Transformer Ratings
Transforver Vector Group Dyn
Transformer KVA rating 164000
Primary Voltage of Transformer (Line-Line) @ KVA rating 170000
Secondary Voltage of Transformer (Line-Line) @ KVA rating 15750
Transformer Impedance (Zt) @ KVA rating 12.76
Transformer Primary Full Load Current I (Line-Line) @ KVA rating 556.99
Transformer Secondary Full Load Current I (Line-Line) @ KVA rating 6011.95
Transformer Ratio 10.79
Current Calculation
Transformer Primary Impedance 305.2122
Transformer Primary Impedance Per Phase 38.9451
Primary Side Injected Current Per Phase 10.27
Secondary Side Current Per Phase 110.86
Ohms
Ohms
Amperes
Amperes
Meter
3 Core Cable
Amp
Amp