uf u0b C0 Lp
application; thus, HIF detection technologies in a resonant -
grounding system can employ some of their techniques. The Fig. 1. Equivalent circuit of a single-phase earth fault in a resonant grounding
HIF detection methods for a resonant grounding system are system
less established. Reference [14] uses the phasor relationship of The third-order differential equation is difficult to solve.
the three-phase current variation before and after the fault to Thus, the equivalent circuit should be simplified into a
calculate the admittance to ground; the faulty feeder has the second-order system to obtain the analytic solutions of the
largest admittance to ground. However, the three-phase electrical parameters, particularly the transient components.
currents are influenced by the inconsistency of the Current For a fault transient process, f is generally over 1,000 rad/s
Transformers (CTs) of the three phases, which affects the when the transition resistance is low; thus,
practical application performance. Reference [15] uses the R | j f L | (1)
active power component of the zero-sequence power
and
frequency current to determine the faulty feeder in the HIF.
1
The HIF active current is small and influenced by the | || j f Lp | (2)
transmission error of CT and potential transformer (PT), j f C0
which will also affect the practical application performance. Under these conditions, the main resonance process is the
References [16],[17] perform the integration of the series resonance among R, L and C0; the effect of the
zero-sequence current of all feeders from the time when the Petersen coil can be ignored. A series resonance process of
zero-sequence voltage is zero up to the actual trigger time. this type and the characteristics of transient electrical
The faulty feeder is the one in which the integration of the parameters are analyzed in detail in [16]-[18]. Feeder
zero-sequence current is no longer proportional to the zero identification methods based on the transient electrical
sequence voltage. The practical application performance is parameters of the low-impedance fault have been successfully
good, but the integration accumulates error easily, and the used in the field [16]-[19].
linear relation and nonlinear relation judgment are strongly However, when the transition resistance is high, the
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
resonant frequency is generally less than 330 rad/s, i.e., III. RESONANCE PROCESS AND DISTRIBUTION OF TRANSIENT
R 3 j f L (3) CURRENT IN THE OVER-DAMPING STATE
or A. Resonance Process in the Over-damping State
1 The resonance process is in an over-damping state when R
| || j f Lp | (4)
j f C0 satisfies the following equation:
1 LP 1
Under such circumstances, the effect of the Petersen coil 3 j0 L R = (8)
increases, whereas the effect of L decreases such that it can be 2 C0 20C0 1-
ignored. According to (3) and the general parameters of the A zero-sequence current through a Petersen coil can be
distribution network (10kV, system zero-sequence expressed as
capacitance current no more than 67A), e.g., a system i0 LP i0 LP _ T +i0 LP _ PF
zero-sequence capacitance current of 33 A, when the cable i0 LP _ T A1e p1t A2 e p2t (9)
line is less than 10 km or the overhead line is less than 80 km i0 LP _ PF B sin(0t )
from the fault point to the bus, the minimum value of R is
A zero-sequence current at the fault point can be expressed
approximately 60 . Therefore, a HIF is known to occur
as
when the fault resistance Rf is more than 20 . An equivalent
circuit of the HIF for a resonant grounding system can be i0 f i0 LP i0C0 =i0 f _ T +i0 f _ PF
L pA L p A (10)
obtained by combining and simplifying the aforementioned i0 f _ T P 1 1 e p1t P 2 2 e p2t
equations based on the assumptions above, as shown in Fig. 2. R R
i0f R i0 f _ PF (1 02 LP C0 ) B sin(0t )
i0C0 i0 Lp where
+ Um 1 U 1 v
uf u0b C0 B = m
Lp | Z | 1 0 2 LP C0 | Z |
- j0 LP 1
Z R R
Fig. 2. Equivalent circuit of a HIF in a resonant grounding system 1 0 2 LP C0 jv0C0 (11)
A system with n feeders (j=1,2,,n), shown in Fig. 3, can B cos p2 B sin
A1 0
be obtained from Fig. 2 by dividing C0 into n branches. The p2 p1
faulty feeder is named feeder n. The healthy feeders are 0 B cos p1 B sin
A2
represented as (i=1,2,,n-1). p2 p1
i0 f R i0n 0 L p
arctan
i0( n 1) i0i i01 R (1 0 2 LP C0 )
i0C0 n + i0L
p
As shown in (9) and (10), both i0f and i0Lp are composed of
uf C0n u0b Lp
C0( n 1)
C0i
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
maximum value of the transient component would appear proportional to u0b_T (the ratio coefficient is 1/R). The other
because of the difference of the two attenuation factors. It can part is i0C0n_T and has the same characteristics as i0i_T.
be proven that the maximum value of the transient component Therefore, the magnitude of the transient current of the faulty
is larger than that of the power frequency component. feeder is not always the largest, and its polarity is neither the
Additionally, this maximum typically varies from tens of same nor the reverse as those of the healthy feeders. Thus, it is
amperes to hundreds of amperes. difficult to detect the HIF directly with the transient current.
