DELUGE VALVE, AUTOMATIC RESETTING, 2-l/2 INCH (65 mm)

MODEL F445 (THREAD x THREAD or GROOVE X GROOVE)


Port Locations:

A - 2-112 NPT
[Aye:,7/l on request)

0 - 2-112 NPT
(IS0 7/l on request)
Outlet

C - I-114 NPT
Main Drain

D - l/2 NPT
Alarm &
Auxiliary Drain

E - 112 NPT 3
Diaphragm Supply 8 176.2mml
Diaphragm Chamber
Pressure Gauge

F - 112 NPT
Alarm Test or
Water Supply
Pressure Gauge

G - 112 NPT
Alarm Test or
Water Supply
Pressure Gauge
FIGURE A
MODEL F445 AUTOMATIC RESETTING DELUGE VALVE
THREAD x THREAD or GROOVE x GROOVE
- DIMENSIONS AND PORT LOCATIONS -

local emergency (manual) release of Inquiries concerning approval by the


the F445 Valve. Verband der Schadeversicherer
should be directed to Grinnell Sales &
The 2-l/2 inch (65 mm), Model F445 The compact and easily installed trim Distribution, Kopersteden 1, NL-7547
Automatic Resetting Deluge Valve is a arrangements have been designed so TJ Enschede, Netherlands, Tel. 31-
quick opening, hydraulically operated that the F445 Valve may be installed 534-283-434 I Fax. 31-534-283-377.
differential type valve designed for fire for either flow left or flow right.
protection system service. It is used as The Model F445 Deluge Valves are
an automatic water control valve in accepted by the City of New York
deluge, preaction, and special types of under MEA 38-92-M.
fire protection systems such as foam-
water and double interlock. The F445 WARNING
Valve also provides for actuation of fire The Model F445 Deluge Valve de-
alarms upon system operation. scribed herein must be installed and
maintained in compliance with this
The automatic resetting feature of the The 2-l/2 inch (65 mm), Model F445 document, as well as with the appli-
F445 provides for easy, external reset- Automatic Resetting Deluge Valve is cable standards of the National Fire
ting, without having to open a valve listed by Underwriters Laboratories Protection Association, in addition to
handhole cover to manually reposition Inc. and Underwriters Laboratories of the standards of any other authorities
a clapper and latch mechanism. Canada. The F445 Valve is also ap- having jurisdiction. Failure to do so
proved by Factory Mutual Research may impair the integrity of this de-
Operation of the F445 Valve is pro- Corporation and the Scientific Ser- vice.
vided by an actuation (detection) sys- vices Laboratory (Australia).
tem that is separate from the normally The owner is responsible for main-
dry system piping. Trim configuration The Model F445 Deluge Valve with taining their fire protection system
options for automatic operation of the either wet or dry pilot actuation and and devices in proper operating con-
F445 include wet pilot actuation, dry galvanized trim is approved by the dition. The installing contractor or
pilot actuation, and electric actuation. Loss Prevention Council (United King- manufacturer should be contacted rel-
Trim arrangements also provide for dom). ative to any questions.

Printed in U.S.A. 5-96 TD114


6
t

100 200 300 400 500 --koo 500 700 1000 2000

FLOW RATE IN FLOW RATE IN


GALLONS PER MINUTE (GPM) LITRES PER MINUTE (LPM)

1 Bar= 100 kPa

GRAPH A-l and A-2


NOMINAL PRESSURE LOSS VERSUS FLOW

Cap Screws and Facing Retainer


Screw are Type 303 stainless steel.

The nominal pressure loss versus flow


Deluge Valve: is shown in Graph A-l and A-2. The
approximate friction loss, based on the
The 2-l/2 inch (65 mm), Model F445 Hazen and Williams formula and ex-
Automatic Resetting Deluge Valve is pressed in equivalent length of Sched-
rated for use at a maximum service ule 40 pipe with C = 120, is 10 feet. The
pressure of 175 psi (12,l bar). The equivalent length of pipe has been cal-
Valve dimensions are shown in Figure culated on the basis of flow rates typi-
A, and all of the ports are NPT cally used with a 2-l/2 inch (65 mm)
threaded per ANSI Standard B1.20.1; size valve.
however, the F445 Valve may be spe-
cial ordered with inlet and outlet pipe Valve Trim:
1 -Body 6 - Cap Screw,
2 -Cover l/2.-13 UNC
thread connections per IS0 7/l.
3 - Diaphragm x 71% Grooved end connections for either The Wet Pilot Actuation Trim, Dry Pilot
4 - Diaphragm ANSI or IS0 pipe connections are cut Actuation Trim, or Electric Actuation
Ring 7 - !eZrdLalve in accordance with Gruvlok standard Trim illustrated in Figure F-l form a
5 - Cap Screw, 6 - Facing groove specifications for steel pipe, part of the laboratory listings and ap-
l/4*-20 UNC 9 - Seat Ring
x 314 IO - Facing Retainer
and they are suitable for use with proval of the F445 Valve and are nec-
(4 reqd) 11 - Retainer Screw grooved end pipe couplings that are essary for proper operation of the F445
FIGURE B listed or approved for fire protection Valve.
system service.
MODEL F445 AUTOMATIC
The trim packages, may be installed
RESETTING DELUGE VALVE The F445 Valve is to be installed verti- on the F445 Valve with either flow left
- ASSEMBLY - cally, as shown in Figure A, with the or flow right, and each package in-
inlet connection at the bottom and the cludes the following items:
outlet connection to the side. Exterior
surfaces of the F445 Valve are painted l Water Supply Pressure Gauge
red, and the year of manufacture is l Diaphragm Chamber
indicated on the Cover. Pressure Gauge
l Diaphragm Chamber Connections
Components- of the F445 Valve are l Actuation Devices (as applicable)
shown in Figure B. The Body and l Main Drain Valve
Cover are ductile iron per ASTM A536, l Alarm Test Valve
Grade 65-45-12 (UNS F33100). Both l Alarm Control Valve
the Diaphragm and Facing are EPDM. l Automatic Drain Valve
The Diaphragm Ring and Center Valve
are bronze per ASTM 862 (UNS To ease field assembly of the trim ar-
CSSSOO),and the Seat Ring is brass rangements, the appropriate compo-
per ASTM B584 (UNS C84400 or nents required for Wet Pilot Actuation,
CSSSOO).The Facing Retainer is brass Dry Pilot Actuation, or Electric Actua-
per ASTM 8584 (UNS C84400). The tion are factory assembled as shown
in Figure F-2.

