Introduction
DUMW-48/50H outdoor power system is compact and intelligent
power system containing max.4 rectifier modules, controller module,
LVD,BLVD, AC and DC distributions. Special protection measures
ensure it could be applied in outdoor environment.
Features
System total capacity up to 12KW output for DUMW-48/50H.
Suitable for outdoor application with various protection measures.
Wide AC input range 90V to 300V.
PFC technique features the system high efficiency, energy-saving and up to
0.99 power factor.
Intelligent fan-cooling technique brings good cooling performance, low failure
rate and high reliability.
Fast on-line expansion of rectifier modules enabled by hot-swap.
N+1 rectifier module redundancy.
Automatic management of battery charging and temperature
compensation function.
Beijing Dynamic Power Co., Ltd. 1
Dust-proof design : Bilayer filter, double shielding, easy to maintain and
replace. Filter EU3.
Audible alarm : Auto alarm when the theft open the door, the sound is up to
100dB. Automatic off after 2 minutes.
Battery compartment anti-theft : Double room design for Anti-theft
Door lock anti-theft : Increase door lock protective box to realize double anti-
theft.
Lamp : Install LED light on the top of the cabinet.
Temperature measurement : Install thermometer on the door, easy for
maintenance staff to check the temperature.
Charge battery control : Automatically detect the battery charging
status.Default factory settings is 10% of the battery.
Smart fan control : Speed control built in: 28 C stop working, 32 C speed
1200 RPM, 35 C speed 2600 RPM.

Beijing Dynamic Power Co., Ltd. 2


Specifications

1) AC Input

AC supply: Nominal:186-285Vac, 1phase


Tolerance:90-300 VAC, 1phase
1 phase three wires input
Frequency: 45-65Hz
Power Factor: 0.99
Voltage wave distortion: <5%
Current Distortion: 5% @50~100% load
Protection: Soft start
Surge protection (SPD: Class B + C)
Internal fuses (L & N)
Over voltage protection

Beijing Dynamic Power Co., Ltd. 3


2) AC Distribution Options

AC input1*100A/2P MCB ,1*SPD (CLASS B+C)


AC output: 1*AC 10A/220V socket ,1*10A/1p MCB

3) DC Output

Voltage: -48VDC (-42--58VDC adjustable)


Current: 200A ultimate capacity (48/50H)
Voltage regulation: 1%
Current sharing: 5%
Ripple and Noise: 200mV p-p
Psophometric noise: 2mVrms
Protection: Over/under voltage shutdown
Short circuit proof
High temperature protection

Beijing Dynamic Power Co., Ltd. 4


4) DC Distribution Options

No. of Load MCB: MCB:7*16/1P; 9*32A/1P


Custom options available
No. of Battery MCB: MCB:2*100A
LVD: LLVD:4*16A/1P MCB, 9*32A/1P MCB
BLVD:3*16A/1P MCB,

5) Rectifier

Type: DZY-48/50H
Efficiency: Typical:94%; (DZY-48/50H)

Beijing Dynamic Power Co., Ltd. 5


6) Monitoring and Control
Monitoring unit: DKD48
Local operation: Menu driven software via keypads
and LCD or PC (Power Suite)
Remote operation: RS232
Visual indications: LCD system status
Green LED System ON
Yellow LED Minor alarm(s)
Red LED Major alarm(s)
Alarm relays: 8 relays
Digital inputs: 4 to 8 options (for monitoring of external equipment),
Custom options available
Current measurements: Battery current
Rectifier current
Alarms: AC failure alarm, Rectifier failure alarm
Load fuse alarm, Battery fuse alarm
LVD operated, Low output voltage alarms
High output voltage alarms, Symmetry alarm
Fan fail, Door
Beijing Dynamic Power Co., Ltd. 6
7) Other Specifications

Cooling: Air cooling


Protection level: IP55
Operating temp: -40 to +75C (-40 to +167F)
Temp range (when full load): -40 to +50C
Storage temp: -40 to +85C (-40 to +185F)
Humidity: Operating: 95% non-condensing
Storage: 99% non-condensing
Dimensions: 800W*800D*2000H(mm)
Weight: 90kg excl. rectifiers

Beijing Dynamic Power Co., Ltd. 7


Different Views of Outdoor Cabinet

Front view (door closed) Right view Left view Right view (30)

Beijing Dynamic Power Co., Ltd. 8


2.0M Air-cooling Outdoor Cabinet Introduction

- Cabinet aluminum type material


- Steel with hot dip galvanize
- 2.0MM thickness
- Epoxy power coating 150 micron (outside only)
- Protection IP 55
- 4 fan cooled ventilate
- 2 filter (W400*H400*D50MM with stainless mesh)
- Outside temperature is 5 degrees lower than inside
temperature
- Cabinet dimension W800*D650*H2000mm, including
the base. (Base Dimension: W800*D650*H150mm)
- 3 point locking and padlock with lock box (stainless
steel)
- Weight: 100KG excl. rectifiers

Beijing Dynamic Power Co., Ltd. 9


Outside Function of Cabinet

Hot air-out nose


Dimension: W550*H400*D160MM
Have stainless steel fly net

Cold air-in nose


Anti-theft padlock box, Dimension: W400*H400*D160MM
2 padlocks at most Have stainless steel fly net

Hot air-out of battery compartment,


thermal control, automatically cooling

Cold air-in of battery compartment


Dimension: W500*H100MM

Beijing Dynamic Power Co., Ltd. 10


Cabinet Structure

Subdivision design of the cabinet, independent cooling,


battery compartment is isolated from the equipment
compartment.
Advantages: prevent the heat from the equipment
compartment entering into the battery compartment to
increase the service life of the battery.