Attenuation factors reflect the duration of the transient
process: fault identification is easier when the attenuation of IV. RESONANCE PROCESS AND DISTRIBUTION OF THE
the transient process is slower. The characteristic roots p1 and TRANSIENT CURRENT IN THE UNDER-DAMPING STATE
p2 satisfy the following conditions:
0 0 1 A. Resonance Process in the Under-damping State
( )2 2 p1 0 1-
0.03 | X L | 0.03 | X L | 0 (1 ) (15) When R is in the following range:
0 0 1 LP
0 1- p2 ( )2
1 R (19)
0.03 | X L | 0.03 | X L | 0 (1 )
2 2 C0
p1 and p2 become closer to each other as R increases. For the the system is in an under-damping state. An under-damping
aforementioned system with 33A system zero-sequence state is the main state of an HIF.
capacitance current, the characteristic roots are typically in the The zero-sequence current through a Petersen coil can be
range of -1681.1<p1<-326.3<p2<-63.3, indicating that the expressed as
duration of the transient component varies from several i0 LP i0 LP _ T +i0 LP _ PF
milliseconds to tens of milliseconds. i e t ( A cos( t ) A sin( t )) (20)
0 LP _ T 3 f 4 f
In conclusion, the magnitude and duration of the fault i0 LP _ PF B sin(0t )
currents transient component in the over-damping state can
satisfy the conditions required for identification. The zero-sequence current at the fault point can be
expressed as
B. Distribution of the Transient Current in the Over-damping i0 f i0 LP i0C0 =i0 f _ T +i0 f _ PF
State LP ( A4 f A3 )
i0 f _ T e t cos( f t ) (21)
The zero-sequence voltage of the bus can be expressed as R
u0b u0b _ T +u0b _ PF LP ( A3 f A4 )
e t sin( f t )
u0b _ T LP p1 A1e p1t LP p2 A2e p2t (16) R
i0 f _ PF (1 0 2 LP C0 ) B sin(0t )
u0b _ PF 0 LP B cos(0t )
where
The zero-sequence current of healthy feeders, which is B sin 0 B cos
equal to its zero-sequence capacitance ground current, can be A3 B sin ; A4 (22)
f
expressed as
i0i i0i _ T +i0i _ PF Both i0f and i0Lp comprise a power frequency component
and transient component (an attenuation sine component).
i0i _ T LP C0i ( A1 p12e p1t A2 p2 2e p2t ) (17)
and f are as follows:
i0i _ PF 0 LP C0i B sin(0t )
2
1
The zero-sequence current of a faulty feeder can be (23)
2RC0
expressed as
i0n i0n _ T +i0n _ PF 1 1
f ( ) 2 02 1 2 (24)
L pA L p A LPC0 2 RC0
i0n _ T P 1 1 LP C0 n A1 p12 e p1t P 2 2 LP C0 n A2 p2 2 e p2t
R R According to (24), f increases with increasing C0 or R.
i0n _ PF (02 LP (C0 C0 n ) 1) B sin(0t ) (18) That is, for a certain system, the resonant frequency increases
i0j is composed of the power frequency component i0j_PF monotonously from 0 along with increasing R. The upper
and transient component i0j_T. i0j_T is the sum of two decaying limit is
direct current components. f max 0 1 326.32rad / s (25)
In a healthy feeder, the power frequency component of i0i corresponding to a frequency of 51.96 Hz. The maximum
leads that of u0b by nearly 90, and the magnitude is directly frequency is slightly higher than the power frequency. An
proportional to C0i. However, for the faulty feeder, the power obvious beat frequency phenomenon would be observed when
frequency component of i0n shares the same phase with i0i, and f 0.
