HVX
Embedded Pole
Vacuum Circuit Breaker up to 24kV
Medium Voltage Distribution

schneider-electric.com/HVX
Contents

Overview 6

HVX range 18

Functions and characteristics 26

Dimensions 42

Order form 54

schneider-electric.com HVX embedded pole catalog | 3


High performer offers wide choice
Operating up to 50 kA and 4,000 A and with voltages ranging from 12 kV to 24 kV, the HVX
series of circuit breakers is a true high performer with a wide choice of configurations for easy
integration.
Benefit from the performance you need, with the level of safety and reliability you deserve.
PM105607

Note: The voltage levels 36 kV and 40.5 kV are also available. Please contact Schneider Electric.

4 | HVX embedded pole catalog schneider-electric.com


Your needs HVX solutions

Safety
State-of-the-art design
Manufacturing controls

Safety Operation with mechanical interlocks


Remote control

Reliability
Compliance with the standards
Fully type-tested equipment

Reliability Limited maintenance

Ease of use
Wide choice of configurations
Easy integration

Ease of use Customer support

schneider-electric.com HVX embedded pole catalog | 5


Overview

6 | HVX embedded pole catalog schneider-electric.com


Field of application 8

Safety 9

Reliability 12

Ease of use 13

A comprehensive solution 15

Schneider Electric services 16

Environment 17

schneider-electric.com HVX embedded pole catalog | 7


Overview Field of application

HVX offers a wide range of performance The result of a sustained development


levels. It controls heavy-duty tasks in harsh effort for application in air-insulated
conditions, low temperatures, and vibrations
under normal, inductive, and capacitive loads. switchgear units
The HVX series of vacuum circuit breakers is the result of Schneider Electrics long
lasting experience in the medium-voltage field.
PM105605

The HVX series offers a proven state-of-the-art design to meet your specifications
for power switching devices in air-insulated switchgear.
A fixed, frontal version
A withdrawable, frontal version
The HVX operating mechanism gives the device an opening and closing speed that
is independent of the operator whether the command is electrical or manual.
It carries out reclosing cycles and is automatically recharged by a geared motor
after each closing.
It also ensures that the open order always takes priority over the close order. In the
event of permanent opening and close orders, it has to maintain the circuit breaker
in the open position as long as the open order is active. Once the open order has
PM105606

been canceled, the close order has to be interrupted then reactivated to enable
closing of the circuit breaker.
Easy integration in modern air-insulated switchgear makes HVX the right choice
for panel builders and end users. An Integration Guide is available containing
instructions on how to do so.

Applications
The circuit breaker is the core component of medium voltage switchgear. The HVX
offer enables panel builders to design switchgear solutions helping to protect
cables, transformers, motors, or generators.
It is widely used in many industries, including power distribution, power generation,
nuclear power, oil and gas, mining and metals, and transport.

Energy Industry - MMM - O&G - Buildings


PM105610
PM105608

Primary substation (> 20 MVA) Heavy industry primary substation


(10-50 MVA)
DM105012

Large switching substation (> 4 MVA) Large MV consumer site (10-50 MVA)
PM105611
PM105609

PM105612
PM103350

MV/LV substation (<4 MVA) MV consumer site (1-5 MVA)

8 | HVX embedded pole catalog schneider-electric.com


Overview Safety
Protection of people and equipment
is our top priority

State-of-the-art design Vacuum interrupter


Schneider Electric's VG range of vacuum interrupters have been developed
PM105613

using the latest computer modeling tools to achieve optimized designs. Based on
advanced one-stop sealing technology, the VG offer minimizes artificial pollution
during the production process.
Based on our patented design and comprehensive knowledge of vacuum
interrupter technology, Schneider Electric's vacuum interrupter is a standout
product in the medium voltage field with its high reliability, compact size, and long
service life.
The special geometry of the contacts and the choice of material used ensures
limited duration of the arc and thus helps to reduce thermal and dielectric stress.

Benefits of vacuum interrupters


Protection of contacts against oxidation and contamination in sealed vacuum
Low contact mass to limit the energy of the drive and to allow high mechanical
endurance
Maintenance-free
Environmentally-friendly

Embedded-pole construction
PM105614

PM105615

The embedded pole is another of Schneider Electric's contributions to medium


voltage products, with its 10 years' plus experience in design and manufacture, and
it has been tried and tested in the field for many years. Employing the embedding
technology, it completely integrates the vacuum interrupter, the main circuit, and the
insulated shaft in an epoxy pole to help protect the main circuit from the outside.
This gives the pole optimum environmental adaptability, since the circuit breaker
can function normally under harsh conditions.

Benefits of embedded poles


Compact and robust design
Protection against vibration, dust, and humidity
High dielectric strength
Compact dimensions and possible use in high altitude
Sealed for life

schneider-electric.com HVX embedded pole catalog | 9


Overview Safety
Protection of people and equipment
is our top priority

Operating mechanism
DM103392

The operating mechanisms have been simplified to increase reliability and give
extended life with very low maintenance.
Instead of the traditional spring operating mechanism, the HVX series incorporates
a single-shaft system and only one torsion spring, reducing the number of parts
and increasing reliability.
The cam output from 3 independent phases is ideal for the vacuum switch.
The transmission mechanism's one-step output and the special axletree design
offers optimum transmission efficiency that helps save energy and provides a
Drive spring- stable, reliable mechanism.
charging
mechanism Operating principle
Energy is stored in the spiral spring by means of the electric motor or manual
crank. Opening and closing of the vacuum interrupter is controlled by the cam;
upon closing, the spring automatically restores the energy for an integrated
automatic on/off operating cycle.
The on/off storage mechanism, with its special mechanism, can absorb the excess
energy of the drive mechanism through a quick on/off operation.
The operating mechanism has electric and manual charging devices. The relevant
interlock prevents manipulation errors after energy storage.

Robust manufacturing controls


PM105616

HVX is manufactured in compliance with ISO 9001 certified by Bureau Veritas.


The following quality controls are implemented to ensure that each product
delivered to panel builders has the same performance as the unit type tested:
Inspection of every incoming batch of critical components with 3D device
dimension checks
Routine tests on all products:
- Dielectric tests on the main circuit
- Tests on auxiliary and control circuits
- Measurement of the resistance of the main circuit
- Design and visual checks
- Mechanical operating tests
Regular mechanical tests on circuit breaker samples are performed until the
device breaks down

10 | HVX embedded pole catalog schneider-electric.com


Overview Safety
Protection of people and equipment
is our top priority

The IEC (1) standard stipulates: Safe operation


"Select equipment that minimizes the risks
The operating interface clearly indicates the status of the circuit breaker. Any
to personnel from improper operation (for
maloperation is prohibited through robust mechanical interlocks.
example, fast acting ground switches on lines,
motor operators to allow remote operation)".
Interface operation
The right choice of components, such OFF button
as withdrawable racking trolley, vacuum

PM105617
interrupter, and operating mechanism, is
crucial to fulfil this IEC recommendation. ON button

(1) IEC 62271-1: Edition 2011

Nameplate

Spring status
indicator

Insertion point for manual


charging of the operating
mechanism

Mechanical
operations Circuit breaker
counter position indicator

Racking trolley
PM105618

The racking trolley moves the circuit breaker from the disconnected position to the
connected position and vice versa. The racking operation can be done either by
rotating a lever on the front of the switchgear with the door closed, or remotely by
activating an electrical command from the control room.
The HVX racking trolley has a robust interlocking system with the LV plug and the
circuit breaker. It can be equipped with an electric motor for remote racking from
the control room.
The materials used to manufacture HVX racking trolley sub-assemblies have been
selected and designed to operate 1,000 cycles under the conditions defined by
the IEC standard.

Remote control
Remote operation is recommended as it allows convenient operation from a
reasonable distance.

schneider-electric.com HVX embedded pole catalog | 11


Overview Reliability

Compliance with standards


PM105619

IEC 62271-100 defines the conditions for switching normal, inductive, and
capacitive loads, as well as fault currents, and for withstanding, mechanical,
thermal, and dielectric stresses.
Proven compliance with HVX is fully type-tested according to the latest edition of standard IEC 62271-100,
IEC 62271-100, 2012 ed. 2 standard 2012 ed. 2.
Certificates of conformity with other standards such as GB/China and Gost/Russia
PM105620

are available on request.

