Вы находитесь на странице: 1из 2

Water-Cooled Optimus (TM)

Job Information

HSS CORPORATE PLAZA TOWER PROJECT

Tag CH-04 Compressor configuration C2

Model Number RTHD Evap configuration F2


Quantity 1 Cond configuration F3
Product Version 181

Unit Information
Capacity 300.00 tons Operating weight 17560.0 lb
Efficiency 0.653 kW/ton Shipping weight 16168.0 lb
NPLV 0.534 kW/ton Length 145.500 in

IPLV 0.525 kW/ton Width 68.200 in

Oil cooler With Oil Cooler Height 76.200 in


A weighted sound pressure (AHRI) 83 dBA Refrig charge (HFC-134a) 625.0 lb

Evaporator Information
Evap leaving temp 44.00 F Number of evap passes 2 pass
Evap entering temp 54.00 F Evap fouling factor 0.00010 hr-sq ft-deg F/Btu
Evap flow rate 716.90 gpm Min evap flow rate 604.00 gpm
Evap pressure drop 2.60 ft H2O Press drop at min evap flow 1.80 ft H2O
Evap fluid type Water Max evap flow rate 2667.00 gpm
Evap fluid concentration 0.00 % Press drop at max evap flow 33.20 ft H2O
Evap fluid freeze point 32.00 F Saturated evap temp 41.30 F
Evap tube type Water only

Condenser Information
Cond entering temp 88.00 F Number of cond passes 2 pass
Cond leaving temp 97.60 F Cond fouling factor 0.00025 hr-sq ft-deg F/Btu

Cond flow rate 900.00 gpm Min cond flow rate 620.00 gpm
Cond pressure drop 12.50 ft H2O Press drop at min cond flow 6.40 ft H2O

Cond fluid type Water Max cond flow rate 1700.00 gpm

Cond fluid concentration 0.00 % Press drop at max cond flow 40.00 ft H2O
Cond tube type 0.028" - enhanced Saturated cond temp 100.10 F

Electrical Information
Unit voltage 380/60/3 Starter type Wye-delta
Unit power 196.00 kW Min circuit ampacity 428.80 A

Max overcurrent protection 700.00 A Starter expected inrush 558.00 A


Motor locked rotor amps 1727.00 A Run load amps/AFD input amps 343.10 A
Short circuit rating 10000.00 A

1/23/2016 Product Version 181

Page 1 of 2
Water-Cooled Optimus (TM)
Job Information

HSS CORPORATE PLAZA TOWER PROJECT

Tag CH-04 Compressor configuration C2

Model Number RTHD Evap configuration F2


Quantity 1 Cond configuration F3
Product Version 181

Information for LEED Projects


Refrig charge (HFC-134a) 625.0 lb IPLV 0.525 kW/ton
Rated capacity (AHRI) 308.80 tons Rated efficiency (AHRI) 0.615 kW/ton

Note: This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANS/CSA C743 for all

versions (which are based on AHRI standard rating conditions) and, therefore, also meets the LEED "Minimum

Energy Performance" prerequisite in the Energy and Atmosphere section.

The LEED Green Building Rating System, developed by the U.S. Green Building Council, provides independent, third-party verification that a building project
meets green building and performance measures.

Notes: All weights +- 3%. Weights include 150 psig water boxes.

Operating weights include refrigerant, oil, and water charges.

Sound pressure measured in accordance with AHRI Standard 575-94.

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Using Vapor Compression Cycle Certification Program, which is
based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may
be found in the AHRI Directory at www.ahridirectory.org.

1/23/2016 Product Version 181

Page 2 of 2