-2-
Wet Pilot Actuation
(Figure F-l, Items 1 through 34)
The Wet Pilot Actuation Trim provides
for connection of a detection system
consisting of wet pilot sprinklers (heat
detectors) and manual control stations
interconnected with minimum l/2 inch
(15 mm) Schedule 40 steel pipe. The
pilot line is connected to the Wet Pilot
Detection connection shown in Figure
F-l. Nominal installation dimensions
for the Wet Pilot Actuation Trim are
shown in Figure D.

Wet pilot sprinklers are to be minimum


l/2 inch (15 mm) orifice listed or ap- I WET I WET

proved automatic sprinklers. Manual


Control Stations are to be either the
- Set Position - - Open Position -
Model F180 or F184 described in Tech-
nical Data Sheet TD121.

The maximum height of a wet pilot line FIGURE C


above the F445 Valve must not exceed MODEL F445 AUTOMATIC RESETTING DELUGE VALVE
the.limitations given in Graph B as a - OPEN AND SET POSITIONS -
function of the minimum water supply
pressure to the F445 Valve and the
length of the pilot line to the most re- When a manual control station is proved automatic sprinklers. Manual
mote pilot sprinkler. opened to operate the F445 Valve, the Control Stations are to be either the
manual control station must remain Model F180 or F184 described in Tech-
Provision must be made for installing open in order for the F445 Valve to nical Data Sheet TD121.
a l/2 inch (15 mm) orifice, Inspectors remain open.
Test Connection at the most hydrauli- Graph C shows the minimum pilot line
cally demanding location of a wet pilot service pressure as a function of the
line (usually adjacent to the highest water supply pressure. The pressure
and most remote wet pilot sprinkler or Dry Pilot Actuation in the dry pilot actuation system must
manual control station). (Figure F-l, Items 1 through 34 plus be automatically maintained using one
Items Dl through D15) of the following maintenance devices,
To determine the most hydraulically The Dry Pilot Actuation Trim provides as appropriate.
demanding location of a wet pilot line, for installation of a detection system
when the choice between two or more consisting of dry pilot sprinklers (heat Model F324 Air Maintenance De-
locations is not readily apparent, de- detectors) and manual control stations vice (pressure reducing type),
termine for each location the elevation interconnected with minimum 112 inch refer to Technical Data Sheet
above the F445 Valve and the equiva- (15 mm) steel pipe. The pilot line, TDlll.
lent length of fittings plus pipe from the which is to be pressurized with air or
F445 Valve to the location. Then, using nitrogen, is connected to the Dry Pilot Model F326 Air Maintenance De-
Graph B, determine the minimum sys- Detection connection shown in Figure vice (compressor control type),
tem supply pressure required for the F. Provision must be made for a 112 refer to Technical Data Sheet
elevation and equivalent length of pipe inch (15 mm) orifice, Inspectors Test TD112.
at each location. Interpolate between Connection at the most remote loca-
the equivalent length plots as neces- tion from the F445 Valve. Nominal in- Model F328 Nitrogen Mainte-
sary. The location requiring the highest stallation dimensions for Dry Pilot Ac- nance Device (high pressure re-
system supply pressure is the most tuation Trim are shown in Figure E. ducing type), refer to Technical
hydraulically demanding location for Data Sheet TD113.
the wet pilot line. (Reference: In no The Dry Pilot Actuation Trim is pro-
case should the required system sup- vided with a listed and approved Model
ply pressure exceed the actual avail- B-l Dry Pilot Actuator, which is de- NOTES
able minimum expected system supply scribed in Technical Data Sheet The dewpoint of the pilot line airpres-
pressure.) TD117W. The Actuator is rated for use sure must be maintained below the
at a maximum pilot service pressure of lowest ambient temperature to which
Operation of a pilot sprinkler or open- 50 psi (3,4 bar) and a maximum water the dry pilot actuation system will be
ing of a manual control station results supply service pressure of 175 psi exposed. Accumulation of water in the
in a rapid pressure drop in the Dia- (12,l bar). pilot line connection to the Actuator
phragm Chamber of the F445 Valve, will lower the air pressure at which
and the force differential holding the Operation of a pilot sprinkler or open- the Actuator will open and possibly
F445 Valve in the set position is elimi- ing of a manual control station re- prevent proper operation. Also, intro-
nated. leases pneumatic pressure from the duction of moisture into the pilot lines
pilot line. In turn, the Dry Pilot Actuator exposed to freezing temperatures can
NOTES opens resulting in a rapid pressure create an ice buildup which couldpre-
Wet Pilot Lines must be maintained at drop in the Diaphragm Chamber of the vent proper operation of the Actuator.
a minimum temperature of 4OF/4C. F445 Valve, and the force differential
holding the F445 Valve in the set posi- An air dryer must be installed where
It is recommended that internallygal- tion is eliminated. the moisture content of the air supply
vanized pipe and cast iron fittings be is not properly controlled at less than
used for wet pilot lines. Dry pilot sprinklers are to be minimum the required value. The desiccant
l/2 inch (15 mm) orifice listed or ap- dryer with mounting accesories de-