HVX circuit breakers have been subjected to the following type


tests, as defined by standard IEC 62271-100:
Dielectric tests
Measurement of the resistance of the main circuit
Temperature rise tests
Short-time withstand current and peak withstand current tests
Additional tests on auxiliary and control circuits
Mechanical operating test at ambient temperature
Short-circuit making and breaking tests
Extended mechanical endurance tests for M2 class
Electrical endurance tests for E2 class
Capacitive current switching tests:
- Line-charging current breaking test
- Cable-charging breaking test
- Single capacitor bank inrush making tests
Out-of-phase making and breaking tests
Normal service conditions Back-to-back capacitor breaking tests on request

HVX is designed to operate according to


IEC 62271-1, in the following conditions:
The declaration of conformity indicates
Ambient air temperature:
the following on the front page:
-25 C to +40 C (contact Schneider Electric
for higher or lower temperatures) The apparatus type defined as fixed or withdrawable and the phase distance
Altitude: The circuit breaker reference defined by the main rated characteristics: rated
Less than or equal to 1,000 m (derating voltage, rated short-circuit breaking current, and rated current
coefficient to be applied for altitudes higher The list of relevant type test reports to assess HVX conformity with the IEC
than 1,000 m) standard
Atmosphere:
No dust, smoke, salt, corrosive, or flammable
gas or vapor
Humidity:
Limited maintenance
- Average relative humidity over 24 h 95%
The state-of-the-art HVX design ensures limited maintenance up to 10,000 cycles.
- Average relative humidity over 1 month 90%
The vacuum interrupter has an expected service life of 30 years.
Please contact us for special service conditions.
HVX can even operate up to 30,000 times with a regular maintenance plan.

12 | HVX embedded pole catalog schneider-electric.com


Overview Ease of use

Wide choice of configurations with


modular design
HVX offers a wide choice of performance levels (up to 50 kA and 4,000 A) within
one circuit breaker family, thus providing panel builders with a high degree of
standardization in their switchgear design.

High-performance breaking devices


kA

50

HVX
40
12 kV/17.5 kV

31.5
HVX
25 24 kV
A
630 1,250 1,600 2,000 2,500 3,150 4,000*
* Forced cooling

Easy integration,with simple and standard


interfaces
Common dimensions based on a modular design ensure easy integration into
various switchgear designs
The breaker offers installation flexibility
Panel builders can use their own trolley design to make it a withdrawable
solution
PM105621

Phase distance

HVX 12/17.5 kV
Phase distance (mm)
Contact 150 210 275
distance
Contact 205 -
distance (mm) 310 -

HVX 24 kV
Phase distance (mm)
150 210 275
Contact
310 -
distance (mm)

schneider-electric.com HVX embedded pole catalog | 13


Overview Ease of use

Schneider Electric offers best-in-class Technical and commercial support


support to customers using HVX embedded
pole circuit breakers. Schneider Electric offers extensive technical and commercial support to panel
builders, including expert advice on how to customize HVX, how to integrate HVX in
switchgear, how to prepare switchgear for testing in the laboratory, how to analyze
the results from type tests to improve switchgear design, special commercial
conditions for circuit breakers needed to verify the technical performance of HVX in
PM105365

assembled switchgear, as well as dedicated training documents and other support


materials.
Please contact your Schneider Electric sales representative for more information.

Customer support
Online document repository
A QR code on the front of the HVX enables customers to easily download various
online documents:
User guide
PM105605

PM105622

Receipt guide
List of spare parts

Product QR code
"FLASH ME" Customer Care Center
Schneider Electric has set up call centers and e-mail contacts in more than 190
countries to provide a rapid response to customer inquiries. Personnel in the
country using HVX are trained to provide qualified answers to customer questions.

Spare parts
PM105387

Under Schneider Electric's spare parts management policy, HVX parts will be
available for at least 12 years after delivery of the product to the customer.

Services
A service contract for the switchgear room can be offered by the local Schneider
service team with packages such as predictive maintenance, preventive
maintenance, 24/7 hotline, emergency on-site intervention, and emergency spare
part delivery.
The availability of the service plan offers varies in different countries.

14 | HVX embedded pole catalog schneider-electric.com


Overview A comprehensive solution

Schneider Electric product portfolios include Protection and control relays


a wide choice of multi-function relays
to be used together with HVX to build a Easergy P5
consistent solution for protection, control, and Easergy P5 reliably protects your electrical equipment from unexpected downtime,
monitoring. while providing you with a powerful digital experience for greater efficiency. To best
protect your electrical network, you need protection relays that:
Comply with the latest standards and regulations, including those for safety,
PM104085

security, and reliability


Are easy to order, install, use, and maintain
Optimize your ownership costs

Sepam
Sepam series 20, series 40, series 60, and series 80 digital protection relays take
Easergy P5 full advantage of Schneider Electrics experience in electrical network protection.

They provide the following functions:


PE60300

Effective fault diagnosis and protection planning


Accurate measurements and detailed diagnosis
Integral equipment control
Local or remote indication and operation
Easy upgrading: communication, digital I/O, analog output, or temperature
acquisition systems can be added due to its modular design
Sepam range
MiCOM
PM102898

MiCOM protection provides the user with a choice of cost-optimized solutions for
specific protection requirements within the distribution network.

The MiCOM relay series offers comprehensive protective function solutions for
power supply systems as well as for various functional and hardware project
stages.

Power meter and circuit monitors


MiCOM range
The PowerLogic power meter replaces a whole set of basic analog meters.
PM105362
PE57123

This cost-effective, high-performance meter provides a wide range of accurate


true-rms metering values.

The PowerLogic series 3000/4000 circuit monitor is designed for critical power
users and large energy consumers, to provide the information needed to confidently
PowerLogic enter the evolving world of deregulation.
range
It can be adapted to meter almost any time-of-use or real-time rate.
PE90501

VAMP arc fault protection relay


The VAMP arc protection unit detects an arc flash in an installation and trips the
feeding breaker. The unique arc fault protection functionality enhances the safety
of both people and property and has made VAMP a leading brand in arc protection
VAMP 120 relays worldwide.

schneider-electric.com HVX embedded pole catalog | 15


Overview Schneider Electric Services
Peace of mind throughout your
installation life cycle

How can you cut costs and Plan


improve performance at the Schneider Electric helps you plan the full design and execution of your solution,
same time? looking at how to secure your process and optimize your time:
Technical feasibility studies: Designing a solution in your environment
When it comes to your electrical distribution
Preliminary design: Accelerated turnaround time to reach a final solution design
infrastructure, the answer is straightforward:
get professional expertise.

Life Cycle Services Install


Life cycle services Schneider Electric will help you to install efficient, reliable, and safe solutions based
on your plans.
Plan
DB408843

What are my options? Project management: Completing your projects on time and within budget
Commissioning: Ensuring your actual performance versus design, through
on-site testing and commissioning, and tools and procedures
Install
How do I install and commission?
Operate
Schneider Electric helps you maximize your installation uptime and control your
Operate capital expenditure through its services offer.
How do I operate and maintain?
Asset operation solutions: Providing the information you need to increase
safety, enhance installation performance, and optimize asset maintenance and
investment
Optimize
How do I optimize? Advantage service plans: Customized service plans that cover preventive,
predictive, and corrective maintenance
On-site maintenance services: Delivering extensive knowledge and
Renew experience in electrical distribution maintenance
How do I renew my solution? Spare parts management: Ensuring spare parts availability and optimizing
your spare parts maintenance budget
PM105360

Technical training: Building the necessary skills and competencies to properly


and safely operate your installations. Specific training materials with documents
and videos are available. Please contact Schneider Electric

Optimize
Schneider Electric proposes recommendations for improved safety, availability,
reliability, and quality.
MP4 electrical assessment: MP4 is the Schneider Electric program for a
site-wide assessment of the electrical installation in order to evaluate risks and
define improvements

60,000+ Renew
Ecofit projects worldwide
Schneider Electric extends the life of your system while providing upgrades.
110+
We offer to take full responsibility for the end-of-life processing of old electrical
Ecofit customized solutions
equipment.
260+ ECOFIT: Keep up to date and improve the performance of your electrical
Ecofit ready solutions, tested for repeatable installations (LV, MV, protection relays, etc.)
success for Schneider Electric and third-party
legacy switchgear MV product end of life: Recycle and recover outdated equipment with end-
of-life services

16 | HVX embedded pole catalog schneider-electric.com


Overview Environment

Environmental performance
PM105623

Schneider Electric is committed to a long-term environmental approach.


The production site is certified to ISO 14001.

The materials used in HVX, insulators, and conductors are identified and can easily
be separated and recycled, as detailed in the "Product Environment Profile" file.
An end-of-service-life manual details procedures for dismantling and processing
components.

HVX fullfills the European regulations of RoHS (Restriction of Hazardous


Substancies) and REACH (Registration, Evaluation, Authorisation and Restriction of
Chemicals).
PM105397
PM105624

PM105625

PM105626
PM105627

RoHS
Compliant

schneider-electric.com HVX embedded pole catalog | 17


HVX range

18 | HVX embedded pole catalog schneider-electric.com


Overview 20

Selection guide 23
HVX 12 kV 23
HVX 17 kV 24
HVX 24 kV 25

schneider-electric.com HVX embedded pole catalog | 19


630/1,250/1,600/2,000/2,500

HVX range Overview


Introduction

HVX fixed and withdrawable types


PM105628

Rated Rated Rated


voltage short- current
(kV) circuit (A)
current
(kA)
12 25
31.5
630/1,250/1,600/2,000/2,500/3,150/4,000*
40
50
17.5 25
630/1,250/1,600/2,000/2,500/3,150/4,000*
31.5
40
1,250/1,600/2,000/2,500/3,150/4,000*
50
24 25
630/1,250/1,600/2,000/2,500
31.5
* Forced cooling
PM105606

HVX fixed type


The HVX fixed version is equipped with drilled and threaded copper connection
terminals at the top and bottom.
The shape and dimensions of conductors are determined by the panel builder
according to the dielectric withstand and temperature rise characteristics of the
whole connection system.
Please contact your Schneider Electric sales representative to request an HVX
Integration Guide for more information.
PM105621

PM105629

Up to 1250 A 1600 A up to 4000 A


rated current rated current

20 | HVX embedded pole catalog schneider-electric.com


HVX range Overview
Introduction

HVX withdrawable type


PM105605

The HVX withdrawable version requires a racking trolley, arms, and tulip-type
contacts for connection to the switchgear power circuit, and an LV connector to
connect the auxiliary circuits.

