Академический Документы
Профессиональный Документы
Культура Документы
Phone: 800-448-0770
Fax: 847-855-6300
www.ohiomedical.com
TABLE OF CONTENTS
Technical
You will notice that the categories on the worksheet coincide with various areas in the hospital. Because of the
manner in which the space is used, the value given for flow is either per room, per bed, or per outlet. For exam-
ple, in areas where only one procedure will be performed, such as surgery, we use a per room value. In areas
where there may be several uses simultaneously and the possibility of vast fluctuations in use, such as a recovery
suite, we calculate the demand per bed. You will also notice the term Simultaneous Use Factor. This is a value
given to the likelihood that the full demand will exist in a particular area at any given time. The most critical areas,
such as surgery, will have the highest likelihood and therefore the greatest value.
To use the worksheet, start by filling in the quantities of each area in the left-hand column. Keep in mind to tally
these figures correctly; either per room, bed or outlet. Also be certain to account for all of the outlets which are
part of the proposed system. Some outlets may be easy to overlook and some departments in the facility may be
known by a slightly different name. If you encounter an area in the facility that is not listed on the worksheet, cat-
egorize it based on what procedures are performed in that area.
With all of the areas accounted for, multiply each quantity by the given Design Flow value, and then multiply by the
Simultaneous Use Factor. Write the value in the right hand column for each line. Finally, total the values for all of
the lines at the bottom of the sheet. This value is the Calculated Peak Demand, expressed in Standard Cubic Feet
per Minute at a vacuum level of 19Hg Gauge.
Having tallied the Calculated Peak Demand, you must adjust for any abnormal conditions. High elevation, opera-
tion on 50 Cycle current or unusual ambient temperatures can affect performance. If considering future expansion,
you may opt for a system with a control package which will allow for an additional pump to be added later.
When the Calculated Peak Demand exceeds the capacity of a 10 Horsepower pump, consider using a triplex or
quadruplex system rather than duplex. For example, if you have chosen a 15Hp duplex system, also consider a
7.5 Hp triplex version where two of the three pumps will meet the Calculated Peak Demand. Demand for
Medical/Surgical Vacuum in a typical facility varies widely in the course of a day, and in times of low demand, a 7.5
Hp pump will be required to operate as opposed to a 15 Hp pump. Each pump on the system is controlled by a
separate vacuum switch, allowing more efficient operation and reducing current spikes caused by the in-rush as
the larger motors start. In many cases, the initial expense of the multiplex system is also lower.
A dedicated Waste Anesthetic Gas Evacuation system is best served by use of a separate simplex or duplex vac-
uum system of either the Water Sealed Liquid Ring or Dry Running Rotary Vane style. Pumps lubricated or sealed
with oil are not to be used for such a system.
TM
You will notice that the categories on the worksheet coincide with various areas in the hospital. Because of the
manner in which the space is used, the value given for flow is either per room, per bed, or per outlet. For exam-
ple, in areas where only one procedure will be performed, such as surgery, we use a per room value. In areas
where there is the possibility of vast fluctuations in use, such as an ICU, we calculate the demand per bed. You
will also notice the term Simultaneous Use Factor. This is a value given to the likelihood that the full demand will
exist in a particular area at any given time. The most critical areas, such as surgery, will have the highest likelihood
and therefore the greatest value.
To use the worksheet, start by filling in the quantities of each area in the left-hand column. Keep in mind to tally
these figures correctly; either per room, bed or outlet. In the case of Ventilators, it is important to consider the type
and requirements of each unit the facility intends to operate. Ventilators powered by medical air require consider-
able capacity and must be accounted for. Also be certain to account for all of the outlets which are part of the pro-
posed system. Some outlets may be easy to overlook and some departments in the facility may be known by a
slightly different name. If you encounter an area in the facility that is not listed on the worksheet, categorize it based
what procedures are performed in that area.
With all of the areas accounted for, multiply each quantity by the given Design Flow value, and then multiply by the
Simultaneous Use Factor. Write the value in the right hand column for each line. Finally, total the values for all of
the lines at the bottom of the sheet. This value is the Calculated Peak Demand, expressed in Standard Cubic Feet
per Minute at a pressure of 50 Pounds per Square Inch Gauge.
Having tallied the Calculated Peak Demand, you must adjust for any abnormal conditions. High elevation, opera-
tion on 50 Cycle current or unusual ambient temperatures can affect performance. If considering future expansion,
you may opt for a system with a control package, which will allow for an additional compressor to be added later.
When the Calculated Peak Demand exceeds the capacity of a 15 Horsepower compressor, consider using a triplex
or quadruplex system rather than duplex. For example, if you have chosen a 20 Hp duplex system, also consid-
er a 7.5 Hp triplex version where two of the three compressors will meet the Calculated Peak Demand. Demand
for Medical Air in a typical facility varies, and in times of low demand, a 7.5 Hp compressor will be required to oper-
ate as opposed to a 20 Hp compressor. Each compressor on the system is controlled by a separate pressure
switch, allowing more efficient operation and reducing current spikes caused by the in-rush as the larger motors
start. In many cases, the initial expense of the multiplex system is also lower.
Please peruse the Accessories tab of the Medical Air Systems section for optional types of air dryers and other
related accessories. The Healthcair Treatment Module is a fabricated package incorporating dual dryers, filters,
regulators, and monitors. It can be used to upgrade existing installations.