the magnitude may be larger or smaller than that of the From (23), is inversely proportional to C0 or R. For the
healthy feeder. Therefore, the HIF feeder cannot be identified same R, the C0 of the cable line system is typically larger than
by the power frequency current. that of the overhead line system; thus, the attenuation speed of
For the healthy feeders, the polarities of their transient the cable line system is slower than that of the overhead line
currents i0i_T are the same, and their magnitudes are directly system. However, for a certain system, a slower attenuation
proportional to C0i. The faulty feeder transient current i0n_T speed corresponds to a larger R. The maximum value of the
comprises two parts. One part is i0f_T and is directly attenuation factor is
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
1
0 1 326.32
1 (26) u0b _ PF 0 LP B cos(0t )
2RC0 s Similar to the over-damping state, the zero-sequence
Although the theoretical minimum value of is 0, the current of healthy feeders, which is equal to its zero-sequence
practical minimum value is sufficiently large for fault capacitance ground current, can be expressed as
detection. Assume that the transition resistance is 10 k and i0i i0i _ T +i0i _ PF
the system zero-sequence capacitance current is 67 A; then, i0i _ T LP C0i ( 2 A3 A3 f 2 2 A4 f )e t cos( f t ) (33)
the attenuation factor will be 1.57. The time constant of the LP C0i ( 2 A4 A4 f 2 +2 A3 f )e t sin( f t )
transient process in the under-damping state generally varies i0i _ PF LP C0i0 2 B sin(0t )
from 0.003 s to 0.6 s.
The zero-sequence current of the faulty feeder can be
According to (21), the peak value of the transient
expressed as
component of the fault point current can be expressed as
i0n i0n _ T +i0n _ PF
BLP
d 04 (1 )2 sin 2 04 (1 ) cos 2 03 (1 ) sin 2 i0n _ T ( A3 LP (C0 C0 n )( A3 2 A3 f 2 2 A4 f ))e t cos( f t )
R f
( A4 LP (C0 C0 n )( A4 2 A4 f 2 2 A3 f ))e t sin( f t )
(27)
Assuming that 1-v1, we also obtain i0n _ PF (0 2 LP (C0 C0 n ) 1) B sin(0t ) (34)
0C0 i0j is composed of a power frequency component and
B Um (28)
transient component (decaying sine component i0j_T), in which
1+ 202C02 R 2
the characteristic of the power frequency component is the
Thus, (27) can be simplified as same as that in the over-damping state. i0i_T leads u0b_T by
Um 02 +0 sin 2 (29) nearly 90, and the magnitude is directly proportional to C0i.
d
R f 1+ 202C02 R 2 i0n_T consists of i0f_T and i0C0n_T, whose characteristics are also
the same as those in the over-damping state.
The magnitude of the transient component decreases with
increasing R. However, the effect of repeats itself after half
V. HIF FEEDER IDENTIFICATION BASED ON TRANSIENT
a cycle. The effect is more obvious for a lower R. The effect
ZERO-SEQUENCE CURRENT PROJECTION
can be ignored when R is sufficiently high. The variation law
of d with R and is shown in Fig. 4. A. Principle of Transient Zero-sequence Current
Projection-based Feeder Identification
102
Peak Value of i0f_T
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
Compare polarity
i0i _ T _ P i0 LP _ T _ P
i0i _ T All the same Yes Bus fault
i0 LP _ T polarity
No
Fig. 5. Relationship between each component in the inner product space
Select reverse polarity as faulty feeder
B. Assessment of the Faulty Feeder Identification Algorithm End
(1) This method provides an effective HIF identification Fig. 6. Algorithm flowchart for faulty feeder identification
for a single-phase earth fault in a resonant grounding system.
It improves the transient analysis and faulty feeder VI. SIMULATION AND VERIFICATION
identification technology in a non-solidly grounding system.
(2) Compared with [16],[17], the new HIF identification A. Simulation Models
method has a more rigorous criterion: no accumulative error The distributed parameter-based ATP simulation model for
and better anti-interference performance. a typical 110 kV/10 kV distribution system is shown in Fig. 7.
(3) Compared with the methods based on inserting For a Petersen coil grounding network, the system is set to be
resistance between neutral and earth, the new method does not over-compensated, with 108% compensation. The network
have to install additional devices and has considerably better comprises three mixed feeders with overhead lines and cables
safety performance. (feeders 1, 2 and 5) together with two cable feeders (feeders 3
(4) Compared with [14],[15], the new method is less and 4). A HIF occurs in phase A of feeder 5.