-3
100 (30,48)

90 (27.43)

80 (24,38)

3
z 70(21,34)
iii
%
80 (18.29)
iii
y"
6 50(15,24)
3

9 40 (12,lQ)

5
ii 30 (9,14)

s
20 (8,lO)

10 (3,05)

0
100 120 140 180 175
El, (%Q) (8.3) (Qn7) (11,O) (12.1)

NOTE: IF THE SUPPLY PRESSURE IS VARIABLE. SUPPLYPRESSURE,PSI(BAR)


ASSUME MINIMUM EXPECTED VALUE.
GRAPH B
WET PILOT LINE DESIGN CRlTERlA

scribed in Technical Data Sheet


TD135 is suitable for use with a max-
imum inlet pressure of 150 psi (IO,3
bar) and for drying system air at a
maximum pressure of 45psi (3,1 bar)
down to a dewpoint of less than
-20F I-29C.

It is recommended that an F328 Ni-


trogen Maintenance Device be utilized
in dry pilot actuation system applica-
tions where the dewpoint must be
maintained below -2OFl-29C. See
Technical Data Sheet TDl13.

It is recommended that internally gal-


25 50 75 109 125 150 175
vanized pipe and cast iron fittings be WATER SUPPLY PRESSURE IN PSI
used for dry pilot lines.
GRAPH C
When a manual control station is DRY PILOT LINE PRESSURE REQUIREMENTS
opened to operate the F445 Valve, the
manual control station must remain
open in order for the F445 Valve to
remain open. . Low pressure alarm setting at D5 - Fig. F-l) is factory set to relieve
approximately 6 psi (0,4 bar) at a pressure of approximately 45 psi
Supervision of the pressure in the dry below the minimum pilot line (3,l bar); however, it may be field ad-
pilot actuation system and/or alarm service pressure requirement justed to a lower pressure, if required.
which separately indicates operation shown in Graph C.
of the detection system is recom-
mended and may be required by the . Fire alarm setting at approxi- Electric Actuation Trim
authority having jurisdiction. A dual mately 15 psi (1 ,O bar) below (Figure F-l, Items 1 through 34 plus
setting low pressure alarm switch, the minimum pilot line service Items El through ES)
such as the unit described in Technical pressure requirement shown The Electric Actuation Trim is required
Data Sheet TD210, is suitable for the in Graph C. for electric operation of the F445 Valve
service. The recommended pressure by a detection system consisting of
settings are as follows: The Pressure Relief Valve (Ref. Item electrical devices such as heat sensi-

-4-
tive thermostats, smoke detectors,
and/or electric manual pull stations.
Information on the various types of So-
lenoid Valves that may be used with The F445 Valve is a differential valve NOTES
this trim package is given in Technical which depends upon water pressure in Proper operation of the Model F445
Data Sheet TDll9. A listed and ap- the Diaphragm Chamber (Ref. Figure Deluge Valve depends upon its trim
proved, 24VDC Solenoid Valve for C) to hold the Center Valve Assembly being installed in accordance with the
non-hazardous locations is supplied closed against the water supply pres- instructions given in this Technical
as standard. Nominal installation di- sure. The nominal trip ratio is 2.5 to 1, Data Sheet. Failure to follow the ap-
mensions for the Electric Actuation i.e., the F445 Valve operates (opens) propriate trim diagram may prevent
Trim are shown in Figure D. when the pressure in the Diaphragm the F445 Valve from funtioning prop-
Chamber is reduced to approximately erly, as well as void listings, approv-
NOTE 40 percent of the water supply pres- als, and the manufacturers warran-
Approval by Factory Mutual is contin- sure. ties.
gent on the use of an FM Approved
24VDC Solenoid Valve. FM only ap- When the F445 Valve is set for service, The F445 Valve must be installed in a
proves solenoid valves for use in non- the Diaphragm Chamber is pressur- readily visable and accessible loca-
hazardous locations. ized through the trim connections from tion.
the inlet side of the systems main con-
The Electric Actuation Trim is only to trol valve, for example an O.S.&Y. gate The F445 Valve, associated trim, and
be used in conjunction with an electric valve or butterfly valve (Ref. Figure wet pilot lines must be maintained at
deluge valve releasing panel (auto- G-l, G-2, or G-3). Opening of an actu- a minimum temperature of 40F/4C.
matic control unit) that is listed or ap- ation device, for example the solenoid
proved (as appropriate) for fire protec- valve in the Electric Actuation Trim Heat tracing of the F445 Valve or its
tion system releasing service. In (Ref. Fig. G-3), releases water from associated trim is not permitted. Heat
addition, the deluge valve releasing the Diaphragm Chamber faster than it tracing can result in the formation of
panel is only to be operated by listed can be replenished through the l/8 hardened mineral deposits which are
or approved (as approriate) fire detec- (3,2 mm) Restriction in the Diaphragm capable of preventing proper opera-
tors. Chamber Supply Connection. This re- tion.
sults in a rapid pressure drop in the
Operation of an electrical device such Diaphragm Chamber and the force dif- The F445 Valve is to be installed in
as heat sensitive thermostat, smoke ferential holding the Center Valve As- accordance with the following criteria:
detector, or electric manual pull station sembly down in the set position is elim-
signals the deluge valve releasing inated. The water supply pressure
panel to energize the Solenoid Valve. then forces the Center Valve Assembly 1. All nipples, fittings, and devices
In turn, the energized Solenoid Valve open permitting water to flow into the must be clean and free of scale and
opens resulting in a rapid pressure system piping, as well as through the burrs before installation. Use pipe
drop in the Diaphragm Chamber of the Alarm Port to actuate system alarms thread sealant sparingly on male
F445 Valve, and the force differential (Ref. Figure C). pipe threads only.
holding the F445 Valve in the set posi-
tion is eliminated. NOTE NOTE
When an actuation device is opened to It is recommended that internally
operate the F445 Valve (e.g., a sole- galvanized pipe and cast iron fit-
NOTES noid valve or manual control station), tings be used for wet or dry pilot
Consult with the Authority Having the actuation device must remain lines.
Jurisdiction regarding installation open in order for the F445 Valve to
criteria pertaining to electric actua- remain open. 2. The F445 Valve must be trimmed in
tion circuitry. accordance with Figure Fl & F-2.

