Protection
VAMP 50 series
with native IEC 61850 and arc flash protection
CUSTOMER BENEFITS
VAMP 50 family:
low and mid range relay series with IEC 61850
EASE OF USE
User-friendliness has always been a feature of
VAMP products, and the VAMP 50 seriesis no
exception. A great deal of effort has gone into
the design of the operational aspects of the new
products.
The rapid setting and download/upload is
achieved with the unique VAMPSET setting
software which dramatically improves usability.
Unicode support allows the menu text and
settings to be translated into various international
languages including for example Russian and
Chinese. The informative human machine
interface shows all of the required information for
the user with support of customised legend texts.
128 x 64 LCD
dot matrix display
Single line diagram and freely
assignable analogue values
VAMP 50 FAMILY
Unicode language support
HMI INTERFACE
Navigation Local port
push buttons USB interface
Function
buttons with:
User configurable
legend texts
The template for user
CB control legend texts is a part of the
Protection setting product documentation.
group selection The texts are printed on a
Freely programmable transparent film allowing
customisation of the relay.
Programmable LEDs
User configurable
legend texts
Remote port:
RS485, RS232 &
Ethernet (RJ-45 or fibre)
Arc, DI/DO
03
Protection VAMP 50 series
Cable
L> (CB, BB)
BB
CB CB
Cable Cable
Standard USB VAMP relays support standard COMTRADE type disturbance recording files which can be
communication uploaded/downloaded for evaluation of any network event recorded.
cable can be used.
The phase sequences for currents and voltages can be read on-line from the clear and explicit
phasor diagram screen for easy commissioning of the relay .
The VAMPSET software
is future-proof, supporting future
updates and new VAMP products. VAMP 50 VAMP 52 VAMP 55
3xI 3xI
Analog inputs 4xU
1 x Io 1 x Io, 1 x U
Digital inputs 2 (7) 2 (7) 2 (7)
I2 Current unbalance
Voltage sags / 1 1 3
U Voltage sags / swells
swells
Analog mA Any measured or calculated value, freely scalable,
AO
output, 1 channel optional
Control
Digital inputs Number of digital inputs (max) 7 7 7 7
Object status
Single line diagram, 8 objects 8 8 8 8
indication
Local and 6 6 6 6
Number of controllable objects
remote control
Interlocking
Configurable
and logic
Condition monitoring
Trip circuit TCS Trip Circuit Supervision
TCS Trip Circuit Supervision with DI for T5...T8
CT Supervision CT Supervision
VT Supervision VT Supervision/Fuse failure supervision
CB wear Breaker wear
07
Protection VAMP 50 series
Protection stages
User-friendliness is also a built-in feature of protection stages, where setting The relay has a large number of standard inverse
views are graphically displayed in the relay and VAMPSET HMI. Disabled curves to adopt various protection requirements.
protection stages are hidden from the menu in order to display only the Unique protection curves can be applied when
necessary information. Protection stages come with two setting groups to standard IEC or IEEE curves do not provide
enable automatic transfer from main setting to alternative setting. This required protection selectivity.
