LOAD ESTIMATE (DESIGN ANALYSIS) ON A 182 SQUARE METER, SINGLE FAMILY DWELLING UNIT, 230 VOLTS SINGLE PHASE
SERVICE

LOAD (COMPUTATION) CONNECTED LOAD DEMAND LOAD

GENERAL LIGHTING
See Table 2.20.3.3
Total Area (Sq. m) 182 Total Area (Sq. m) x (Va/Sq.
Dwelling @ 24 VA/Sq. m 24 m) 4,368 VA
Single Appliance Load
Load Type VA Rating Units VA Rating x Units
Single Appliance Load 1500 3 1500 x 3 4500 VA
Laundry 1500 1 1500 x 3 1,500 VA
See Table 2.20.3.13a & Table 2.20.3.13b
TOTAL: 10,368 VA
Application of Demand Factor (Single Dwelling) 3000 + (Total-3000)(DF)
FIRST 3000 VA @ 100% DF
REMAINING @ 35% DF 3000 + (10,368-3000)(0.35) 5578.8 VA
See Table 2.20.3.3
KITCHEN LOADS

Load Type W-Rating Units DF W-Rating x Units x DF


5000 x 1 x 1 (For Connected)
Electric Range (@ 80% DF) 5000 1 0.8 & 5000 x 1 x .8 (For
Demand) 5000 VA 4000 VA
4000 x 1 x 1 (For Connected)
Electric Range (@80% DF) 4000 1 0.8 & 4000 x 1 x .8 (For
Demand) 4000 VA 3200 VA
3500 x 1 x 1 (For Connected)
Oven (@ 80% DF) 3500 1 0.8 & 3500 x 1 x .8 (For
Demand) 3500 VA 2800 VA
See Table 2.20.3.16
AIR-CONDITIONING UNITS

V - Rating x x Ampere x
HP-Rating Load Type Units DF AMP
Units x DF
1 Window-Type ACU 3 1 8 230 x 8 x 3 x 1 5520 VA 5520 VA
1.5 Split-Type ACU 1 1 10 230 x 10 x 1 x 1 2300 VA 2300 VA
See Table 4.30.14.2
OTHER LOADS

V - Rating x x Ampere x
HP-Rating Load Type Units DF AMP
Units x DF
1 Water Pump 1 1 8 230 x 8 x 1 x 1 1840 VA 1840 VA
See Table 4.30.14.2
Load Type VA Rating Units DF VA - Rating x Units x DF
Water Heater 3500 1 1 3500 x 1 x 1 3500 VA 3500 VA

TOTAL CONNECTED LOAD TOTAL DEMAND LOAD

36,028 28738.8
SERVICE ENTRANCE CONDUCTOR
SEC = (TOTAL DEMAND FACTOR + TOTAL OTHER LOADS + 25% OF HIGHEST RATING MOTOR) / 230V
SEC = [5578.8 VA + (28738-5578.8)VA + (2300VA x .25) ] / 230V (Amperes) 127.4513043 (Use 38THHN)
See Table 3.10.1.16
AMPERE TRIP RATING
AT = (TOTAL DEMAND FACTOR + TOTAL OTHER LOADS + 150% OF HIGHEST RATING MOTOR) / 230V
AT = [5578.8 VA + (28738-5578.8)VA + (2300VA x 1.5) ] / 230V (Amperes 139.9513043 (Use 150AT)
See Section 2.40.1.6