110 kV 10 kV Overhead line:20 km
affected by PT and CT errors. Cable Line:3 km Overhead line:15 km L1
(5) The new method is not affected by the line type, fault Overhead line:9 km
Cable line:9 km Overhead line:6 km L2
resistance, fault inception angle or fault location. It is based
Cable line:12 km
on the fault characteristics derived through detailed equivalent lp L3
Cable line:15 km L4
circuit analysis. Cable line:6 km Overhead line:12 km L5
(6) The new method operates according to the
zero-sequence voltage which is less influenced by the Fig. 7. Simulation model of a resonant grounding system
switching transients. So the probability of the false detection The line parameters are listed in Table I.
during normal operation can be reduced greatly. TABLE I
Line Parameters of the Model
(7) The new methods cannot be used for the only one
Resistance Inductance Capacitance
feeder or two feeders circuit case. This is a typical problem Parameters (/km) (mH/km) (F/km)
for methods based on the current amplitude and polarity in R+ R0 L+ L0 C+ C0
faulty feeder identification. Overhead Line 0.17 0.32 1.017 3.56 0.115 0.0062
Cable Line 0.27 2.7 0.255 1.109 0.376 0.276
C. Faulty Feeder Identification Criteria Based on Transient
Zero-sequence Current Projection B. Verification of the HIF Equivalent Circuit
i0j_T_P can be calculated using the following equation: According to the simulation model in Fig. 7, a fault was
applied at feeder 5s terminal with a fault inception angle of
90. The equivalent circuit shown in Fig. 2 is the basis of the
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
analysis and calculation in this paper. The simulations of the illustrate that the lumped parameter equivalent circuit in Fig. 2
equivalent circuit in Fig. 2 (corresponding to the system in Fig. can be used to simulate a HIF. Therefore, the calculation and
7) have also been performed such that the error of the two analysis of transient electrical parameters based on the
models can be compared. The waveforms of i0j and i0Lp in the equivalent circuit are trustworthy.
distributed parameter model are shown in Fig. 8. The
C. Verification of the Faulty Feeder Identification Method
waveforms in the lumped parameter equivalent circuit in Fig.
2 (corresponding to the system in Fig. 7) are also shown in Fig. The waveforms of u0b, u0b_T, i0j, i0j_T and i0j_T_P in the
8. The system is in the over-damping state when Rf is 26 in over-damping state (Rf = 26 ) and under-damping state (Rf =
Fig. 8(a), and the system is in the under-damping state when 1500 ) in a distributed parameter model are shown in Figs. 9
Rf is 1,500 in Fig. 8(b). and 10, respectively, and feeder 5 is the faulty feeder. To
i0f in lumped parameter i0Lp in lumped parameter make the graphics more intuitive, only the typical waveforms
i0f in distributed parameter i0Lp in distributed parameter of three feeders (faulty feeder and two healthy feeders) are
40
20 drawn; the other two healthy feeders are proportional to
00 feeders 1 and 2.
I(A)
-20
-20 u0b i05 i01 i02
I/A
80
80 80
-40 60
60 60
-60 40
U(kV)
40 40
I(A)
-80
-80
I/A
0.06 0.08 0.10 0.12 0.14 20
20 20
0.6
0.7 0.8 0.9 1
t(s) 1.1 1.2 1.3 1.4
t/s 4 00 0
aZero-sequence current of fault point and Petersen coil in over-damping
x 10 -20 -20
-20
state 0.06
0.06 0.07
0.07 0.08
0.08 0.09
0.09 0.10
0.1 0.11
0.11
30 t(s)
t/s
(a) Zero-sequence component
20 16
80
80
10 60
60 12
I(A)
8
I/A
0 40
40
U(kV)
I(A)
I/A
20
20 4
-10
00 0
-20 -20
-20 -4
-30
-30 0.06
6000 0.07
7000 0.08
8000 0.09
9000 0.10
10000 0.11
11000
0.05
0.5 0.10
1 1.5 0.20
2 2.5 0.30
3 3.5 0.40
4 4.5 0.50
5 t(s)
t/s
t(s)
t/s 4 (b) Transient component
x 10
bZero-sequence current of the fault point and Petersen coil in the 60
60 12
under-damping state 40
40 8
Fig. 8. Currents of the fault point and Petersen coil in different resonance
U(kV)
20
20 4
I(A)
states
I/A
15 15
I/A
0
00 0
I/A
U(kV)
t/s
I(A)
5
Lumped Parameter Model 33.24 -34.49 -551.28 -193.18
0 0
TABLE III
Parameter Verification in the Under-damping State -5 -5
Transient Zero-sequence The Parameters of i0f_T -10
-10
-10
Current at the Fault Point d(A) f (rad / s) (1/s) ( ) 0.05
0.05 0.1
0.1 0.15 0.2
0.2 0.25
t(s) 0.3
0.3 0.35 0.4
0.4 0.45 0.5
0.5
t/s
Distributed Parameter Model 1.97 325.98 8.56 55.13 (a) Zero-sequence component
88 0.6 8
Lumped Parameter Model 1.95 326.20 8.68 55.38 0.3
Fig. 8 illustrates that the over-damping state has a larger
I/A
0
44 -0.3 4
transient current peak value and faster attenuation speed. -0.6
U(kV)
Furthermore, in the under-damping state, a clear beat 00 45,000 46,000 47,000 48,000 49,000 50,000
0
I(A)
t/s
I/A
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
(b) Transient component reverse polarity of the current projection component. Thus,
2 6
the faulty feeder can be accurately identified.
