The document calculates the cooling load of a building at the University of Rizal System-Morong College of Engineering. It considers various factors that contribute to heat gain, such as floor space, volume, windows, walls, partitions, ceiling, number of occupants, and equipment. The total cooling load is calculated to be 12,502.048 KJ/hr. Based on this cooling load value, the document recommends selecting an air conditioning unit with model CW-1200 FPH or CW-1202FPH.
The document calculates the cooling load of a building at the University of Rizal System-Morong College of Engineering. It considers various factors that contribute to heat gain, such as floor space, volume, windows, walls, partitions, ceiling, number of occupants, and equipment. The total cooling load is calculated to be 12,502.048 KJ/hr. Based on this cooling load value, the document recommends selecting an air conditioning unit with model CW-1200 FPH or CW-1202FPH.
The document calculates the cooling load of a building at the University of Rizal System-Morong College of Engineering. It considers various factors that contribute to heat gain, such as floor space, volume, windows, walls, partitions, ceiling, number of occupants, and equipment. The total cooling load is calculated to be 12,502.048 KJ/hr. Based on this cooling load value, the document recommends selecting an air conditioning unit with model CW-1200 FPH or CW-1202FPH.
Considering the temperature in Morong, Rizal which is equal to 35 C
I. Floor space
Heat gain = Floor space x Factor
= (11.48 ft. x 13.448 ft.) x 3 = 463.15 Btu/hr x 1.055 = 488.62 KJ/hr
II. Volumetric capacity
Heat gain = Volumetric capacity x Factor
= (11.48ft. x 13.448 ft. x 7.872ft.) x .6 = 2187.54 Btu/hr x 1.055 = 2307.86 KJ/hr
III. Window exposed to the sun
Heat gain = Window exposed to the sun x Factor
= [(5.74(2)ft. x 4.72ft.)] x 45 = 2429.856 Btu/hr x 1.055 = 2563.49 KJ/hr
IV. All windows not included in III
NONE
V. Wall exposed to sun
Heat gain = Wall space x Factor
= [(13.448 x 7.872)-(5.74(2)ft. x 4.72ft.)+(11.48 x 7.872)] x 13 = 1838.85 Btu/hr x 1.055 = 1939.99 KJ/hr VI. All exterior walls not included in V
Heat gain = Wall space x Factor
= [(13.448 x 7.872) + (11.48 x 7.872)] x 9 = 1766.10 Btu/hr x 1.055 = 1863.23 KJ/hr
VII. Partitions
Heat gain = Partition space x Factor
= (11.48ft. x 7.872ft.) x 4 = 527.124 Btu/hr x 1.055 = 556.116 KJ/hr
VIII. Ceiling or roof
Heat gain = Floor space x Factor
= (15 ft. x 14.17 ft.) x 3 = 361.48 Btu/hr x 1.055 = 381.36 KJ/hr
IX. Number of people
Heat gain = 5 x 600
= 3000 Btu/hr x 1.055 = 3165 KJ/hr
X. Lights and electrical equipment in use
Heat gain = [(LIGHT ) + (APPLIANCE)
x Factor = [(1 x 80 w) + (1 x 100W)] x 3 = 380 Btu/hr x 1.055 = 400.9 KJ/hr
XI. Total Cooling load
Total Heat gain = ( 672.72 + 1251.26 +826.065 + 275.355 +1674.60 +
= 2575.81 +556.116 +672.72 +3798 +199.395 ) KJ/hr = 12 502.048 KJ/hr Total Cooling load is 13,666.57 KJ/hr Conclusion: With this Cooling Load Value it is recommended to select the model CW 1200 FPH / CW 1202FPH