Racking trolley
PM105618

The HVX racking trolley allows panel builders to design switchgear solutions with
enhanced safety features. It has a robust interlocking system with the switchgear
door, LV plug, circuit breaker, and ground switch. It can be equipped with an
electric motor for remote racking from the control room.

Racking trolley

Arms Arms
The shape and size of HVX arms depend on the rated lightning impulse withstand
PM105630

voltage, the rated normal current, and the racking trolley stroke.

Tulip-type contacts
The shape of HVX contacts is tulip-type. The size depends on the rated current to
provide a maximum contact surface optimizing heat dissipation and offering good
Tulip-type contacts compensation characteristics for electrodynamic forces. The panel builder needs
to provide fixed-type contacts with the correct shape, tolerance, and material
characteristics compatible with the HVX tulip-type contacts.

LV connector
PM105631

The HVX LV connector enables the auxiliary circuits to be connected to the


switchgear control cabinet with the circuit breaker in either the disconnected or the
service position.
LV connector, cubicle side
The HVX LV connector is interlocked with the circuit breaker operating mechanism
to prevent any manual close commands without the LV connector latched onto the
PM105631

circuit breaker frame.

LV connector circuit breaker side

schneider-electric.com HVX embedded pole catalog | 21


HVX range Overview
Main characteristics

Main electrical characteristics according


to IEC 62271-100

Common characteristics
Rated voltage Ur kV 12 17 24
Rated power frequency withstand voltage Ud kV 28 (1) 38 50
Rated lightening impulse withstand voltage Up kV 75 95 125
Rated frequency f Hz 50/60 50/60 50/60
Rated short circuit breaking current Isc kA 25-31.5-40-50 25-31.5-40-50 25-31,5
Rated short circuit making current @50 Hz Ip kA 2,5 Isc 2,5 Isc 2,5 Isc
Rated short circuit making current @60 Hz Ip kA 2,6 Isc 2,6 Isc 2,6 Isc
Rated duration of short circuit tk s 3 3 3
Operating sequence O-0.3s-CO-3 min-CO
O-180s-CO-3 min-CO
O-0.3s-CO-15s-CO (3)
Opening time ms 40-70 40-70 40-70
Arcing time ms 15 15 15
Closing time ms 30-60 30-60 30-60
Service temperature C -25 to +40 -25 to +40 -25 to +40
Mechanical endurance M2 M2 M2
Electrical endurance E2 E2 (2) E2 (3)
Line charging breaking current A 10 10 10
C2 C2 C2
Cable charging breaking current A 25 25 31,5
C2 C2 C2
Single capacitor bank and back-to-back capacitor bank breaking capacity (3) (3) (3)

Higher number of operation cycles upon maintenance plan 30,000 30,000 30,000
Number of switching cycles vacuum interrupter at rated current 30,000 (3) 30,000 (3) 30,000 (3)
Number of full short circuit operations 100 (3) 100 (3) 100 (3)

(1) Please contact Schneider Electric for 42 kV 5 min


(2) Please contact Schneider Electric for 50 kA
(3) Please contact Schneider Electric

22 | HVX embedded pole catalog schneider-electric.com


HVX range Selection guide
HVX 12 kV
Fixed and withdrawable type
PM105606

HVX - -
Rated voltage (kV) Type

Value Code Designation Code


12 12 Withdrawable E
17.5 17 Rated current (A) Fixed F
24 24
Value Code
PM105605

Rated short-circuit 630 06


current (kA) 1,250 12
Value Code 1,600 16 Phase distance (mm)

25 25 2,000 20 Value Code


31.5 31 2,500 25 150 150
40 40 3,150 31 210 210
50 50 4,000 40 275 275

Model Rated Rated Rated Phase distance Contact Weight


Withdrawable

voltage short- current (mm) distance (kg)


(kV) circuit (A) (mm)
current
Fixed

(kA)
150 210 275 F E
HVX 12-25-06 630 p p p 205 95 105
HVX 12-25-12 1,250 p p p 205 105 115
HVX 12-25-16 1,600 p p 310 175 200
HVX 12-25-20 F E 12 25 2,000 p p 310 175 200
HVX 12-25-25 2,500 p 310 195 250
HVX 12-25-31 3,150 p 310 195 250
HVX 12-25-40 4,000 * p 310 195 250
HVX 12-31-06 630 p p p 205 95 105
HVX 12-31-12 1,250 p p p 205 105 115
HVX 12-31-16 1,600 p p 310 175 200
HVX 12-31-20 F E 12 31 2,000 p p 310 175 200
HVX 12-31-25 2,500 p 310 195 250
HVX 12-31-31 3,150 p 310 195 250
HVX 12-31-40 4,000 * p 310 195 250
HVX 12-40-12 1,250 p p 310 175 200
HVX 12-40-16 1,600 p p 310 175 200
HVX 12-40-20 2,000 p p 310 175 200
F E 12 40
HVX 12-40-25 2,500 p 310 195 250
HVX 12-40-31 3,150 p 310 195 250
HVX 12-40-40 4,000 * p 310 195 250
HVX 12-50-12 1,250 p p 310 195 200
HVX 12-50-16 1,600 p p 310 195 200
HVX 12-50-20 2,000 p p 310 195 200
F E 12 50
HVX 12-50-25 2,500 p 310 195 250
HVX 12-50-31 3,150 p 310 195 250
HVX 12-50-40 4,000 * p 310 195 250
* Forced cooling

schneider-electric.com HVX embedded pole catalog | 23


HVX range Selection guide
HVX 17 kV
Fixed and withdrawable type

Model Rated Rated Rated Phase distance Contact Weight

Withdrawable
voltage short- current (mm) distance (kg)
(kV) circuit (A) (mm)
current

Fixed
(kA)
150 210 275 F E
HVX 17-25-06 630 p p p 205 90/95 105
HVX 17-25-12 1,250 p p p 205 105 115
HVX 17-25-16 1,600 p p 310 175 200
HVX 17-25-20 F E 17 25 2,000 p p 310 175 200
HVX 17-25-25 2,500 p 310 195 250
HVX 17-25-31 3,150 p 310 195 250
HVX 17-25-40 4,000 * p 310 195 250
HVX 17-31-06 630 p p p 205 95 105
HVX 17-31-12 1,250 p p p 205 105 115
HVX 17-31-16 1,600 p p 310 175 200
HVX 17-31-20 F E 17 31 2,000 p p 310 175 200
HVX 17-31-25 2,500 p 310 195 250
HVX 17-31-31 3,150 p 310 195 250
HVX 17-31-40 4,000 * p 310 195 250
HVX 17-40-12 1,250 p p 310 175 200
HVX 17-40-16 1,600 p p 310 175 200
HVX 17-40-20 2,000 p p 310 175 200
F E 17 40
HVX 17-40-25 2,500 p 310 195 250
HVX 17-40-31 3,150 p 310 195 250
HVX 17-40-40 4,000 * p 310 195 250
HVX 17-50-12 1,250 p p 310 195 200
HVX 17-50-16 1,600 p p 310 195 200
HVX 17-50-20 2,000 p p 310 195 200
F E 17 50
HVX 17-50-25 2,500 p 310 195 250
HVX 17-50-31 3,150 p 310 195 250
HVX 17-50-40 4,000 * p 310 195 250
* Forced cooling

24 | HVX embedded pole catalog schneider-electric.com


HVX range Selection guide
HVX 24 kV
Fixed and withdrawable type

Model Rated Rated Rated Phase distance Contact Weight

Withdrawable
voltage short- current (mm) distance (kg)
(kV) circuit (A) (mm)
current

Fixed
(kA)
150 210 275 F E
HVX 24-25-06 630 p p 310 175 190
HVX 24-25-12 1,250 p p 310 175 190
HVX 24-25-16 F E 24 25 1,600 p 310 255 280
HVX 24-25-20 2,000 p 310 255 280
HVX 24-25-25 2,500 p 310 255 280
HVX 24-31-06 630 p 310 255 280
HVX 24-31-12 1,250 p 310 255 280
HVX 24-31-16 F E 24 31 1,600 p 310 255 280
HVX 24-31-20 2,000 p 310 255 280
HVX 24-31-25 2,500 p 310 255 280

schneider-electric.com HVX embedded pole catalog | 25


Functions and
characteristics

26 | HVX embedded pole catalog schneider-electric.com


Opening and closing functions 28

Charging functions 30

Low voltage connection 31

Racking trolley 32

Locking functions 33

Other complementary devices 34

Secondary wiring diagrams 35

schneider-electric.com HVX embedded pole catalog | 27


Functions and Opening and closing functions
characteristics

Opening release
F11/F12 Closing release Operating mechanism
F2
Undervoltage Opening release F11/F12
release F4
Anti-pumping The F11/F12 release is used to open the circuit breaker. The release coil is actuated
relay K01 by the auxiliary power supply.
The coil is designed for short operation only; it is therefore routed via an auxiliary
DM105013

switch contact controlled by the circuit breaker shaft, and upon release it interrupts
the current circuit.