TM
Electrical Connections:
Miscellaneous:
SPECIAL CONSIDERATION
The performance data for Medical Air and Vacuum Systems is based upon standard atmospheric conditions.
Significant deviations from these standards must be accounted for in proper selection of the systems.
Elevation
If the site is above sea level, the reduced barometric pressure of the atmosphere affects the performance of
Medical/Surgical Vacuum Systems in two ways. First, the maximum vacuum level obtainable is reduced. In addi-
tion, the capacity or flow characteristics of a vacuum pump at a given vacuum level are reduced.
Base on their performance curves, different types of vacuum pumps react differently. Please consult the factory
for help in selection of systems for higher altitudes.
Temperature
These systems are intended to be installed indoors, in a controlled climate. Temperatures should never approach
freezing or exceed 104 degrees Fahrenheit. These extremes will affect overall system performance, maintenance
intervals and equipment life as well.
In addition, these systems will generate heat, and this heat load must be considered when designing the mechan-
ical space in which they are to be installed.
To calculate the heat generated by the air or vacuum system, use Brake Horsepower of the system multiplied by
2,545 BTU/Hr. ___ BHP x 2,545 BTU/Hr = _____ BTU/Hr generated by the system. In the case of multiplex sys-
tems, use the horsepower value of the units that are intended to operate under normal conditions. If you do not
know the Brake Horsepower requirement, use the nameplate Horsepower value.
This formula can also be used to calculate the heat load that a totally recirculated, water sealed, liquid ring pump
will contribute to the cooling water loop or chiller.
Liquid ring vacuum pumps using water as a sealing fluid are subject to decreased performance if the water tem-
perature is substantially greater then 60 degrees Fahrenheit.
Inertia Bases
When installed above ground, it may be advisable to mount reciprocating compressors on an inertia base. This
will eliminate the transfer of vibration and related noise to the structure. Rotary vane and Liquid ring style units do
not require inertia bases.
Seismic Certification
Most systems can be certified for use in various seismic zones. Please consult the Medical Sales Department for
help in selecting a system.
TM
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
2 of 4
T E C H N I C A L S U P P O R T
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
3 of 4
T E C H N I C A L S U P P O R T
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
4 of 4
SUGGESTED MEDICAL GAS MASTER ALARM POINTS SUGGESTED MEDICAL GAS MASTER ALARM POINTS
FOR LEVEL 1 FACILITIES FOR LEVEL 1 FACILITIES
Source/Mainline Source/Mainline
Isolation Valve Isolation Valve 261920* Actuating Pressure Switch
(Reserve In Use, Activate HP Cylinders
set at 85 PSIG)
Typical Nitrogen (N2) Installation
Check Valve
Located
in Pigtail
Source/Mainline Source/Mainline
Isolation Valve Isolation Valve 261920* Actuating Pressure Switch
(Reserve In Use, Activate HP Cylinders
set at 85 PSIG)
Typical Nitrogen (N2) Installation
Check Valve
Located
in Pigtail
1 1
1/4" NPT MALE
TO 1/8" NP T FE MALE
FOR SWITCH
RE DUCING BUSHING
1/4" NP T CLOS E
NIPP LE (2)
1
FOR SWITCH 1
1/4 " NPT 1/4" NPT MALE
CLOSE NIPPLE TO 1/8" NPT FEMALE
REDUCIN G BU SHING
1
1
FOR GAUGE
1/4" NPT MALE
GAUGE TO 1/8" NPT FEMALE
REDUCIN G BU SHING
Manifold Sizing
Medical Air Manifold:
Divide total by 2 for each Bank Divide total by 2 for each bank Divide total by 2 for each bank
CONVERSION CHART
ACFM / SCFM
Vacuum Vacuum Vacuum
Level Conversion Level Conversion Level Conversion
(Gauge Factor (Gauge Factor (Gauge Factor
1" 1.03 11" 1.58 21" 3.33
TM
MISCELLANEOUS CONVERSIONS
#/Hr to ACFM: #/Hr(1/60)(379/MW)(760/P)(460+T/250)
ACFM to #Hr: ACFM(60/1)(MW/379)(P/760)(520/460+T)
NOTE: Where MW is the molecular w eight, P is the operating pressure in TORR,
and T is the operating temperature in oF.
TM
Example: A vacuum receiver needs to be sized for a new installation. The forming vol-
ume is 0.8 Ft3, and the box volume is 1.2 Ft3. The initial pressure in the mold
is 29.75 Hg (barometric pressure). The required pressure to form the sheet in
the mold is 22 Hg. The pressure produced by the vacuum pump will be consid-
ered to be a maximum of 28 Hg.
First one must determine what are the appropriate variables, and then covert them to the
appropriate units.
V2 To be determined
V1 2 Ft3 (0.8 Ft3 + 1.2 Ft3)
P1 14.61 PSIA (29.76 Hg(A) converted to PSIA)
P2 0.98 PSIA (28 Hg(G) first converted to 2 Hg(A), then converted to PSIA)
P3 3.93 PSIA (22 Hg(G) first converted to 8 Hg(A), then converted to PSIA)
V2 = 2 (3.93 14.61)/(0.98-3.93)
V2 = 7.24 Ft3 or times 7.48 gal/1 Ft3;
V2= 54 gal
Another formula is useful where an existing tank is to be used. If the receiver size is known,
one will wish to calculate the pressure in the combined system.