Beijing Dynamic Power Co., Ltd. 11


Cooling Fan of the Cabinet
- Four fans are installed in total, fans are tilted 45 degrees
in accordance with the air-out channel to realize smooth
ventilation.
- Our DKD48 controller has the alarm function of fan failure.
- The fan start-up temperature is set at 28 before delivery.
The fan speed is 1200 RPM when the temperature reached
32, and 2600 RPM when the temperature reached 35.

Beijing Dynamic Power Co., Ltd. 12


Large area design of air inlet and outlet to improve the cooling effect

Nose design of hot air outlet, air-out in


front and from below, increase the area
of air-out and improve the cooling effect.
Equipped with stainless steel mesh, can
be disassembled to clean, easy to
maintain.

Nose design of cold air inlet, air-in


from below and in front, increase the
area of air-in and improve the cooling
effect. Equipped with stainless steel
mesh, can be disassembled to clean,
easy to maintain.
Beijing Dynamic Power Co., Ltd. 13
Design of Cold Air Inlet

1 dust-proof mesh 2 dust-proof mesh


EU3 EU3

- Modular design, easy to maintain.


- Two layers of dust-proof cotton, increase the level of protection.
- High compatibility design, fans are optional.

1
2

Beijing Dynamic Power Co., Ltd. 14


Design of Hot Air Outlet

Fans are tilted 45 degrees in accordance with


the air-out channel to realize smooth air-out
and increase the efficiency of air-out.

Beijing Dynamic Power Co., Ltd. 15


Cooling Design of Battery Compartment

Install 2 fans in battery comprtment for


cooling, increase the effeciency of cooling.

Install fly net and dust-proof cotton in battery


comprtment, increase the area of air-in and improve
the service life of battery.

Beijing Dynamic Power Co., Ltd. 16


Lock Anti-theft Design

- Install anti-theft lock box outside the


cabinet to protect the padlock.
- Quadruple anti-theft: lock box, 2 padlocks
and 3 point lock on the door.
- High anti-theft level with high security.

Beijing Dynamic Power Co., Ltd. 17


Design of Cabling Rack

Install professional cabling rack inside the cabinet to


make the cabling in order and good looking.

Beijing Dynamic Power Co., Ltd. 18


Design of Cabling Hole

Increase the size and the number of the cabling holes,


the cabling holes are installed on both sides at the
back of the rack, easy to install the cable.

Beijing Dynamic Power Co., Ltd. 19


Design of Battery Anti-theft

- Install the battery compartment protection


door, and the padlock can be installed on each
door of the battery compartment.
- The height of each battery compartment is
increased by 2.5CM.

Beijing Dynamic Power Co., Ltd. 20


Design of Battery Protective Pad

Install protective pad on each battery to avoid


battery wear.

Beijing Dynamic Power Co., Ltd. 21


Design of Telecom Equipment Rack

Subrack is installed in 10cm to 15cm from the top of the cabinet, and
telecom equipment rack is installed in 10cm to 15cm (non opening),
prevent the cooling channel being blocked by the equipment.

10-15cm

Beijing Dynamic Power Co., Ltd. 22


Design of Lighting

Install LED light on the top of the cabinet, the light needs to
be manually switched on after the door is opened, when the
work is finished, it needs to be switched off manually.

Beijing Dynamic Power Co., Ltd. 23


Installation Location of LED Light Switch

LED light switch is installed on the left side inside the cabinet,
it will not affect the cabling and the installation of other
telecom equipment.

Beijing Dynamic Power Co., Ltd. 24


Design of Temperature Display inside the Cabinet

Install thermometer on the door, easy for maintenance


staff to check the temperature.

Beijing Dynamic Power Co., Ltd. 25


Alarm Function

Install the alarm inside the cabinet, it will automatically alarm


when the door is opened, the alarm will last 2 to 3 minutes and
automatically turned off. After the work is finished, you just need
to close the door. The maximum sound is 100dB.

Beijing Dynamic Power Co., Ltd. 26


Design of Cabling Rack

Install professional cabling rack inside the


cabinet to make the cabling in order and good
looking.

Add two cabling holes on the front of the


cabinet.

Beijing Dynamic Power Co., Ltd. 27


Thermal Isulation Design

Epoxy power coating 90 -120 micron (outside only), light


color (greyish white dedicated in telecom area) is adopted to
avoid absorbing the heat from sunlight.

Beijing Dynamic Power Co., Ltd. 28


Effect Sketch of Cabinet Cooling

hot air outlet


(the area of air-out is greatly increased)

cold air inlet


(the area of air-in is greatly increased)

The temperature outside the cabinet is 5 degrees


lower than the temperature inside the cabinet.

Beijing Dynamic Power Co., Ltd. 29


Optimization of DC Distribution
Add LLVD function to the rack power supply to fairly distribute the critical load and the s
econdary load and intelligently manage and protect the battery.

BLVD Battery
AC AC LLVD
3*16A/1 2*100A/1P
INPUT OUTPUT 4*16A/1P,9*32A/1P
P MCB

LLVD:46V
BLVD:43.2V
Beijing Dynamic Power Co., Ltd. 30
Battery Charging Management

Charging current of our DKD48 controller is


adjustable, normally between 10% and 20% of
the battery, its factory settings is 10% of the
battery. It can automatically detect the battery
charging status.

Beijing Dynamic Power Co., Ltd. 30