Вы находитесь на странице: 1из 5

LOGICS OF RGMO for allowed single jump

ADS A TG Integral block

Speed -
X B

100 s T

B + 3000 MIN

2900 MAX

E S

C RESET DOM

A GT Ton= 40 ms D
S
1.8

E R

BOILER NOT RESETDOM

STABLE
S
E

D Ton= 3 MIN H
R

FREQUENCY INFL OFF

RUNBACK ACTIVE
CALCULATION BLOCK Z

INPUTS

C, A, D, SPEED, CMC UNIT DMD (FROM CMC PANEL), EHTC LOAD DMD, CMC ON (IN EHTC), ACTUAL
LOAD

Y1= IF (C, A, 0)

for a allowed single jump Y2= IF (D, Y2, Y1)

Y3= IF (SPEED>3000, (3000-SPEED)*3.333, 3.333*Y2)

Y4= IF (CMC ON, CMC UNIT DEMAND, EHTC LOAD DMD)

Y5= - (Y4*0.01/60)

Y6= IF (SPEED>3000, -25, Y5)

OUTPUT= MIN (Y3, (525- ACTUAL LOAD), 0.05*Y4)

CMPT

Z.OUTPUT IN OUTCTL G
INCTL OUTCTL
+25 HI +25
HI
-25 LO -25
LO
LT
+25 F
OUTRATEINC
Z.Y6 0.1
OUTRATEDEC

F H
TPULSE= 1 SEC

G= RGMO MEGAWATT CORRECTION


LOGICS OF RGMO for allowed multiple jumps

ADS A TG Integral block

Speed -
X B

100 s T

B + 3000 MIN

2900 MAX

E S

C RESET DOM

A GT Ton= 40 ms D
S
1.8

E R

BOILER NOT RESETDOM

STABLE
S
E

D Ton= 3 MIN H
R

FREQUENCY INFL OFF

RUNBACK ACTIVE
CMC UNIT DMD
1
(CMC PANEL) J
UMS
EHTC LOAD SP
2

SEL 2
CMC ON

CALCULATION BLOCK Z

INPUTS

C, A, D, SPEED, J, ACTUAL LOAD, E, K

Y1= IF (C, A, 0)

for allowed MULTIPLE jumps Y2= IF (D, K, 0)

Y3= IF (SPEED>3000, (3000-SPEED)*3.333, 3.333*Y2)

Y4= IF (E, 0, Y2)

Y5= - (J*0.01/60)

Y6= IF (SPEED>3000, -25, Y5)

OUTPUT= MIN (Y3, (525- ACTUAL LOAD), 0.05*J)

CMPT

Z.OUTPUT IN OUTCTL G
INCTL OUTCTL
+25 HI +25
HI
-25 LO -25
LO
LT
+25 F
OUTRATEINC
Z.Y6 0.1
OUTRATEDEC
F TPULSE= 1 SEC H

G= RGMO MEGAWATT CORRECTION

ADD CMPT ATAG

Z.Y1 IN 1 OUT INCTL OUTCTL


IN OUTCTL
Z.Y2 IN2 +25 +7.5 HI
HI
0 Z.Y4 LO
ADD LO
1 RANGE CLAMP
0 SCALE ENABLE

INCTL OUTCTL K

+7.5 HI
0 LO
1 RANGE CLAMP
0 SCALE ENABLE

ATAG

Вам также может понравиться