0
D. Verification of the Field Data
I/A
1 3
To verify the reliability of the method, we selected groups
U(kV)
0
I(A)
0.06
6500 7000
0.07
7500 8000
t/s
0.08
8500 9000
0.09
9500 -6
10000
U(kV)
I(A)
Table IV shows the projection coefficients of the transient 0
I/A
0
current with respect to the bus transient voltage for all feeders -5
-5 -5
in Fig. 7. -10
-10 -10
-200 00 0.02
200 0.04
400 0.06
600 0.08
800 0.10
1000
TABLE IV t(s)
t/s
Simulation Results (a) Zero-sequence component
Fault Inception Angle, 15 15
Projection coefficient 10
10 10
0 /4 /2 3/4
i01_T -8.7e-05 -3.5e-01 -6.7e-01 -3.2e-01 -8.7e-05 55 5
U(kV)
I/A
00 0
I/A
U(kV)
I(A)
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
over-damping and under-damping states, the magnitudes of [5] B. D. Russell, B. M. Aucoin, L. C. Benner, Randomness fault detection
system. U.S. Patent 5 485 093, 1996.
i0i_T_P are considerably smaller than those of i0n_T_P and have [6] K. Y. Lien, S. L. Chen, C. J. Liao, T. Y. Guo, Energy variance criterion
completely reversed polarity, a clear fault characteristic. This and threshold tuning scheme for high impedance fault detection, IEEE
conclusion is the same as that obtained in the theoretical Trans. Power Del., vol. 14, no. 3, pp. 810-817, Jul. 1999.
[7] F. B. Costa, B. A. Souza, N. S. D. Brito, J. A. C. B. Silva, W. C. Santos.
analysis in section V.
Real-time detection of transients induced by high-impedance faults
based on the boundary wavelet transform, IEEE Trans. Ind. Appl., vol.
VII. CONCLUSIONS 51, no. 6, pp. 5312-5323, May 2015.
[8] D. I. Jeerings, J. R. Linders, Unique aspects of distribution system
For a resonant grounding system, the transient process of a harmonics due to high impedance ground faults, IEEE Trans. Power
HIF is the parallel resonance between the system capacitance Del., vol. 5, no. 2, pp. 1086-1094, Apr. 1990.
to ground and the Petersen coil. The parallel resonance can be [9] A. A. Girgis, W. Chang, E. B. Makram, Analysis of high-impedance
fault generated signals using a Kalman filtering approach, IEEE Trans.
divided into the over-damping and under-damping states Power Del., vol. 5, no. 4, pp. 1714-1724, Oct. 1990.
based on the variations of the fault resistance. In the [10] A. R. Sedighi, M. R. Haghifam, O. P. Malik, and M. H. Ghassemian,
over-damping state, the transient zero-sequence current is High impedance fault detection based on wavelet transform and
statistical pattern recognition, IEEE Trans. Power Del., vol. 20, no. 4,
composed of two decaying direct current components. The Oct. 2005.
under-damping state consists only of one decaying sine [11] M. Michalik, W. Rebizant, M. Lukowicz, S.J. Lee, and S.H. Kang,
component with a resonant frequency that varies from 0 to High-impedance fault detection in distribution networks with use of
wavelet-based algorithm, IEEE Trans. Power Del., vol. 21, no. 4, Oct.
slightly higher than the power frequency. The attenuation time 2006.
constant typically varies from 0.6 ms to 600 ms. [12] J. R. Macedo, J. W. Resende, and C. A. Bissochi Jr., Proposition of an
In both the over-damping and under-damping states, the interharmonic-based methodology for high-impedance fault detection in
distribution systems, IET Generation, Transmission & Distribution,
transient zero-sequence current of a healthy feeder is vol. 9, no. 16, pp. 2593-2601, Mar. 2015.
