Вы находитесь на странице: 1из 2

Datasheet Electric Actuator Type EA 11

Advantages
- Simple handling
- Stable and highly chemical resistant housing due to PP-GF
- Long life time due to roust concept and the choice of best electronic
- Universal use thanks to wide rang power supply and standard interfaces
- Flexible configuration thanks to the modular concept
- Additional safety due to fail-safe unit and battery pack (optional)

Combinations
Type 107: EA 11 + Ball valve Type 546 (DN10 - DN50)
Rated voltage Nominal torque Mdn
AC: 100 - 230 V, 50/60Hz 10 Nm
AC/DC: 24 V, 56/60 Hz
Rated voltage tolerance Peak torque
10% 20 Nm
Rated Output Duty cycle at 25C / 15 min
AC: 40 VA at 100 - 230 V 40%
AC/DC: 22 VA at 24V Cycles at 20C and Mdn
Electric impedance 150000
230 V, 100 k Control time s/90 at Mdn
24 V, 4.7 k 5
Protection class Actuating angle
IP 65/67 max. 270, set to 90
Overload protection Weight
Current / time dependent 1.857 kg
Ambient temperature Accessories
-10 to +45C Fail-safe unit including battery
Allowable humidity Emergency manual override plug set
max. 80% at 31C Heating element
Connectors Heating element + Fail safe unit + Battery
F05 Adapterset for F05 (WS14/11)
Position indicator Adapter unit WS14 for F05
optically integrated Adapter sleeve WS11 for F05
Emergency manual override Battery as spare part
integrated Connector set
Housing materials Limit switch Ag-Ni
PP fiberglass reinforced, flame retardant,
external stainless steel screws

Combinations
Electrically actuated Ball Valve Type 107
Type 107 is based on the Ball Valve Type 546 (d16DN10 to d63DN50) with the electric actuator
EA11. The Type 107 is designed for automated standard applications with no special demands.
Ball Valve Electric Manual Ball Dimensions Materials Standards
electrically actuator Valve
actuated
Type 107 EA 11 Type 546 DN 10 - DN 50 PVC-U, PVC-C, ABS, all standards
PP, PVDF

Exploded view

1. Limit switches S1 6. Electrical supply unit, without protection against


and S2 accidental contact
2. Direct current motor 7. Shaft for emergency manual override
3. Optical position 8. Connections for DIN plug or cable gland
indicator
4. Plug for accessories 9. Assembly bolt for accessories
5. Terminal strip for external connections max. 1.5 mm

Dimensions and wiring diagram



1 Adapter SW14 for F05