P3 = (P1V1+P2V2)/(V1+V2) Equ. 1.2
Example: Say that a 60 gal receiver is available from stock, what will be the final pressure
in the combined system?
First one must determine what are the appropriate variables, and then convert them to the
appropriate units.
In most cases the system volume is equivalent to the tank volume. Generally if the pipework
associated with the system is greater than 10% of the tank volume, that the volume of the
pipework should be taken into account. These formulas also do not account for the collapse
of the plastic in the mold. In most cases, the forming volume is so much smaller than the sys-
tem volume that it does not add much to the calculations. These formulas also do not
account for leaks in the system.
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
2 of 6
T E C H N I C A L S U P P O R T
Note that this formula does not account for leaks in the system
Example: The 60 gal receiver from the previous example has been installed. The process
requires that the vacuum pump should pull the combined system from 22.4 Hg
to 28 Hg in approximately 10 seconds to increase the detail on the molded
plastic. Will the S3 be able to accomplish this?
t = To be determined
V 9.22 Ft3 (1.2 Ft3 = 8.02 Ft3) {note that the forming volume is approximately 0}
P1 3.7 PSIA (22.4 Hg(G) determined by equation 1.2)
PF 0.98 PSIA (28 Hg(G) first converted to 2 Hg(A), then converted to PSIA)
QAVG 37 ACFM
The average flowrate is determined by adding the flows at different vacuum levels. The aver-
age capacity of the pump should be taken between the starting vacuum level and the ending
vacuum level. For this example, the values are for the S3.
5 Hg 55 ACFM
19 Hg 44 ACFM
22 Hg 43 ACFM
25 Hg 35.9 ACFM 43 + 38 + 31
28 Hg 31 ACFM 3 = 37.33 or 37 Avg. ACFM
29 Hg 21 ACFM
t = 9.22 * LN (3.8/0.98)/37
t = 0.331 min or times 60 s/1 min;
t = 20 s
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
3 of 6
T E C H N I C A L S U P P O R T
Basically the S3 will take 10 seconds too long to accomplish this pulldown. Try the S5 using
the same parameters. All of the values remain the same, except for the average flowrate of
the pump For the S5 from 22 Hg to 28 Hg:
QAVG = 82 ACFM
t = 9.22 * :N (3.8/0/98)/82
t = 0.149 min or times 60 s/1 min;
t=9s
In answer to the question that was posed in the example, the S3 will not be able to satisfy the
requirement, but the S5 does satisfy the requirement.
Another way to work this problem is to determine what flowrate is required given a specific
time period.
Example: The 60 gal receiver from the previous example has been installed. The process
requires that the vacuum pump should pull the combined system from 22.4 Hg
to 28 Hg in approximately 10 seconds to increase the detail on the molded plas-
tic. Will the S3 be able to accomplish this?
From the values that been used in the previous pump down examples:
From what has been shown here, knowing the average volumetric flowrates, is that the SC-
10TR will be the best choice.
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
4 of 6
T E C H N I C A L S U P P O R T
Example:
Convert 20#/Hr of air to volumetric flowrate 25 Hg and 100oF.
V = m (1/60)(379/MW)(P1/P2)(T2/T1)
m = 20#/Hr
P1 = 760 mmHg(A) = 29.92 Hg(A)
P2 = 25 Hg(G) = 125 mmHg(A), or 4.92 Hg(A)
T1 = 460 + 60oF = 520oR
T2 = 460 + 100oF = 560oR
V = 20 (1/60)(379/29)(760/125)(560/520), or V = 20 (1/60)(379/29)(29.92/4.92)(560/520)
V = 29 ACFM @ 25 Hg and 100oF (Volumetric flowrates should be described at a specific
pressure and temperature
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
5 of 6
T E C H N I C A L S U P P O R T
M = V (60/1)(MW/379)(P2/P1)(T1/T2),
using the same symbols as above. Equ. 1.7
Example:
m = V (60/1)(MW/379)(P2/P1)(T1/T2)
V = 300 ACFM
P1 = 760 mm Hg = 29.92 Hg
P2 = 28.5 Hg = 36 mmHg, or 1.42 Hg(A)
T1 = 460 + 60oF = 520oR
T2 = 460 + 100oF = 520oF, note that since T1 = T2, the division is 1, and it may be neglected
Note that all calculations involving pressure and temperature should be performed at absolute
conditions.
Ohio Medical Corporation - 1111 Lakeside Drive, Gurnee, IL 60031-4099 - Phone: 800-448-0770 - Fax: 847-855-6300
6 of 6
Affects of Altitude on Vacuum
Systems
Series of Technical White Papers from Ohio Medical Corporation
This paper supplements the Squire-Cogswell white paper titled: ACFM vs.
SCFM vs. ICFM published in 2004 and explains the differences in compressor
performance with respect to the varying atmospheric conditions. The paper
also addresses appropriate CFM terminology that should be use in
comparing compressors (SCFM) and sizing them properly (ACFM) for the off
Standard conditions for the altitude and conditions for the area.