Characteristics
Power supply V a.c. 110/120*/220/230
V d.c. 24*/48/60/110/125/220
Operating range V a.c. 0.85 to 1.1 Ua
V d.c. 0.7 to 1.1 Ua
Consumption V a.c. 180 W
V d.c. 180 W
* Please contact Schneider Electric

Closing release F2
The F2 release is used to close the circuit breaker. The release coil is actuated by
the auxiliary power supply.
The coil is designed for short operation only; it is therefore routed via an auxiliary
Overcurrent
switch contact controlled by the circuit breaker shaft, and upon release it interrupts
release F3
the current circuit.

Characteristics
Power supply V a.c. 110/120*/220/230
DM103419

V d.c. 24*/48/60/110/125/220
Operating range V a.c. 0.85 to 1.1 Ua
V d.c. 0.85 to 1.1 Ua
Consumption V a.c. 180 W
Opening release
F11/F12 V d.c. 180 W
* Please contact Schneider Electric

Overcurrent release F3
The F3 release is used to open the circuit breaker in the event of overcurrent or
DM103419

short-circuit.
Closing release The power to activate the overcurrent release comes from the current transformer
F2 of the high voltage circuit, not from the auxiliary voltage supply. Thus the tripping
function of this coil is independent of the auxiliary voltage supply.

Characteristics
Rated supply current A 0.5/1/5
Operating range A 90%-110% of rated supply current
Consumption W 180
DM103420

Overcurrent release
F3

28 | HVX embedded pole catalog schneider-electric.com


Functions and Opening and closing functions
characteristics

Undervoltage release F4
DM103421

The F4 release opens the circuit breaker automatically, when the auxiliary voltage
drops below a certain level. Thus the undervoltage release protects the circuit
breaker against a drop or loss of the auxiliary voltage supply.
Undervoltage release
F4
Characteristics
Power supply V a.c. 110/220/230
V d.c. 24*/48/60/110/125/220
Operating range Opening 0.35 to 0 Uop
Consumption V a.c. approx. 12 W
V d.c. approx. 12 W
* Please contact Schneider Electric
DM103424

Anti-pumping relay K01


Anti-pumping relay
K01 The anti-pumping relay prevents continous closing and opening of the circuit
breaker (anti-pumping).
If both ON and OFF commands are permanently present on the circuit breaker
at the same time, the circuit breaker will carry out a CLOSE-OPEN sequence; it
remains in this open position until the CLOSE command is discontinued and a new
CLOSE command is issued again.

schneider-electric.com HVX embedded pole catalog | 29


Functions and Charging functions
characteristics
Circuit breaker charging motor and
auxiliary contacts

Auxiliary switch in
switching position Operating mechanism
S11/S12
Auxiliary switch in
charging position S2
Charging motor M1
The electric motor charges the spring of the actuator automatically as soon as it is
DM105014

discharged. This allows the circuit breaker to switch the second close-open-cycle
within the rated operating sequence.

Characteristics
Power supply V a.c. 110/220/230
V d.c. 24*/48/60/110/125/220
Operating range V a.c. 0.85 to 1.1 Ua
V d.c. 0.85 to 1.1 Ua
Consumption V a.c. approx. 100 W
V d.c. approx. 100 W
* Please contact Schneider Electric

Operating time of motor


Motor charging time 4~12s

Open/closed auxiliary contacts


The number of contacts available depends on the options chosen on the operating
Charging motor M1 mechanism.
In the basic configuration, the circuit breakers operating mechanism comprises
a total of:
8 normally closed (NC) contacts; some contacts are already used, free contacts
DM103426

as per wiring diagram

Charging motor M1 8 normally open (NO) contacts; some contacts are already used, free contacts
as per wiring diagram

Auxiliary switch in switching position S11/S12


The auxiliary contacts in switching position indicate the ON/OFF status of the circuit
breaker. They are actuated directly by the main shaft of the circuit breaker via a
DM105046

mechanical link. The position of the main shaft corresponds to the position of the
auxiliary switches and indicates whether the breaker is in ON or OFF.
Auxiliary switch in switching
position S11/S12
Characteristics
Rated operational voltage (Ue) V a.c./ d.c. 230
Rated operational current (Ic) A 15
Rated short-time withstand current (Icw) A 250 (during 3s)
Rated breaking capacity with inductive charge L/R=10 ms L/R=20 ms
Voltage V d.c. 48 125 125 220
Charging current A 10 3,8 2 1
DM103423

Auxiliary switch in charging position S2


The auxiliary switch is used to control the charging motor and to indicate the
Auxiliary switch in
charging status..
charging position S2
When contact S2 is closed, the motor is charging the spring of the driving
mechanism automatically. When charging is complete, it breaks the electrical
charging circuit.
For technical datas of S2 please refer to the table in S11/S12.

30 | HVX embedded pole catalog schneider-electric.com


Functions and Low voltage connection
characteristics

Withdrawable version
PM105632

An optional flexible LV plug and socket system enables connection of the circuit
breaker auxiliary circuits to the switchgear control cabinet. It consists of an elbow-
type connector mounted on the frame of the circuit breaker and a removable
connector with 58 male pins mounted on a 525 mm flexible duct. This LV connector
is to be connected to the LV cabinet of the cubicle.
The counter part connector equipped with the female contacts is assembled in the
low voltage cabinet of the switchgear.
PM105631

The LV plug collects electrical commands and status information from the circuit
LV connector, breaker terminal blocks and from the racking trolley terminal blocks. The number
cubicle side of pins in the LV plug (maximum 58) may limit the number of available position
contacts for the switchgear LV cabinet.
For the withdrawable version, the LV plug is interlocked with the racking trolley and
LV connector,
circuit breaker the operating mechanism to prevent any manual close commands without the LV
side plug latched onto the circuit breaker frame.

Fixed version
PM105621

The breaker is equipped with a set of terminal blocks or with an LV plug to connect
the circuit breaker auxiliary circuit with the LV wiring from the LV box.

schneider-electric.com HVX embedded pole catalog | 31


Functions and Racking trolley
characteristics

Withdrawable version
DM105016

In the withdrawable version the HVX is mounted on a racking trolley to move the
circuit breaker between test position and service position .
The HVX racking trolley comprises:
A frame with 4 wheels for moving the circuit breaker
A drive system with a rotating shaft to move the circuit breaker inside the
switchgear compartment
An optional motor drive for electrical operation
A set of auxiliary contacts to indicate the service or withdrawn position of the
circuit breaker
A set of mechanical levers to interlock the trolley
A system to latch the racking trolley to the switchgear frame to withstand the
mechanical forces of the short circuit
An interlock between the racking trolley and the door of the panel

The circuit breaker is equipped with devices to operate the shutter mechanism.

Grounding
DM105018

DM105019

The racking trolley is grounded using an additional grounding system on the bottom
of the trolley. On request this can be equipped with grounding bars on the sides of
the racking trolley.
Underneath grounding Side grounding

32 | HVX embedded pole catalog schneider-electric.com


Functions and Locking functions
characteristics

HVX withdrawable version interlocking


DM105020

The following table describes the interlocking functions available on the


withdrawable version of HVX.

How to use the table


Each box describes the possible status of parts interlocked with the circuit breaker
at a given status.
Removed: The circuit breaker with the racking trolley is extracted from the
switchgear with the racking trolley
Disconnected: The circuit breaker is inside the switchgear compartment; its
power connections are separated from the switchgear contacts by shutters and
the LV auxiliary circuits are connected
Intermediate: The circuit breaker is moving from the disconnected position
to the service position or vice versa
Service: The circuit breaker power connections are connected to the switchgear
Interlock contacts, the LV auxiliary circuits are connected, and the switchgear door is
closed and locked
DM105021

Circuit breaker status


DM105023

DM105024

DM105025
200
Racking-in

Racking-out

Parts Removed Disconnected Intermediate Service


Compartment shutters Open Prohibited Not possible Operating Mandatory
Closed Mandatory Mandatory Not possible
Switchgear door Open Possible Possible (1) Prohibited Prohibited
Closed Possible Preferred Mandatory (2) Mandatory
Door handle Unlocked Unlocked Locked (2) Locked (2)
LV connector Disconnected Mandatory Possible (1) Prohibited Prohibited
Connected Not possible Preferred Mandatory (3) Mandatory (3)
CB operating mechanism Open Possible Preferred Mandatory Possible
Closed Possible Possible Prohibited (4) Possible (5)
Ground switch position Open Possible Possible Mandatory Mandatory
Closed Possible Possible (1) Prohibited Prohibited
(1) Impossible to rack-in (4) Impossible to activate the close command
(2) Impossible to access the CB compartment (5) Impossible to rack-out
(3) Impossible to access the LV plug

Specific interlocking
DM105022

This is a mechanical device, which allows the panel builders to create their own
interlock. Fixed type circuit breakers, which are converted into a withdrawable
circuit breaker by the customer using the customer's own racking trolley, need to
have an interlock between the circuit breaker and the trolley.

