DUBAI MUNCIPALITY REQUIREMENTS AS PER LATEST MEEETING HELD ON 11-APR-2016

DEAD LOAD As per panel, Purlin & Flange Brace Self weight
COLLATERAL LOAD 0.25 kN/m2 (minimum) (may be changed based on muncipality engineer)
LIVE LOAD 0.60 kN/m2 (minimum)
WIND LOAD 162 & Exp C (or) 1.00 kN/m2 (whichever is greater)
SEISMIC LOAD None
TEMPERATURE LOAD Based on Building width
MEZZANINE DEAD LOAD 2.00 kN/m2 (for 100mm slab thickness incl. deck panel wt.)
MEZZ FLOOR FINISH LOAD 1.00 kN/m2 (minimum even floor finish is not there)
MEZZ GYPSUM PARTITION LOAD 1.00 kN/m2 (minimum even partition is not there or 200mm blockwall considered in some locations)
MEZZANINE COLLATERAL LOAD 0.25 kN/m2 (minimum)
MEZZANINE LIVE LOAD 5.00 kN/m2 (minimum)
PATTERN LOADING None
MIN THICKNESS FOR "I" SECTION 6mm (minimum)
MIN THICKNESS FOR COLD FORMED 1.5mm (minimum)
BRACING TYPE Rod Bracing for both roof & wall
STRUT TUBE @ EAVE As per design
SAG ROD 12mm Dia. (Rows may be changed based on muncipality engineer)
STRESS RATIO 0.95 (maximum)
SANDWICH PANEL B2 Class (minimum)
VERTICAL DEFLECTION LIMIT Span / 240 for Live ; Span / 180 for Total
HORIZONTAL DEFLECTION LIMIT If full height sheeting or partial block wall height less than half of the building height - H / 100
HORIZONTAL DEFLECTION LIMIT If full height block wall or partial block wall height more than half of the buidling height - H / 200
0.7 TIMES IN DEFLECTION LIMIT Not allowed at all