Due to the atmospheric variation in air pressure, temperature and density the
fluid properties are constantly changing (i.e. - conditions are dependent on
location, time of the year, altitude, etc.) Thus, it is important to understand
that the conditions in Los Angeles vary significantly from the conditions in
Denver, and a vacuum pumps performance (capacity and operation) will vary
significantly. The intent of this paper is to provide a better understanding of
how vacuum pumps capacity varies with respect to altitude, so we can
properly select and size vacuum pumps for their specified and intended
applications.
The term cubic feet per minute (CFM) describes the fluid flow rate, (measured in volume
- ft3) not the weight per minute on the inlet side of a compressor. The vacuum pumps
performance capability is measured in how many one ft3 cubes of fluid are able to move
per minute through the system.
1 ft
1 ft
1 ft
1 ft 1 ft
1 ft 1 ft
Figure 2 Constant Volume
Condition
Now consider a constant weight (mass) condition. A balloon filled with 31 actual cubic
feet of air in Los Angeles is then taken up to Denver. The balloon now contains 38
standard cubic feet of air.
A variation in air pressure results in a variation in air density, as show in Figure 4, and is
consistent with constant volume concept in Figure 2. Another way to look at this is to
analyze the number of air molecules in a 120-gallon receiver tank at atmospheric pressure
at Los Angels and at Denver, where the former (higher pressure) tank occupies a greater
number of molecules. The weight and density vary primarily because the atmospheric
pressure is significantly different between the two cities, as show in Table 1. Note the
terms for actual and standard for the volumes described above leads us to SCFM
and ACFM.
To simplify the understanding of the affect of vacuum pumps with respect to variation in
altitude, the following illustration simplifies and points out the concept to understand
prior to proceeding with a more theoretical view point on the matter. For this paper, we
will assume only the attitude is varying, while keeping other conditions constant (like
temperature, humidity, etc,).
As a general Rule of Thumb, for every 1000 feet above sea level, the maximum
possible vacuum is reduced by approximately one in-Hg (0.491 psi). By using this rule
one can quickly determine the maximum possible vacuum for the area. Note the
accuracy of this Rule, as there is only a 0.16% difference between the approximated
and the actual pressure (shown in Table 2).
24.00 psi
= 0.802
29.92 psi
Then, the 80.2% rating can be assigned to the vacuum pump to determine its capability in
Denver.
The 80.2% rating applied to the maximum possible vacuum (24.68 in-Hg) results in a
maximum vacuum of 19.79 in-Hg for this pump in Denver. This is a very important
point to understand and consider for vacuum performance and sizing for your location. If
the user needs a vacuum that can achieve 22 in-Hg in Denver, a pump with at least a 89%
vacuum capability is needed, or a pump that will achieve at least 26.7 in-Hg capability in
Los Angeles.
In a closed system vacuum pumps use kinetic energy to move air through a closed
system. At low vacuum levels large volumes of air can be evacuated through the system,
but at higher vacuum levels, the capacity decreases, due to increased leakage from a
larger pressure differential with the environment and there is additional resistance to
flow. This phenomena is illustrated in Figure 5.
% CAPABILITY
0 5 10 15 20 25
VACUUM (in-Hg)
Finally, a specifier can use the Rule of Thumb for sizing a vacuum system properly. In
addition, the reference pressure, temperature, and required vacuum must be specified, in
addition to the required capacity and capability. When specifying the vacuum
requirement, the worst case conditions should be used (i.e. - generally hot days lower
air density). Other important factors to consider in vacuum system sizing are:
Vacuum requirement or demand in a given day
Normal operating conditions
Other operating conditions (hot days are the worst)
Single-stage or two-stage vacuum
Electrical characteristics and power requirement
Area classification (Elevation)
NOMENCLATURE
P1 Barometric pressure at the non-standard site in psia
T1 Ambient air temperature in R
PF Pressure after the inlet filter in psia
TF Air temperature after the inlet filter in R
Psat Saturation Pressure
Relative Humidity at the non-standard site
Tstd Standard temperature in degrees in R (60F = 60 + 460 = 520 R)
Pstd Standard air pressure in psia (14.696 psia)
The primary reason for all the difficulties described above is because air is a
compressible fluid, due to the atmospheric variation in air pressure,
temperature and density - the fluid properties are constantly changing. The
conditions are dependent on location, time of the year, altitude, etc. Thus, it is
important to understand that the conditions in Los Angeles vary significantly
from the conditions in Denver. The terms SCFM, ACFM and ICFM are often
used to define the different instances and conditions of a compressors
capacity and operation. If the CFM terms are used appropriately, they can be
useful in the direct and relative comparison to their operating conditions, and
to other source systems. The intent of this paper is to provide a better
understanding of SCFM, ACFM and ICFM and their meaning, so we can
properly select and size compressors for their specified and intended
applications.
The term cubic feet per minute (CFM) describes the fluid flow rate, (measured in volume
- ft3) not the weight per minute on the inlet side of a compressor. The compressors
performance capability is measured in how many one ft3 cubes of fluid are able to move
per minute through the inlet.
1 ft
1 ft
1 ft
1 ft 1 ft
1 ft 1 ft
Figure 2 Constant Volume
Condition
Now consider a constant weight (mass) condition. A balloon filled with 31 actual cubic
feet of air in Los Angeles is then taken up to Denver. The balloon now contains 38
standard cubic feet of air.