This part is installed during the manufacturing process.

schneider-electric.com HVX embedded pole catalog | 33


Functions and Other complementary devices
characteristics

Blocking magnet on
racking trolley Y1

DM105026

DM105027
Operation counter
DM105028

Y1 position

Y0
position

Operation counter
DM103425

Operation counter
The operation counter installed on the operating interface records the number of
opening/closing cycles.
DM103427

Blocking magnet
Blocking magnet
on closing Y1
Blocking magnet on closing Y1
If the controlling power supply to operate this magnet is lost, the circuit breaker
cannot perform the normal closing operation (including manual closing).

Blocking magnet on racking trolley Y0


If the secondary controlling power supply is lost, the trolley cannot be racked in or
out (either manually or by motorization).
DM103428

Blocking magnet
on racking trolley
Y0

Insulating sleeves for breaker


DM105029

Insulating sleeves For fixed type breakers that are converted to withdrawable types, insulating sleeves
for breaker can be ordered to improve the dielectric withstand at the contact point.

34 | HVX embedded pole catalog schneider-electric.com


DM105030

-Q1
-Q0

schneider-electric.com
trolley

1
Functions and

1
characteristics

-Q0

service
position

test
position

Drawing number: ASX000525-01

1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)
device

-Q0 Units incorporated in the circuit breaker according to the order -Q1 Units incorporated in the switchgear trolley according to the order

-M1 Motor for operating mechanism -S8 Test position switch


-S11/12 Auxiliary switch position indicator -S9 Service position switch
-S2 Micro switch for motor control -Y0 Blocking magnet for trolley (optional)
-S6 Micro switch for blocking magnet
-Y1 Blocking magnet for closing (optional)
-F11 Opening release
-F12 Opening release (optional)
-F2 Closing release
-F3 Overcurrent release (optional)
-F4 Undervoltage release (optional)
-K01 Anti-pumping relay
-S61 Micro switch actuated by trolley operation or trolley not in end position
Secondary wiring diagrams
HVX withdrawable type with anti-pumping

HVX embedded pole catalog | 35


DM105031

-Q0 -Q1

trolley

1
1
Functions and
characteristics

36 | HVX embedded pole catalog


-Q0

service
position

test
position

Drawing number: ASX000525-02

1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)

-Q0 Units incorporated in the circuit breaker according to the order -Q1 Units incorporated in the switchgear trolley according to the order

-M1 Motor for operating mechanism -S8 Test position switch


-S11/12 Auxiliary switch position indicator -S9 Service position switch
-S2 Micro switch for motor control -Y0 Blocking magnet for trolley (optional)
-S6 Micro switch for blocking magnet
-Y1 Blocking magnet for closing (optional)
-F11 Opening release
-F12 Opening release (optional)
-F2 Closing release
anti-pumping device

-F3 Overcurrent release (optional)


-F4 Undervoltage release (optional)
-K01 Anti-pumping relay
-S61 Micro switch actuated by trolley operation or trolley not in end position
HVX withdrawable type without
Secondary wiring diagrams

schneider-electric.com
DM105032

-Q0

trolley

schneider-electric.com
1
Functions and
characteristics

-Q0

Drawing number: ASX000525-03

1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)

-Q0 Units incorporated in the circuit breaker according to the order

-M1 Motor for operating mechanism -F12 Opening release (optional)


-S11/12 Auxiliary switch position indicator -F2 Closing release
-S2 Micro switch for motor control -F3 Overcurrent release (optional)
-S6 Micro switch for blocking magnet -F4 Undervoltage release (optional)
-Y1 Blocking magnet for closing (optional) -K01 Anti-pumping relay
-F11 Opening release -S61 Micro switch actuated by operation
Secondary wiring diagrams
HVX fixed type with anti-pumping device

HVX embedded pole catalog | 37


DM105033

-Q0

trolley

1
Functions and
characteristics

38 | HVX embedded pole catalog


1

-Q0
device

Drawing number: ASX000525-04

1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)

-Q0 Units incorporated in the circuit breaker according to the order

-M1 Motor for operating mechanism -F12 Opening release (optional)


-S11/12 Auxiliary switch position indicator -F2 Closing release
-S2 Micro switch for motor control -F3 Overcurrent release (optional)
-S6 Micro switch for blocking magnet -F4 Undervoltage release (optional)
-Y1 Blocking magnet for closing (optional) -K01 Anti-pumping relay
-F11 Opening release -S61 Micro switch actuated by operation
HVX fixed type without anti-pumping
Secondary wiring diagrams

schneider-electric.com
DM105034

-Q1
-Q0

trolley

schneider-electric.com
1
Functions and
characteristics

-Q0
2

service
position

test
position

Drawing number: ASX000525-05

1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)
4. If circuit breaker is without blocking magnet for trolley Y0, refer to 2 in the wiring diagram

-Q0 Units incorporated in the circuit breaker according to the order -Q1 Units incorporated in the switchgear trolley according to the order

-M1 Motor for operating mechanism -S8 Test position switch


-S11/12 Auxiliary switch position indicator -S9 Service position switch
-S2 Micro switch for motor control -Y0 Blocking magnet for trolley (optional)
-S6 Micro switch for blocking magnet -M2 Motor for racking trolley
-Y1 Blocking magnet for closing (optional)
-F11 Opening release
-F12 Opening release (optional)
-F2 Closing release
-F3 Overcurrent release (optional)
-F4 Undervoltage release (optional)
-K01 Anti-pumping relay
with anti-pumping device

-S61 Micro switch actuated by trolley operation or trolley not in end position
Secondary wiring diagrams
HVX motorized trolley withdrawable type

HVX embedded pole catalog | 39


DM105035

-Q1
-Q0

trolley

1
1
Functions and
characteristics

40 | HVX embedded pole catalog


2

-Q0
2

service
position
test
position

Drawing number: ASX000525-06


1. This circuit diagram shows the maximum circuit breaker equipment. The standard equipment does not include optional items. If optional items are required, these should be stated when placing the order.
2. Circuit breaker is in discharge and open position, racking trolley is in service position.
3. If circuit breaker is without blocking magnet for closing Y1, refer to 1 in the wiring diagram (no Y1, no S6)
4. If circuit breaker is without blocking magnet for trolley Y0, refer to 2 in the wiring diagram

-Q0 Units incorporated in the circuit breaker according to the order -Q1 Units incorporated in the switchgear trolley according to the order

-M1 Motor for operating mechanism -S8 Test position switch


-S11/12 Auxiliary switch position indicator -S9 Service position switch
-S2 Micro switch for motor control -Y0 Blocking magnet for trolley (optional)
-S6 Micro switch for blocking magnet -M2 Motor for racking trolley
-Y1 Blocking magnet for closing (optional)
-F11 Opening release
-F12 Opening release (optional)
-F2 Closing release
-F3 Overcurrent release (optional)
-F4 Undervoltage release (optional)
-K01 Anti-pumping relay
-S61 Micro switch actuated by trolley operation or trolley not in end position
without anti-pumping device
Secondary wiring diagrams
HVX motorized trolley withdrawable type

schneider-electric.com
Notes

schneider-electric.com HVX embedded pole catalog | 41


Dimensions

42 | HVX embedded pole catalog schneider-electric.com


HVX 12 kV withdrawable type 44

HVX 12/17.5 kV fixed type 46

HVX 17.5 kV withdrawable type 48

HVX 24 kV withdrawable type 50

HVX 24 kV fixed type 52

schneider-electric.com HVX embedded pole catalog | 43


Dimensions HVX 12 kV withdrawable type
Dimensions drawing

628.5
DM105036

L
624.5
43
35 86

12
93
55 55

205
622

523

35
297

260
HVX

154
146
83

76
4
19

25 320

C 370

D 383

13.5 E 13.5 437


313 296 200 50

A
P P

16
55

HVX 12 vacuum circuit breaker


Rated voltage (kV) 12
Rated short-circuit current (kA) 25; 31.5
Rated current (A) 630; 1,250

Rated current Rated Installation dimensions


(A) short-circuit (mm)
current (kA) P A C D E L
150 502 457 492 503 494
630 1,250 25 31.5 210 650 605 640 653 638
275 850 801 836 853 844

44 | HVX embedded pole catalog schneider-electric.com


Dimensions HVX 12 kV withdrawable type
Dimensions drawing
DM105037

L 606.5
43 602
35 86

NOTE3

M
NOTE2

310
55 55 NOTE1

W
H

707
297

280
HVX

165

76
119
4
C 25 320

D 370

13.5 E 13.5 383 200 50

359
293 296

P P

16
16 8.5
55

Note 1: For rated current 2,000 A


Note 2: For rated current 2,500 A
Note 3: Heat sink for rated current 2,500 A

Rated current Rated Installation dimensions


(A) short-circuit current (mm)
(kA) P A C D E L H M W
1,600 2,000 25 31.5 210 650 582 640 653 638 691.5 118 79
1,250 1,600 2,000 40 275 850 777 836 853 844 729.5
1,250 1,600 2,000 50 210 650 582 640 653 638 691.5 128 79
275 850 777 836 853 844 729.5
2,500 3,150 4,000 (1) 25 31.5 40 275 850 777 836 853 844 729.5 148 109
50 275 850 777 836 853 844 729.5 158 109