When a Solenoid Valve is energized to 3. Care must be taken to make sure


operate the F445 Valve, the Solenoid that check valves, strainers, globe
Valve must remain energized in order valves, etc. are installed with the
for the F445 Valve to remain open. flow arrows in the proper direction.

4. Drain tubing to the drip funnel must


be installed with smooth bends that
will not restrict flow.

5. The main drain and drip funnel drain


may be interconnected provided a
check valve is located at least 12
inches (300 mm) below the drip fun-
nel.

6. Suitable provision must be made for


disposal of drain water. Drainage
water must be directed such that it
will not cause accidental damage to
property or danger to persons.

7. Connect the Diaphragm Chamber


Supply Control Valve to the inlet side
of the systems main control valve ir
order to facilitate setting of the F445

-5-
1211*
(300mm)

II
I
SOLENOID VALVE k:T Nd;LT6T
LINE
(FOR ELECTRIC (FOR WET PILQT
ACTUATION) ACTUATION)

l/2 NPT,
DIAPHRAGM
KEER

wj (158.8mm)

Left View Front View


FIGURE D
NOMINAL INSTALLATION DIMENSIONS FOR
WET PILOT ACTUATION TRIM OR ELECTRIC ACTUATION TRIM
* MINIMUM CLEARANCE, ADDITIONAL 2 (50 mm) RECOMMENDED

Deluge Valve (Ref. Figure G-l, G-2, service pressure requirement To reset the Pressure Relief Valve,
or G-3). shown in Graph C. first loosen the jam nut and then
adjust the cap accordingly - clock-
8. An Inspectors Test Connection, as . Fire alarm setting at approxi- wise for a higher pressure setting or
described in the Technical Data sec- mately 15 psi (1,O bar) below counterclockwise for a lower pres-
tion, must be provided for Wet or Dry the minimum pilot line service sure setting. After verifying the de-
Pilot Actuation. pressure requirement shown sired pressure setting, tighten the
in Graph C. jam nut.
9. An Air Maintenance Device, as de-
scribed in the Technical Data Sec- 12. Unused pressure alarm switch con- 14. Conduit and electrical connections
tion, must be provided for Dry Pilot nections must be plugged. are to be made in accordance with
Actuation. the requirements of the authority
13. The Pressure Relief Valve provided having jurisdiction and/or the Na-
10. A desiccant dryer, when specified for with the Dry Pilot Actuation Trim is tional Electric Code.
Dry Pilot Actuation, is to be installed factory set to relieve at a pressure of
between a drip leg and the Air Main- approximately 45 psi (3,l bar),
tenance Device. which can typically be used for a
maximum normal dry pilot actuation
11. The Low Pressure Alarm Switch for system pressure of 40 psi (2,8 bar).
Dry Pilot Actuation is to be adjusted The Pressure Relief Valve may be
as follows: reset; however, it must be be reset
to relieve at a pressure which is in
l Low pressure alarm setting at accordance with the requirements of
approximately 6 psi (0,4 bar) the authority havng jurisdiction.
below the minimum pilot line

-6-
II *
IO &l/4
(250mm)

---I
(209,6mm)

DRY PILOT ACTUATOR

Left View Front View


FIGURE E
NOMINAL INSTALLATION DIMENSIONS FOR
DRY PLIOT ACTUATION TRIM
* MINIMUM CLEARANCE, ADDITIONAL 2 (50 mm) RECOMMENDED

auxiliary drains in the system. Close 6. Open the Alarm Control Valve (Fig.
the auxiliary drain valves after water F), if it was closed to silence local
ceases to discharge. Leave the Main alarms.
Steps 1 through 11 are to be performed Drain Valve open.
when initially setting the F445 Valve; It is recommended that the Alarm
after an operational test of the fire 4. Depress the plunger of the Auto- Control Valve be wire sealed in the
sprinkler system; or, after system op- matic Drain Valve to verify that it is open position with a No. 16 twisted
eration due to a fire. open and that the F445 Valve is wire, the ends of which are secured
completely drained. by a lead seal. The wire seal should
1. Close the Diaphragm ChamberSup- be looped through the hole in the
ply Control Valve. 5. Clean the Strainer in the Diaphragm handle and tightly twisted around the
Chamber Supply connection by re- pipe nipple adjacent to the handle.
2. Close the Main Control Valve, and if moving the clean-out plug and
the system is equipped with Dry Pilot strainer basket. The Strainer may be 7. Reset the actuation system.
Actuation, close the Air Supply Con- flushed out by momentarily opening
trol Valve (Ref. Figure F-l). the Diaphragm Chamber Supply Manual Actuation - Push the oper-
Control Valve. ating lever up; however, do not close
3. Open the Main Drain Valve and all the hinged cover at this time.