A variation in air pressure results in a variation in air density, as show in Figure 4, and is
consistent with constant volume concept in Figure 2. Another way to look at this is to
analyze the number of air molecules in a 120-gallon receiver tank at 80 psia and 100 psia,
where the higher pressure tank occupies a greater number of molecules. The weight and
density vary primarily because the atmospheric pressure is significantly different between
the two cities, as show in Table 1. Note the terms for actual and standard for the
volumes described above leads us to SCFM and ACFM.
The term standard cubic feet per minute (SCFM) is usually used as a standard reference
condition for flow rate performance for atmospheric pressure at sea level, as opposed to
actual cubic feet per minute (ACFM) is typically used to rate flow rate performance of
compressor systems for actual pressure and temperature. SCFM is defined as air at
14.696 psia and 520R (60 F). Sometimes other conditions are used, such as 530R
(70F), 528R (68F), 0% and 36% Relative Humidity for describing the standard
conditions. It is important to remember SCFM is defined by a fixed set of conditions or
common reference point for comparing different compressors systems. Otherwise the
consequences are the improper sizing of the compressor system for its true application.
This point will be apparent in the two examples to follow.
Pstd T
ACFM = SCFM 1 Equation 1
( )
P1 Psat1 1 Tstd
For this example we will reference a 30-hp compressor operating at 1020 rpm, and use it
in Los Angeles and Denver to demonstrate how SCFM and ACFM should be used.
Assume the requirement for compressed air is 125 psig discharge pressure, and 100
SCFM of demand, and the site ambient conditions are T1 = 80 F (540 R), P1 = 14.7 psia
and = 75%, and this results in the following:
ACFM = 106.6
If we assume that all ambient conditions remain the same with the exception of moving
the compressor to Denver, where the atmospheric pressure will drop to P1 = 12.12 psia,
the resulting volumetric flow requirement becomes:
ACFM = 130.0
In order to deliver the same amount of work (100 SCFM at 125 psig), the compressor in
Denver must ingest larger quantities of the lower-density air, due to the change in the
atmospheric pressure.
To provide the required 100 SCFM of work in Denver, the compressor must be able to
process 130 ACFM.
For this example we will reference the first example for Los Angeles and Denver and
change the conditions to a hot humid day. Assume the same requirements and conditions
except for the ambient temperature of T1 = 100 F (560 R) and relative humidity of =
100%, which results in the following:
The results at the higher temperature and higher humidity condition show an even greater
amount of air is needed (approximately 10% more air is needed compared to Example 1)
to meet capacity requirements. Thus, we recommend using hot humid days to calculate
the worst case conditions for sizing a system. Tables can be constructed to size systems
from Equation 1, but it is up to the specifier to determine the proper conditions. Table 4
in Appendix A shows the expansion ratio conversions for SCFM and ACFM for the
conditions described in this example.
ICFM
The term Inlet Cubic Feet per Minute (ICFM) is used by compressor vendors to establish
the conditions at the inlet of compressor in front of the inlet filter, blower, or booster.
If the pressure and temperature condition at the inlet is the same as after the filter, blower,
or booster, then the ICFM and ACFM values will be the same. However, as the air
passes through these components, there will be always be a pressure drop or rise, and
Equation 2 is used to approximate ACFM.
P1 TF
ACFM = ICFM Equation 2
PF T1
Then ICFM is used to measure inlet capacity, which will approximate ACFM for this
type of a system. Note, when a blower or booster is added, the inlet may experience
significantly higher pressure and temperature conditions than the actual ambient
conditions. Greater the difference in pressure and temperature, greater the difference in
ACFM and ICFM. Finally, there are losses (air seal, heat, etc.) associated with the use of
these components and coupled with the pressure and temperature differences, the use of
ICFM will result in a misleading outcome in determining a compressors capability.
Note at higher altitudes, the specifier must account for the decrease in air pressure when
estimating a compressors performance and sometimes blowers or boosters are used for
economic reasons, but this is not always the best solution. Thus, in certain markets, like
the Medical, where tighter controls are employed, ICFM should not be used to determine
a compressors capacity, instead ACFM should be used.
Finally, the reference pressure, temperature, and discharge pressure must be specified, in
addition to the required capacity. When specifying the compressed air requirement, the
worst case conditions should be used (i.e. - generally hot humid days, as shown in
Example 2). Otherwise, there will be confusion in the sizing process. Other important
factors to consider in compressor capacity and system sizing are:
Air requirement or demand in a given day
Normal operating conditions
Other operating conditions (hot humid days are the worst)
Single-stage or two-stage compressor (compression ratio)
CFM reduction due to flow resistance
Electrical characteristics and power requirement
Area classification (Elevation)
Compressors with a higher CFM rating will pump more air than
compressors with lower CFM
1
TERMINOLOGY
ACFM Actual Cubic Feet per Minute
CFM Cubic Feet per Minute
GPM Gallons per Minute
NOMENCLATURE
Constants:
g Acceleration Due to Gravity (32.2 ft./sec2)
- Specific Weight (lb/ft3)
- Density of Fluid (slugs/ft3)
- Dynamic Viscosity (lb*s/ft2)
- Equivalent Roughness (.0005 ft. for Galvanized Pipe)
KL Loss Coefficient for Fittings (Found in Industrial Literature or College Text)
Variables:
zn Height at Position n (ft.)
V - Velocity of Fluid (ft/sec.)
