Вы находитесь на странице: 1из 2

3-3.

SPECIFICATIONS (HEAT PUMP TYPE)


AO90TPCMF , AO72TPCMF
Model AO90TPC AO72TPC
,Hz 3W4,50Hz 3W4,50Hz
Power Requirement
V 380 - 415 380 - 415
Cooling 28.0 22.4
Total Capacity kW
Heating 31.5 25.2
Cooling 9.03 7.23
Total Input Watts kW
Heating 8.50 7.64
Cooling 15.2 12.5
Total Ampacity A
OUTDOOR

OUTDOOR
Heating 14.3 13.0
UNITS

UNITS
Starting Current A 81 70
EER Cooling 3.10 3.10
W/W
COP Heating 3.71 3.30
Type Plate Fin Coil Plate Fin Coil
Heat Exchanger Rows x Stages 3 X 30 + 2 X 30 2 X 30 + 2 X 30
Fin Pitch 1.8 1.8
Air Circulation High m3/h 9800 9800
Fan Type x Qty Propeller x 2 Propeller x 2
Fan Motor Output W 150 x 2 150 x 2

ZR22K3E-TFD ZR22K3E-TFD
Model ZR48K3E-TFD ZR36K3E-TFD
ZR72KCE-TFD ZR68KCE-TFD

Hermetically sealed Hermetically sealed


Compressor Type
scroll type scroll type
Motor Output kW 1.5/3.4/4.9 1.5/2.5/4.8
Internal Protector(OCR) Internal Protector(OCR)
Protection
High Pressure Relief Valve High Pressure Relief Valve

Dimensions Net 1,380 x 1,300 x 650 1,380 x 1,300 x 650


mm
(H x W x D) Gross 1,535 x 1,400 x 770 1,535 x 1,400 x 770
Net 313 307
Weights kg
Gross 349 343
Noise Level (Sound Pressure) dB (A) 57 56
Type R407C R407C
Refrigerant
Charge kg 10 9
Type EMIKARATE RL 32CF EMIKARATE RL 32CF
Refrigerant OIL
Charge cc 1120/1360/1774 + 2000 1120/1242/1774 + 2000
Liquid 12.70 12.70
Size mm
Gas 28.58 28.58
Pipe
Max Length 100 100
m
Max Height 50 50
Cooling -15 to 52 -15 to 52
Operation (Outdoor) C
Heating -15 to 21 -15 to 21
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27CDB / 19CWB, and outdoor temperature of 35CDB / 24CWB.
Heating : Indoor temperature of 20CDB / (15CWB), and outdoor temperature of 7CDB / 6CWB.
Voltage : 230 [V] ;Pipe length : 7.5[m] ; Height difference (Between outdoor unit and indoor unit) : 0[m]

- (03 - 04) -
OUTDOOR
UNITS

OUTDOOR UNIT INDOOR UNIT A INDOOR UNIT B INDOOR UNIT C


TH21 TH21 TH21
TH22 TH22 TH22

TH23 TH23 TH23


EEV EEV EEV

THD1
COMP.1
SP SP LP
OIL
SEPARATOR THD2 THs
HEAT PUMP TYPE

COMP.2
3W.V.
ACCUMU
THD3 LATOR
COMP.3 SV4

SV5

SV3 SV2 SV1

HP
3-6. REFRIGERANT CIRCUIT

MODEL : AO90TPCMF, AO72TPCMF

H.E.1
THHO1

- (03 - 14) -
4WV2
E.E.V.1

H.E.2 THHO2 3W.V.


RECEIVER
4WV1 TANK

E.E.V.2

THO
:Strainer
:Solenoid valve

:Heat exchanger
:4-way valve :Thermistor
TH D:Discharge thermistor
THs:Suction thermistor
:Expansion valve THo:Outdoor temp thermistor
TH HO :Outdoor unit H.E. outlet thermistor
TH21:Indoor Room temp thermistor
:Capillary tube TH22 :Indoor unit inlet thermistor
TH23 :Indoor unit H.E. middle thermistor

:Service port
:Pressure sensor
HP:High pressure
:3-way valve LP:Low pressure

1) Outlet air thermistor is not used in


compact wall mounted indoor unit.

OUTDOOR
UNITS

Вам также может понравиться