change can be universal for the entire relay or or based on protection
function. Protection
Feeder Motor Voltage
Type of fault. IEEE Device No. IEC Symbol Protection function / measurement 50 52 52 55
50/51 3I > Three-phase non-directional overcurrent, low-set stage, definite or inverse time
Short circuit 50/51 3l >> Three-phase non-directional overcurrent, high-set stage, definite time
50/51 3l >>> Three-phase non-directional overcurrent, high-set stage, definite time
Earth-fault 50N/51N l0 > Non-directional earth-fault, low-set stage, sensitive, definite or inverse time
50N/51N l0 >> Non-directional earth-fault, high-set stage, definite time
50N/51N l0 >>> Non-directional earth-fault, high-set stage, definite time
50N/51N l0 >>>> Non-directional earth-fault, high-set stage, definite time
67N-IEF l 0T Intermittent transient intermittent earth-fault protection
67N or 50N/51N l > Directional or non directional earth-fault, low-set stage, sensitive, definite or inverse time
67N or 50N/51N l >> Directional or non dir. earth-fault, high-set stage, definite or inverse time
59N U0> Residual overvoltage, low-set stage
59N U0>> Residual overvoltage, high-set stage
50N/51N U0>>> Residual overvoltage, high-set stage
59N U0>> Restricted earth fault (application)
59N U0>>> Residual overvoltage, high-set stage
50N/51N REF Restricted earth fault (application)
49M T> Three-phase thermal overload (motors & generators)
Overload 49F T> Three-phase thermal overload (feeders & cables)
59 1U>/3U> One-/three-phase overvoltage, low-set stage 1 1 3
59 1U>>/3U>> One-/three-phase overvoltage, high-set stage 1 1 3
59 1U>>>/3U>>> One-/three-phase overvoltage, high-set stage 1 1 3
59 3U>>>> Three-phase overvoltage, high-set stage 3
59 3U>>>>> Three-phase overvoltage, high-set stage 3
Voltage 24 Uf >, Uf >> Volts/hertz overexcitation protection
27 1U</3U< One-/three-phase undervoltage, low-set stage 1 1 3
n = number of 1 1 3
voltage channels 27 1U<</3U<< One-/three-phase undervoltage, high-set stage
27 1U<<</3U<<< One-/three-phase undervoltage, instantaneous stage 1 1 3
27 3U<<<< Three-phase undervoltage, instantaneous stage 3
27 3U<<<<< Three-phase undervoltage, instantaneous stage 3
27P U1<, U1<<, U1<<< Three-phase undervoltage, instantaneous stage stage for generator applications
47 U2>, U2>>, U2>>> Negative sequence overvoltage
Arc protection 50ARC/50NARC 3 I> / I0>, L> Electrical arc protection stage, point sensors, optional
79 O --> I Auto-reclosure
68 Inrush and cold load detection
46 I2 / I1 > Current unbalance protection (in feeder mode)
46 I2 > Phase unbalance protection (in motor mode)
47 I2 >> Phase sequence / incorrect phase sequence protection
48 Excessive starting time
37 3I< Loss of load / under current protection
86 Latched trip
66 Restart inhibit
32 P</P<< One-/Three-phase reverse power and underpower protection 1 1
Other functions 68F2 I f2> Magnetising inrush
68F5 I f5> Transformer overexcitation
50BF CBFP Circuit breaker failure protection
81H/81L f ><, f >><< Overfrequency and underfrequency protection
81H/81L f >>><<< Overfrequency and underfrequency protection
81L f<, f<< Underfrequency protection
81L f<<< Underfrequency protection
81R df/dt Rate of change of frequancy (ROCOF) protection
25 Synchrocheck
99 8 Programmable stages
DR Disturbance recorder
08
Protection VAMP 50 series
BB
CB
VAMP 50
Cable 3I
50 / 51 49F 46R
T> I2/ I1 >
3I>
3I> >
50BF 68
3I> > >
CBFP If2 >
Io
50N/ 51 N 68F5
If5 >
I0>, I0> >
I0>> >
I0>> >>
50NA RC
ArcI 0>
50A RC 74TC 86
A rc I> TC S Loc kout
09
Protection VAMP 50 series
L1
L2
L1
L3
L2
L3
+
1 -
+
1 -
X2:1
~
Front - 0
X2:2 Comm. option
X2:1
~
VAMP 50 Remote
Front - 0
VAMP 50
X2:2 C omm. option
Protection functions
X1:1 Re mote
68
X1:2 IL1 50 / 51 50N/ 51 N
X3:17
I0>, I 02 > If2 >T1
X1:3 3I>
X1 :1 X3:16 +
X1 :2 IL1X1:4 IL2 3I> >
I 0 >>
I 02 >> 74TCT2 X3:15
T1 X3:1 7
X1 :3 X1:5
3I> > >
TC S X3:14 + X3:1 6 +
X1 :4 ILX1:6
2 IL3 50BF T3 X3:13
T2 X3:1 5
86
X1 :5 X1:7 C BFP X3:12 X3:1 4 +
46R
X1 :6 ILX1:8
3
I0 5A
I2/ I1 > 50A RC
Loc kout
T4 T3
X3:11
X3:1 3
X1 :7 X1:9 1A X3:1 2
A rc I> X3:10
X1 :8 IX1:10
0
49F T4 X3:1 1
A1
5A
1A X3:7
X1 :9 X1:11 U /UL1/U12 T >
I/O extension 0 50NA RC
X3:9
X3:1 0
module
X6:7
X3:20 X3:1 9
mA out option
X6:8 Bloc king a nd
X3:20
output ma trix mA out option
X3:3 DI1 - X3:1 AO+
DI
X3:4
X3:3 DI1 - DI1 + X3:2 AO- X3:1 AO+
DI mA X3:2 AO -
X3:4 DI1 +
mA
X3:5 DI2 -
X3:5 DI2 -
X3:6 DI2 +
X3:6 DI2+
Option module arc 0ption module advanced arc I/O extension module
A rc option Arc option DI / DO mo dule Module arc has two arc sensor
X6:1 BO+ BI/ O X6:1 BO1+ BI/ O X6:1 T5 interfaces and connectivity from/to
X6:2 BO- X6:2 BO1-
X6:3 BI1+ X6:2 other relays via BI/O channel.