D - Diameter of Pipe (in. or ft.)
A Cross Sectional Area of Pipe (in.2)
L Pipe Length (ft.)
hL Head Loss (ft.)
pn Pressure at Node n
f Friction Factor
2
INTRODUCTION
Ever since the development of piping systems throughout civilization there has been the
need to analyze pipe size for optimal flow. In 1738 Daniel Bernoulli had developed an
equation to represent all variables within a piping system, as shown below:
2 2
p1V p V
+ 1 + z1 = 2 + 2 + z 2 + hL (1)
2g 2g
From Bernoullis equation, we can see how pressure, velocity and position relate to one
another, and many derivations can be created from this equation. Depending on the
assumptions made and under certain conditions, some of the variables become negligible
and can be removed to simplify the equation, and result in a simpler solution. The nature
of this paper is to solve for the pressure drop (or commonly referred to the back pressure)
which is essentially the pressure difference between two points in a piping system. The
pressure drop is critical when sizing pipe. A pump that is integrated within a piping
system is designed such that it will withstand certain forces at the inlet and exhaust. If
the pump is subjected to forces greater than the ones prescribed, there is a high potential
for damage to the internal pump components, and thus the designed flow will be affected.
This paper will focus on the flow of air, although it can be shown that other fluids can
also be modeled using the same methodology. Like other media that flows within a
piping system, air has its own characteristics which benefit and hinder the process.
There are numerous ways in which to solve for the pressure drop of piping system. That
is to say, one can incorporate the use of a computer with a plethora of software available.
However, the underlying equations used in these programs follow the same fundamental
laws of physics found in any collegiate Fluid Mechanics textbook. In addition, sound
engineering judgment should be used when sizing pipe. While a cost-effective solution
may look good on the bottom line, a safe and reliable system should have precedence in
any design.
Assumptions:
1. Air Flow will be turbulent.
2. The temperature for the ambient air will be 70oF
3. Air flow will be defined using ACFM.
3
BACKGROUND:
Laminar Flow
Figure 1
Turbulent Flow
Figure 2
To see if the flow of air will be turbulent or laminar, we solve for a parameter referred to
as the Reynolds number. The Reynolds number is a dimensionless number which is
obtained from the following equation:
V D (2)
Re =
4
To determine if the flow rate is laminar or turbulent, the Reynolds number should be
calculated. The combination of the Reynolds number, equivalent roughness and pipe
diameter we can determine the friction factor from the Moody chart. (Moody charts can
be found in industrial literature and in college text books.) The friction factor is used in
the equations below.
OTHER EQUATIONS:
Some of the other equations used to determine the pressure drop are in this section. We
can solve for the velocity of the flow by dividing the ACFM by the cross sectional area:
A = r2 (4)
Once the velocity is found, we can then check to see if the flow is turbulent, or laminar,
by utilizing the Reynolds equation (as mentioned previously).
The pressure drop in a piping system can be broken down into two (2) equation forms:
And the constant KL is found in tables of either college text, or industrial references.
Combining Equations (6) and (7) we can solve the pressure differential directly:
V2
p1 p 2 = K L (8)
2g
5
Once the pressure drop has been calculated for the pipe length and all of the
fittings/valves, the total pressure drop can be found by the summation of all components.
In Equation form:
The reader might be wondering that since air is a gas, shouldnt the flow be characterized
as compressible? The answer to this question is dependent on many conditions.
Depending on the length of the pipe and the complexity of the arrangement of fittings and
valves, the pressure drop may, or may not, be small relative to the initial pressure. If the
pressure drop is small enough, then you can assume the fluid is incompressible.
Otherwise, the flow is Compressible, and complicates the analysis. An example to find
the pressure ratio is as follows:
We have a pipe length of 7-0 and the pressure drop should be no greater than 1.0 psi
per 7-0. The pressure at the beginning is 14.7 psi.
( p1 p2 ) (10)
p1
1 psi
(7 ft )
7 ft = .068 = 6.8%
14.7 psi
This ratio is small enough to assume an incompressible flow. Sound judgment and
experience should be used when applying this equation. In different industries, different
values are used to make the difference.
6
EXAMPLE:
Given: A Squire-Cogswell S750TR-T2 system needs to have an exhaust line sized
properly. The customer needs to pipe the system to the outside the building. The
customer knows that there will be 100 ft. of pipe, three 90o elbows, and two 45o elbows.
All Piping will be galvanized ( = 0.0005 ft.). Air temperature is 60oF and atmospheric
pressure is 14.7 psi.
Known: The given flow rate is 163.8 ACFM per pump. The exhaust for the pump is 1-
1/2. (It is always advisable to check with the manufacturer of the pump for a back
pressure allowance. Depending on the manufacturer of the pump, the allowable back
pressure may vary.) The back pressure should not be greater than 1 psi.
Solution:
Find the velocity of the fluid from the flow rate using equation (3):
ft 3 1min ft 3
V = 163.8 = 2.73
min 60 sec sec
ft 3 1
V = 2.73
sec Cross Sectional Area of Pipe
Therefore:
ft 3 1 ft
V = 2.73 2
= 222.6
sec (0.0625 ft ) 3.14 sec
The next variable we look for is the Reynolds Number using equation (2):
slugs ft.
