Вы находитесь на странице: 1из 4

Commissioning Instruction CI/LLT100-EN 06.

2016

LLT100
Laser level transmitter

Quick start guide

Measurement made easy

Introduction Standard precaution


The LLT is a high performance laser level transmitter that accu- WARNING Bodily injury
rately measures level, distance and position over long ranges in
industrial environments. The LLT, using an eye-safe pulsed laser Read the LLT100 operating instructions care-
beam, features advanced timing and sophisticated signal process- fully before working with the product. For
ing for pinpoint accuracy. personal and system safety and for optimum
performance, make sure you thoroughly un-
derstand the contents before installing, using
Features or maintaining this instrument.

-
-
-
-
Range up to 100 m (330 ft) for level of solids
Range up to 30 m (100 ft) for level of liquids
Range up to 200 m (660 ft) for positioning applications
Narrow laser beam easy to aim
i All servicing of the equipment is to be per-
formed at factory by qualified serviceperson-
nel only.

-
-
-
-
-
Measures solid surface even at large angles
Measures liquid level even for clear liquids
Rugged and robust aluminum or stainless steel enclosure
No calibration required
Easy and intuitive setup
i No user/operator adjustments inside the
LLT100 level transmitter are recommended by
the manufacturer.

- Explosion proof class 1/division 1 (zone 1)


- 2-wire power from the 4-20 mA loop
- HART communication
- Embedded HMI/Display
LLT100 electrical connection

HART terminal - 2 wires HART terminal with heater option - 2 + 2 wires

Internal protective
earth (ground)
External DC supply:
+24Vdc, 3W

Cover lock
screw M4 0 V (Return)

External ground External ground


termination point termination point

*Optional Pos ( + ) *Optional Pos ( + )


Ext. Meter (+) Ext. Meter (+)
Neg ( ) Neg ( )

Attention Location of Ground


The Ground symbols is used to identify protective
earth conductor terminals.
Attention Direct current
Use wires and cable glands rated 90C minimum

Mounting

Do not mount or aim the Only for liquids:


LLT100 directly over/into fill- Laser beam must be as perpendicular to
ing material. the surface as possible, not exceeding
90 5 to the surface.

2 CI/LLT100 EN | Laser level transmitter LLT100


Easy setup
1. Rotate the housing: unscrew the stop tang-screw by approximately 1 rotation (do not pull it out), and then, once the
desired position has been reached, re-tighten the stop tang-screw.
2. Connect the cables (15.5Vdc to 42Vdc) to the LLT100 laser level transmitter.
*If using HART the minimum input voltage is 21Vdc.
3. Power on the transmitter.
4. Press the Right arrow key on the display and choose your access level with the Up and Down arrow keys .
5. Use the Easy Setup menu for setting the main parameters:

a Choose the required language.


b Choose the measurement mode: standard, clear liquid, positioning or dust/vapor.
c Enter the vessel height (URP).
d Set the sensor offset from the vessel top.
e Choose the primary variable (PV) for the 4-20 mA Output: level, ullage, volume.
f Choose the unit of the primary variable (PV): m, cm, mm, ft.
g Set the value for vessel empty (LRV).
h Set the value for vessel full (URV).
i Enable or disable the filling rate.
j Set the Tag name.
6. Once the settings are completed, simply press Exit to return to the distance view.

Detailed setting information are found in the user manual.

General model

Sensor offset

Vessel height
(URP) Vessel full (20 mA)
(URV)

Ullage

Level

Vessel empty (4 mA)


LRV

Laser level transmitter LLT100 | CI/LLT100-EN 3


Specification Contact us

CI/ LLT100-EN 06.2016


Environmental conditions
ABB Inc.
Process Automation
Operating temperature -40C ... +60C (-40F ... +140F), up to
Level Measurement Products
280C (535F) with cooling tube
3400, Rue Pierre-Ardouin
Altitude Up to 2000m
Qubec (Qubec) G1P 0B2
Relative humidity 0 100% Canada
Electrical equipment Class III Tel.: +1 800 858-3847 (North America)
Pollution degree 4 (IP66 / IP67 / Type 4X) Tel.: +1 418 877-2944 (other countries)
Overvoltage Category 1 Fax: +1 418 877-2834
Output
E-Mail: Lasers@ca.abb.com

Analog 4 ... 20 mA, NAMUR compliant For more information and up to date documents,
Digital HART 7 (multi-variable output) please follow this link:

Communication Local HMI, EDD/DTM, handheld www.abb.com/level


Power supply
Powered from the loop 4 ... 20 mA, 15.5 ... 42 Vdc Note
We reserve the right to make technical changes or
Heated lens option 24 Vdc (3W)
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or possi-
ble lack of information in this document.

We reserve all rights in this document and in the sub-


ject matter and illustrations contained therein. Any
reproduction, disclosure to third parties or utilization
of its contents - in whole or in parts is forbidden
without prior written consent of ABB.