X6:3 BI+ X6:4 BI1- X6:3 DI3 DI
The operating time for arc flash fault
X6:4 BI- X6:5 n/a X6:4 Comm
X6:5 L1 + X6:6 S1 X6:5 DI4 trip is typically 15 ms.
L> X6:7 S1 L>
X6:6 L1 - X6:8 S2 X6:6 DI5 DI The arc module advanced arc with
X6:7 L2+ X6:9 S2 X6:7 Comm three sensors reaches typical operation
X6:10 S3
X6:8 L2- X6:11 S3 X6:8 Di6
time of 7 ms.
10
Protection VAMP 50 series
ArcI 01 > 27 (1
59N 1 U<
50A RC
1 U< <
A rc I> U0>
1 U< < <
U0> >
79
O 1
8 pgr
50 BF 74TC 86
CBFP TC S Loc kout
CB
VAMP 52
Cable 3I
50 / 51 49F 46R
T> I2/ I1 >
3I>
3I> >
Uo, UL or U 68F5 68
3I> > > If5 > I f2 >
Io 67NT
50N/ 51 N
I0T>
I0>, I0> >
I0 >>> 67N 59 (1
I0 >>>> 1 U>
D I0> 1 U> >
1 U> > >
50NA RC I0> >
ArcI 01 > 27 (1
59N 1 U<
50A RC
1 U< <
A rc I> U0>
1 U< < <
U0> >
79
O 1
M
Fiber or
RTD 1 ... 1 2
RS485
VIO 12A
8 pgr
50 BF 74TC 86
CBFP TC S Loc kout
1) Alternative to Uo protection
L1
L2
L3
L1 + 1 -
L2
L3 X2:1
~
Front - 0
X2:2 Comm. option
Remote 1 -
VAMP 52
X1:1
X1:2 IL1
VAMP 52 T1Front
X3:17
- 0
X2: 1
~ X1:3 X3:16
Protection functions
X2: 2
X1:4 IL2 Comm. option
T2 X3:15 +
X1:5 50 / 51 50N/51N 27
X3:14
Remote
+
IL3 3I> I0> , I02> U<
X1:6 X3:13
3I>> I0>>, I02> > U<< T3
X1: 1 X1:7 X3:12
da
3I>>> U<<<
dn
I
67NT
X1: 3 X1:9 I /I 1A
> CBFP
X3:16X3:10
2
59N 1
UX1:05
I> U >> ArcI >
X1:11 U0/UL1/U12 U >>
2 0
X3:14
+
0
X3:9
X1: 6 IL3
47 50NARC
X3:13X3:8
I/O I extension
>>
2
49
ArcI 01 > T3
T>
X1: 7 module X3:12
48 74TC
I0 X6:1 68
X3: 11
X1:8 5A Ist >
If2 >
TCS
T4
X1: 9
1A
X6:2
Arc
66
option 86 X3:10
X1:10
X6:3 N>
59
Lockout
C1 X3: 7
U0 X1: 11
U / U 1/
U12
X6:4
37
or U>
SF X3: 9
X3:18
X6:5 3I<
U>>
X3:19
DI / DO module X3: 8
I/O extension X6:6 U>>>
module
X6:7 67N X3:20
X6:1 I> mA out option
X6:8 0 79
X6:2 Arc option I >> Auto Reclose
X6:3
0
X3:3 DI1 -
X3:4 DI1+ DI
mA
X3:5 DI2 -
X3:6 DI2+
Should the voltage Option module arc Option module advanced arc
transformer connection A rc option Arc option
be phase to phase the X6:1 BO+ BI/ O X6:1 BO1+ BI/ O
X6:2 BO1-
voltage measuring mode is X6:2 BO- X6:3 BI1+
X6:3 BI+ X6:4 BI1-
selected 1LL X6:5 n/a
X6:4 BI-
X6:5 L1 + X6:6 S1
L> X6:7 S1 L>
X6:6 L1 - X6:8 S2
X6:7 L2+ X6:9 S2
X1:11 X1:10 X6:10 S3
X6:8 L2- X6:11 S3
X1:11 X1:10
12
Protection VAMP 50 series
Typical application/VAMP 55
Cable
BB
VAMP 55
VT
59 27 27P
U2 >
81 H/ 81 L 81 L 81 R
f> < f< df/d t
f> >< < f< <
25
f, v
8 p gr
X2: 1
~ VAMP 52 Front - 0
X2: 2 Protection functions Comm. option
50 / 51 50N/51N 27
Remote
3I> I0> , I02> U<
X6:1 I0> 79
X6:2 Arc option I0> > Auto Reclose
X6:3
or
X6:4 IF X3:18
X6:5 DI / DO
X6:6 module
X3:19
X3:20
VAMP 55
X6:7 Autorecloser Blocking and
X6:8 matrix output matrix mA out option
:3 DI1 -
:4 DI1+ DI
mA
:5 DI2 -
:6 DI2+
X6:6 DI5 DI
X6:7 Comm
X6:8 Di6
Dimensional drawings
DEFAULT
PANELMODEL VAMP 50
MOUNTING VAMP 50 SERIES
mm
in 158 128 213 80
6.22 5.04 8.39 3.15
Vamp 52
F1 F2
6.73
9.5
0.37
Vamp 52
120 2
4.72
OK
139
5.47
F2
F1
Vamp 52
OK
1
0.0 .0-10 F2
4-
F1
0.3
9
>2
0
0.79
Vamp 52
Vamp 52
OK
F2
F1
OK
F2
F1
15
Protection VAMP 50 series
97.4
105 3.83 80 85
4.13 3.14 3.34
(94)* OK
F1
(3.70)* F2
10 140
0.39 5.51
2 138
5.43
* Without panel gasket
83
1
3.26
S
Vamp 52
1.0-18
0.03-0.70
OK
F1
F2
3
3a
min. 2.5mm2
1 2 3
4 5 6
7 8 9
x3
1 0 11
12 13
14 15
16 17
18 19
20
x1
3b mm
3c in
P 50S
SVAM
Vamp 52
11.50 78 OK
F1F1
F1
3.07
F2
0.45
F2
F2
16
Protection VAMP 50 series
Measuring circuit
Rated phase current IN 1A/5A
Current measuring range 0.00550 x IN
Rated neutral current I0N 1 A or 5 A (optionally 0.2 A or 1 A)
Current measuring range 0.00310 x IN
Thermal withstand 4 x IN (continuous)
100 x IN (for 1 s)
Rated frequency fN 50 / 60 Hz (4565 Hz)
I/O
Digital inputs (external voltage) 2 pcs (7 option)
Selectable nominal voltage (threshold) 24 / 110 / 220 V ac / dc
Trip contacts 4 pcs (5 option)
Disturbance tests
Standard & Test class / level Test value
Emission EN 61000-6-4 / IEC 60255-26
Conducted EN 55011 class A / IEC 60255-25 0.01 - 30 MHz
Emitted EN 55011 class A / IEC 60255-25 / CISPR 11 30 - 1 000 MHz
Immunity EN 61000-6-2 / IEC 60255-26
1Mhz damped oscillatory wave IEC 60255-22-1 2.5kVp CM, 1kVp DM
Static discharge (ESD) EN 61000-4-2 class IV / IEC 60255-22-2 8 kV contact, 15 kV air
Fast transients (EFT) EN 61000-4-4 class IV / IEC 60255-22-4 class A 4 kV / (2 kV signal ports), 5/50 ns, 5 kHz
Surge EN 61000-4-5 class III / IEC 60255-22-5 2 kV, 1.2/50 ms, CM
1 kV, 1.2/50 ms, DM
Conducted HF field EN 61000-4-6 class III / IEC 60255-22-6 0.15 - 80 MHz, 10 Vemf
Emitted HF field EN 61000-4-3 class III / IEC 60255-22-3 80 - 2700 MHz, 10 V/m
Voltage interruptions EN 61000-4-29 / IEC 60255-11 30%/1s, 60%/0.1s, 100%/0.05s
Voltage alternative component EN 61000-4-17 / IEC 60255-11 12% of operating voltage (DC) / 10min
Voltage dips and short interruptions EN 61000-4-11 30%/10ms, 100%/10ms, 60%/100ms
>95%/5000ms
Power-frequency magnetic field EN 61000-4-8 300A/m (continuous), 1000A/m / 1-3s
Pulse magnetic field EN 61000-4-9 1000A/m, 1.2/50 ms
Mechanical tests
Standard & Test class / level Test value
Device in operation
Vibrations IEC 60255-21-1, class II / IEC 60068-2-6, Fc 1Gn, 10Hz 150 HZ
Shocks IEC 60255-21-2, class II / IEC 60068-2-27, Ea 10Gn/11ms
Device de-energized
Vibrations IEC 60255-21-1, class II / IEC 60068-2-6, Fc 2Gn, 10Hz 150 HZ
Shocks IEC 60255-21-2, class II / IEC 60068-2-27, Ea 30Gn/11ms
Bump IEC 60255-21-2, class II / IEC 60068-2-27, Ea 20Gn/16ms
Environmental conditions
Standard & Test class / level Test value
Device in operation
Dry heat EN / IEC 60068-2-2, Bd +65C
Cold EN / IEC 60068-2-1, Ad -40C
Damp heat, cyclic EN / IEC 60068-2-30, Db From +25C to +40C, From 93% RH to 98% RH,
6 days
Damp heat, static EN / IEC 60068-2-78, Cab +40C, 93% RH, 10 days
Flowing mixed gas corrosion test, IEC 60068-2-60, Ke +25C, 75% RH,
method 2 10 ppb H2S, 200 ppb NO2, 10 ppb CL2
Flowing mixed gas corrosion test, IEC 60068-2-60, Ke +25C, 75% RH,
method 4 10 ppb H2S, 200 ppb NO2, 10 ppb CL2,
200 ppb SO2
Device in storage
Dry heat EN / IEC 60068-2-2, Bb +75C
Cold EN / IEC 60068-2-1, Ad -40C
Casing
Standard & Test class / level
Degree of protection (IEC 60529) IP54
Dimensions (W x H x D) 130 x 170 x 210 mm
Material 1 mm steel plate
Weight 2.0 kg
Colour code RAL 7032 (Casing) / RAL 7035 (Back plate)
Package
Standard & Test class / level
Dimensions (W x H x D) 260 x 160 x 215 mm
Weight (Terminal, Package and Manual) 2.4 kg
18
Protection VAMP 50 series
Order codes
V5 - - V50 or V52 V55
Relay type Relay type
= Default = Default
S = Slim line S = Slim line
Phase current inputs [A] Nominal voltage [V]
3 = 5A 4 = 50...400 V (default size)
Earth-fault current input [A] X = None
A = 1A/5A
B = 0.2 A / 1A
Supply Voltage [V] Supply Voltage [V]
A = 40.. 265 Vac / dc A = 40.. 265 Vac / dc
B = 18 ... 36 Vdc B = 18 ... 36 Vdc
mA output option mA output option
A = None A = None
B = mA output B = mA output
DI nominal activation voltage DI nominal activation voltage
1 = 24 Vdc / 110 Vac 1 = 24 Vdc / 110 Vac
2 = 110 Vdc / 220Vac 2 = 110 Vdc / 220Vac
Relay type 3 = 220 Vdc 3 = 220 Vdc
Optional I/O extension modules Optional I/O extension modules
0 Overcurrent & earth fault relay
A = None *** A = None
2 Feeder and motor protection relay
B = Digital I/O; 4 x DI, 1 x DO B = Digital I/O; 4 x DI, 1 x DO
5 Voltage protection relay C = Arc (2 x Arc sensor + BIO)
D = Advanced arc (3 x Arc sensor + BIO)***
Optional communication module 1 Optional communication module 1
A = None A = None
D = Plastic / Plastic serial fibre interf. D = Plastic / Plastic serial fibre interf.
