Вы находитесь на странице: 1из 2

JobName/Location: Tag#:

Date: For: File Resubmit


PONo.: Approval Other
Architect: GC:
Engr: Mech:
Rep:
(Company) (ProjectManager)

ARNU093B1G2
MultiVDucted(LowStatic)
9,600 Btu/hIndoorUnit
Performance: EnteringMixedAir:
TotalCoolingCapacity(Btu/h) 9,600 CoolingMax(FWB) 76
HeatingCapacity(Btu/h) 10,900 HeatingMin(FDB) 59
PowerInput(W) 30 UnitData:
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor: 80FDB/67FWB Indoor: 70FDB RefrigerantType R410A
Outdoor 95FDB Outdoor 47FDB/43FWB
: :
RefrigerantControl EEV
Electrical: SoundPressuredB(A)(H/M/L) 34/33/32
PowerSupply(V/Hz/) 208230/60/1 FilterType Washable
RatedAmps(A) 0.1 FilterQuantity 1
Piping: FilterDimensions 295/8"x65/8"x1/4"
Refrigerant: NetUnitWeight(lbs) 47
LiquidLine(in,OD) 1/4Flare ShippingWeight(lbs) 51
VaporLine(in,OD) 1/2Flare
Fan:
Condensate: Type Sirocco
CondensatePumpDrain(in,OD) 1Plain FanQuantity 3
Motor/Drive BrushlessDigitallyControlled/Direct
ControlsFeatures:
Autochangeover Selfdiagnos cs MotorQuantity 2
(HeatRecoveryonly) Sleepmode AirflowRateH/M/L(CFM) 335/300/265
Autoopera on Timer(on/o)
ExternalStaticPressure(ESP)(inwg) 0.08
Autorestart Weeklyschedule
Childlock So dry(dehumidifica on) MinimumESP/FanSettingValue 0/78
Dualthermistorcontrol Fanspeedcontrol MaximumESP/FanSettingValue 0.15/115
Hotstart
OptionalAccessories: Notes:
1.ThePowerInputisratedathighspeed.
2.Maximumli is27inchesfrombo omofunit.Checkvalvenotincluded(fieldsupplied).
WirelessHandheldRemoteControllerPQWRHDF0
3.RequiresanLGProgrammableThermostat,SimpleControllerwithModeoraSimple
LGProgrammableThermostatPREMTB10U ControllerwithoutMode.
4.SeeEngineeringManualforsensibleandlatentcapaci es.
SimpleControllerwithMode(Black)PQRCVCL0Q 5.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard3745.
6.Atfactoryfanspeedse ng.
SimpleControllerwithMode(White)PQRCVCL0QW 7.Maximumstaticpressuremayresultinreducedairflow(CFM).
8.Allcommunica oncabletobeminimum18AWG,2conductor,stranded,shieldedandmust
SimpleControllerwithoutMode(Black)PQRCHCA0Q complywithapplicablelocalandnationalcode.
9.Powerwiringcablesizemustcomplywiththeapplicablelocalandna onalcode.
SimpleControllerwithoutMode(White)PQRCHCA0QW 10.Thisunitcomeswithadrynitrogencharge.
11.Thisdataisrated0 abovesealevel,with25 ofrefrigerantlineperindoorunitanda0
DryContactUnit(1contact,24VACexternalpower)PQDSB1 leveldifferencebetweenoutdoorandindoorunits.Allcapacitiesarenetwithacombination
DryContactwithEconomizerInterfacePQDSBC1 ratiobetween95105%.
12.Mustfollowinstalla oninstruc onsintheapplicableLGinstalla onmanual.
DryContactforThirdPartyThermostatPQDSBNGCM1
WallMountedTemperatureSensorPQRSTA0

Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.LGLifesGoodisaregisteredtrademarkofLGCorp./www.lghvac.com VRFSBDG002US014B11 Page1of2
JobName/Location:

ARNU093B1G2 Tag#:
MultiVDucted(LowStatic) Date:
9,600 Btu/hIndoorUnit PONo.:

Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.LGLifesGoodisaregisteredtrademarkofLGCorp./www.lghvac.com VRFSBDG002US014B11 Page2of2

Вам также может понравиться