-7-
LOW PRESSURE
ALARM SWITCH +::)11
(ORDERED
SEPARATELY 1
I I ;
. I I
\

DI I

SOLENOID VALVE

El

E2
DI
E3

l/2 NPT CONNECTION


:D9 FROM MODEL F324,
TO DRIP FUNNEL
hNCE
D7
Dl3

DRY PILOT LINE


t PRESSURE GAUGE
TO DRIP FUNNEL

\ 314 NPT CONNECTION


27 FOR WATER MOTOR
ALARM

25 23 -

(GREEN TINT) 14
DIAPHRAGM CHAMBER
SUPPLY CONTROL VALVE
DIAPHRAGM (NORMALLY OPEN)
----- .-- _.CHAMBER
_- I5
KitSSUKt GA&t

\> DIAPHRAGM CHAM,BER


SUPPLY CONNECTION
a. 3
\
79 I9

25
ALTERNATE
PRESSURE ALARM
r- C,.II-rCI I I rtCI7Im.I

24

24

SYST
SUPP
GAUG AUTOMATIC
DRAIN VALVE

I8

NOTE: Refer to Page 9 for the corresponding bills of materials.


FIGURE F-l
VALVE TRIM ASSEMBLY

-8-
1 - 306 lb. Water 28 - l/2 x 2 Nipple
Pressure 29 - l/2 x2-l/i
Gauge Nipple
(2 reqd) INCLUDED ONLY WITH DRY
30 - l/2 x 3-112
PILOT ACTUATION TRIM
2 - I/4 Gauge Nipple
Test Valve 31 - 112 x 4-112
3 - Model F160 Nipple
Manual Con- 32 - 112 x 10-l/2
trol Station Nipple
4 - 1-l/4 Angle 33 - l/4 x 3 Nipple
Valve 34 - l-114 x 3
5 - l/2 Ball Valve Nipple
(3 reqd)
6 - l/2 Swing Dl - Model B-l
Check Valve Dry Pilot
7 - 112 Spring Actuator
Loaded D2 - 250 lb. Air
Check Valve Pressure
6 - Priming Supply Gauge
Restriction D3 - l/4 Gauge Test
9 - l/2 Y-Strainer Valve
10 - Model F793 D4 - i/2 Globe Valve
Automatic D5 - l/4 Pressure
Drain Valve Relief Valve
11 - Drip Funnel D6 - i/4 Plug
support Plug D7 - l/2 Tube
12 - Drip Funnel Connector
support D8 - l/2 Tube,
13 - Drip Funnel 24 long
14 - 3/32 Vent DQ - 112 90 Elbow
Ftttlng DlO - t/2 x l/2 x 114
15 - i/4 Tube, Tee (2 reqd)
24 long Dl 1 - 112 Tee
16 - i/2 Tube (2 reqd)
Connector Dt2 - l/4 x l-112
17 - l/2 Tube, Nipple
24 long Dt3 - 112.x l-112
is - 114 Plug Nipple
19 - l/2 Plug (6 reqd)
20 - 3/4 Plug Dt4 - l/2 x2-112
21 - 112 x l/4 Nipple
Bushing D15 - 112 x 5 Nipple
22 - l/2 Union
(4 reqd)
23 - l/2 90 Elbow El - 112 90 Elbow
(5 reqd) *. E2 - l/T Tube
24 - l/2 Tee (6 reqa) Connector
25 - l/2 x l/4 x l/2 E3 - l/2 Tube,
WATER w
Tee (2 reqd) 24 long
26 - l/2 x l/2 x 3l4 E4 - l/2 x l-112
Tee Nipple
27 - l/2 x l-112 (2 reqd)
Nipple E5 - 24VDC Solenoid
(16 reqd) Valve

NOTES:

1. Wet Pilot Actuation Trim consists NOTE.


of Items 1 through 34. Assemble in alphabetical order.
2. Dry Pilot Actuation Trim consists of
Items 1 through 34 plus Items Dl FIGURE F-2
through D15. STANDARD ORDER FACTORY ASSEMBLED VALVE TRIM
3. Electric Actuation Trim consists of
Items 1 through 34 plus El through
E5. any solder type sprinklers which
Wet Pilot Actuation - Replace oper-
ated pilot sprinklers andlor reset the were possibly exposed to a temper-
4. The illustrated arrangement, shown ature greater than their maximum
manual control stations.
on Page 8, is for Flow Right. A rated ambient must be replaced.
Flow Left arrangement can be ob-
Dry Pilot Actuation - Replace oper-
tained using the same bill of materi- 8. Open the Diaphragm Chamber Sup
ated pilot sprinklers and/or reset the
als. ply Control Valve and allow time for
manual control stations. Re-estab-
lish dry pilot pneumatic pressure. full pressure to build up in the Dia-
5. The nipples utilized in the trim ar- phragm Chamber.
rangements are Schedule 40 black Electric Actuation - Reset the elec-
steel per ASTM A53 or Al35 and 9. Operate (open) the Manual Control
tric detection system in accordance
they are threaded per ANSI B1.20.1. Station to vent trapped air from the
with the manufacturers instructions
Fittings are either malleable iron per to de-energize the solenoid valve. Diaphragm Chamber. If necessary,
ANSI 816.3 or cast iron per ANSI first open the hinged cover, and then
816.4. NOTE fully pull down on the operating
In order to prevent the possibility lever. SLOWLY close the operating
FIGURE F of a subsequent operation of an lever, by pushing it up, after aerated
VALVE TRIM ASSEMBLY overheated solder type sprinkler, water ceases to discharge from the

-9-
SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS-NORMALLY DRY

A
t + + t
WET PILOT SPRINKLER DETECTION SYSTEM
(MINIMUM I/ZPIPE AND AUTOMATIC SPRINKLERS)

