Академический Документы
Профессиональный Документы
Культура Документы
: 1502-0065
Documentation Heinzmann Controller for StG 10 StG 30 and , StG40Actuators
1. Function:___________________________________________________________2
1.1 Use and general function: 2
1.2 Protection functions: 2
2. Assembly:__________________________________________________________3
2.1 Wiring: 3
2.2 Terminal strip allocation: 4
3. Retrofitting PANDAROS to field systems: _______________________________5
3.1 Retrofitting PANDAROS to dia.ne systems: 5
3.2 Comparison of terminal strips when retrofitting: 5
3.3 Retrofitting PANDAROS to EMS 2000 systems: 5
3.4 Documentation when retrofitting: 6
4. Settings: ___________________________________________________________6
4.1 Current range: 6
4.2 Position settings auto adjust: 6
5. Cumulative failure transmitting output:__________________________________8
5.1 General: 8
5.2 Controller warnings / self-resetting: 8
5.3 Controller emergency shutdowns: 8
6. Troubleshooting: ____________________________________________________9
6.1 Failure message - warning: 9
1. Function:
An equipment redesign by Heinzmann (quarter 3 / 2004) has produced the following new type
designation: PANDAROS PDC 6-40.6-06-S1-A
The parameters for the controller have been factory-preset by the manufacturer to GE Jenbachers
specifications. Different sets of parameters are required to control the STG10, STG30 and STG40
actuators. The STG40 requires a higher parameter setting for the current limiter to achieve its higher
nominal moment.
For logistical reasons there are therefore two different GEJ part numbers with the relevant set of
parameters depending on the actuator type.
Pandaros TL 369160 for actuator STG10 with TL 118918 and STG 30 with TL 281814.
Pandaros TL 438222 for actuator STG40 with TL 305256.
Short-circuit protection:
If a short circuit occurs in the power output side of the actuator circuit, the amplifiers output transformer is
switched off automatically.
The controller is pole-error protected and short-circuit protected at all the digital and analogue inputs and
outputs of the control electronics against the positive and negative of the power supply.
Current limiter:
A peak current of 6.4 A for a maximum of 5 seconds and a constant current of 3.2 A are permitted in
order to protect the StG10 and StG30 actuators from thermal overload. The permissible peak current for
the StG40 is 9.0 A for a maximum of 5 seconds and the constant current is 4.5 A. The controller
guarantees these limiting conditions by automatically reducing the current to the permissible constant
current within a maximum of 80 ms approx. 5 seconds after the permissible constant current has been
exceeded. The power consumption of the actuator can be checked by measuring the current at the output
side of the actuator circuit.
The current limiter is only activated if the actuator is obstructed or overloaded. This is an
indication of the incorrect setting of a mechanical component (control rod assembly, throttle
valve) or a malfunction or that the nominal moment of the actuator is insufficient for the
application.
2. Assembly:
The controllers control electronics are contained in a metal housing (B x H x D = 165 x 105 x 65mm),
which is suitable for top-hat rail mounting. The connection is established via the terminal strip on the
circuit board.
2.1 Wiring:
Cable sets with prepared connectors (for actuators) are used to make the electrical connection with the
actuators.
TL 234658 StG 10 Type 2 and 3 engines Cable length approx. 9 m.
TL 234666 StG 30, StG 40 Type 6 engines Cable length approx. 11 m.
The connection with the actuators is established by means of two cables, L1 and L2, of equal length.
L1: 2-pole, 1.5 mm, shielded plastic-sheathed cable (engine connection)
L2: 3-pole, 0.75 mm, shielded plastic-sheathed cable (signal connection)
Both cables are led to the connection on the actuator in a common connector (MIL). The cable shields
must be led to the terminal strip on the controllers circuit board. The shield for the signal cable L2 must
be connected to the corresponding terminal strip (14 | GND). The shields for L1 and L2 must be earthed
at the entry to the module interface box.
Alge servo amplifier (TL- No. 319169) and Heinzmanns Pandaros controller (TL- No. 369160 / TL - Nr.
438222) Fa. Heinzmann.
/ output / supply). At the shunt resistor a 0 5V voltage signal is generated from the 0 200mA signal
and adjusted to a 0 - 20 mA setpoint signal by the signal transducer.
The composite part number TL 415434 when retrofitting the EMS 2000 is made up of the necessary
shunt resistor and the signal transducer. The PANDAROS controller is not included in this composite part
number.
4. Settings:
As supplied, the preset 0% and 100% position of the controller is only approximate. All other settings,
such as control circuit amplification and current limitation have already been adjusted to the optimum
value for operating with the STG10, STG30 and STG40. It is essential that the 0% and 100% position is
set accurately before the engine is operated for the first time. The setting is made by means of an auto
adjust function, i.e. when a wire jumper is connected to the Pandaros controller the actuator is adjusted
automatically for the 0% and 100% position.
The auto adjust function must be carried out each time the controller or the actuator is replaced. An auto
adjust is also required when the Pandaros is retrofitted to a field system and mechanical changes are
made, e.g. adjustments to the control rod assembly!
5.1 General:
The controller has a cumulative failure transmitting outlet (warning and emergency shutdown), in the form
of a group alarm via a switching transistor output. When an internally monitored failure occurs, the
transistor switches over and internally connects the failure transmitting output (terminal 10) to the earth
for the power supply (0V | terminal 20. Pandaross internal diagnosis system can distinguish between
self-resetting error warnings and errors which will result in emergency shutdown of controllers output
stage and the actuator motor.
This cumulative failure transmitting output (warning and emergency shutdown) is integrated by means of
a pull-up resistor directly into the dia.ne AMM as warning number 1192 with the text Actuator/Controller
Failure (closed-circuit principle). In general, controllers in new installations have been switched off during
engine standstill since the year 2000 to extend their service life. As the controller is not activated during
engine standstill (no power supply), the controllers cumulative failure transmitting output is only
monitored by the dia.ne AMM when the engine is running.
The failure transmitting output is automatically reset when the controller data are again within the
defined error limits. The current warning on the dia.ne AMM can then be reset.
In the event of an emergency shutdown the controller blocks the actuator at the 0% position. The fault
must first be rectified and the controllers active failure transmitting output reset so that the actuator can
be restarted. The controller is reset by resetting the power supply and released for operation. Resetting is
done by switching the controllers power supply off and on again and is only necessary in installations in
which the controller and the actuator can still be operated during engine standstill.
Since the year 2000, controllers in new installations have been switched off during engine standstill in
order to extend the service life of the controllers and actuators. It is not necessary to reset the power
supply, as described above, during engine standstill after rectifying a fault as the controller has already
been switched off while the fault was being rectified. On engine startup the controllers power supply is
automatically switched on again with the ignition request and the cumulative failure transmitting output is
reset at the same time. It is possible to operate the actuator again, and the current Warning No. 1192 on
the dia.ne AMM can be reset.
6. Troubleshooting: