Ampac MultiAmp - DH 250mA Door Holder Item Numbers: 4510-1100

Supply Installation Guide 4510-1101

Description
The MultiAmp-DH 250mA Door Holder Supply (DHS)
provides up to 250mA of current at 24 VDC to
operate door holders.

Features
Automatic Door Release System (ADRS)
Conventional detectors are installed and connected
directly to the DHS.

Release / Reset
A manual release and/or Reset is initiated by
depressing the “Release/Reset’ button for at least 1 Front Panel Layout
second. Terminating
EOL 3K3
Remote Trigger (Release / Reset)
Doors can be released or the circuit “Reset” by the
Maximum of 32
application of a local +VDC or and external +/- 12 to Devices per Zone

24VDC supply input. - + DOOR HOLDER

Specifications +

N1236
Power Supply DETECTOR CCT. DANGER

Supply Voltage 230 VAC +/- 10% @ 47-63Hz - ZONE SWT


0V TRIG 0V 24V
REMOTE TRIGGER
Output Voltage 24 VDC @ 250mA (nominal) OPTIONS 1 & 2 230V AC
TB3 50Hz
1 TB2 L N
Environmental
+ V TRIS 0V
TB1
Temperature -5º to +45º C OR
Humidity 25% to 95% (relative) 2
BRD42DHPS1

+ -
Zone Detection Circuit EXT. 12-28VDC

No of Zones 1 (one), 2-wire system


Zone Monitoring Open and short-circuit Rear View and Cabling Diagram
Zone Current 4mA max
EOL Value 3k3 ohm As shown above, observing polarity connect the;
No of detectors 32 (max) 1. Detector circuit to TB3 1 (-ve) & 2 (+ve).
2. Door holder to TB3 3 (-ve) & 4 (+ve)
Input 3. Remote trigger to TB2 in either a local +VDC or
Remote Input Inactive state: 0 to 2 VDC external 12 to 24VDC configuration as shown
Active state: 8 to 30 VDC 4. With no voltage applied mains to TB1
5. Place the DHS over the back box, tighten securing
See PDS212-0012 for door holder specifications screws and insert the two screw caps.

Installation Testing
Surface Mount 1. Press and hold the “Release” button for at least 1
Locate the back box over a flat surface, securing with second, the “Released” indicator should then be
at least two (2) screws, tightened evenly to prevent illuminated and the door released.
distortion. 2. Create an alarm on the detector circuit, The
“Released” indicator will be illuminate and the door
Flush Mount released.
Locate the back box inside the wall cavity with the 3. Remove the alarm condition and press “Reset” to
front edge level with the wall surface. revert normal operation.

Conduit Entries Item Numbers


20mm conduit entries, side, rear, and top or bottom Flush Mount: 4510-1100
depending on back box used. Surface Mount: 4510-1101
Note: back box included in packaging

N1236
MAN1533 Website: www.ampac.net