(1) The rated current 4,000 A requires forced cooling in the panel.

schneider-electric.com HVX embedded pole catalog | 45


Dimensions HVX 12/17.5 kV fixed type
Dimensions drawing
DM105038

427.5

406.5

D
112

55 55
A

205
480

438.5
214
254

217

30
HVX

48 250
119 4xM12
90
E
384.5
405.5

B VIEW A
P P

II
DETAIL B
50

M12 H25
11
22

2xM10 H15

11
22
30

M12 52

HVX vacuum circuit breaker


Rated voltage (kV) 12; 17.5
Rated short-circuit current (kA) 25; 31.5
Rated current (A) 630; 1,250

Rated current Rated Installation dimensions


(A) short-circuit (mm)
current (kA) P D E
150 460 400
630 1,250 25 31.5 210 576 520
275 706 650

46 | HVX embedded pole catalog schneider-electric.com


Dimensions HVX 12/17.5 kV fixed type
Dimensions drawing
DM105039

427
427
407.5
D 407.5
112
112

310
310

664
55 55
629

577

438.5
438.5
214

254

237
237

HVX

4xM12 119 48 250 48 250

E 385.5 385.5

Ir 2,000 A 405 Ir 2,500 A 405

P P VIEW A DETAIL B
40 80

M16 H32

C B

40
4xM12 H25

DETAIL C
170
F

M12 G

Ir 2,500 A

HVX vacuum circuit breaker


Rated voltage (kV) 12; 17.5
Rated short-circuit current (kA) 25; 31.5; 40; 50
Rated current (Ir) (A) 1,250; 1,600; 2,000; 2,500; 3,150; 4,000 (1)

Rated current Rated Installation dimensions


(A) short-circuit current (kA) (mm)
P D E F G
1,250 40 50 210 576 520 30 0
1,600 2,000 25 31.5 40 50 275 704 650 26 137.5
2,500 3,150 4,000 (1) 25 31.5 40 50 275 704 650 26 137.5

(1) The rated current 4,000 A requires forced cooling in the panel.

schneider-electric.com HVX embedded pole catalog | 47


Dimensions HVX 17.5 kV withdrawable
type
Dimensions drawing
DM105040

628.5
L 624.5
43 35 86

12
93
55 55

205
622

523

35
260
HVX

154

76
83

4
19

25 320

370
C
383
D
437
13.5 E 13.5
313 296 200 50

A
P P

16
55

HVX vacuum circuit breaker


Rated voltage (kV) 17.5
Rated short-circuit current (kA) 25; 31.5
Rated current (A) 630; 1,250

Rated current Rated Installation dimensions


(A) short-circuit (mm)
current (kA) P A C D E L
150 502 462 492 503 494
630 1,250 25 31.5 210 650 610 640 653 638
275 850 806 836 853 844

48 | HVX embedded pole catalog schneider-electric.com


Dimensions HVX 17.5 kV withdrawable
type
Dimensions drawing
DM105041

L 606.5

43 602
35 86

NOTE3

M
NOTE2

310
55 55 NOTE1

W
H

707
297

280
HVX
8

165
83

76
119 4
C 25 320

D 370

383 200 50
13.5 E 13.5
359
293 296

P P

16
16 8.5
55

Note 1: For rated current 2,000,A


Note 2: For rated current 2,500 A
Note 3: Heat sink for rated current 2,500 A

Rated current Rated Installation dimensions


(A) short-circuit current (mm)
(kA) P A C D E L H M W
1,600 2,000 25 31.5 210 650 582 640 653 638 691.5 118 79
1,250 1,600 2,000 40 275 850 777 836 853 844 729.5
1,250 1,600 2,000 50 210 650 582 640 653 638 691.5 128 79
275 850 777 836 853 844 729.5
2,500 3,150 4,000 (1) 25 31.5 40 275 850 777 836 853 844 729.5 148 109
2,500 3,150 50 275 850 777 836 853 844 729.5 158 109

(1) The rated current 4,000 A requires forced cooling in the panel

schneider-electric.com HVX embedded pole catalog | 49


Dimensions HVX 24 kV withdrawable type
Dimensions drawing
DM105042

L
43

12
35
55 55

310

787
775

93
74
119
296.5

325

167
HVX
82.5

76
18

370 49.5 4

18
25
C 50 383 300 50
447 38
D 2
441 306
E 13.5

P P

8
03
105

8-10mm

HVX vacuum circuit breaker


Rated voltage (kV) 24
Rated short-circuit current (kA) 25
Rated current (A) 630; 1,250

Rated current Rated Installation dimensions


(A) short-circuit (mm)
current (kA) P A C D E L
210 650 612 646 653 648
630 1,250 25
275 850 802 836 853 844

50 | HVX embedded pole catalog schneider-electric.com


Dimensions HVX 24 kV withdrawable type
Dimensions drawing
DM105043

844
43

12
NOTE1

M
NOTE2

148

310

827
815
55 55 NOTE3

M
W
119
296.5

325

167
82.5

76
25 370 4

22.5
18

802
50
836 49.5 38
853 13.5 383
447

850 A2 306 300 50


275 275

8
105

8-10mm

Note 1: Heat sink for rated current 2,500 A


Note 2: For rated current 3,150 A
Note 3: For rated current 4,000 A

HVX vacuum circuit breaker


Rated voltage (kV) 24
Rated short-circuit current (kA) 25; 31.5
Rated current (A) 1,600; 2,000; 2,500

Rated current Rated Installation dimensions


(A) short-circuit (mm)
current (kA) A
M W
1,600 2,000 2,500 25 31.5 135 79 431
630 1250 31.5 93 35 441

schneider-electric.com HVX embedded pole catalog | 51


Dimensions HVX 24 kV fixed type
Dimensions drawing

457.5
DM105044

D 436.5

112

310
55 55
635.5

630

438.5
214

254

282

HVX

4xM12 119 57.5 275


89.5
E 414

435

P P B VIEW A

DETAIL B

45
21

4xM8

M12 H35
21
27

M12 103

Rated current Rated Installation dimensions


(A) short-circuit current (kA) (mm)
P D E F G
210 600 560 27 103
630 1,250 25
275 756 700 26 137.5

52 | HVX embedded pole catalog schneider-electric.com


Dimensions HVX 24 kV fixed type
Dimensions drawing
DM105045

457.5 457.5
436.5 436.5
756
112 112

310

310
692
55 55
674

644
438.5

438.5
214

254

282

282
HVX

32.5 275 32.5 275


(4X) M12 119
89.5 89.5
700 414 414
Ir 2,000 A 435 Ir 2,500 A 435

B
VIEW A

DETAIL B
275 275
40 80

M16 H32

40
4xM12 H25
26

M12 137.5

HVX vacuum circuit breaker


Rated voltage Rated current Rated short-circuit current
(kV) (A) (kA)
24 1,600; 2,000; 2,500 25
630; 1,250; 1,600; 2,000; 2,500 31.5

schneider-electric.com HVX embedded pole catalog | 53


Order form

54 | HVX embedded pole catalog schneider-electric.com


HVX 12 kV/17.5 kV/24 kV order form 56
Basic equipment 56
Options and accessories 57

Spare parts 58

schneider-electric.com HVX embedded pole catalog | 55


Order form HVX 12 kV/17.5 kV/24 kV
order form
Basic equipment

To fill in the form, please check the boxes that match your choices.
Accessories: Each breaker requires 1 plug-in connector for cubicle and its
pins.
Basic equipment per order: 1 trolley hand crank and 1 charging mechanism
for every 5 circuit breakers. 5 is the minimum order quantity. Additional
accessories should be ordered as required.

Basic equipment Product range: HVX 12 kV 24 kV Quantity


Version type Withdrawable (E) Fixed (F)

Standard IEC 62271-100

Rated voltage 12 kV 17.5 kV 24 kV

630 A 1,250 A 1,600 A


Rated current
2,000 A 2,500 A 3,150 A 4000 A

Rated short-circuit
25 kA 31.5 kA 40 kA 50 kA
current

Phase distance (P) 150 mm 210 mm 275 mm

Opening release (F11)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V *

Closing release (F2)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V *

Charging motor (M1)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V *

Wiring diagram Standard Non-standard * Drawing No

Type of grounding (withdrawable type only)

Underneath grounding Side grounding Other

Low voltage plug type 58-pin plug-in connector Wiring by terminal block in the frame

Documentation language English

Type of rack-in Manual operating mechanism Motor operating mechanism

Motor drive for racking trolley

DC220V * DC110V * DC48V * Other (on request) *

Limited selection of voltages for motorisation of racking trolley available

Operating sequence

O-0.3 s-CO-3 min-CO Standard O-3 min-CO-3 min-CO O-0.3 s-CO-15 s-CO (on request)

56 | HVX embedded pole catalog schneider-electric.com


Order form HVX 12 kV/17.5 kV/24 kV
order form
Options and accessories

Optional equipment 1
Anti-pumping relay (K01) With Without

Capacitor application Yes No

Optional equipment 2
Blocking magnet on closing (Y1)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V * Without

Blocking magnet on racking trolley (Y0)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V * Without

Second opening release (F12)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V * Without

Undervoltage release (F4)

DC220V DC125V DC110V AC230V AC220V AC110V

DC60V * DC48V * DC24V * Without

Overcurrent release (F3) 0.5 A * 1A* 5A* Without

Interlock with door With Without

Delivery time * Longer delivery time is possible

Special conditions (please contact Schneider Electric Application Engineer)

1 ................................................................................................................................................................................................................................................................