E = Glass/Glass serial fibre interf. E = Glass/Glass serial fibre interf.
F = Rx Plastic / Tx Glass serial fibre interf. F = Rx Plastic / Tx Glass serial fibre interf.
G = Rx Glass / Tx Plastic serial fibre interf. G = Rx Glass / Tx Plastic serial fibre interf.
K = K = RJ-45 10Mbps ethernet interf. K = K = RJ-45 10Mbps ethernet interf.
inc IEC 61850 inc IEC 61850
P = Profibus interface P = Profibus interface
R = 2 x ST 100Mbps ethernet fibre R = 2 x ST 100Mbps ethernet fibre
interface, inc. IEC 61850 !! interface, inc. IEC 61850 !!
S = 2 x RJ-45 100Mbps ethernet S = 2 x RJ-45 100Mbps ethernet
interf. inc. IEC 61850 interf. inc. IEC 61850
B = RS 485 interface (2-wire) B = RS 485 interface (4-wire) with
Default model with option for module 2 option for module 2
L = RS232 interface L = RS232 interface with option for
with option for module 2 module 2
M = RS-232 inteface with option for M = RS-232 inteface with option for
module 2 and ext I/O + IRIG B module 2 and ext I/O + IRIG B
Optional communication module 2 Optional communication module 2
A = None A = None
B = IRIG-B timesyncro. input ** B = IRIG-B timesyncro. input **
C = RTD interface (Glass fibre) ** C = RTD interface (Glass fibre) **
E = RJ-45 10 Mbps ethernet interf. E = RJ-45 10 Mbps ethernet interf.
Slimline model (S) inc. IEC 61850 ** inc. IEC 61850 **
G = LC 100 Mbps ethernet fibre G = LC 100 Mbps ethernet fibre
interf. inc. IEC 61850 ** interf. inc. IEC 61850 **
PCP coating PCP coating
Note:
= Default = Default
** Option available only with communication module 1: B and L
ACCESSORIES
Order code Description Note
VX052-3 USB programming cable (Vampset) Cable length 3 m
VX054-3 Interface cable to VPA 3 CG (Profibus module) for RS 232 Cable length 3 m
VX044 Interface cable to VIO 12 (RTD module) Cable length 2 m
VSE001PP Fibre optic Interface Module (plastic - plastic) Max. distance 1 km
VSE001GG Fibre optic Interface Module (glass - glass) Max. distance 1 km
VSE001GP Fibre optic Interface Module (glass - plastic) Max. distance 1 km
VSE001PG Fibre optic Interface Module (plastic - glass) Max. distance 1 km
VSE002 RS485 module
VPA3CG Profibus DP fieldbus option board Requires external power module,
to be used when both ethernet and
profibus communications are needeed
VIO 12 AA RTD Module, 12pcs RTD inputs, Optical Tx Communication (24-230 Vac/dc)
VIO 12 AB RTD Module, 12pcs RTD inputs, RS 485 Communication (24-230 Vac/dc)
VIO 12 AC RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs,
RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)
VIO 12 AD RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs,
RS232, RS485 and Optical Tx/Rx Communication (48-230 Vac/dc)
VA 1 DA-6 Arc Sensor Cable length 6 m
VA 1 DA-20 Arc Sensor Cable length 20 m
V50WAF V50 wall assembly frame
20
Protection VAMP 50 series
NRJED111266EN 05-2015