approximately orthogonal to the transient zero-sequence [13] S. J. Huang, C. T. Hsieh, High-impedance fault detection utilizing a
voltage of the bus, and the polarity of the current projection Morlet wavelet transform approach, IEEE Trans. Power Del., vol. 14,
no. 4, Oct. 1999.
with respect to transient voltage is negative. The transient
[14] H. Ma, X. Zeng, Y. Wang, Z. Li, Grounding fault protection with fault
current of the faulty feeder consists of the transient current at resistance measuring for ineffectively earthed power systems, in Proc.
the fault point and the transient capacitance ground current; IEEE/PES Transmission and Distribution Conference & Exhibition,
the former is directly proportional (scale factor is the Aug. 2005, pp. 1-3.
[15] T. Welfonder, V. Leitloff, R. Fenillet, S. Vitet, Location strategies and
reciprocal of the fault resistance) to the magnitude of the evaluation of detection algorithms for earth faults in compensated MV
transient voltage of the bus. The polarity of the projection distribution systems IEEE Trans. Power Del., vol. 15, no. 4, pp.
current with respect to the transient voltage is positive, and the 1121-1128, Oct. 2000.
[16] G. Druml, W. Klein, O. Seifert, New adaptive algorithm for detecting
magnitude is larger than those of the healthy feeders. low- and high ohmic faults in meshed networks, in Proc. 2009 CIRED.
The faulty feeder can be identified by comparing the [17] G. Druml, A. Kugi, O. Seifert, A New Directional Transient Relay for
magnitude and polarity of the transient current projection High Ohmic Earth Faults, in Proc. 2003 CIRED.
[18] Y. D. Xue, J. Li, and B. Y. Xu, Transient Equivalent Circuit and
component for each feeder. The feeder with the reverse Transient Analysis of Single-phase Earth Fault in Arc Suppression Coil
polarity of a transient current projection component among at Grounded System, in Proc. CESS, vol. 35, no. 22, pp. 5703-5714, Nov.
least 3 feeders with the highest projection current is the faulty 2015. (in Chinese)
[19] B. Y. Xu, Y. D. Xue, J. Li and Y. Chen, Single phase fault detection
feeder. If the polarity of all the projection currents is the same, technique based on transient current and its application in non-solid
it is a bus fault. The transient analysis and transient faulty grounded network, Proc. 7th Int. Conf. on Developments in Power
feeder identification method is verified by digital simulation System Protection, 2001, pp. 141-144.
[20] O. Chaari, S. P. Bastard, and M. Meunier, Pronys method: an efficient
and field data.
tool for the analysis of earth fault currents in Petersen-coil-protected
This paper established a novel faulty feeder identification networks, IEEE Trans. Power Del., vol. 10, no. 3, pp. 1234-1241, Jul.
method of HIF using parallel resonance electrical parameters 1995.
between the Petersen coil and capacitance to ground. This
Yongduan Xue (M13) received B.S., M.S., and Ph.D.
method is different from the identification method of degrees from Xi'an Jiaotong University, Xian, China,
low-resistance earth faults based on the series resonance in 1992, 1997, and 2003, respectively. He is a
electrical parameter between the line inductance and system Professor at the College of Information and Control
Engineer, China University of Petroleum, Qingdao,
capacitance to ground that ignores the effect of the Petersen China. His research interests include neutral grounding
coil. and single line-to-ground fault self-healing technology.
REFERENCES
[1] M. Aucoin., Status of high impedance fault detection, IEEE Trans. Xiaoru Chen was born in 1990. She received her
Power App. Syst., vol. PER-5, no. 3, pp. 39-40, Mar. 1985. bachelors degree in electrical engineering and
[2] Griffel D, Harmmand Y. A new deal for safety and quality on MV automation from China University of Petroleum,
networks, IEEE Trans. Power Del., vol. 12, no. 4, pp. 1428-1433, Oct. Qingdao, China, in 2014. She is currently pursuing her
1997. masters degree in electrical engineering at China
[3] Detection of Downed Conductors on Utility Distribution Systems University of Petroleum, Qingdao, China. Her research
IEEE PES Tutorial Course 90EH0310-3-PWR, 1989. interest is ineffectively grounded system fault
[4] B. D. Russell, C. L. Benner. Arcing fault detection for distribution detection.
feeders: security assessment in long term field trials, IEEE Trans.
Power Del., vol. 10, no. 2, pp. 676-683, Apr. 1995.
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2641045, IEEE
Transactions on Power Delivery
0885-8977 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.