Вы находитесь на странице: 1из 2

Frascold Selection Software 3 v1.

5 - 07/03/2017

System data (input):


Refrigerant: R507
Reference temperature: dew point temperature
Calculation mode: Refrigeration / Air Cond.
Operating mode: Subcritical
Condensing temperature: 95 F
Liquid subcooling: 0 F
Evaporating temperature: -40 F
Suction gas superheating: 20 F
Evaporator superheating: 10 F
Compressors:
#1 Name: NRL2-50-186Y
n of fixed speed compressors : 2
n of variable speed compressors: 0

Output data: (NRL2-50-186Y (x2))


Refrigerating capacity 363.68 kBtu/hr
Refrigerating capacity[ref] 190.867 kBtu/hr
Evaporator capacity 353.059 kBtu/hr
Power input 81.338 kW
Condenser capacity, theor. 624.686 kBtu/hr
Current 113.68 A
COP 1.31 W/W
Mass flow 5535 lb/hr
Operating frequency 60 Hz
Power supply 460/3/60/PWS -
Selection mode Refrigeration / Air Cond. -
Operating mode 100% of the capacity, with Eco -
Evaporating pressure 20 psi
Suction gas superheating 20 F
Suction gas temperature -20 F
Discharge temperature 171.07 F
Condensing pressure 241 psi
Liquid temperature 26.36 F
Sat. intermediate temp. (bubble) 17.36 F
Intermediate pressure 70 psi
Mass flow, injection 2821 lb/hr
Mass flow, compressor outlet 8356 lb/hr
Capacity, economiser heat exch. 133.76 kBtu/hr
Ratio (%) 100.0% %
Note -

Oil flow 59 l/min


Heat Exchanged (oil Cooler) - kBtu/hr
Oil Temperature at Oil Cooler Outlet - F
Certified by Frascold tentative data -

Legend:
*ref: At conditions according to EN 12900
- Suction gas superheating = 18 F
- Liquid subcooling = 0 F
Certified by:
- Frascold data
Frascold Selection Software 3 v1.5 - 07/03/2017