0.00238 3 222.6 (0.125 ft.)
ft s
Re =
VD
Re = = 176,471
7 lb s
3.74 10
ft 2
7
Once the Reynolds number is found then the flow can be determined as either turbulent
or laminar. In this example, the flow is turbulent. The frictional factor can be found
from knowing the Reynolds number, relative roughness and diameter of the pipe.
2
100 ft. 1 slugs ft
p1 p 2 = 0.029 0.00238 222.6
3
0.125 ft. 2 ft sec
lb
p1 p 2 = 1368
ft.2
lb 1 ft 2
p1 p 2 = 1368
ft.2 144in 2
p = 9.49 psi
Second we solve for the minor losses (i.e. through fittings and valves) using equation (8):
V2
p1 p 2 = K L
2g
ft
2
ft
2
222.6 222.6
lb s
p1 p 2 = 0.0765 3 3 1.5
s
ft ft + 2 .4 ft
2 32.2 2 2 32.2 2
s s
lb
p = 359
ft 2
lb 1 ft 2
p = 359 2
ft 144in 2
p = 2.50 psi
8
pTotal = 9.49 psi + 2.50 psi
As we can see from this solution, the pressure drop is much higher than what should be
observed in the pumps. Therefore, other iterations of the example are shown in Table 1:
Major Losses
Pipe Minor Losses Total
Pressure
Iteration Size Pressure Drop Pressure
Drop in Pipe
(in.) in Fittings (psi) Drop (psi)
(psi)
1 1 1/2 9.49 2.20 11.99
Table 1
EXPERIMENT:
The above theory was tested in our lab to see if the data correlated with the solutions.
The experiment was set up as seen in the following pictures:
9
Pressure Measuring Device:
Merical DP2000I (Accuracy 0.05%R)
Pump:
45 lpm Volumetric Free Flow, 12 VDC, 4.0 Amp
Pipe Size:
1/8 (.269ID)
Fittings:
1/8 Tees (Qty. 2)
1/8 Pipe Nipples (as appropriate)
1/8 Pipe Couplings (as appropriate)
Temperature - 70oF
Pressure 14.7 PSIA
Flow Rate:
The pressure drop was measured at different pipe lengths. Refer to the data below.
Major
P P
Losses
Length Minor Losses Calculated (psi) Calculated Measured
Calculated
(psi) (psi)
(psi)
Tee Branch Flow: 0.05(2) = 0.10
6 0.04 0.18 0.19
Elbow: 0.04(1) = 0.04
Tee Branch Flow: 0.05(2) = 0.10
12 0.09 Elbow: 0.04(1) = 0.04 0.23 0.23
1 Coupling: 0.002(1) = 0.002
Tee Branch Flow: 0.05(2) = 0.10
24 0.17 Elbow: 0.04(1) = 0.04 0.32 0.30
3 Couplings: 0.002(3) = 0.006
Tee Branch Flow: 0.05(2) = 0.10
36 0.26 Elbow: 0.04(1) = 0.04 0.41 0.37
5 Couplings: 0.002(5) = 0.010
Tee Branch Flow: 0.05(2) = 0.10
48 0.35 Elbow: 0.04(1) = 0.04 0.49 0.42
7 Couplings: 0.002(7) = 0.014
Table 2
10
Pressure Drop Experiment
0.9
0.8
0.7
Pressure Drop (psi)
0.6
Calculated
0.5
Measured
0.4
0.3
0.2
0.1
0
6 12 24 36 48
Pipe Length (Inches)
Figure 3
As we can see from the data above, the calculated and measured data points correlate
with each other. The average difference is 0.03 psi between the calculated and measured
data points. The non-linear behavior of the measured values is attributed to the random
behavior of air. From Figure 3, one can see that the pressure data separates from the 12
point. The separation of data points can be attributed to leaks or irregularities in the pipe
(i.e. burrs, surface irregularities from galvanizing etc.) The leaks in the piping system
will decrease the flow rate, this in turn decreases the pressure. It is also interesting to
note that as the pipe length increases, so does the pressure. This is both demonstrated in
the measured and calculated values.
11
CONCLUSION:
The pressure drop in the piping system directly affects the performance of the pump.
Essentially the pressure drop produces additional forces that directly and indirectly affect
the internal parts. It should be noted that having an excess size diameter of pipe can be
detrimental as well (i.e. oversized). If the area is increased, the excess (stagnant) air will
act as an obstruction to the flow and therefore create a greater turbulence. Another
detrimental effect, besides damage to the internal components of the pump, is the
reduction of air capacity the pump removes. The back pressure acts as an obstruction to
the flow, therefore hindering capacity.
The example could be solved in different ways. In fact we could have different pipe sizes
in this line. That is to say, we could have calculated for a run 50-0 of 1 Dia. and
50-0 of 3 Dia. The calculation above is good for approximating the pipe size for the
entire length of the pipe, and it is also good for solving for smaller sections of pipe. In
addition, this paper makes lot of assumptions regarding the condition of the air flow and
the ambient conditions. It can be argued that a more detailed analysis would be
appropriate, and in other cases a more general solving approach would be appropriate.
As shown in the example, there are many steps that need to be followed to give us an
optimized pipe size. There are many opportunities to overlook error by using these
equations. Therefore, it is recommended to use sound industry judgment when solving
for the pressure drop and interpreting the results.