2 ................................................................................................................................................................................................................................................................

(For other requirements, please write here and attach relevant drawings or accessories)

Accessories Drawing Quantity


Accessories for HVX withdrawable type

Crank for manual circuit breaker rackout CHD8000092R0114

Crank for charging the operating mechanism AGSH30498-01

58-pole connector with female pins, loose component for use in low voltage cabinet ASXN00151-01

Accessories for HVX fixed type

Crank for charging the operating mechanism AGSH30498-01

58-pole connector with female pins, loose component for use in low voltage cabinet ASXN00151-01

schneider-electric.com HVX embedded pole catalog | 57


Order form Spare parts

Opening release F11/F12 References


HVX voltage (kV) 12 17.5 24

DC p p p 24 V d.c. AGSH31484-01
p p p 48 V d.c. AGSH31483-01
DM103419-B

p p p 60 V d.c. AGSH31483-01
p p p 110 V d.c. AGSH31482-01
p p p 125 V d.c. AGSH31482-01
p p p 220 V d.c. AGSH31481-01
AC p p p 110 V a.c. AGSH31482-01
p p p 220/230 V a.c. AGSH31481-01

Closing release F2 References


HVX voltage (kV) 12 17.5 24
p p p 24 V d.c. AGSH31484-01
DC
p p p 48 V d.c. AGSH31483-01
DM103419-B

p p p 60 V d.c. AGSH31483-01
p p p 110 V d.c. AGSH31482-01
p p p 125 V d.c. AGSH31482-01
p p p 220 V d.c. AGSH31481-01
p p p 110 V a.c. AGSH31483-01
AC
p p p 220/230 V a.c. AGSH31482-01

Overcurrent release (F3) References


HVX voltage (kV) 12 17.5 24
p p p 0.5 A AGSH31482-01
Without F12
DM103419-B

p p p 1A AGSH31484-01

p p p 5A AVXN01742-01

p p p 5A AVXN01742-01
With F12

58 | HVX embedded pole catalog schneider-electric.com


Order form Spare parts

Charging motor (M1) References


HVX voltage (kV) 12 17.5 24

DC p p p 24 V d.c. AGSH33016-01
p p p 48 V d.c. AGSH33017-01
p p p 60 V d.c. AGSH33018-01
p p 110 V d.c. (Isc 31.5 kA, Ir 1,250 A) AGSH33019-01
p p 110 V d.c. (Isc 40kA or Isc 31.5 kA, Ir 1,600 A) AVXN00401-01
p p p 125 V d.c. AGSH33019-01
p p 220 V d.c. (Isc 31.5 kA, Ir 1,250A) AGSH33020-01
p p 220 V d.c. (Isc 40 kA or Isc 31.5 kA, Ir 1,600 A) AVXN00402-01
p 110 V d.c. (Isc 25 kA, Ir 1,250 A) AGSH33019-01
p 110 V d.c. (Isc 31.5 kA or Ir 1,600 A) AVXN00401-01
DM103426-B

p 220 V d.c. (Isc 25 kA, Ir 1,250 A) AGSH33020-01


p 220 V d.c. ( Isc 31.5 kA or Ir 1,600 A) AVXN00402-01
AC p p 110 V a.c. (Isc 31.5 kA, Ir 1,250 A) AGSH33019-01
p p 110 V a.c. (Isc 40 kA or Isc 31.5 kA, Ir 1,600 A) AVXN00401-01
p p 220 V a.c. (Isc 31.5 kA, Ir 1,250 A) AGSH33020-01
p p 220 V a.c. (Isc 40kA or Isc 31.5 kA, Ir 1,600 A) AVXN00402-01
p p 230 V a.c. (Isc 31.5 kA, Ir 1,250 A) AGSH33020-01
p p 230 V a.c. (Isc 40 kA or Isc 31.5 kA, Ir 1,600 A) AVXN00402-01
p 110 V a.c. (Isc 25 kA, Ir 1,250 A) AGSH33019-01
p 110 V a.c.(Isc 31.5 kA or Ir 1,600 A) AVXN00401-01
p 220 V a.c. (Isc 25 kA, Ir 1,250 A) AGSH33020-01
p 220 V a.c.(Isc 31.5 kA or Ir 1,600 A) AVXN00402-01
p 230 V a.c. (Isc 25 kA, Ir 1,250 A) AGSH33020-01
p 230 V a.c. (Isc 31.5 kA or Ir 1,600 A) AVXN00402-01

Operation counter References


HVX voltage (kV) 12 17.5 24
p p p Operation counter AGSH31816-01
DM103425-B

Operation
counter

Auxiliary contacts References


HVX voltage (kV) 12 17.5 24
DM105015

S11+S12 p p p 8NC+8NO AVX002294-03

schneider-electric.com HVX embedded pole catalog | 59


Order form Spare parts

Anti-pumping relay K01 References


HVX voltage (kV) 12 17.5 24

DC p p p 24 V d.c. AGSH31506-01
p p p 48 V d.c. AGSH31506-02
DM103424-B

p p p 60 V d.c. AGSH31506-03
p p p 110 V d.c. AGSH31506-04
p p p 125 V d.c. AGSH31506-05
p p p 220 V d.c. AGSH31506-06
AC p p p 110 V a.c. AVX001154-01
p p p 220/230 V a.c. AGSH31506-08

LV plug assembly on withdrawable/fixed circuit breaker References


HVX voltage (kV) 12 17.5 24

p p p 58-pole connector with male pins on CB side ASXN00152-01M


DM105047
DM105048

p p p 58-pole connector with female pins, ASXN00151-01S


loose component for use in low voltage cabinet

For the plug and socket system, pins, and special tools, please refer to the user
guide

Terminal block for fixed circuit breaker References


HVX voltage (kV) 12 17.5 24

p p p Terminal block AVXN01855-01M


DM105049

60 | HVX embedded pole catalog schneider-electric.com


Order form Spare parts

Racking trolley for manual operation References


HVX voltage (kV) 12 17.5 24

Without door p p Phase distance = 150 mm CHD8000037R0170


DM105050

interlock p p Phase distance = 210 mm, Isc 31.5 kA, Ir 1,250 A CHD8000037R0171
p p Phase distance = 210 mm, Isc 40 kA or Ir 1,600 A CHD8000037R0172
p p Phase distance = 275 mm CHD8000037R0173
p Phase distance = 210 mm CHD8020028R0126
p Phase distance = 275 mm CHD8020028R0127

With door p p Phase distance = 150 mm CHD8000037R0174


DM105051

interlock p p Phase distance = 210 mm, Isc 31.5 kA, Ir 1,250 A CHD8000037R0175
p p Phase distance = 210 mm, Isc 40 kA or Ir 1,600 A CHD8000037R0176
p p Phase distance = 275 mm CHD8000037R0177
p Phase distance = 210 mm CHD8020028R0148
p Phase distance = 275 mm CHD8020028R0149

Motorized racking trolley References


HVX voltage (kV) 12 17.5 24

Without door p p Phase distance = 210 mm, Isc 31.5 kA, Ir 1,250 A CHD8000037R0127
DM105052

interlock p p Phase distance = 210 mm, Isc 40 kA or Ir 1,600 A CHD8000037R0183


p p Phase distance = 275 mm CHD8000037R0128
p Phase distance = 275mm CHD8020028R0128
p p Phase distance = 210 mm, Isc 31.5 kA, Ir 1,250 A CHD8000037R0185
DM105017