INSPECTORS
RESTRICTION SPECIFIED1
TEST
CONNECTION
IAT THE MOST
WATERFLOW
HYDRAULICALLY
DEMAND I NG
LOCATION OF THE
WET PILOT LINEI

DIAPHRAGM WATER SUPPLY PRESSURE GAUGE


CHAMBER

DIAPHRAGM CHAMBER SUPPLY CONNECTIOd


WATER
SUPPLY

FIGURE G-l
DELUGE VALVE SYSTEM SCHEMATIC
-WET PILOT ACTUATION-

SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS-NORMALLY DRY

4 A
-DRY PILOT SPRINKLER DETECTION SYSTEM
LOW PRE IMINIMUM I/ZPIPE AND AUTOMATIC SPRINKLERS)
ALARM E
Y 1 nrnnnlvl
I I Y. , . . .,..--
Lnr!MD)ttT
DRY PILOT ACTUATOR
PRESSURE
STATION DRAIN /
GAUGE
I WHEN
4 SPECIFIED INSPECiORS
DRAIN I
RESTRICTION ATMO;;HERE TEST
CONNECTION
I I u ,7
I I n - I AT THE MOST
,WATERFLOW REMOTE
/

MAIN DRAIN 1

-II m-- MODEL F445 DELUGE VALVE

DIAPHRAGM
CHAMBER
c
DRAIN
WATER SUPPLY PRESSURE GAUGE

SUPPLY
MAIN CONTROL VALVE
CONTROL----
(NORMALLY OPEN1
VALVE
(NORMALLY
OPEN I

DIAPHRAGM CHAMBER SUPPLY CONNECTION 1 I


WATER
SUPPLY

FIGURE G-2
DELUGE VALVE SYSTEM SCHEMATIC
- DRY PILOT ACTUATION-

-10-
SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS-NORMALLY DRY

ELECTRIC DETECTION SYSTEM


(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.

DELUGE VALVE

POWER SUPPLY WATERFLOW PRESSURE


(TYPICALLY ALARM SWITCH
120 VOLTS AC)

MODEL F445 DELUGE VALVE

D I APHRAGM I WATER SUPPLY PRESSURE GAUGE

DIAPHRAGM CHAMBER SUPPLY CONNECTION J, I


WATER
SUPPLY

FIGURE G-3
DELUGE VALVE SYSTEM SCHEMATIC
- ELECTRIC ACTUATION-

Manual Control Station drain tubing. notify the proper authorities and ad-
Close the hinged cover and insert a vise those responsible for monitoring
new break rod in the small hole proprietary andlor central station
t;;ugh the top of the enclosing alarms.

If wet pilot actuation is being used,


crack open the Inspectors Test Con-
nection and any other vent valves, to
relieve trapped air. After the dis-
charge of air has stopped, close the
vent valves and the Inspectors Test
Connection.

10. Inspect drain connections from the


Manual Control Station, Solenoid
Valve, Dry Pilot Actuator, and Alarm
Devices, as applicable. Any leaks
must be corrected before proceed-
ing to the next step.

11. Slowly open the Main Control Valve.


Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, the F445 Valve is ready to
be placed in service and the Main
:;;;:A Vave must then be fully