12
1111 Lakeside Drive Gurnee, IL 60031-4099 847-855-0500 www.ohiomedical.com
1. Ohio Medical Corporation warrants to the original purchaser its Medical Vacuum and Compressed Air
Systems to be free from functional defects in material and workmanship for a period of twenty four (24)
months from the date of shipment, or for a period of twelve (12) months from the date of start-up, whichever
comes first.
a. Start-up shall only be done by an authorized representative of Ohio Medical Corporation.
2. In the event there is a functional defect either in material or workmanship Ohio Medical Corporation will only
repair or replace any part or component which is proven to be defective.
a. System Components sold as individual items are not warranted to include job site installation and wiring,
and the warranty set forth in Paragraph 1 is limited to complete units which include all factory installed
components and interconnected piping and wiring.
b. Labor on site is limited to functional defects in workmanship found to be defective at the time of start-up.
c. The replacement of normal wearing or maintenance items (including but not limited to packings,
mechanical seals, oil seals, piston rings, contacts, coils, fuses, etc.) made in connection with normal
maintenance services are not covered by this warranty.
3. To obtain service within the warranty period, first contact your authorized Ohio Medical Corporation dealer or
the Ohio Medical Corporation Service Department. Ohio Medical Corporation responsibility under this
warranty shall be limited to providing at Ohio Medical Corporation sole discretion new or similar rebuilt
replacement parts to replace any component found to be defective within the warranty period.
a. Labor to repair any part or component proved to be defective within the warranty period will be provided
at no charge for any item returned to our factory adequately packaged and insured with shipping costs
prepaid. Standard surface freight shipping cost and return of the repaired part or component will be paid
by Ohio Medical Corporation.
b. Before returning any part or component to the factory, proper return authorization must first be obtained
from Ohio Medical Corporation Service Department.
4. The warranty is valid only when the product has been property installed according to Ohio Medical
Corporation specifications, used in a normal manner and serviced according to factory recommendations. It
does not cover failure due to damage which occurs in shipment or failures which result from accidents,
misuse, abuse, neglect, mishandling, alteration, misapplication or damage that may be attributable to acts of
God. Similarly, this warranty does not apply to units that are re-sold or rented to others by the purchaser.
5. Ohio Medical Corpioration shall not be liable for incidental or consequential damages resulting from the use of
this product. There are no expressed or implied warranties which extend beyond the warranty of fitness for a
particular purpose to the equipment and/or to its parts and components.
6. THE CONDITIONS OF THE BUYERS RESPONSIBILITY ARE:
a. The equipment is stored properly before installation.
b. The equipment is installed according to Ohio Medical Corporation specifications and installation
procedures.
c. The room where the equipment is installed meets stated operating temperatures.
d. The equipment is placed into initial operation by an authorized representative of Ohio Medical
Corporation.
e. The equipment is properly maintained and is not repaired or altered unless by an authorized
representative of Ohio Medical Corporation.
Producers of Ohmeda Suction and Oxygen Therapy Devices, Aeros Instruments Portable Suction Machines and
Squire-Cogswell Medical Gas Pipeline Equipment, Medical and Industrial Vacuum Systems and Air Compressor Packages
1111 Lakeside Drive Gurnee, IL 60031-4099 847-855-0500 www.ohiomedical.com
1. OHIO MEDICAL CORPORATION warrants the Medical Gas Pipeline Equipment to be free from functional defects
in material and workmanship for a period of twenty-four (24) months from the date of shipment or twelve (12) months
from the date of start-up, whichever occurs first. Within said period Ohio Medical Corporation will repair or replace
any part or component which is proven to be defective in either material or workmanship.
2. To obtain service within the warranty period, first contact the Ohio Medical Service Department.
3. Ohio Medical Corporation's responsibility under this warranty shall be limited to providing at Ohio Medical
Corporation's sole discretion, new or replacement parts to replace any component found to be defective within the
warranty period. Installation of user replaceable items will be the user's responsibility.
4. Labor to repair any part or component proved to be defective within the warranty period will be provided at no charge
for any item returned to our factory adequately packaged and insured with shipping costs prepaid. Standard surface
freight shipping cost to return the repaired part or component to the user will be paid by Ohio Medical Corporation.
a. Before returning any part or component to the factory, proper return authorization must first be obtained
from Ohio Medical Service Department.
b. The user will be required to issue a purchase order for replacement items. Upon receipt of the defective
items, Ohio Medical Corporation will issue a credit to the user in the amount equal to the purchase order.
5. This warranty is valid only when the product has been properly installed according to Ohio Medical Corporation
specifications, used in a normal manner and serviced according to factory recommendations. The warranty does not
cover failures due to damage which occurs in shipment or failures which result from accidents, misuse, abuse,
neglect, mishandling, alteration, misapplication or damage that may be attributable to acts of God.
6. Ohio Medical Corporation shall not be liable for incidental or consequential damages resulting from the use of this
product. There are no expressed or implied warranties which extend beyond the warranties set forth above. Ohio
Medical Corporation makes no warranty of merchantability or fitness for a particular purpose to equipment and to its
parts and components.
Producers of Ohmeda Suction and Oxygen Therapy Devices, Aeros Instruments Portable Suction Machines and
Squire-Cogswell Medical Gas Pipeline Equipment, Medical and Industrial Vacuum Systems and Air Compressor Packages