With door
interlock p p Phase distance = 210 mm, Isc 40 kA or Ir 1,600 A CHD8000037R0186

p p Phase distance = 275 mm CHD8000037R0187

Motor for motorized racking trolley References


HVX voltage (kV) 12 17.5 24

Motor p p p DC 110 V d.c. AVXN00051-01


p p p DC 220 V d.c. AVXN00051-02
p p p DC 48 V d.c. AVXN00066-01
DM105053

Motor p p p 220 V d.c.-2 A (800/1,000 mm width cubicle) RL-TRC-10-A1


controller p p p 110 V d.c.-2.5 A (800 mm width cubicle) RL-TRC-10-B1
p p p 110 V d.c.-4.6 A (1,000 mm width cubicle) RL-TRC-10-B2
p p p 48 V d.c.-4.2 A (800 mm width cubicle) RL-TRC-10-C1
p p p 48 V d.c.-7.2 A (1,000 mm width cubicle) RL-TRC-10-C2

schneider-electric.com HVX embedded pole catalog | 61


Order form Spare parts

Micro switches inside the trolley (draw in/out position) References


HVX voltage (kV) 12 17.5 24

S8 p p p Micro switch inside the trolley CHD8100235P0102


DM105054

S9 p p p Micro switch inside the trolley CHD8100235P0102

Interlock References
HVX voltage (kV) 12 17.5 24

Racking trolley p p Withdrawable type CB AVXN00206-02M


DM105055

interlock p Withdrawable type CB AVXN00206-11M


Fixed type CB (to modify a fixed type CB into a
p p p AVXN00013-02M
withdrawable CB)
Micro switch p p p Draw-out interlock micro switch AVXN00128-01M
S61

Pushbuttons References
HVX voltage (kV) 12 17.5 24
p p p Close/open red/black pushbutton AVXN00336-01M
DM105056

Close Open

Front cover References


HVX voltage (kV) 12 17.5 24
p p Phase distance 150 mm AVXN01136-01M
DM105057

p p Phase distance 210 mm AVXN01136-02M


p p Phase distance 275 mm AVXN01136-03M
p Phase distance 210 mm AVXN01137-01M
p Phase distance 275 mm AVXN01137-02M

62 | HVX embedded pole catalog schneider-electric.com


Order form Spare parts

IP cover References
HVX voltage (kV) 12 17.5 24
p p L x H: 498 mm x 620 mm AVXN00340-01M
(PD=150mm, Isc 31.5 kA, Ir 1,250 A)
p p L x H: 638 mm x 620 mm AVXN00340-02M
(PD = 210 mm, Isc 31.5 kA, Ir 1,250 A)
p p L x H: 844 mm x 620 mm ASXN00686-01M
DM105058

(PD = 275 mm, Isc 31.5 kA, Ir 1,250 A)


p p L x H: 638 mm x 684 mm AVXN00340-03M
(PD=210mm, Isc 40 kA or Ir 1,600 A)
p p L x H: 844 mm x 684 mm AVXN00340-04M
(PD=275mm, Isc 40 kA or Ir 1,600 A)
p L x H: 638 mm x 775 mm ASXN00677-01M
(PD=210mm, Ir 1,250 A, Isc 25 kA)
p L x H: 844 mm x7 75 mm ASXN00677-02M
(PD=275mm, Ir 1,250 A, Isc 25 kA)
p L x H: 844 mm x 815 mm ASXN00672-03M
(PD=275mm, Ir 1,600 A or Isc 31.5 kA)

Shutter lifting device References


HVX voltage (kV) 12 17.5 24
p Phase distance 150 mm, Contact distance 205 mm AVXN00591-01M
p Phase distance 210 mm, Contact distance 205 mm AVXN00591-02M
p Phase distance 275 mm, Contact distance 205 mm AVXN00591-03M
p AVXN00591-21M
DM105059

Phase distance 210 mm, Contact distance 310 mm


p Phase distance 275 mm, Contact distance 310 mm AVXN00591-22M
p Phase distance 150 mm, Contact distance 205 mm AVXN00591-31M
p Phase distance 210 mm, Contact distance 205 mm AVXN00591-32M
p Phase distance 275 mm, Contact distance 205 mm AVXN00591-33M
p Phase distance 210 mm, Contact distance 310 mm AVXN00591-21M
p Phase distance 275 mm, Contact distance 310 mm AVXN00591-22M
p Phase distance 210 mm, Contact distance 310 mm ASXN00677-01M
p Phase distance 275 mm, Contact distance 310 mm ASXN00677-02M

Grounding of the racking trolley References


HVX voltage (kV) 12 17.5 24
Side grounding of trolley AVXN01856-01M
p p
(2 x AVXN00203-01 required)
DM105018

DM105019

Underneath grounding of trolley AVXN01856-03M


p p
(PD = 275 mm)
Underneath grounding of trolley AVXN01856-02M
p p
(PD =150 mm/210 mm)
Underneath grounding of trolley AVXN01856-04M
p
Underneath Side (PD = 210 mm)
grounding grounding Underneath grounding of trolley AVXN01856-05M
p
(PD = 275 mm)

schneider-electric.com HVX embedded pole catalog | 63


Order form Spare parts

AC magnets are operated with a rectifier

Blocking magnets on racking trolley (Y0) References


HVX voltage (kV) 12 17.5 24

DC p p p 24 V d.c. ASX000597-01
p p p 48 V d.c. ASX000597-03
p p p 60 V d.c. ASX000597-08
p p p 110 V d.c. ASX000597-04
DM103428-B

p p p 125 V d.c. ASX000597-05


p p p 220 V d.c. ASX000597-06
p p p 230 V d.c. ASX000597-07
AC p p p 110 V a.c. ASX000597-04
p p p 220 V a.c. ASX000597-06
p p p 230 V a.c. ASX000597-07
AC magnets are operated with a rectifier

Blocking magnets on closing (Y1) References


HVX voltage (kV) 12 17.5 24

DC p p p 24 V d.c. AVXN00186-08
p p p 48 V d.c. AVXN00186-06
DM103427-B

p p p 60 V d.c. AVXN00186-05
p p p 110 V d.c. AVXN00186-04
p p p 125 V d.c. AVXN00186-03
p p p 220 V d.c. AVXN00186-02
p p p 230 V d.c. AVXN00186-01

AC p p p 110 V a.c. AVXN00186-04


p p p 220 V a.c. AVXN00186-02
p p p 230 V a.c. AVXN00186-01

AC magnets are operated with a rectifier

Clusters References
HVX voltage (kV) 12 17.5 24
p p p Ir = 630 A, Isc 25 kA ASXN00439-06
p p p Ir = 630 A, Isc = 31.5 kA or Ir=1,250 A , Isc 31.5 kA ASXN00439-07
DM105060

p p Ir 1,250 A, Isc 40 kA or Ir = 1,600/2,000 A, Isc 50 kA ASXN00439-03


p p Ir = 2,500/3,150/4,000 A, Isc 40 kA ASXN00439-04
p p Ir = 2,500/3,150/4,000 A, Isc = 50 kA ASXN00439-05
p Ir = 1,600/2,000/2,500 A, Isc 31.5 kA ASXN00439-02

64 | HVX embedded pole catalog schneider-electric.com


Order form Spare parts

Arms References
HVX voltage (kV) 12 17.5 24
p Ir = 630 A, Isc 31.5 kA AVXN00372-01
p Ir = 1250 A, Isc 31.5 kA AVXN00672-01
p Ir = 630 A, Isc 31.5 kA AVX8000009R0101
DM105062

p Ir = 1250 A, Isc 31.5 kA AVX8000008R0101


p p Ir 1,250 A, Isc 40 kA or Ir = 1,600/2,000 A, Isc 50 kA ASXN00745-21
p p Ir = 2,500/3,150/4,000 A, Isc 50 kA ASXN00745-22
p Ir = 630/1,250 A, Isc 25 kA ASXN00661-01
p Ir = 630 A/1,250 A , Isc = 31.5 kA AVX8020001R0101
p Ir = 1,600/2,000 A/ 2,500 A, Isc 31.5 kA ASXN00661-21

Insulating sleeves References


HVX voltage (kV) 12 17.5 24

Ir 1,250 A Ir 1,250 A Ir 1,250 A


DM105061

CHD8000134P0104
Isc 31.5 kA Isc 31.5 kA Isc 25 kA

Ir 1,250 A Ir 1,250 A Ir 1,250 A


Isc 40 kA or Isc 40 kA or Isc 31.5 kA or NVE44473
Ir 1,600 A Ir 1,600 A Ir 1,600 A

schneider-electric.com HVX embedded pole catalog | 65


TOOLS

schneider-electric.com

This international web site allows you to access all the


SchneiderElectric solutions and product information via:
Comprehensive descriptions
Range datasheets
A download area
Product selectors

You can also access information dedicated to your


business and contact your Schneider Electric country
support.
PM103687

66 | HVX embedded pole catalog schneider-electric.com


TOOLS

Web selector

This site allows you to access the Schneider Electric


products in just two clicks via a comprehensive range of
datasheets, with direct links to:
Complete libraries: technical documents, catalogs,
FAQs, brochures
Selection guides from the e-catalog
Product discovery sites and their animations
You will also find illustrated overviews, news to which
you can subscribe, and a list of country contacts

Training

Training allows you to acquire the expertise (installation


design, work with power on, etc.) to increase efficiency
and improve customer service.

The training catalog includes beginners courses in


electrical distribution, knowledge of MV and LV
switchgear, operation and maintenance of installations,
and design of LV installations to give a few examples.

schneider-electric.com HVX embedded pole catalog | 67


Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies. All rights reserved.

Schneider Electric Industries SAS

35 rue Joseph Monier


92500 Rueil-Malmaison, France
Tel : +33 (0)1 41 29 70 00

www.schneider-electric.com

SAS capital social 928 298 512


954 503 439 RCS Nanterre

28, 07, 2016


NRJED316716EN