NOTE
After setting a fire protection system,

-ll-
manufacturers instructions to ener- 7. Slowly open the Main Control Valve.
gize the solenoid valve. Close the Main Drain Valve as soon
as water discharges from the drain
The following procedures and inspec- 3. Verify that the F445 Valve has connection. Observe the Automatic
tions should be perform as indicated, tripped, as indicated by the flow of Drain Valve for leaks. If there are
in addition to any specific require- water into the system. leaks, determine/correct the cause
ments of the NFPA, and any impair- of the leakage problem. If there are
ment must be immediately corrected. 4. Close the Diaphragm ChamberSup- no leaks, the F445 Valve is ready to
It is also recommended that fire protec- ply Control Valve. be placed in service and the Main
tion systems be inspected by a quali- Control Vave must then be fully
fied Inspection Service. 5. Close the systems Main Control opened.
Valve.
NOTES
The operational test procedure, 6. Reset the F445 Deluge Valve in ac- Quarterly Dry Pilot Actuator Test
waterflow pressure alarm test proce- cordance with the Valve Setting Pro- Procedure For Dry Pilot Actuation
dure, and low pressure alarm test pro- cedure.
cedure will result in operation of the Proper operation of the Dry Pilot Actu-
associated alarms, Consequently, no- ator for dry pilot actuation should be
tification must be given to the owner Five Year Internal Valve Inspection verified at least quarterly as follows:
and the fire department, central sta-
tion, or other signal station to which Once every five years during the an- 1. Close the Main Control Valve.
the alarms are connected. nual operation procedure and prior to
the F445 Valve being reset, the inter- 2. Open the Main Drain Valve.
Before closing a fire protection system nal parts of the F445 valve should be
main control valve for maintenance cleaned and inspected for wear and 3. Open the Inspectors Test Connec-
work on the fire protection system damage. Special consideration should tion on the Dry Pilot Line.
which it controls, permission to shut be given to the condition of the Dia-
down the effected fire protection sys- phragm. The Diaphragm should be re- 4. Verify that the flow of water from the
tems must first be obtained from the placed if there are any sign of deterio- Dry Pilot Actuator drain connection
proper authorities and all personnel ration due to age or chemicals in the increases to a full flow.
who may be affected by this decision water. If the water supply contains
must be notified. chemicals which tend to attack an 5. Verify that the Diaphragm Chamber
EPDM type rubber, then the frequency pressure has decreased to below
of the Diaphragm inspection should be 25% of the water supply pressure.
Annual Operation Test Procedure increased to at least annually.
6. Close the Inspectors Test Connec-
Proper operation of the F445 Valve Worn or damaged parts must be re- tion and allow the dry pilot line pres-
(i.e., opening of the F445 Valve as placed and the F445 Valve must be sure to re-establish. Check the Dry
during a fire condition) should be veri- reassembled in accordance with Fig- Pilot Actuator drain for leaks. Any
fied at least once a year as follows: ure B. The Cap Screws securing the leaks must be corrected before pro-
Cover should be uniformly tightened ceeding to the next step.
If water must be prevented from using a cross-draw sequence.
flowing beyond the riser, perform the 7. Slowly open the Main Control Valve.
following steps. Close the Main Drain Valve as soon
Quarterly Solenoid Valve Test Pro- as water discharges from the drain
a. Close the Main Control Valve. cedure For Electric Actuation connection. Observe the Automatic
Drain Valve for leaks. If there are
b. Open the Main Drain Valve. Proper operation of the Solenoid Valve leaks, determine/correct the cause
for electric actuation should be verified of the leakage problem. If there are
c. Open the Main Control Valve at least quarterly as follows: no leaks, the F445 Valve is ready to
one turn beyond the position at be placed in service and the Main
which water just begins to flow 1. Close the Main Control Valve. Control Vave must then be fully
from the Main Drain Valve. opened.
2. Open the Main Drain Valve.
d. Close the Main Drain Valve.
3. Test the automatic control unit (del- ~~;u~erly Waterflow Alarm Test Pro-
Determine the type of actuation/de- uge releasing panel) in accordance
tection system, and operate the with the manufacturers instructions
F445 Valve accordingly. to energize the solenoid valve. Testing of the the system water-flow
alarms should be performed quarterly.
NOTE 4. Verify that the flow of water from the To test the waterflow alarm, open the
Be prepared to quickly perform Solenoid Valve drain connection in- Alarm Test Valve, which will allow a
Steps 3, 4, and 5, if water must be creases to a full flow. flow of water to the Pressure Alarm
prevented from flowing beyond the Switch and/or Water Motor Alarm.
riser. 5. Verify that the Diaphragm Chamber Upon satisfactory completion of the
pressure has decreased to below test, close the Alarm Test Valve.
Wet Pilot Actuation - Open the 25% of the water supply pressure.
Inspectors Test Connection.
6. Reset the electric detection system Quarterly Low Pressure Alarm Test
Dry Pilot Actuation - Open the in accordance with the man- Procedure And Condensate Drain
Inspectors Test Connection. ufacturers instructions to de-ener- Procedure For Dry Pilot Actuation
gize the solenoid valve. Check the
Electric Actuation - Test the del- Solenoid Valve drain for leaks. Any For Dry Pilot Actuation, testing of the
uge releasing panel (automatic con- leaks must be corrected before pro- Low Pressure Alarm Switch and drain-
trol unit) in accordance with the ceeding to the next step.

-12-
age of the pilot line condensate should Standard Order
be performed quarterly as follows. Factory Assembled Black Trim:

1. Close the Diaphragm ChamberSup- Seller warrants for a period of one year Specify: (specify type trim) for use with
ply Control Valve. from the date of shipment (warranty the Model F445 Automatic Resetting
period) that the products furnished Deluge Valve, PSN (specify).
2. Close the Main Control Valve. hereunder will be free from defects in
material and workmanship. Wet Pilot Actuation
3. Open the Main Drain Valve. Trim .. . .. . . .PSN 52-445-l-101
For further details on Warranty, see Dry Pilot Actuation
Trim .. . . .PSN 52-445-i -102
4. Drain the dry pilot line condensate Price List. Electric Actuation
as follows. Trim With 24VDC
Solenoid Valve . .PSN 52-445-l -103
a. Close the Gauge Test Valve
located below the Dry Pilot Special Order
Line Pressure Gauge. Factory Assembled
Galvanized Trim:
b. Remove the l/4 Plug from the
Gauge Test Valve. Specify: (specify type trim) for use with
the Model F445 Automatic Resetting
c. Crack Open the Gauge Test Deluge Valve, PSN (specify).
Valve and allow all conden-
sate, if any, to drain out. Wet Pilot Actuation
Trim . . .PSN 52-445-2-101
Dyrr;! Actuation
d. Close the Gauge Test Valve, . . . . . . . . . . . . . . . . . .PSN 52-445-2-102
replace the Plug, and then Electric Actuation
open the Gauge Test Valve. Trim With 24VDC
Solenoid Valve .. .PSN 52-445-2-103
5. Open the Inspectors Test Connec- All orders for Model F445 Valves, trim,
tion, and slowly relieve pneumatic accessories, and replacement parts Special Order Electric Actuation
pressure. Verify that the Low pres- must include the description and Prod- Trim With Separately Ordered Sole-
sure Alarm Switch is operational and uct Symbol Number (PSN), where ap- noid Valve Trim:
that the low pressure set points are plicable.
as follows: Specify: (specify Factory assembled
or Unassembled), (specify black or
. Low pressure alarm setting at ANSI Pipe Connection Valves: galvanized) Electric Actuation Trim
approximately 6 psi (0,4 bar) With Separately Ordered Solenoid
below the minimum pilot line Specify: 2-l/2 inch, (specify Thread x Valve for use with the Model F445 Au-
service pressure requirement Thread or Groove x Groove), Model tomatic Resetting Deluge Valve.
shown in Graph C. F445 Automatic Resetting Deluge
Valve for ANSI Pipe Connection, PSN When ordering Electric Actuation Trim
. Fire alarm setting at approxi- (specify). With Separately Ordered Solenoid
mately 15 psi (1 ,O bar) below Valve, refer to Technical Data Sheet
the minimum pilot line service Thread x Thread TD119 for information on separately
pressure requirement shown (NPT) PSN 52-445-l-001 ordered, UL Listed Solenoid Valves
Groove x Groove that may be suitable for use in hazard-
in Graph C. (73.0 mm O.D.) PSN 52-445-l-002
ous locations or that have voltage rat-
6. Close the Inspectors Test Connec- ings other than 24VDC.
tion, and allow the Dry Pilot Line to IS0 Pipe Connection Valves:
automatically repressurize. NOTE
Factory Mutual Approval for electric
Specify: 2-l/2 inch, (specify Tapered
7. Open the Diaphragm Chamber Sup- Thread x Thread; Parallel Thread x actuation of the F445 Valve is contin-
ply Control Valve. gent on the use of the FM Approved
Thread; or, Groove x Groove), Model
24VDC Solenoid Valve provided with
F445 Automatic Resetting Deluge
6. Slowly open the Main Control Valve. the Standard Order Electric Actua-
Valve for IS0 Pipe Connection, PSN
Close the Main Drain Valve as soon tion lkim, PSN 52-445-l-103 or PSN
(specify).
as water discharges from the drain 52-445-2- 103.
connection. Observe the Automatic Tapered
Drain Valve for leaks. If there are Thread x Thread Accessories:
leaks, determine/correct the cause (IS0 7/l) PSN 52-445-4-001
of the leakage problem. If there are Parallel Refer to the following Technical Data
Thread x Thread Sheets (TD), as applicable.
no leaks, fully open the Main Control (IS0 7/i) PSN 52-445-4-002
Valve. Groove x Groove Pressure Alarm Switch TD213
(76.1 mm O.D.) PSN 52-445-4-003 Low Pressure Alarm Switch TD210
Model F324 Air Maintenance
Trim: Device . . . . . . . . . . .._....._ TDlll
Model F326 Air Maintenance
Device . . . . . . . . . . . . . . . . . . . TD112
Unless otherwise specified, all trim ar- Model F326 Nitrogen Maintenance
rangements are provided factory as- Device . . . . . . . . . . . . . . . . . . TD113
sembled as shown in Figure F-2. Un- Desiccant Dryer TD135
assembled trim packages as shown in Model F160 or F184
Manual Control Stations TD121
Figure F-l can be provided on special
order. Product Symbol Numbers
(PSN) need not be specified when or-
dering unassembled trim.

-13-
Replacement Valve Parts (Fig. B):

Specify: (description) for use with


Model F445 Automatic Resetting Del- The following are the nominal weights
uge Valve, PSN (specify). for the valves and trim:

2 - Cover . .. . .PSN 92-445-l-002 2-112 Thread x Thread


3 - Diaphragm . . .PSN 92-445-l -063 Model F445 Deluge Valve . . 41 Ibs. (16.6 kg)
4 - Diaphragm Ring . . . . .PSN 92-445-1-004 2-i/2 Groove x Groove
5 - Cap Screw, Model F445 Deluge Valve . . 44 Ibs. (20,Okg)
i/4*-20 UNC Wet Pilot Actuation Trim ... 24 Ibs. (IO,9 kg)
x 3!4 . . . . . . . . . . .PSN 62-634-I-104 Dry Pilot Actuation Trim ... 34 Ibs. (I 5,4 kg)
6 - Cap Screw, Electric Actuation Trim
l/2--13 UNC With 24VDC Solenoid Valve 27 Ibs. (12,2 kg)
x716 .. . . . .PSN 62-634-l-111
7 - Center Valve . . . . .PSN 92-445-l -005
8 - Facing . . . .PSN 92445-l -006
10 - Facing Retainer.. . . . .PSN 92-445-1-006
11 - Retainer Screw . .PSN 62-679-i -012

Replacement Trim Parts (Fig. F-l):

Specify: (description) for use with


Model F445 Automatic Resetting Del-
uge Valve, PSN (specify).

1 - 300 lb. Water


Pressure Gauge . . . .PSN 92-343-l -005
2 - 114 Gauge Test
Valve . . . . . . . . . .PSN 46-005-l-002
3 - F160 Manual
Control Station , . . .PSN 52-269-l -001
4 - l-1/4 Angle
Valve . . . . . . . . . . . . .PSN 46-046-l-007
5 - l/2 Ball Valve . . . .PSN 46-050-I -004
6 - l/2 Swing
Check Valve . . . .PSN 46-049-l-004
7 - l/2 Spring
Loaded Check
Valve .. . . .PSN 92-322-l -002
6 - Prfming Supply
Restriction ... . . . .PSN 92-020-I-009
9 - 112 Y-Strainer . . . . . .PSN 52-353-i -005
10 - F793 Auto-
matic Drain Valve . . .PSN 52-793-i -004
11 - Drip Funnel
Support PtUQ . . .PSN 92-21 i-l-005
12 - Drip Funnel
support . . . . . . . . . .PSN 92-21 l-l-003
13 - Drip Funnel . . . . .PSN 92-343-l -007
14 - 3l32 Vent
Fitting . , . . . . .PSN 92-032-l -002
Dl - B-1 Dry Pilot
Actuator . . . . . .PSN 52-260-i-001
D2 - 250 lb. Air
Pressure Gauge . . .PSN 92-343-l-012
D3 - 114 Gauge
Test Valve . . . . . . .PSN 46-005-l-062
D4 - 112 Globe
Valve . . . . . . . . . . . . . .PSN 46-047-I -004
D5 - l/4 Pressure
Relief Valve .... .PSN 92-343-i -020
E5 - 24VDC Sole-
noid Valve . . . . . .PSN 52-267-l-024

-14-
-15